", fl .,.

e

'),t

,/ .

VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 July 23, 1999 United States Nuclear Regulatory Commission Serial No.99-379 Attention: Document Control Desk SS&UBAG RO Washington, D. C. 20555-0001 Docket No. 50-280 50-281 License No. DPR-32 DPR-37 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNITS 1 AND 2 REVISIONS TO EMERGENCY PLAN IMPLEMENTING PROCEDURES Pursuant to 10 CFR 50.54(q), enclosed are revisions to four Surry Power Station Emergency Plan Implementing Procedures. The revisions do not implement actions which decrease the effectiveness of our Emergency Plan. The Emergency Plan and Implementing Procedures continue to meet the standards of 10 CFR 50.47(b). Please update your manual by performing the actions described in the enclosed tabulation of changes.

Very truly yours,

~D~

E. S. Grecheck Site Vice President Enclosure Commitments contained in this letter: None.

cc: U.S. Nuclear Regulatory Commission (2 copies)

Region II Atlanta Federal Center 61 Forsyth Street S.W., Suite 23T85 Ao~5 _ --

Atlanta, Georgia 30303 Mr. R. A. Musser NRC Senior Resident Inspector Surry Power Station 9907300031 990723 PDR ADOCK 05000280 F , ' PDR'

e

' *. \,a'"

    • J '
  • Serial No.99-379 Surry EPIP Revisions VIRGINIA ELECTRIC AND POWER COMPANY REVISION TO SURRY POWER STATION EMERGENCY PLAN IMPLEMENTING PROCEDURE Enclosed are rev1s1ons to Surry Power Station Emergency Plan Implementing Procedures. Please take the following actions in order to keep your manual updated with the most recent revisions.

REMOVE AND EFFECTIVE INSERT: EFFECTIVE DESTROY: DATE: DATE:

EPIP-4.02, Rev. 18., ,,...,,-- 09/10/98 EPIP-4.02, Rev. 19 07/22/99 EPIP-4.16, Rev. 13t / 08/05/98 EPIP-4.16, Rev. 14 07/22/99

../

EPIP-4.21, Rev. 7 Y 05/01/94 EPIP-4.21, Rev. 8 07/22/99

./'

V EPIP-4.30, Rev. 6V 10/14/98 EPIP-4.30, Rev. 7 07/22/99 Emergency Plan Privacy and Proprietary Material have been removed.

Reference Generic Letter No. 81-27

.j

  • NUMBER PIP-4.02 PROCEDURE TITLE RADIATION PROTECTION SUPERVISOR CONTROLLING PROCEDURE (With 2 Attachments)

//

/

/

RE,VISION PAGE 1 of 20 18

/

PURPOSE

/en/c/y/

Establish a radiation protection program during an eme ./rg (including the dispatch o monitoring teams).

/

./

~//

//

/

ENTRY CONDITIONS /'

Any one of the following:

1. Emergency classification o/f-an Alert. Site Area Emergency or General Emergency .
2. Activation by EPIP-4.01.;~ADIOLOGI AL ASSESSMENT DIRECTOR CONTROLLING PROCEDURE. . /

I

3. Whenever deemed ne~ssary by the RadioJogical Assessment Director.

I

/

/'

/

/

/

/

//'

I

/

/1 I

/

I I

APPROVAL RECOMMENDED SNSOC APPROVAL APPROVAL EFFECTIVE

.l*~~~-

DATE

'--:?. ~ / //DATE

~' <:. /_; . /~ 'f}6fa,f, p

CHAIRMAN SNSOC STATION MANAGER Form No. 72375B(Apr 91)'

NUMBER PROCEDURE TITLE REVISION EPIP-4.02 RADIATION PROTECTION SUPERVISOR CONTROLLING 18 PROCEDURE PAGE 2 of 20 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 1 INITIATE PROCEDURE:

  • By:

Date:

Time:

2 ESTABLISH RADIATION PROTECTION SUPERVISOR (RPS) OFFICE:

a) Evaluate HP area radiation levels:

\

1) Do surveys and sampling

)

2) Use fri skers. personnel contamination monitors and count room analysis equipment for indications of abnormal readings b) Verify HP area - HABITABLE b) lI HP area NOT habitable, THEN do the following:
1) Establsh RPS Office in a habitable area (consider DSC, ALARA Office. Alternate
  • DSC or Emergency Switchgear Room).
2) Notify Exposure Control personnel.
3) GO TO Step 3.

c) Establish RPS Office in Supervisor HP (Operations)

Office

  • -4*

NUMBER PROCEDURE TITLE REVISION RADIATION PROTECTION SUPERVISOR CONTROLLING EPIP-4.02 PROCEDURE 18

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 3 of 20 3 ESTABLISH COMMUNICATIONS:

a) Check TSC - ACTIVATED a) GO TO Step 3.d.

b) Notify RAD that RPS Office has been established c) Coordinate establishment of Radiological Protection Communications Network between the following locations (as permitted by personnel av a i l ab i l i ty ) :

  • Chemistry
  • osc d) Do radio checks:
1) Get portable HP radios, chargers and batteries
2) Use appropriate Announce/Talk Group(s)
3) Verify radio operability 3) Notify RAD of radio inoperability.

4 ESTABLISH ACCESS CONTROL:

a) Assign individual to control RCA access or to rope off RCA entrance b) Limit RCA access to approved individuals

NUMBER PROCEDURE TITLE REVISION

  • - EPIP-4.02 RADIATION PROTECTION SUPERVISOR CONTROLLING 18 PROCEDURE
  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 4 of 20

~~ 5 ESTABLISH EXPOSURE CONTROL:

a) Have Exposure Control personnel initiate EPIP-4.27, EXPOSURE CONTROL EMERGENCY RESPONSE b) Notify Exposure Control personnel of HP area habitability

~~ 6 EVALUATE HP READINESS:

a) Identify available HP resources:

  • Have on-duty HP staff report to HP area
  • Have Exposure Control provide number and location of personnel on shift b) Notify RAD of HP readiness

~~ 7 ASSIGN INPLANT/ONSITE TEAMS:

a) Check personnel available for a) GO TO Step 8.

assignment as inplant and onsite team leaders b) Assign team leaders c) Assign inplant and onsite monitoring EPIP packages to team leaders d) Assign one team member for each inplant and onsite team

..)

NUMBER PROCEDURE TITLE REVIS ION

-- EPIP-4.02 RADIATION PROTECTION SUPERVISOR CONTROLLING 18 PROCEDURE PAGE 5 of 20 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED

~~8 GET STATUS UPDATE FROM RAD:

  • Emergency classification
  • Plant status
  • Meteorological status
  • HP assistance required
  • Areas requiring monitoring (e.g .. Chemistry Office, Security) 9 ASSIGN INDIVIDUAL TO MONITOR TEAM DISPATCH USING ATTACHMENT 1, MONITORING TEAM LOCATIONS

NUMBER PROCEDURE TITLE REVISION EPIP-4.02 RADIATION PROTECTION SUPERVISOR CONTROLLING 18 PROCEDURE PAGE 6 of 20 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED

  • A m1n1mum of 2 (two) Offsite Monitoring Teams must be dispatched, i.e .. sent into the field, at a Site Area Emergency or General Emergency.
  • Emergency conditions may require immediate implementation of radiological protection response actions. Attachments to this procedure and associated documentation may be completed after the fact should these conditions exist.

10 CHECK ANY OF THE FOLLOWING ACTIONS GO TO Step 22.

REQUIRED (BASED ON CONSULTATION WITH RAD OR DEGRADING RADIOLOGICAL CONDITIONS):

  • EOP and Accident Mitigation Task support: GO TO Step 11
  • Inplant monitoring - GO TO Step 12
  • Onsite monitoring - GO TO Step 13
  • Brief Inplant/Onsite Monitoring or Damage Control Teams -

Initiate Attachment 2, TEAM BRIEFING

  • Offsite monitoring - GO TO NOTE prior to Step 14
  • Control Room/TSC/OSC/LEOF monitoring - GO TO Step 15
  • Contaminated personnel - GO TO Step 16
  • Evacuation Monitoring ~GOTO Step 18
  • Request for Post Accident Sampling - GO TO Step 19
  • Respiratory Protection - GO TO Step 20
  • Rec~ipt of sample analysis data - GO TO Step 21

I I NUMBER PROCEDURE TITLE REVISION RADIATION PROTECTION SUPERVISOR CONTROLLING 18 EPIP-4.02 PROCEDURE PAGE 7 of 20 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE: Tasks to prevent/reduce core damage or terminate a radiological release may be identified as Accident Mitigation Tasks and as such should be expedited by all practical means.

11

  • PROVIDE SUPPORT FOR EMERGENCY OPERATING PROCEDURE (EOP) AND ACCIDENT MITIGATION TASK ACTIVITIES, AS NEEDED:
  • Assure EOP and Accident Mitigation Task teams are expedited through HP
  • Update RAD about HP support in progress

t t NUMBER PROCEDURE TITLE REVISION EPIP-4.02 RADIATION PROTECTION SUPERVISOR CONTROLLING 18 PROCEDURE PAGE 8 of 20 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 12 INITIATE INPLANT MONITORING:

a) Consult with RAD to determine location and type of surveys required b) Ask for assessment of radiological hazards in area of surveys c) Verify Inplant Monitoring Team c) Assign Inplant Monitoring Team Leader assigned Leader.

d) Do briefing with Team Leader:

1) Have Team Leader initiate EPIP-4.14, INPLANT MONITORING
  • 2) Give Team Leader location and type of surveys required
3) Determine route of entry that should minimize exposure
4) Assign team number
5) Assign the following: 5) l.E. radio NOT available, THEN have team use Gai-Tronics
  • Portable radio system for communications.
  • Radio talk group e) Complete Attachment 2, TEAM BRIEFING f) Dispatch team(s) g) Notify RAD when survey information is received and when team returns h) RETURN TO Step 10

NUMBER PROCEDURE TITLE REVISION EPIP-4.02 RADIATION PROTECTION SUPERVISOR CONTROLLING PROCEDURE 18

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 9 of 20 13 INITIATE ONSITE MONITORING:

a) Consult with RAD to determine location and type of surveys required b) Ask for assessment of radiological hazards in area of surveys c) Check if transportation required c) GO TO Step 13.e.

d) Assign vehicle (duplicate keys to vehicles are located in the Supv. HP Operations office key locker) e) Verify Onsite Monitoring Team e) Assign Onsite Monitoring Team Leader assigned Leader.

f) Do briefing with Team Leader:

1) Have Team Leader initiate EPIP-4.15, ONSITE MONITORING
2) Give Team Leader location and type of surveys requ{red
3) Assign team number
4) Assign the following: 4) lI radio NOT available, THEN have team use Gai-Tronics
  • Radio (portable or mobile) system for communications.
  • Radio talk group*

g) Complete Attachment 2. TEAM BRIEFING h) Dispatch team(s) i) Notify RAD when survey information is received and when team returns

  • j) RETURN TO Step 10

NUMBER PROCEDURE TITLE REVISION RADIATION PROTECTION SUPERVISOR CONTROLLING 18 EPIP-4.02 PROCEDURE PAGE 10 of 20 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED CAUTION: Emergency Kits #1 and #2 have 120 Volt air samplers and friskers with AC power cords. Vehicles assigned to teams with these kits have to be equipped with an inverter or equipment substitutions must be made prior to team departure from the HP area. Emergency Kit #3 has a 12 Volt battery clamp air sampler.

