IR 05000261/2019002

From kanterella
Jump to navigation Jump to search
NRC Integrated Inspection Report 05000261/2019002, and Independent Spent Fuel Storage Installation Inspection (ISFSI) Report 07200060/2019001
ML19218A137
Person / Time
Site: Robinson, 07200060  
(DPR-023)
Issue date: 08/05/2019
From: Randy Musser
NRC/RGN-II, Division Reactor Projects II
To: Kapopoulos E
Duke Energy Progress
Reeder D
References
IR 2019001, IR 2019002
Download: ML19218A137 (11)


Text

August 5, 2019

SUBJECT:

H. B. ROBINSON STEAM ELECTRIC PLANT - NRC INTEGRATED INSPECTION REPORT 05000261/2019002, AND INDEPENDENT SPENT FUEL STORAGE INSTALLATION INSPECTION (ISFSI) REPORT 07200060/2019001

Dear Mr. Kapopoulos:

On June 30, 2019, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at H. B. Robinson Steam Electric Plant. On July 15, 2019, the NRC inspectors discussed the results of this inspection with you and other members of your staff. The results of this inspection are documented in the enclosed report.

The NRC inspectors did not identify any finding or violation of more than minor significance.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with 10 CFR 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely,

/RA/

Randall A. Musser, Chief Reactor Projects Branch 3 Division of Reactor Projects

Docket No. 05000261, 07200060 License No. DPR-23

Enclosure:

As stated

Inspection Report

Docket Number:

05000261, 07200060

License Number:

DPR-23

Report Number:

05000261/2019002, 07200060/2019001

Enterprise Identifier: I-2019-002-0017, I-2019-001-0131

Licensee:

Duke Energy Progress, LLC

Facility:

H. B. Robinson Steam Electric Plant,

H. B. Robinson (ISFSI - 07200060)

Location:

Hartsville, SC 29550

Inspection Dates:

April 1, 2019 to June 30, 2019

Inspectors:

A. Beasten, Resident Inspector

M. Fannon, Senior Resident Inspector

C. Fontana, Emergency Preparedness Inspector

J. Hamman, Acting Senior Resident Inspector

W. Loo, Senior Health Physicist

S. Sanchez, Senior Emergency Preparedness Insp

J. Walker, Emergency Response Inspector

A. Wilson, Project Engineer

Approved By:

Randall A. Musser, Chief

Reactor Projects Branch 3

Division of Reactor Projects

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees

performance by conducting an integrated inspection and ISFSI inspection at H. B. Robinson

Steam Electric Plant in accordance with the Reactor Oversight Process. The Reactor Oversight

Process is the NRCs program for overseeing the safe operation of commercial nuclear power

reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

None.

PLANT STATUS

Unit 1 began the inspection period at rated thermal power. On May 17, 2019, the unit was down

powered to 52 percent for turbine valve testing. The unit was returned to rated thermal power

on May 18, 2019. On June 21, 2019, the unit was down powered to 53 percent for turbine valve

testing. The unit was returned to rated thermal power on June 21, 2019, and remained at or

near rated thermal power for the remainder of the inspection period.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in

effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with

their attached revision histories are located on the public website at http://www.nrc.gov/reading-

rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared

complete when the IP requirements most appropriate to the inspection activity were met

consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection

Program - Operations Phase. The inspectors performed plant status activities described in

IMC 2515 Appendix D, Plant Status and conducted routine reviews using IP 71152, Problem

Identification and Resolution. The inspectors reviewed selected procedures and records,

observed activities, and interviewed personnel to assess licensee performance and compliance

with Commission rules and regulations, license conditions, site procedures, and standards.

REACTOR SAFETY

71111.01 - Adverse Weather Protection

Summer Readiness Sample (IP Section 03.01) (1 Sample)

(1)

The inspectors evaluated summer readiness of offsite and alternate alternating

current (AC) power systems from June 10 through 14, 2019.