NOTE: Emergency Kit #1 is located in the Environmental Monitoring vehicle.

Emergency Kits #2 and #3 are located in the Maintenance Services Building. Instruments for these kits are stored separately in the HP Emergency Response Storage Area.

14 INITIATE OFFSITE MONITORING:

a) Determine from RAD:

  • Need for offsite monitoring teams
  • Number of offsite teams required
  • Initial location of each team b) Ask for assessment of possible radiological hazards in area of surveys c) Assign 2 individuals to each Offsite Monitoring Team (at least 1 an HP Tech) d) Assign vehicle (duplicate keys to vehicles are located in the Supv. HP Operations office key locker) e) Use EPIP-4.16, OFFSITE MONITORING to brief Team Leader f) RETURN TO Step 10

NUMBER PROCEDURE TITLE REVISION

... RADIATION PROTECTION SUPERVISOR CONTROLLING EPIP-4.02 18 PROCEDURE PAGE 11 of 20 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE: HP personnel should begin monitoring the LEOF within 60 minutes following declaration of an Alert or higher classification.

~~ 15 INITIATE CONTROL ROOM/TSC/OSC/LEOF MON ITO RI NG:

a) Establish monitoring of emergency response centers b) Determine frequency of monitoring based on:

  • Spread of contamination from service buildings
  • Increase or decrease of effluent release
  • Increase in emergency classification
  • Change in plume direction c) Assign EPIPs:
  • EPIP-4.17, MONITORING OF EMERGENCY RESPONSE FACILITIES
  • EPIP-4.18, MONITORING OF LEOF d) Notify RAD as to the habitability of emergency response centers e) RETURN TO Step 10

NUMBER PROCEDURE TITLE REVISION EPIP-4.02 RADIATION PROTECTION SUPERVISOR CONTROLLING 18 PROCEDURE PAGE 12 of 20 RESPONSE NOT OBTAINED 16 CHECK PERSONNEL - CONTAMINATED RETURN TO Step 10.

a) Check contaminated personnel - a) GO TO Step 16.d.

INJURED b) Check transport to offsite b) GO TO Step 16.d.

medical facility - REQUIRED c) GO TO Step 17 d) Use normal station procedures to decontaminate individual Cs) and record results e) Notify RAD of results f) Identify location where individual(s) was contaminated g) Evaluate set-up of access controls h) RETURN TO Step 10

NUMBER PROCEDURE TITLE REVISION EPIP-4.02 RAD I ATI ON PROTECTION SUPERVISOR CONTROLLING 18 PROCEDURE PAGE 13 of 20 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 17 HELP TRANSPORT CONTAMINATED INJURED PERSONNEL:

a) Do personnel surveys b) Check if decontamination prior b) GO TO Step 17.d.

to transport practical c) Use normal station decontamination procedures d) Notify RAD of need to transport contaminated personnel e) Assign HP Tech to accompany injured individual:

1) Have HP Tech use normal HP procedure(s) for response to contaminated injured personnel
2) Give HP Tech portable survey instrument f) Check if dosimetry needed by f) GO TO Step 17.h.

ambulance personnel

  • g) Have HP Tech issue dosimetry h) Notify RAD when ambulance departs i) RETURN TO Step 10

NUMBER PROCEDURE TITLE REVISION RADIATION PROTECTION SUPERVISOR CONTRITLLING EPIP-4.02 PROCEDURE 18

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 14 of 20 18 INITIATE EVACUATION MONITORING:

a) Check evacuation - ORDERED a) lE evacuation planned but NOT ordered, THEN GO TO Step 18.c.

b) GO TO Step 18.d c) Do the following when notified of pending evacuation:

1) Consult with RAD regarding need of additional onsite surveys to support evacuation
2) Check surveys - REQUIRED 2) lE surveys NOT required, THEN GO TO Step 18.d.
3) Dispatch Monitoring Teams to determine radiation and contamination levels
4) Notify RAD of survey results d) Assign EPIP-4.21, EVACUATION AND REMOTE ASSEMBLY AREA MONITORING e) Assign Evacuation and Remote Assembly Area monitoring kit located in Maintenance Services Building (Kit #4) f) Help team get transportation or make arrangements for transportation with Security g) Notify RAD when team is dispatched and when survey results are available h) RETURN TO Step 10

NUMBER PROCEDURE TITLE REVISION RAD I ATI ON PROTECTION SUPERVISOR CONTROLLING EPIP-4.02 18 PROCEDURE PAGE 15 of 20 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 19 INITIATE POST ACCIDENT SAMPLING MON ITO RING:

a) Take inplant survey to determine dose rate at sample station b) Notify RAD of survey results c) Assign EPIPs:

  • EPIP-4.22, POST ACCIDENT SAMPLING OF CONTAINMENT AIR
  • EPIP-4.23, POST ACCIDENT SAMPLING OF REACTOR COOLANT
  • EPIP-4.24, GASEOUS EFFLUENT SAMPLING DURING AN EMERGENCY
  • EPIP-4.25, LIQUID EFFLUENT SAMPLING DURING AN EMERGENCY ct) Provide HP coverage during sampling and sample preparation e) RETURN TO Step 10

NUMBER PROCEDURE TITLE REVISION RADIATION PROTECTION SUPERVISOR CONTROLLING 18 EPIP-4.02 PROCEDURE PAGE 16 of 20 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 20 EVALUATE RESPIRATORY PROTECTION REQUIREMENTS:

a) Evaluate the following:

  • Airborne activity
  • Presence of noxious gases or oxygen deficient air b) Evaluate the need for recommending relocation of non-essential personnel from affected areas c) Evaluate the need for initiating EPIP-4.05, RESPIRATORY PROTECTION d) RETURN TO Step 10 21 NOTIFY RAD WHEN ANY OF THE FOLLOWING SAMPLE ANALYSIS RESULTS RECEIVED:
  • Sample analysis data requested by RAD
  • Aonormal or unexpected analysis data

NUMBER PROCEDURE TITLE REVISION EPIP-4.02 RADIATION PROTECTION SUPERVISOR CONTROLLING 18 PROCEDURE PAGE 17 of 20 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 22 IDENTIFY ADDITIONAL ACCESS CONTROL REQUIREMENTS:

a) Check if abnormal radiological a) lI NO abnormal radiological conditions exist: conditions, THEN do the following:

  • Airborne contamination greater than 0.30 DAC 1) Use normal station access control procedures.
  • Deposition greater than 1000 dpm per 100 cm2 2) GO TO Step 23.
  • Area dose rate greater than 1000 mR/hr b) Consult with RAD about areas for which access is to be controlled c) Establish access control by:
  • Requiring HP notification prior to entry
  • Roping and posting affected areas d) Evaluate HP area radiation levels:
1) Do surveys and sampling
2) Use fri skers, personnel contamination monitors and count room analysis equipment for indications of abnormal readings

**=1 . !

NUMBER PROCEDURE TITLE REVISION RAD I ATI ON PROTECTION SUPERVISOR CONTROLLING EPIP-4.02 PROCEDURE 18

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 18 of 20

_ _ 23 EVALUATE STAFFING REQUIREMENTS:

a) Consult with RAD about projected duration of emergency b) Check if relief schedule and/or b) GO TO Step 24.

increased staffing schedule required c) Prepare schedule d) Give schedule to RAD for approval e) Check schedule - APPROVED e) GO TO Step 24.

f) Perform callout of personnel

  • 24 g) Notify RAD when callout complete CHECK RELIEF - AVAILABLE 1.£. NO relief available. THEN GO TO Step 26.

25 TRANSFER RESPONSIBILITIES TO RELIEF:

a) Notify successor about plant conditions and HP actions underway b) Notify RAD of change of position c) Stay with new RPS for approximately 30 minutes to facilitate turnover

____J

NUMBER PROCEDURE TITLE REVISION EPIP-4.02 RADIATION PROTECTION SUPERVISOR CONTROLLING PROCEDURE 18

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 19 of 20

~~ 26 CONTINUE ASSESSMENT:

a) Check if emergency condition a) GO TO Step 27.

still exists b) Verify initial TSC b) WHEN TSC activated, THEN communications established establish communications with RAD.

c) Do the following:

1) RETURN TO Step 8
2) Have survey(s) and sampling repeated as necessary to determine/monitor onsite radiological conditions
  • ~~ 27 SECURE FROM EMERGENCY:

a) Notify HP staff b) Maintain access control c) Consult with RAD about reco~ery actions d) Restore procedures and equipment used during the emergency

NUMBER PROCEDURE TITLE REVISION RADIATION PROTECTION SUPERVISOR CONTROLLING EPIP-4.02 18 PROCEDURE PAGE 20 of 20 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 28 TERMINATE EPIP-4.02:

  • Give completed EPIP-4.02, forms and other applicable records to the RAD
  • Completed by:

Date:

Time:

-END-

, r t J NUMBER ATTACHMENT TITLE REVISION EPIP-4.02 18

  • ATTACHMENT MONITORING TEAM LOCATIONS PAGE 1 1 of 1 TEAM MEMBERS RADIO LOCATION TIME NUMBER TALK GROUP

NUMBER ATTACHMENT TITLE REVISION EPIP-4.02 TEAM BRIEFING FORM 18

  • ATTACHMENT PAGE 2 1 of 1 SECTION 1: (TO BE COMPLETED BY TEAM LEADER)

DATE _ _ __ TIME DISPATCHED _ _ __ TEAM DESIGNATION _ _ _~

TASK*----------------------------~

LOCATION _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __

EXPECTED CONDIT IONS _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __

DOSE RATES _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __

CONTAMINATION LEVELS _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _~

SECTION 2: (TO BE COMPLETED BY INDIVIDUAL GIVING BRIEFING)

RADIO TALK GROUP:

  • TEAM PERSONNEL DATA NAME TLD REMAINING DOSE RESP. QUAL. Y/N DOSE & STAY TIME _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __

PROTECTIVE CLOTHING/RESPIRATORY PROTECTION FULL PCs w/PLASTICS w/o PLASTICS _ _ PAPER SU IT ONLY STREET CLOTHES SCBA_ _ PAPR_ _ FULL FACE _ _

COMMUNICATIONS EQUIPMENT_ _ _ _ _ _ _ _ _ _ _~ (DO NOT USE RADIO IN ESGR)

SPECIAL INSTRUCTIONS _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __

Level 2 Controlled Distribution

  • Maintained ljqltllll,Iffih'&~ar!Pl(D&lllE)R Do not removegoi"~QlOJWPJM fQrrfi.Eflro<<ork EMERGENCY PLAN IMPLEMENTING PROCEDURE
  • NUMBER EPIP-4.16 PROCEDURE TITLE OFFSITE MONITORING (With 3 Attachments)

REVISION 13 PAGE 1 of 16 PURPOSE To provide guidance for Offsite Monitoring Teams in obtaining equipment, tracking the plume, taking samples and transmitting data.