Impending Severe Weather Sample (IP Section 03.03) (1 Sample)

(1)

The inspectors evaluated readiness for impending adverse weather conditions for

unseasonable high temperatures on May 24 through May 30, 2019.

71111.04 - Equipment Alignment

Partial Walkdown Sample (IP Section 03.01) (3 Samples)

The inspectors evaluated system configurations during partial walkdowns of the following

systems/trains:

(1)

'B' containment vessel spray train while the 'A' containment vessel spray train was out

of service for planned maintenance on April 3, 2019

(2)

'A' and 'B' auxiliary feedwater, following system restoration from maintenance, on

April 30, 2019

(3)

'A' and 'B' emergency diesel generators while the dedicated shutdown emergency

diesel generator was out of service for emergent maintenance on June 11, 2019

71111.05Q - Fire Protection

Quarterly Inspection (IP Section 03.01) (6 Samples)

The inspectors evaluated fire protection program implementation in the following selected

areas:

(1)

Fire zone 16, 'A' and 'B' battery rooms, on April 25, 2019

(2)

Fire zone 6, auxiliary feedwater pump room, on April 30, 2019

(3)

Fire zone 5, component cooling pump room, on May 2, 2019

(4)

Fire zone 25D, dedicated shutdown emergency diesel generator building, on

May 25, 2019

(5)

Fire zone 20, emergency switchgear rooms and electrical equipment area, on

June 12, 2019

(6)

Fire zone 1, 'B' emergency diesel generator room on June 24, 2019

71111.11Q - Licensed Operator Requalification Program and Licensed Operator Performance

Licensed Operator Performance in the Actual Plant/Main Control Room (IP Section 03.01) (1 Sample)

(1)

The inspectors observed and evaluated licensed operator performance in the control

room during a downpower to 50 percent for turbine valve testing on May 17, 2019.

Licensed Operator Requalification Training/Examinations (IP Section 03.02) (1 Sample)

(1)

The inspectors observed and evaluated licensed operator requalification training on

May 28, 2019.

71111.12 - Maintenance Effectiveness

Routine Maintenance Effectiveness Inspection (IP Section 02.01) (3 Samples)

The inspectors evaluated the effectiveness of routine maintenance activities associated with

the following equipment and/or safety significant functions:

(1)

'A' component cooling water pump and system

(2)

'B' emergency diesel generator

(3)

Maintenance Rule (a)(2) evaluation for steam dump system following repetitive

functional failure on January 17, 2019

71111.13 - Maintenance Risk Assessments and Emergent Work Control

Risk Assessment and Management Sample (IP Section 03.01) (4 Samples)

The inspectors evaluated the risk assessments for the following planned and emergent work

activities:

(1)

'A' emergency turbine trip quadvoter solenoid valve reset failure on April 1, 2019

(2)

'A' motor driven auxiliary feedwater pump maintenance outage on May 7, 2019

(3)

'C' motor driven auxiliary feedwater pump diesel generator maintenance outage on

May 29 and 30, 2019

(4)

Dedicated shutdown diesel generator out of service for air compressor belt failure on

June 11, 2019

(5)

Risk assessment for week of April 8, 2019, with cross-train maintenance on B motor

driven auxiliary feedwater pump and trip risk due to reactor protection testing, on

April 10, 2019

71111.15 - Operability Determinations and Functionality Assessments

Operability Determination or Functionality Assessment (IP Section 02.02) (5 Samples)

The inspectors evaluated the following operability determinations and functionality

assessments:

(1)

Nuclear condition report (NCR) 2266358, dedicated shutdown uninterruptable power

supply batteries due to water intrusion from east wall of the 4kV room on April 2, 2019

(2)

NCR, 2270762, service water header isolation valve contactor pickup voltage test

results on May 6, 2019

(3)

NCR 2273379, turbine stop valve difficult to open following turbine valve testing on

May 17, 2019

(4)

NCR 2277463, 'A' service water sling ring slipping on June 17, 2019

(5)

NCR 2277371, service water to 'A' auxiliary feedwater seal cooling solenoid valve