ENTRY CONDITIONS Entry from EPIP-4.02, RADIATION PROTECTION SUPERVISOR CONTROLLING PROCEDURE .

APPROVAL RECOMMENDED SNSOC APPROVAL APPROVAL EFFECTIVE DATE DATE DATE

  • CHAIRMAN SNSOC STATION MANAGER Form No. 723758(Apr 91)

NUMBER PROCEDURE TITLE REVISION EPIP-4.16 OFFSITE MONITORING 13 PAGE 2 of 16 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 1 INITIATE PROCEDURE:

  • By:

Date:

Time:

NUMBER PROCEDURE TITLE REVISION EPIP-4.16 OFFSITE MONITORING 13 PAGE 3 of 16 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED CAUTION: Emergency Kits #1 and #2 have 120 Volt air samplers and friskers with AC power cords. The vehicle assigned to the team with one of these kits has to be equipped with an inverter or equipment substitutions must be made prior to the team's departure from the HP area.

Emergency Kit #3 has a 12 Volt battery clamp air sampler.

NOTE:

  • Offsite Monitoring Teams consist of 2 individuals. one being an HP Technician.
  • Emergency Kit #1 is located in the Environmental Monitoring vehicle. Emergency Kits #2 and #3 are located in the Maintenance Services Building. Instruments are stored separately in the HP Emergency Response Storage area.

2 GET BRIEFING FROM RPS:

  • Logistics:
  • Staging area
  • Monitoring equipment required
  • Monitoring locations
  • Samples or surveys required
  • Anticipated radiation levels o Where to report survey data (TSC or LEOF) o Arrangements for return of samples to station for analysis
  • Radiation protection:
  • Protective clothing
  • Dosimetry
  • Respiratory protection*

NUMBER PROCEDURE TITLE. REVIS ION EPIP-4.16 OFFSITE MONITORING 13 '

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 4 of 16 CAUTION: Specific authorization is required before ingesting KI.

~~ 3 SEND COMPLETED ATTACHMENT 3, RADIOPROTECTIVE DRUG DOSAGE, SIDE EFFECTS AND MEDICAL STATEMENT TO RAD

~~ 4 GET DOSIMETRY:

  • DAD - ON
  • ~~
  • SRO - ZEROED 5 GET EQUIPMENT FROM HP EMERGENCY RESPONSE STORAGE:

a) Get instruments specified during briefing (e.g., portable monitoring device, air sampler) b) Get respirators c) Check equipment:

  • Battery check
  • Calibration sticker
  • Response check d) Record instrument data on Attachment 1, OFFSITE MONITORING DATA SHEET

NUMBER PROCEDURE TITLE REVISION EPIP-4.16 OFFSITE MONITORING 13 PAGE 5 of 16 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED

~~ 6 RECORD TEAM DATA ON ATTACHMENT 1:

  • Team identification number
  • Team Leader and Member names

~~ 7 GET VEHICLE (duplicate keys to vehicles are located in Supv. HP Operations office key locker)

NOTE: Radio contact should be with the TSC until the LEOF (or CEOF) is activated.

8 INITIATE RADIO COMMUNICATIONS:

a) Depress mode key on radio until EPl appears on the display b) Establish radio contact with appropriate emergency center (TSC, LEOF or CEOF) c) Ask for telephone number in case of radio failure d) Notify emergency center radio operator of the following:

  • Current location
  • Designated monitoring location NOTE: Two offsite monitoring emergency kits are stored in the Maintenance Services Building and one in the Environmental Monitoring vehicle.

~~ 9 GET EMERGENCY KIT

. -~

NUMBER PROCEDURE TITLE REVIS ION

  • EPIP-4.16 OFFSITE MONITORING 13 PAGE 6 of 16 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE:
  • The Health Physics Monitoring Map identifies monitoring locations.

Copies of the map are available in the Emergency Kit, HP Office, TSC and LEOF.

  • Pre-selected Monitoring Point H-1.9 may not be accessible by vehicle.

~~ 10 GO TO DESIGNATED STAGING AREA OR MONITORING LOCATION (Refer to HP Monitoring Map for directions as needed)

NOTE: Dosimetry (SRDs/DADs) should be periodically checked while performing monitoring activities .

  • 11 RECORD DOSIMETER READING IN MONITORING DATA SECTION OF ATTACHMENT 1 L_ __

NUMBER PROCEDURE TITLE REVIS ION EPIP-4.16 OFFSITE MONITORING 13 PAGE 7 of 16 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE: Completed samples should be placed in clean containers (e.g ..

plastic bags), kept for future laboratory analysis, and labeled with the following information (1) Team identification number, (2) Name, (3) Location, (4) Date. (5) Time. (6) Volume (if applicable).

12 CHECK ANY OF THE FOLLOWING l I directed to return to station, SAMPLING ACTVITIES - REQUIRED: THEN GO TO Step 21.

  • Track plume: l I NO immediate action required, GO TO Step 13 THEN wait in low background area for further instructions
  • Sample noble gas: (periodically check with command GO TO Step 14 facility).
  • Sample particulate and iodine:

GO TO Step 15

  • Determine air sample activity:

GO TO Step 16

  • Surface soil sample:

GO TO Step 18

  • Vegetation sample:

GO TO Step 19

  • Surface water sample:

GO TO Step 20

NUMBER PROCEDURE TITLE REVISION EPIP-4.16 OFFSITE MONITORING 13 PAGE 8 of 16 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED

~~ 13 FIND PLUME:

a) Get portable survey instrument from emergency kit b) Open beta shield c) Hold survey meter out of vehicle window d) Go through plume in a crosswind direction e) Check readings while traversing e) l.E NO readings above background plume until maximum point are observed, THEN do the (plume centerline) is located following: ~-

1) Ask appropriate emergency center where to relocate.
  • f) Record open window readings on Attachment 1 g) Close beta shield h) Record closed shield readings
2) RETURN TO Step 13.b .

on Attachment 1 i) Record dosimetry reading on Attachment 1 j) Notify emergency center of the following:

  • Dosimetry reading
  • Monitoring readings
  • Monitoring location k) Check if additional mon ito ring k) lI NO additional actions is required required, THEN go to a low background area outside the plume and wait for further instructions (periodically check with command facility).

l) RETURN TO Step 11

NUMBER PROCEDURE TITLE REVISION OFFSITE MONITORING EPIP-4.16 13 I PAGE 9 of 16 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED

~~ 14 TAKE NOBLE GAS SAMPLE:

a) Get 100 cc gas chamber from emergency kit b) Go to plume centerline or sample location specified c) Take off top of gas chamber d) Wave gas chamber in air e) Make sure petcocks are closed f) Put top of chamber back on g) Put chamber in labeled plastic

  • bag h) Record location on Attachment 1 i) Notify emergency center of status j) Check if additional monitoring
  • j) lI NO additional actions is required required. THEN go to a low I ,

background area outside the plume and wait for further instructions (periodically check with command facility).

k) RETURN TO Step 11

NUMBER PROCEDURE TITLE REVISION EPIP-4.16 OFFSITE MONITORING 13 PAGE 10 of 16 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED CAUTION: Vehicle should be turned off if/when connecting or disconnecting air sampler cables. Do not touch engine or hoses as they may be hot.

15 TAKE PARTICULATE AND IODINE SAMPLE:

a) Ask emergency facility to determine sample volume required b) Get air sampler c) Insert particulate filter and silver zeolite cartridge into sampler d) Check if high humidity d) GO TO Step 15.g.

  • conditions exist e) Keep sample away from moisture f) Notify emergency center of weather conditions g) Get air sample:
1) Turn on air sampler
2) Get volume specified by emergency facility (minimum 2.5 ft3 air sample) h) Remove iodine cartridge and particulate filter from sampler i) Put iodine cartridge and particulate filter into separate, labeled plastic bags j) Record sample parameters in Air Sample Data section of Attachment 1:
  • Sample ID
  • Date
  • Time
  • Location
  • Volume k) Check if determination of I-131 k) RETURN TO Step 11.

activity required

NUMBER PROCEDURE TITLE REVISION EPIP-4.16 OFFSITE MONITORING 13 PAGE 11 of 16 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED

~~ 16 DETERMINE AIR SAMPLE ACTIVITY:

a) Go to,a low background area b) Turn on frisker b) 1£ frisker NOT operable, THEN GO TO Step 17.

c) Get a background count rate (cpm) ct) Put on a clean pair of gloves e) Take silver zeolite cartridge from plastic bag f) Hold influent side of silver

  • zeolite cartridge 1/4 inch from detector for at least 30 seconds to get a good count g) Check gross counts - ON SCALE g) Do the following:
1) Ask command facility which of the following actions is preferred:
  • Taking another sample of smaller volume
  • Measuring readings and converting results using an R0-2 meter.
2) 1£ another sample required, THEN RETURN TO Step 15.

1£ converting R0-2 readings, THEN GO TO Step 17.

h) Calculate net count rate:

GROSS (cpm) - BACKGROUND (cpm) NET C cpm) i) Obtain conversion factor for specific sample volume from Attachment 2 (STEP 16 CONTINUED ON NEXT PAGE)

'e, NUMBER PROCEDURE TITLE REVISION EPIP-4.16 OFFSITE MONITORING 13 PAGE 12 of 16 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 16 DETERMINE AIR SAMPLE ACTIVITY: (Continued) j) Calculate activity:

NET (cpm) x Conversion Factor= ACTIVITY (µCi/ml) k) Calculate Thyroid COE dose rate:

ACTIVITY (µCi/ml) x 1.57 E+9 = Thy COE, mR/hr l) Put sample in lebled plastic bag m) Record results in Air Sample section of Attachment 1 n) RETURN TO Step 11

}

NUMBER PROCEDURE TITLE REVIS ION EPIP-4.16 OFFSITE MONITORING 13 PAGE 13 of 16 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 17 CONVERT R0;2 MEASUREMENTS TO CPM:

a) Take background reading (mR/hr) b) Record results on Attachment 1 c) Hold influent side of silver zeolite cartridge about 1/4 inch from detector for at least 30 seconds to get a good reading d) Determine gross mR/hr e) Record results on Attachment 1 f) Calculate net mR/hr:

  • Gross mR/hr - Background mR/hr = Net mR/hr g) Record results on Attachment 1 h) Change mR/hr to approximate CPM:

Net mR/hr x 10,000 = Net CPM i ) Record results on Attachment 1 (Use appropriate units) j) RETURN TO Step 16.i

NUMBER PROCEDURE TITLE REVISION EPIP'-4.16 OFFSITE MONITORING 13

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 14 of 16

~~ 18 GET SURFACE SOIL SAMPLE:

a) Go to location specified by the emergency center b) Find an area to sample for surface deposition that is flat and open (away from buildings, trees and vegetation) c) Find an approximate 1 ft2 area to take sample d) Take top 1/4 to 1/2 inch layer of soil e) Put soil sample in labeled

  • plastic bag f) Notify emergency center of status g) Check if add it i on a1 *monitor i ng g) lE NO additional actions is required required. THEN go to a low background area outside the plume and wait for further instructions (periodically check with command facility).

h) RETURN TO Step 11 1

J NUMBER PROCEDURE TITLE REVIS ION EPIP-4.16 OFFSITE MONITORING 13 PAGE 15 of 16 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED

~~ 19 GET VEGETATION SAMPLE:

a) Locate vegetation to yield a sample representative of surface deposition (e.g.,

healthy grass, crops) b) Collect about 4 pounds of vegetation c) Put sample in a labeled container d) Notify command facility of your location e) Check if additional sampling - e) l..E. additional sampling NOT REOU I RED required, THEN go to a low background area and wait for further instructions (periodically check with command facility).

f) RETURN TO Step 11

}

NUMBER PROCEDURE TITLE REVIS ION EPIP-4.16 OFFSITE MONITORING 13 PAGE 16 of 16 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED

~~ 20 GET SURFACE WATER SAMPLE:

a) Locate body of water to yield a sample representative of surface deposition (e.g., lake, pond, puddle) b) Collect about 1 gallon of surface water in a labeled container (preferably plastic) c) Notify command facility of your location d) Check if additional sampling - d) lI additional sampling NOT REQUIRED required. THEN go to a low background area and wait for further instructions (periodically check with command facility).

e) RETURN TO Step 11 21 TAKE SAMPLE(S) TO COUNT ROOM FOR ANALYSIS (or designated alternate facility as appropriate) 22 TERMINATE EPIP-4.16:

  • Give completed EPIP-4.16, forms and other applicable records to the Radiation Protection Supervisor
  • Completed by:

Date:

Time:

-END-

NUMBER* ATTACHMENT TITLE REVIS ION EPIP-4.16 OFFSITE MONITORING DATA SHEET 13 ATTACHMENT PAGE 1 1 of 2 TEAM IDENTIFICATION No.:

NAME(s):

INSTRUMENT DATA:

INSTRUMENT MODEL No. SERIAL No.

MONITORING DATA:

I LOCATION DATE/ TIME DAD/SRO WINDOW OPEN I WINDOW CLOSED I READING mR/hr I mR/hr AIR SAMPLE DATA: NEXT PAGE

NUMBER ATTACHMENT TITLE REVISION EPIP-4.16 OFFSITE MONITORING DATA SHEET 13 ATTACHMENT PAGE 1 2 of 2 AIR SAMPLE DATA:

AIR SAMPLE ID.:

DATE / TIME: LOCATION:

GROSS CPM: BACKGROUND (BKG) CPM: NET CPM (GROSS - BKG):

AIR SAMPLE VOLUME (ft3):

ACTIVITY,µ Ci/ml NET CPM x Conversion Factor (from Attachment 2)

THYROID COE, mR/hr Activity,µ Ci/ml x l.57E+9 Al R SAMPLE ID.:

DATE / TIME: LOCATION:

GROSS CPM: BACKGROUND (BKG) CPM: NET CPM (GROSS - BKG):

AIR SAMPLE VOLUME (ft3):

ACTIVITY, µ Ci/ml NET CPM x Conversion Factor (from Attachment 2)

THYROID COE, mR/hr Activity,µ Ci/ml x l.57E+9 AIR SAMPLE ID.:

DATE / TIME: LOCATION:

GROSS CPM: BACKGROUND (BKG) CPM: NET CPM (GROSS - BKG):

AIR SAMPLE VOLUME (ft 3 ):

ACTIVITY,µ Ci/ml NET CPM x Conversion Factor (from Attachment 2)

THYROID COE, mR/hr Activity,µ Ci/ml x l.57E+9

.. l

  • . ' . NUMBER ATTACHMENT TITLE REVISION EPIP-4.16 FRISKER CONVERSION FACTOR 13 ATTACHMENT PAGE 2 1 of 1 CONVERSION FACTOR 10-8 9 8

7 6

5 4

3"'

2 '

9 I'\. -.....

8 7

6 5

" ~

3 4

'"' ~

2 9

8 7

6 5

4 3

2 9

8

"""I'\. -.....

7 5

6

' f'li,.

r--

4 i,,."'

3 2

9 8

7 6

5 4

3 2

3

  • 0.1

,4 5 6 7 8 9 1

2 3 4 VOLUME (cubic feet) 5 6 7 89 10 4 5 6 7 8 9 100

~

NUMBER ATTACHMENT TITLE REVISION EPIP-4.16 RADIOPROTECTIVE DRUG DOSAGE. 13

  • ATTACHMENT 3

SECTION I:

SIDE EFFECTS AND MEDICAL STATEMENT DOSAGE AND SIDE EFFECTS PAGE 1 f 1 CAUTION Potassium Iodide should not be used by people allergic to Iodine. Keep out of reach of children. In case of overdose or allergic reaction, contact a physician or public health authority.

DIRECTIONS FOR ADULT USE: One (1) tablet once a day. DO NOT take tablet for more than 10 days.

SIDE EFFECTS:

Usually, side effects occur when people take higher doses for longer periods of time. Do not take more than the recommended dose and do not take dose for longer than the time that is recommended to you. Side effects are unlikely due to low doses over short periods of time. Possible side effects are skin rashes, swelling of salivary glands, and "iodism" (metallic taste, burning of mouth and throat, sore teeth and gums, symptoms of head cold, and sometimes stomach upset and diarrhea). A few people have an allergic reaction with more serious symptoms. These could be fever and joint pains, swelling of parts of the face and body, and severe shortness of breath, requiring immediate medical attention. Taking iodide may rarely cause overactivity of the thyroid gland, underactivity of the thyroid gland, or enlargement of the thyroid gland (goiter).

WHAT TO DO IF SIDE EFFECTS OCCUR:

If side effects are severe or if you have an allergic reaction, stop taking potassium iodide and call a doctor.

SECTION I I:

Team Leader and Team Member document review of this form by checking the applicable boxes below. respectively.

Check all that apply.

Items 2 through 5 should be answered to the best of your knowledge.

1. have read Section I, "DOSAGE AND SIDE EFFECTS".
2. do not have a known sensitivity to Iodine, nor do have a medical condition that would make me reluctant to take Iodine tablets.
3. have a known sensitivity to Iodine.
4. have a medical condition that may negate my being able to take Kl tablets, e.g ..

hyperthyroidism, hypothyriodism, etc.

5. am currently taking thyroid hormone tablets.
6. am a Declared Pregnant Worker under provisions of, or hereby state my intention to declare pregnancy in accordance with, VPAP-2101, Radiation Protection Program.

TEAM LEADER NAME:  ; DATE: _ _ _ _ __

(print) (signature) 1 TEAM MEMBER NAME: DATE: _ _ _ _ __

(print) (signature)

  • NUMBER EPIP-4.21 PROCEDURE TITLE EVACUATION AND REMOTE ASSEMBLY AREA MONITORING (With 1 Attachment)

REVISION 7

PAGE 1 of 8 PURPOSE To collect personnel dosimetry, monitor station personnel evacuating from the site, and provide instructions for decontamination.

ENTRY CONDITIONS Any one of the following:

1. Activation by EPIP-4.01, RADIOLOGICAL ASSESSMENT DIRECTOR CONTROLLING PROCEDURE .
  • 2. Activation by EPIP-4.02, RADIATION PROTECTION SUPERVISOR CONTROLLING PROCEDURE.
3. Activation by EPIP-5.05, SITE EVACUATION.

ENTERED BY MAY - I 1995

,I I

8PM I AP~RECOMMENDED SNSOC APPROVAL APPROVAL EFFECTIVE DATE DATE DATE 4- '2,() -t:; 5- tgca._ 41'2.,l'i(' 5/ 1116 CHAIRMAN SNSOC STATION MANAGER

--- --- - - -- -- ---- ----- --- - - - - - -- . ~\

9505240094 950515 I PDR ADOCK 05000280 - i


~E' ----- ----- -- PDR

-- -____ _____/

1 Form No. 723758(Apr 91)

NUMBER PROCEDURE TITLE REVISION EPIP-4.21 EVACUATION AND REMOTE ASSEMBLY AREA MONITORING 7

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 2 of 8 1 INITIATE PROCEDURE:
  • By:

Date:

Time:

2 GET BRIEFING FROM RPS:

a) Determine Remote Assembly Area (RAA) to be used b) Review route to designated RAA:

  • Primary RAA: Take Rt. 650 to intersection with Rt. 628;
  • turn left onto Rt. 628; go 1.1 miles to second set of power lines
  • Secondary RAA: Take Rt. 650 to Rt. 617; turn right; go to Rt. 10 and proceed west to Community Center {right side of Rt. 10 towards Richmond) c) Review radiological conditions d) Check if parking areas are to be surveyed prior to evacuation e) Get phone number for back-up communications in case of radio failure:

f) Get radio talk group assignment:

g) Determine required monitoring equipment (e.g., portable monitoring device, frisker)

  • h) Determine dosimetry requirements

NUMBER PROCEDURE TITLE REVISION EPIP-4.21 EVACUATION AND REMOTE ASSEMBLY AREA MONITORING 7

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 3 of 8 3 GET REQUIRED EQUIPMENT:

a) Get instruments from HP emergency response storage area:

  • Do battery check
  • Check calibration sticker
  • Do response check b) Get dosimetry:
  • DAD - ON OR
  • SRO - ZEROED c} Get copies of blank Personnel Contamination Reports (PCRs}

and blank survey maps d} Get vehicle with mobile radio d) Do the following:

1) Get vehicle and portable radio.
2) Set portable radio to assigned talk group:

a) Move three position toggle switch to B.

b) Move mode selector knob to position 2, 3 or 4.

e} Check radio - OPERABLE e) GO TO Step 3.f

1) Depress mode key until AND assigned talk group is displayed (N/A for portable) Make sure to contact station upon arrival at RAA using
2) -Establish communications alternate means:

with RPS prior to leaving site

  • Security radio
  • Automatic Ringdown to TSC (Primary RAA only)
  • Commercial telephone f) Get Emergency Kit #4 from Maintenance Services Building

NUMBER PROCEDURE TITLE REVISION EPIP-4.21 EVACUATION AND REMOTE ASSEMBLY AREA MONITORING 7

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 4 of 8 4 DO SURVEY OF PARKING AREA PRIOR TO GO TO Step 5.

EVACUATION IF PREVIOUSLY DIRECTED BY RPS:

a) Monitor parking areas to determine contamination levels prior to evacuation b) Notify RPS of survey results NOTE: Attachment 1 shows location of Primary RAA and Secondary RAA.

5 GO TO DESIGNATED RAA NOTE: SRDs should be securely fastened to the accompanying TLD .

  • 6 CHECK IF RADIOLOGICAL RELEASE -

OCCURRED

.II NO release occurred, THEN do the fa 11 owing:

a) Get dosimetry from evacuees b) Have evacuees follow directions provided to the public (e.g.,

radio EBS messages), if any c) Release evacuees d) Return to station e) GO TO Step 15.