EV-1903A buzzing on June 17, 2019

71111.18 - Plant Modifications

Temporary Modifications and/or Permanent Modifications (IP Section 03.01 and/or 03.02) (3 Samples)

The inspectors evaluated the following temporary or permanent modifications:

(1)

Engineering change (EC) 407387, Evaluate the effects of emergency diesel

generator frequency changes on maximum differential pressure used for motor

operated valve calculations

(2)

EC 414811, Repair Howell-Bunger valve protective structure and related components

(3)

EC 415325, Revise 'C' reactor coolant pump lower oil reservoir high level alarm

setpoint

71111.19 - Post-Maintenance Testing

Post Maintenance Test Sample (IP Section 03.01) (5 Samples)

The inspectors evaluated the following post maintenance tests:

(1)

Work order (WO) 20143826, 'A' emergency turbine trip quadvoter solenoid valve

reset failure on April 1, 2019

(2)

OST-352-1, 'A' containment spray train annual lubrication on April 3, 2019

(3)

WO 20217595, 'A' motor driven auxiliary feedwater system control valve, FCV-1424,

maintenance on May 7, 2019

(4)

OST-101-3, 'C' charging pump maintenance on June 17, 2019

(5)

WO 20113512, 'C' motor driven auxiliary feedwater pump and diesel generator

maintenance outage on June 25 and 26, 2019

71111.22 - Surveillance Testing

The inspectors evaluated the following surveillance tests:

Inservice Testing (IP Section 03.01) (1 Sample)

(1)

OST-908-2, Component Cooling Water Pump 'A' Test, on May 2, 2019

Surveillance Tests (other) (IP Section 03.01) (4 Samples)

(1)

MST-I-RCS-FLW-CH-1, Reactor Coolant System Channel 1 Operation Test, on

May 16, 2019

(2)

OST-551-1, Turbine Valve Test, on May 17, 2019

(3)

OST-202, Steam Driven Auxiliary Feedwater System Component Test, on

June 11, 2019

(4)

MST-030, 4kV Undervoltage to Reactor Protection Test, on June 27, 2019

71114.01 - Exercise Evaluation

Inspection Review (IP Section 02.01-02.11) (1 Sample)

(1)

The inspectors evaluated the biennial emergency plan exercise during the week of

May 20, 2019. The exercise scenario simulated a radiologically hot particle on an

individuals shoe inside the Central Alarm Station that caused their dosimeter to alarm

and ultimately led to the declaration of an Alert. A reactor coolant system leak inside

containment developed and increased enough to cause a reactor trip and safety

injection, and eventually containment pressure increased to meet the threshold for

declaring a Site Area Emergency. As the leak size increased, fuel damage began to

occur, creating conditions that led to a General Emergency simulated classification

and allowed the Offsite Response Organizations to demonstrate their ability to

implement emergency actions.

71114.04 - Emergency Action Level and Emergency Plan Changes

Inspection Review (IP Section 02.01-02.03) (1 Sample)

(1)

The inspectors evaluated submitted Emergency Action Level, Emergency Plan, and

Emergency Plan Implementing Procedure changes during the week of May 20, 2019.

This evaluation does not constitute NRC approval.

71114.06 - Drill Evaluation

Select Emergency Preparedness Drills and/or Training for Observation (IP Section 03.01) (1

Sample)

(1)

The inspectors evaluated the conduct of a routine emergency planning drill on

April 9, 2019. The drill involved a seismic event that resulted in a loss of coolant

accident and loss of spent fuel cooling inventory.

71114.08 - Exercise Evaluation Scenario Review

Inspection Review (IP Section 02.01 - 02.04) (1 Sample)

(1)

The inspectors reviewed and evaluated in-office, the proposed scenario for the

biennial emergency plan exercise at least 30 days prior to the day of the exercise.

OTHER ACTIVITIES - BASELINE

71151 - Performance Indicator Verification

The inspectors verified licensee performance indicators submittals listed below:

EP01: Drill/Exercise Performance (IP Section 02.12) (1 Sample)

(1)

EP01: Drill & Exercise Performance for the period January 1, 2018, through

March 31, 2019.