7 HAVE* EVACUEES REMAIN IN VEHICLES UNTIL SURVEYS ARE COMPLETED 8 GET DOSIMETRY FROM EVACUEES

NUMBER PROCEDURE TITLE REVISION EPIP-4.21 EVACUATION AND REMOTE ASSEMBLY AREA MONITORING 7

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 5 of 8 9 MONITOR VEHICLES AND EVACUEES:

a) Check vehicle(s) - CONTAMINATED a) GO TO Step 9.c.

b) Isolate vehicle(s) c) Check evacuee(s) - CONTAMINATED c) GO TO Step 10.

d) Record data on Personnel Contamination Reports 10 DO FOLLOW-UP ACTIONS FOR IF NO contamination on vehicles or CONTAMINATED VEHICLES(S) OR evacuees, THEN do the following:

EVACUEE(S):

1) Have evacuees follow directions a) Notify RPS of survey results provided to the public (e.g.,

radio EBS messages), if any

  • b) Ask RPS for disposition instructions:
  • Send vehicle or individual.

back to plant

2) Release evacuees
3) Notify RPS of survey results
4) Ask RPS for follow-up instructions
  • Try to decontaminate at RAA: 5) GO TO Step 13.

GO TO Step 11 OR

  • Send vehicle or evacuee to Surry County Evacuation Assembly Center for decontamination: GO TO NOTE prior to Step 12
  • Return to station: GO TO Step 13

NUMBER PROCEDURE TITLE REVISION EPIP-4.21 EVACUATION AND REMOTE ASSEMBLY AREA MONITORING 7

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 6 of 8 11 DECONTAMINATE AT RAA:

a) Check if contamination found on a) GO TO Step 11.e.

clothing b) Remove contaminated clothing c) Put contaminated clothing in poly bag d) Replace clothing with paper or plastic clothing e) Check if localized e) IF decontamination successful, contamination exists THEN do the following:

1) Have evacuees follow directions provided to the
  • public (e.g., radio EBS messages), if any
2) Release evacuees
3) RETURN TO Step IO.a.

f) Try to decontaminate using mechanic's soap g) Clean area with drying towels (diapers) h) RETURN TO Step 10

NUMBER PROCEDURE TITLE REVISION EPIP-4.21 EVACUATION AND REMOTE ASSEMBLY AREA MONITORING 7

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 7 of 8 NOTE: Attachment 1 shows the location of Surry County's Primary and Alternate Evacuation Assembly Centers.

12 DECONTAMINATE AT SURRY COUNTY EVACUATION ASSEMBLY CENTER:

a) Ask RPS for assistance to transport evacuee(s) to Surry County Evacuation Assembly Center b) Go with evacuee(s) to Evacuation Assembly Center c) Try to decontaminate evacuee RETURN TO Step 10 d) 13 MONITOR DECONTAMINATION AREA 14 CLEAN ANY AREAS FOUND TO BE CONTAMINATED 15 COMPLETE SURVEYS AND MAKE SURE THE FOLLOWING DATA HAS BEEN RECORDED ON EACH FORM:

  • Date
  • Time
  • Instrument used and serial number 16 GET ALL BAGS CONTAINING CONTAMINATED MATERIAL

NUMBER PROCEDURE TITLE REVISION EPIP-4.21 EVACUATION AND REMOTE ASSEMBLY AREA MONITORING 7

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 8 of 8

)7 RETURN TO STATION 18 TAKE DOSIMETRY TO EXPOSURE CONTROL 19 TERMINATE EPIP-4.21:

  • Give completed EPIP-4.21, forms and other records to the Radiation Protection Supervisor
  • Completed By: - - - - - - -

Date:

Time:

  • -END-

NUMBER ATTACHMENT TITLE REVISION I

  • EPIP-4.21 LOCATION OF REMOTE ASSEMBLY AREAS 7 I

ATTACHMENT PAGE 1 1 of 1 PRAA: Primary Remote Assembly Area (Under power lines, 1.1 miles east of intersection at Rt. 650 and Rt. 628)

SRAA: Secondary Remote Assembly Area (Surry Parks and Recreation Community Center) N EAC1: Evacuation Assembly Center, Surry County High School EAC2: Evacuation Assembly Center, Surry County Elementary School s

Surry Power Station

Level 2 Contro1¥aT&0I*'h~~~R

. Maintained ~lJ,ijRi; !Be~aill~~TIO N Do noi:~~sR:kMrlmlfflllf6MfiijJE1[~rtPROCEDURE NUMBER PROCEDURE TITLE REVIS ION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE (With 2 Attachments) 1 of 21 PURPOSE To provide instructions for execution of the MIDAS Class A Model.

ENTRY CONDITIONS Any one of the following:

1. Entry from EPIP-4.01, RADIOLOGICAL ASSESSMENT DIRECTOR CONTROLLING PROCEDURE.
2. Entry from EPIP-4.03. DOSE ASSESSMENT TEAM CONTROLLING PROCEDURE.
3. Direction by the Radiological Assessment Director or Radiological Assessment Coordinator.

APPROVAL RECOMMENDED SNSOC APPROVAL APPROVAL EFFECTIVE

~~

DATE DATE DATE io/~r ~~~ ,o.c;.'t8 1(:)- \~- ~~

CHAIRMAN SNSOC STATION MANAGER Form No. 723758(Apr 91)

CONTINUOUS ACTION PAGE FOR EPIP-4.30 MIDAS screens have selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that.was entered before initiating a run, or to return to a previous screen. When all information on the screen is correct, the CONFIRM ~ox i~

selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

  • ACCIDENT RUN MENU SELECTION (CONFIRM. EXIT, RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
  • RUN TYPE ANO TIME SELECTION (CONFIRM, RESET)
  • RELEASE OPTION SELECTION (CONFIRM, RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM. RESET)
  • RELEASE TIMING SELECTION (CONFIRM, RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM, EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. l£ the touch screen feature is activated, THEN use the touch screen to make entries IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:

a) Do not touch the screen when prompted to do so by the procedure.

bl Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image). which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired, THEN press the "D COPY/S COPY" key while the screen is displayed.
3. l£ a particular terminal malfunctions. THEN dose projections can be made from any one of the other terminals.
4. l.E a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

NUMBER PROCEDURE TITLE REVIS ION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 2 of 21 NOTE:
  • Dose assessments should be performed within 15 minutes after a radiological release. MIDAS may underestimate the effects of a release which begins or ends during the current 15-minute period.
  • An abnormal run is one in which a red bar containing messages that meteorological or radiation monitor data is missing appears on the screen.
  • Pressing the DIALOG key causes the terminal to display three l i'nes of text and allows the operator to read system messages during a*

run.

  • Attachment 2. Design Basis Accident Technical Overview, provides assumptions and default values used in the MIDAS code and EPIPs.

1 INITIATE PROCEDURE:

a) By: _ _ _ _ _ _ _ _ __

Date: _________ ~

Ti me: __________

b) Press START/STOP button (the top button near the lower right front of terminal) c) Ensure STOP/START button stays in the engaged position d) Press LOCK key on the keyboard e) Verify LOCK and TEK indicating e) Do the following:

lights - ON

1) Notify RAD/RAC MIDAS terminal mal functioning.

2). Initiate Attachment 1.

f) Verify MIDAS in one of the f) ll in CEOF. THEN ensure "Black following locations being used: Box" ABC switch positioned to "B" for Surry.

  • Surry HP Office
  • Surry LEOF g) Verify - INITIAL MIDAS RUN g) GO TO Step 5 .

CONTINUOUS ACTION PAGE FOR EPIP-4.30.

NOTE:

  • MIDAS screens have selection boxes th*at may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered before initiating a run. or to return to a previous screen. When all information on the screen is correct, the CONFIRM box is selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:
  • ACCIDENT RUN MENU SELECTION (CONFIRM, EXIT. RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
  • RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
  • RELEASE OPTION SELECTION (CONFIRM; RESET)
  • DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
  • RELEASE TIMING SELECTION (CONFIRM, RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM, EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. lE the touch screen feature is activated, THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) bJ Do not touch the screen when prompted to do so by the procedure.

Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image). which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired, THEN press the "D COPY/S COPY" key while the screen is displayed.
3. lE a particular terminal malfunctions, THEN dose projections can be made from any one of the other terminals.
4. lE a terminal lock-up occurs, THEN refer to Attachment 1 for response actions.

NUMBER PROCEDURE TITLE REVIS ION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE 3 of 21 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 2 DO INITIAL ASSESSMENT:

a) Press RETURN b) Verify USERNAME displayed b) lE "Local>" appears. THEN type C SMIDAS and RETURN TO Step 2.a.

l.E message "Local -715 or Local -013" appears. THEN do the following:

1) Press CTRL K keys.
2) WHEN "Local>" appears. THEN type C NMIDAS.
3) Wait for USERNAME to appear.
4) l.E USERNAME appears. THEN do the following:

a) GO TO Step 2.c.

b) Continue using manually entered monitor and met data.

l.E USERNAME does NOT appear,

  • THEN do dose assessment using manual EPIPs.

c) Type MIDAS d) Press RETURN e) Verify MIDAS in one of the e) l.E in CEOF, THEN do the following locations being used: following:

  • Surry HP Office 1) Type SU (Surry Site ID).
  • Surry LEOF 2) Press RETURN.

(STEP 2 CONTINUED ON NEXT PAGE)

CONTINUOUS ACTION PAGE FOR EPIP-4.30 MIDAS screens have* selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered before initiating a run, or to return to a previous screen. When all information on the screen is correct, the CONFIRM h,ox i~

selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

  • ACCIDENT RUN MENU SELECTION (CONFIRM, EXIT, RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
  • RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
  • RELEASE OPTION SELECTION (CONFIRM, RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
  • RELEASE TIMING SELECTION (CONFIRM, RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM, EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. l£. the touch screen feature is activated, THEN use the touch screen to make entries IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:

a) b)

Do not touch the screen when prompted to do so by the procedure.

Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key wi.11 produce light text on a -black background (reverse image). which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired. THEN press the "D COPY/S COPY" key while the screen is displayed.
3. l£. a particular terminal malfunctions, THEN dose projections can be made from any one of the other terminals.
4. l£. a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE 4 of 21 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 2 DO INITIAL ASSESSMENT: (Continued) f) WHEN the following prompt appears ENTER: [Sl] SURRY 1

[S2J SURRY 2

[Rl] SURRY 1 TREND

[R2] SURRY 2 TREND

[EX] EXIT THEN type appropriate unit (Sl or S2) g) Press RETURN h) WHEN the following prompt appears

[XX] FUNCTION OR TASK CODE

[XXX] FUNCTION AND TASK CODE

  • [ FM] FUNCTION MENU

[CTRL-ZJ EXIT THEN type TS (touch screen) i) Press RETURN j) Verify MIDAS connected to Surry j) lE. MIDAS is connected to North VAX Anna VAX (i.e .. connection made using C NMIDAS), THEN GO TO Step 6.

k) Check if quick assessment k) GO TO Step 5.

desired l) Touch REAL TIME QUICK DOSE PROJECTIONS on the ACCIDENT RUN MENU SELECTION screen m) Touch CONFIRM

  • . l

CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:

  • MIDAS screens have selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data th~t was entered before initiating a run, or to return to a previous screen. When all information on the screen is correct, the CONFIRM qox i~

selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

  • ACCIDENT RUN MENU SELECTION (CONFIRM, EXIT. RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
  • RUN TYPE AND TIME SELECTION (CONFIRM. RESET)
  • RELEASE OPTION SELECTION (CONFIRM. RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM. RESET)
  • RELEASE TIMING SELECTION (CONFIRM, RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM, EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow

.(EX VEL) for Release Point 1 is "O.OOE+OO" based on no containment release.)