EP02: ERO Drill Participation (IP Section 02.13) (1 Sample)

(1)

EP02: Emergency Response Organization Drill Participation for the period

January 1, 2018, through March 31, 2019.

EP03: Alert & Notification System Reliability (IP Section 02.14) (1 Sample)

(1)

EP03: Alert & Notification System Reliability for the period January 1, 2018, through

March 31, 2019.

IE04: Unplanned Scrams with Complications (USwC) Sample (IP Section 02.03) (1 Sample)

(1)

Unplanned scrams with complications from April 1, 2018 to March 31, 2019

MS05: Safety System Functional Failures (SSFFs) Sample (IP Section 02.04) (1 Sample)

(1)

Safety system functional failures (MS05) from April 1, 2018 to March 31, 2019

MS06: Emergency AC Power Systems (IP Section 02.05) (1 Sample)

(1)

Emergency alternating current power systems (MS06) from April 1, 2018 to

March 31, 2019

71152 - Problem Identification and Resolution

Semiannual Trend Review (IP Section 02.02) (1 Sample)

(1)

The inspectors reviewed the licensees corrective action program for trends that might

be indicative of a more significant safety issue.

From January 1, 2019 through June 30, 2019, the inspectors noticed a potential

adverse trend in operator rounds, specifically as it relates to awareness of oil levels in

operating plant equipment. During this timeframe, NRC inspectors identified oil levels

of operating equipment on multiple occasions that were trending down or which were

found out of range of the sightglass/bubbler:

  • On Monday, February 4, 2019, the inspectors noticed that the oil level in the

'A' charging pump crankcase sightglass was out of range and questioned the

licensee on the expected condition of the pump, which was running at the

time. Maintenance was called out to add oil to the 'A' charging pump

crankcase.

On Monday, February 11, 2019, the inspectors again noticed that the oil level

in the 'A' charging pump crankcase sightglass was out of range, and

questioned the licensee on the condition of the pump and the expected

operator actions. Oil was added to the pump, and work request (WR)

20134243 was initiated to capture the increased frequency of oil addition.

This WR was converted to nuclear condition report (NCR) 02258398 on

February 19, 2019.

On May 7, 2019, the inspectors observed that the oil level in the 'C' charging

pump crankcase sightglass was out of range, and challenged the licensee on

the expected condition of the pump, which was running at the time. The oil

level had been recorded as meeting the operator rounds requirements earlier

that day, but the oil level had decreased throughout the shift. An investigation

revealed that the oil was leaking past a gasket. The licensee entered this

event into their corrective action program as NCR 02271852.

On June 17, 2019, inspectors observed the 'A' service water booster pump oil

level had dropped approximately 25 percent since June 13. The inspectors

questioned the licensee about the expected condition of the pump, which was

running at the time, and if any oil leaks had been reported. No leaks had been

reported, and the licensee entered the issue into their corrective action

program on June 20, 2019 as NCR 02278429 in order to identify the oil leak

and determine the impact of the leak.

None of the conditions challenged the operability of the equipment affected, and upon

discovery, oil was added to each piece of equipment affected. The licensee entered

the potential adverse trend into the corrective action program as NCR 2281986 to

determine the appropriate actions needed to address the issue.

OTHER ACTIVITIES - TEMPORARY INSTRUCTIONS, INFREQUENT AND ABNORMAL

60855.1 - Operation of an Independent Spent Fuel Storage Installation at Operating Plants

Operation of an Independent Spent Fuel Storage Installation at Operating Plants (1 Sample)

(1)

The inspectors evaluated the licensees activities related to long-term operation and

monitoring of their independent spent fuel storage installation on

June 17 through 24, 2019.

INSPECTION RESULTS

No findings were identified.

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

Inspection to M and other members of the licensee staff.

On July 15, 2019, the inspectors presented the integrated inspection results to

M and other members of the licensee staff.