  • Release Point 2: Process Vent
1. lE the touch screen feature is activated. THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) Do not touch the screen when prompted to do so by the procedure.

b) Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image). which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired. THEN press the "D COPY/S COPY" key while the screen is displayed.
3. lE a particular terminal malfunctions. THEN dose projections can be made from any one of the other terminals.
4. l£. a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

NUMBER PROCEDURE TITLE REVIS ION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE 5 of 21 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE:

  • Meteorological (MET) parameters with good values are backlit in gray with their value under the parameter name.
  • Rate of rainfall (inches per lS minutes) may be obtained from the Virginia Power Weather Center (Innsbrook. 8-730-3025). Zero (0) may be entered if data is not available; However, using 2ero during periods of rainfall may yield unrepresentative results.
  • The Stability Class letter designator (A-G) should be used in lieu of a Delta T numerical value. This is preferred because numerical values must be entered in °F. but station monitoring systems display the parameter in °C.
  • EPIP-4.10. Determination of X/0, contains instructions for getting meteorological information. e.g. inches rainfall, when on-site measurements unavailable.

__ 3 ENTER METEOROLOGICAL. DATA:

a) Check gray boxes - APPEAR a) GO TO Step 3.f.

b) Touch RAIN box C) Put in rate of rainfall (inches per 15 minutes) d) Touch CONFIRM e) GO TO Step 3.j f) Do one of the following:

  • Use LAST MET and touch each box to activate parameter
  • Touch box for each MET parameter to be entered and put in value using the NUM pad g) Verify the entered value g) Enter parameter value again.

appears under the parameter name (STEP 3 CONTINUED ON NEXT PAGE)

CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:

  • MIDAS screens have selection boxes that may include RESET, CONFIRM and EXIT. The RESET box is used to clear any data that was entered before initiating a run. or to return to a previous screen. When all information on the screen is correct, the CONFIRM qox is.

selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

  • ACCIDENT RUN MENU SELECTION (CONFIRM, EXIT, RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM. RESET)
  • RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
  • RELEASE OPTION SELECTION (CONFIRM, RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
  • RELEASE TIMING SELECTION (CONFIRM, RESET)
  • WEATHER SELECTION (CONFIRM. RESET)
  • MORE REPORTS SELECTION (CONFIRM, EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point .1 is "0.00E+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. l£. the touch screen feature is activated, THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) b)

Do not touch the screen when prompted to do so by the procedure.

Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image). which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired. THEN press the "D COPY/S COPY" key while the screen is displayed.
3. l£. a particular terminal malfunctions. THEN dose pr_ojections can be made from any one of the other terminals.
4. l£. a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

7

NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 6 of 21 3 ENTER METEOROLOGICAL DATA: (Continued) h) Ensure values for each of the following parameters are entered (touch the appropriate box and enter the value using the NUM pad as needed):
  • Delta temperature [enter letter of Stability Class (A-G) in Delta T field]:

DELTA T (o C) SIGMA THETA ( 0 ) STABILITY CLASS

~ -0.67 ~ 22.5 A (most unstable)

-0.66 to -0.60 22.4 to 17.5 B

-0.59 to -0.53 17.4 to 12.5 C

-0.52 to -0.18 12.4 to 7.5 D

-0.17 to +0.53 7.4 to 3.8 E

+0.54 to +1.41 3.7 to 2 .1 F

> +1.41 < 2.1 G (most stable)

  • Upper and lower wind speed (mph)
  • Lower wind direction (degrees)
  • Ambient temperature (°F)
  • Rain (inches per 15 minutes) i) Touch CONFIRM after all MET parameters are correctly entered (STEP 3 CONTINUED ON NEXT PAGE)

CONTINUOUS ACTION PAGE FOR EPIP-4.30 MIDAS screens have selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered before initiating a run. or to return to a previous screen. When all information on the screen is correct. the CONFIRM ~ox i~

selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

  • ACCIDENT RUN MENU SELECTION (CONFIRM, EXIT, RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
  • RUN TYPE AND TIME SELECTION (CONFIRM, RESET) .~
  • RELEASE OPTION SELECTION (CONFIRM, RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
  • RELEASE TIMING SELECTION (CONFIRM, RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM, EXIT)
  • Surry release points are assigned as follows*:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. l[ the touch screen feature is activated, THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) b)

Do not touch the screen when prompted to do so by the procedure.

Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a b1ack background (reverse image). which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired. THEN press the "D COPY/S COPY" key while the screen is displayed.
3. l[ a particular terminal malfunctions. THEN dose projections can be made from any one of the other terminals.
4. l[ a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

NUMBER PROCEDURE TITLE REVIS ION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE 7 of 21 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 3 ENTER METEOROLOGICAL DATA: (Continued) j) Verify run proceeds into j) lE Red Warning message appears calculation mode (i.e., rad monitor data invalid). THEN do the following:

1) Touch EXIT.
2) RETURN TO Step 2.j.

4 GET REPORTS:

a) Check if SPECIAL REPORT appears a) lE DATA RESULT SCREEN appears.

following calculation routine THEN touch CONTINUE multiple times to step through data results and calculation routine until the SPECIAL REPORT appears .

  • b) Make a print of SPECIAL REPORT (touch "D COPY/S COPY")

c) Touch CONTINUE d) WHEN page 1 of the RADIOLOGICAL STATUS REPORT appears, THEN press "D COPY/S COPY" e) Touch CONTINUE f) WHEN page 2 of the RADIOLOGICAL STATUS REPORT appears, THEN press "D COPY/S COPY" g) Touch MORE REPORTS h) Wait for MORE REPORTS SELECTION screen to appear (STEP 4 CONTINUED ON NEXT PAGE)

CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:

  • MIDAS screens have selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered .*

before initiating a run, or to return to a previous screen. When all information on the screen is correct. the CONFIRM box is selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

ACCIDENT RUN MENU SELECTION (CONFIRM, EXIT, RESET)

MISCELLANEOUS PARAMETERS (CONFIRM, RESET)

  • RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
  • RELEASE OPTION SELECTION (CONFIRM. RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM. RESET)
  • RELEASE TIMING SELECTION (CONFIRM, RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM. EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+OO" based on no contai~ment release.)
  • Release Point 2: Process Vent
1. l.E. the touch screen feature is activated. THEN use the touch screen to make entries IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:

a) Do not touch the screen when prompted to do so by the ~rocedure.

b) Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image), which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired, THEN press the "D COPY/S COPY" key while the screen is displayed.
3. l.E. a particular terminal malfunctions, THEN dose projections can be made from any one of the other terminals.
4. l.E. a terminal lock-up occurs, THEN refer to Attachment 1 for response actions.

t

NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE 8 of 21 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 4 GET REPORTS: (Continued) i) Check with RAD/RAC about need i) WHEN NO additional reports are for the following specific needed. THEN do the following:

reports (to support State assessments): 1) Touch EXIT twice to return to the ACCIDENT RUN MENU

  • MET. RAD, l/0. DOSE

SUMMARY

SELECTION SCREEN.

  • DOSE/DOSE RATE PLOTS
  • Additional SPECIAL REPORT 2) GO TO Step 15.
  • Additional RADIOLOGICAL STATUS REPORT j) Touch box for desired report k) Touch CONFIRM l) Check if REPORT PARAMETER 1) GO TO Step 14.

SELECTION screen appears m) Set projection time on REPORT PARAMETER SELECTION SCREEN:

1) Touch PROJ. TIME box to scroll to duration specified by RAD/RAC (Use 2-hour default duration if no duration specified)
2) Touch CONFIRM n) GO TO Step 14

CONTINUOUS ACTION PAGE FOR EPIP-4.30 MIDAS screens have selection boxes that may include RESET, CONFIRM and EXIT. The RESET box is used to clear any data that was entered C before initiating a run. or to return to a previous screen. When all information on the screen is correct. the CONFIRM b.ox is.

selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

  • ACCIDENT RUN MENU SELECTION (CONFIRM, EXIT, RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
  • RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
  • RELEASE OPTION SELECTION (CONFIRM, RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM. RESET)
  • RELEASE TIMING SELECTION (CONFIRM, RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM, EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. l£. the touch screen feature is activated, THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) bJ Do not touch the screen when prompted to do so by the procedure.

Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image), which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired. THEN press the "D COPY/S COPY" key while the screen is displayed.
3. l£. a particular termina-1 malfunctions. THEN dose projections can be made from any one of the other terminals.
4. l£. a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

. I I

NUMBER PROCEDURE TITLE REVIS ION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 9 of 21 NOTE: CHRRMS (Unit 1: RMS-127/128, Unit 2: RMS-227/228) readings may be used to select MIDAS LOCA accident type.

HOURS CONTAINMENT HIGH RANGE RADIATION AFTER LOCA MONITOR READING (R/hr) 0 ~l. 3E+4 ~4.5E+2 ~l. 54 1 ~5. OE+3 ~l. 8E+2 ~l. 3 2 ~3.7E+3 ~l.4E+2 ~1.2 4 ~2.8E+3 ~8.6E+l ~1.0 MIDAS ACCIDENT LOCA LOCA LOCA TYPE SELECTION MELT GAP PC

  • 5 DO ENHANCED DOSE ASSESSMENT WITH DEFAULT DATA:

a) Verify MIDAS system default data to be used Ci .e .. real a) GO TO Step 6.

time meteorological and radiation monitor data. and default accident isotope mix) b) Touch REAL TIME ENHANCED DOSE PROJECTIONS c) Touch CONFIRM d) WHEN the OBA ACCIDENT TYPE SELECTION menu appears, THEN touch the selection box for the accident type designated by the RAD/RAC e) Touch CONFIRM f) RETURN TO Step 3

CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:

  • MIDAS screens have *selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered .

before initiating a run. or to return to a previous screen. When all information on the screen is correct. the CONFIRM QOX is.

selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

ACCIDENT RUN MENU SELECTION (CONFIRM. EXIT, RESET)

MISCELLANEOUS PARAMETERS (CONFIRM. RESET)

  • RUN TYPE ANO TIME SELECTION (CONFIRM. RESET)
  • RELEASE OPTION SELECTION (CONFIRM, RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM. RESET)
  • RELEASE TIMING SELECTION (CONFIRM. RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM, EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. l£. the touch screen feature is activated. THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) b)

Do not touch the screen when prompted to do so by the procedure.

Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image). which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired. THEN press the "D COPY/S COPY" key while the screen is displayed.
3. 1£ a particular terminal malfunctions. THEN dose projections can be made from any one of the other terminals.
4. 1£ a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

.r

NUMBER PROCEDURE TITLE* REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE 10 of 21 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE:

  • Each input screen will appear with preselected values backlit in white. Changes are made by pressing the appropriate box and using the touch screen keypad in the upper right quadrant on the screen.

Keypad entries are entered by touching EN on the keypad. Times between midnight.and 0100 must be entered as 2400 through 2459 using the previous date.

  • Use of bad radiation monitor or source term data (equal to zero) during a previous run will require selection of a new (different) release option.

6 USE REAL TIME ALL SCREEN DOSE PROJECTIONS TO DO ENHANCED DOSE ASSESSMENT WITH OPTIONAL OPERATOR INPUT DATA:

a) Verify user input is desired a) RETURN TO Step 5.

for Release Date/Time, Release Option, Monitor Data or Sample Data b) Touch REAL TIME ALL SCREEN DOSE PROJECTIONS c ) Touch CONFIRM d) WHEN MISCELLANEOUS PARAMETERS d) Adjust choices on the screen appears. THEN verify MISCELLANEOUS PARAMETERS screen default choices are to be used per RAD/RAC instructions Touch MANUAL if manual input of weather data is desired.

e ) Touch CONFIRM

CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:

  • MIDAS screens have selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered ~

before initiating a run, or to return to a previous screen. When **

all information on the screen is correct, the CONFIRM pox i?

selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

  • ACCIDENT RUN MENU SELECTION (CONFIRM. EXIT. RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
  • RUN TYPE AND TIME SELECTION (CONFIRM. RESET)
  • RELEASE OPTION SELECTION (CONFIRM, RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM. RESET)
  • RELEASE TIMING SELECTION (CONFIRM, RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM. EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+OO" based on no containment release.)
  • Release Point 2: Process Vent
l. l£. the touch screen feature is activated. THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) b)

Do not touch the screen when prompted to do so by the procedure.

Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: C~pying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image), which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired. THEN press the "D COPY/S COPY" key while the -screen is displayed.
3. l£. a particular terminal malfunctions. THEN dose projections can be made from any one of the other terminals.
4. l£. a terminal lock-up occurs, THEN refer to Attachment 1 for response actions.

t

NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE 11 of 21 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE:

  • Run type is preset to PROJECTED (FORECAST) DOSE.
  • PROJECTION TIME (HOURS) is preset to 1, 2, 4 and 8.

7 INPUT DATE AND TIME INFORMATION:

a) WHEN RUN MODE ANO INTEGRATION a) I.E. current date/time NOT to be TIME SELECTION screen appears, used, THEN do the following:

THEN verify current date/time to be used 1) Touch START DATE OF INTEGRATION and then use the touch screen NUM pad to enter date in the format:

MO/DY/YR HR:MN. (MIDAS will provide"/" marks between the pairs of digits for month, day and year. and a colon between the pairs of digits for hours and minutes.)

2) Touch EN when entry is complete.

b) Touch CONFIRM

CONTINUOUS ACTION PAGE FOR EPIP-4.30 MIDAS screens have selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered before initiating a run. or to return to a previous screen. When all information on the screen is correct. the CONFIRM box is selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

  • ACCIDENT RUN MENU SELECTION (CONFIRM, EXIT. RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM. RESET)
  • RUN TYPE AND TIME SELECTION (CONFIRM. RESET) .-r
  • RELEASE OPTION SELECTION (CONFIRM. RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM. RESET)
  • RELEASE TIMING SELECTION (CONFIRM. RESET)
  • WEATHER SELECTION (CONFIRM. RESET)
  • MORE REPORTS SELECTION (CONFIRM. EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. 1.£. the touch screen feature is activated. THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) Do not touch the screen when prompted to do so by the procedure.

b) Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image). which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired. THEN press the "D COPY/S COPY" key while the screen is displayed.
3. 1.£. a particular terminal malfunctions. THEN dose projections can be made from any one of the other terminals.
4. 1.£. a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE 12 of 21 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE: If rad data was bad or the source term data was equal to zer.o in a previous run. a new release option must be selected different from the one previously selected.

~~ 8 SELECT RELEASE (SOURCE TERM)

OPTION:

a) Use RELEASE OPTION SELECTION screen b) Select one of the following release options:

RELEASE OPTIONS SELECTION AND TRANSITION STEPS Radiation monitor data is available 1) Touch MANUAL ENTRY OF EACH for manual entry and/or predictive MONITOR READING dose assessment is desired based on 2) Touch CONFIRM a potential release 3) GO TO Step 9 1). Touch MONITOR DATA FROM Radiation monitor data i s available V &F FILE from file 2) Touch CONFIRM

3) GO TO Step 11 Isotopic release rates are available 1) Touch MANUAL ENTRY OF for manual entry and/or predictive ISOTOPE RELEASE RATE dose assessment is desired based on 2) Touch CONFIRM a potential release 3) GO TO Step 10 Isotopic concentrations and flow 1) Touch MANUAL ENTRY OF rates of each release path are known, ISOTOPE CONCENTRATION and/or predictive dose assessment is 2) Touch CONFIRM desired based on a potential release 3) GO TO Step 10
1) Touch DEFAULT OBA ACCIDENT Design Basis Assident Default (OBA) 2) Touch CONFIRM
3) GO TO Step 11

CONTINUOUS ACTION PAGE FOR EPIP-4.30 MIDAS screens have selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered before initiating a run, or to return to a previous screen. When all information on the screen is correct. the CONFIRM Qox i$

selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

  • ACCIDENT RUN MENU SELECTION (CONFIRM. EXIT. RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
  • RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
  • RELEASE OPTION SELECTION (CONFIRM, RESET)
  • ~BA ACCIDENT TYPE SELECTION (CONFIRM. RESET)
  • RELEASE TIMING SELECTION (CONFIRM, RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM. EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "0.00E+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. 1£ the touch screen feature is activated, THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) Do not touch the screen when prompted to do so by the procedure.

b) Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image). which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired. THEN press the "D COPY/S COPY" key while the screen is displayed.
3. 1£ a particular terminal malfunctions, THEN dose projections can be made from any one of the other terminals.
4. I.E. a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6

  • STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED PAGE 13 of 21 CAUTION:
  • Double counting will occur if more than one monitor in each release pathway is entered.
  • Default flow rates will automatically be used if flow rates are not entered and may result in overconservative dose projections .

NOTE:

  • Monitor readings may be obtained from ERFCS Group Review screens if RMS data is not available to MIDAS.
  • Monitor readings from RM-VG-123 (Vent Vent High Range) or RM-GW-122 (Process Vent High Range) may be obtained from Operations if Kaman monitors (RM-VG-131 or RM-GW-130) or Victoreen monitors CRM-VG-110 or RM-GW-102) are offscale or out of service .
  • CHRRMS (Unit 1: RMS-127/128, Unit 2: RMS-227/228) readings may be used to select MIDAS LOCA accident type.

HOURS AFTER LOCA CONTAINMENT HIGH RANGE RADIATION MONITOR READING CR/hr) 0 21. 3E+4 24.5E+2 21.54 1 25.0E+3 21. 8E+2 21.3 2 23.7E+3 21..4E+2 21. 2 4 22.8E+3 28.6E+l 21.0 MIDAS ACCIDENT LOCA LOCA LOCA TYPE SELECTION MELT GAP PC 9 ENTER MONITOR DATA MANUALLY:

a) WHEN the OBA ACCIDENT TYPE SELECTION screen appears, THEN select accident type specified by the RAD/RAC (STEP 9 CONTINUED ON NEXT PAGE)

CONTINUOUS ACTION PAGE FOR EPIP-4.30 MIDAS screens have selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered before initiating a run. or to return to a previous screen. When all information on the screen is correct, the CONFIRM pox i) selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

ACCIDENT RUN MENU SELECTION (CONFIRM, EXIT. RESET)

MISCELLANEOUS PARAMETERS (CONFIRM, RESET)

  • RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
  • RELEASE OPTION SELECTION (CONFIRM, RESET)
  • DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
    • RELEASE TIMING SELECTION (CONFIRM. RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM, EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. lE the touch screen feature is activated. THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) Do not touch the screen when prompted to do so by the ~rocedure.

b) Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image). which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired. THEN press the "D COPY/S COPY" key while the screen is displayed.
3. lE a particular terminal malfunctions. THEN dose projections can be made from any one of the other terminals.
4. lE a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE 14 of 21 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 9 ENTER MONITOR DATA MANUALLY: (Continued) b ) To uc h CON F!RM c) WHEN RADIATION MONITOR READINGS screen appears. THEN do the following: *

1) Touch the box for each monitor to be entered (one at a time)
2) Enter radiation and flow values for each monitor using EN on the NUM pad (Enter monitor and flow rate values by making two entries on the NUM pad separated by a comma; e.g .. 1E6.25000 for cpm,flow rate)
3) WHEN entry for one monitor is complete. THEN repeat Step 9.c.1 through 9.c.2 unti 1 al 1 monitor data is entered d) WHEN al 1 entries have been made, THEN touch CONFIRM e) GO TO Step 12

CONTINUOUS ACTION PAGE FOR EPIP-4.30 . 1 MIDAS screens have selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered before initiating a run. or to return to a previous screen. When all information on the screen is correct. the CONFIRM b.ox i~

selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

ACCIDENT RUN MENU SELECTION (CONFIRM, EXIT. RESET)

MISCELLANEOUS PARAMETERS (CONFIRM, RESET)

  • RUN TYPE AND TIME SELECTION (CONFIRM. RESET)
  • RELEASE OPTION SELECTION (CONFIRM, RESET)
  • DBA ACCIDENT TYPE SELECTION (CONFIRM. RESET)
  • RELEASE TIMING SELECTION (CONFIRM. RESET)
  • WEATHER SELECTION (CONFIRM. RESET)
  • MORE REPORTS SELECTION (CONFIRM, EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. 1£ the touch screen feature is activated, THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) Do not touch the screen when prompted to do so by the procedure.

b) Use the "mouse" to position cross-hairs at desired location on screen.

cl Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image). which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired. THEN press the "D COPY/S COPY" key while the screen is displayed.
3. l£. a particular terminal malfunctions; THEN dose projections can be made from any one of the other terminals.
4. l£. a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE GF MIDAS CLASS A MODEL 6 PAGE 15 of 21 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED

. ?"

NOTE:

  • An input is required for each active release point.
  • Zero is an acceptable input for radiation level or flow.

~~ 10 ENTER STATION INVENTORY OR SAMPLE DATA:

a) Check if isotopic release RATE a) 1£ isotopic CONCENTRATION is to is to be used be entered, THEN do the following:

1) Select each isotope.
2) Enter concentration using the NUM pad.
3) Enter flow rate in bottom box of center column .
4) GO TO Step 10.c b) Select each isotope Enter release rates (for each selection) using the NUM pad c) Touch CONFIRM after all data c) lf a data entry error was made, has been correctly entered THEN re-enter the correct data using the NUM pad and touch CONFIRM when complete.

d) GO TO Step 12

CONTINUOUS ACTION PAGE FOR EPIP-4.30 MIDAS screens have selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered before initiating a run. or to return to a previous screen. When all information on the screen is correct. the CONFIRM box is selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

ACCIDENT RUN MENU SELECTION (CONFIRM. EXIT, RESET)

MISCELLANEOUS PARAMETERS (CONFIRM. RESET)

  • RUN TYPE AND TIME SELECTION (CONFIRM. RESET)
  • RELEASE OPTION SELECTION (CONFIRM, RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM. RESET)
  • RELEASE TIMING SELECTION (CONFIRM, RESET)
  • WEATHER SELECTION (CONFIRM. RESET)
  • MORE REPORTS SELECTION (CONFIRM. EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. lE. the touch screen feature is activated, THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) Do not touch the screen when prompted to do so by the procedure.

b) Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positinned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image). which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired, THEN press the "D COPY/S COPY" key while the screen is displayed.
3. l£ a particular terminal malfunctions. THEN dose projections can be made from any one of the other terminals.
4. l£ a terminal lock-up occurs, THEN refer to Attachment 1 for response actions.

NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE 16 of 21 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE:

  • The UNKNOWN MIX option may not appear on all OBA ACCIDENT TYPE SELECTION screens.
  • CHRRMS (Unit 1: RMS-127/128, Unit 2: RMS-227/228) readings may be used to select MIDAS LOCA accident type.

HOURS CONTAINMENT HIGH RANGE RADIATION AFHR LOCA MONITOR READING (R/hr) 0 ~l. 3E+4 ~4.5E+2 ~1.54 1 ~5.0E+3 ~l.8E+2 ~1.3 2 ~3.7E+3 ~l. 4E+2 ~l. 2 4 ~2.8E+3 ~8.6E+l ~1.0 MIDAS ACCIDENT LOCA LOCA LOCA TYPE SELECT,ION MELT GAP PC 11 ENTER ACCIDENT TYPE:

a) Verify OBA ACCIDENT TYPE a) lI accident type screen does SELECTION screen appears NOT appear, THEN GO TO Step 12.

b) Select accident type as specified by RAD/RAC:

  • FUEL HANDLING
  • WGTR (Waste Gas Decay Tank Rupture)
  • LOCKED ROTOR c) Touch CONFIRM

.! "' )

CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:* MIDAS screens have selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered before initiating a run. or to return to a previous screen. When all information on the screen is correct. the CONFIRM box i~

selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

  • ACCIDENT RUN MENU SELECTION (CONFIRM, EXIT. RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
  • RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
  • RELEASE OPTION SELECTION (CONFIRM, RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
  • RELEASE TIMING SELECTION (CONFIRM. RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM. EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "0.00E+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. l I the touch screen feature is activated. THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) b)

Do not touch the screen when prompted to do so by the procedure.

Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image)_. which may improve the resolution of ma~s/isopleths.

2. WHEN a print of an individual screen is desired. THEN press the "D COPY/S COPY" key while the screen is displayed.
3. l I a particular terminal malfunctions. THEN dose projections can be made from any one of the other terminals.
4. l I a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE 17 of 21 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 12 ENTER RELEASE TIMING SELECTION:

a) Verify NO "abnormal run" a) lE. recovering from an "abnormal occurred run", THEN GO TO Step 13.e.

b) Check if trip occurred GREATER b) IF time of trip is unknown or THAN 15 minutes ago within the past 15 minutes.

THEN GO TO Step 12.d.

c) Touch TRIP DATE box on the RELEASE TIMING SELECTION screen and enter date and time of trip using the NUM pad d) Check if ti me of start of d) GO TO Step 12.g.

release since trip is known e) Touch RELEASE START MINS SINCE TRIP box f) Enter number of minutes using the NUM pad

  • g) Check if 120 minute release duration is to be used g) IF release duration is known, THEN do the following:
1) Touch DURATION box.
2) Enter number of minutes using the NUM pad.
3) GO TO Step 12. i.

h) Touch DURATION box and enter 120 minutes using the NUM pad i ) Touch CON FIRM j) Verify run is proceeding into j) lE. meteorological data is not calculation mode and data available and the manual entry result screen appears screen appears. THEN RETURN TO Step 3.

1£. error warning messages appear. THEN touch EX IT and RETURN TO Step 2.j.

k) RETURN TO Step 4

J*

CONTINUOUS ACTION PAGE FOR EPIP-4.30 MIDAS screens have selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered before initiating a run. or to return to a previous screen. When all information on the screen is correct.* the CONFIRM Qox is selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

  • ACCIDENT RUN MENU SELECTION (CONFIRM. EXIT. RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM. RESET)
  • RUN TYPE AND TIME SELECTION (CONFIRM. RESET)
  • RELEASE OPTION SELECTION (CONFIRM. RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM. RESET)
  • RELEASE TIMING SELECTION (CONFIRM. RESET)
  • WEATHER SELECTION (CONFIRM. RESET)
  • MORE REPORTS SELECTION (CONFIRM. EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. l£. the touch screen feature is ~ctivated. THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) b)

Do not touch the screen when prompted to do so by the procedure.

Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image). which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired. THEN press the "D COPY/S COPY" key while the screen is displayed.
3. l£. a particular terminal malfunctions. THEN dose projections can be made from any one of the other terminals ..
4. l£. a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

NUMBER PROCEDURE TITLE REV'I SION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE 18 of 21 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 13 RESTART PROCEDURE FOR ABNORMAL RUN:

a) Touch REAL TIME ALL SCREENS DOSE PROJECTIONS box on ACCIDENT RUN MENU SELECTION screen b) Touch CON F!RM c) WHEN the next screen requesting run type and time selection*

information appears. THEN touch CONFIRM without making any changes d) Refer to Step 8 to select a new release option e) Wait for RELEASE TIMING SELECTION screen to appear f) Touch CONFIRM without making any changes g) Verify that the run proceeds g) IE. meteorological data NOT into the cilculation mode available and the manual entry WEATHER SELECTION screen appears. THEN RETURN TO Step 3.

h) RETURN TO Step 4

CONTINUOUS ACTION PAGE FOR EPIP-4.30 .r 1 NOTE:

  • MIDAS screens have selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered before initiating a run, or to return to a previous screen. When all information on the screen is correct. the CONFIRM oox is selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:
  • ACCIDENT RUN MENU SELECTION (CONFIRM, EXIT, RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
  • RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
  • RELEASE OPTION SELECTION (CONFIRM. RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM. RESET)
  • RELEASE TIMING SELECTION (CONFIRM, RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM. EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. lE the touch screen feature is activated. THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) Do not touch the screen when prompted to do so by the procedure.

b) Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image), which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired, THEN press the "D COPY/S COPY" key while the screen is displayed.
3. lE a particular terminal malfunctions. THEN dose projections can be made from any one of the other terminals.
4. l£. a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

NUMBER PROCEDURE TITLE* REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE 19 of 21 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE:

  • Displays may be graphic or tabular, depending on what was selected in the MORE REPORTS menu. Map features allow the user to put on or take off map overlays using function keys.
  • Instructions at the bottom of all graphic and tabular plume menus provide directions on how to move within them.
  • Graphic displays of plumes should not be used to determine emergency classifications. Instead, use the printed Special Report information.
  • Point of Interest allows the user to select specific points to determine X/0, dose or dose rate values through the location of the terminal cursor. The cursor is moved using the "joy disk" to any location and then th~ space bar is toggled to display values.

14 EVALUATE DISPLAYS:

  • a) Set map scale:
1) Do one of the following:
  • Use default distance (miles)

QR

  • Touch MAP SCALE box and enter miles of interest using NUM pad
2) Touch CONFIRM b) Check use of MAP FEATURtS - b) II use of map features is NOT DESIRED: desired. THEN GO TO Step 14. c.
1) Touch MAP FEATURES
2) Select (highlight) desired options on screen menu
3) Touch CONFIRM (STEP 14 CONTINUED ON NEXT PAGE)

CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:

  • MIDAS screens have selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered before initiating a run. or to return to a previous screen. When all information on the screen is correct. the CONFIRM .box i.s selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:
  • ACCIDENT RUN MENU SELECTION (CONFIRM, EXIT. RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
  • RUN TYPE AND TIME SELECTION (CONFIRM. RESET)
  • RELEASE OPTION SELECTION (CONFIRM, RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
  • RELEASE TIMING SELECTION (CONFIRM. RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM, EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for,Release Point 1 is "O.OOE+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. 1£ the touch screen feature is activated, THEN use the touch screen to make entries IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:

a) b)

Do not touch the screen when prompted to do so by the procedure.

Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image). which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired, THEN press the "D COPY/S COPY" key while the screen is displayed.
3. 1£ a particular terminal malfunctions. THEN dose projections can be made from any one of the other terminals.
4. l.E. a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE 20 of 21 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 14 EVALUATE DISPLAYS: (Continued) c) Check enlargement of selected c) IF use of SELECT AREA feature area of display - DESIRED: is NOT desired, THEN GO TO Step 14.d.

1) Touch SELECT AREA
2) Touch screen at two points bounding the desired area
3) Touch RESTORE when use of this function is complete d) Check use of POINT OF INTEREST d) 1£ POINT OF INTEREST feature is feature - DES IRED: NOT desired, THEN GO TO Step 14.e.
1) Touch POINT OF INTEREST, move cursor to desired location using "joy disk",

and toggle the space bar (Place mouse cross-hairs at desired point and click)

2) WHEN POINT OF INTEREST function complete, THEN move cursor to bottom right-hand corner of the plot and press the space bar (Place mouse cross-hairs at bottom right corner of plot and click) e) Touch CONTINUE f5 Touch MORE REPORTS g) RETURN TO Step 4.h

~~ 15 CHECK IF MIDAS OPERATIONS CAN BE RETURN TO Step 5.

TERM I NA TED:

  • Event - TERMINATED
  • RAD/RAC directs termination of MIDAS opera ti on

CONTINUOUS ACTION PAGE FOR EPIP-4.30 MIDAS screens have selection boxes* that may include RESET, CONFIRM and EXIT. The RESET box is used to clear any data that was entered before initiating a run, or to return to a previous screen. When all information on the screen is correct. the CONFIRM box is selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

  • ACCIDENT RUN MENU SELECTION (CONFIRM, EXIT, RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
  • RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
  • RELEASE OPTION SELECTION (CONFIRM. RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
  • RELEASE TIMING SELECTION (CONFIRM, RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM, EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "0.00E+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. lE. the touch screen feature is activated, THEN use the touch screen to make entries IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:

a) b)

Do not touch the screen when prompted to do so by the procedure.

Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image), which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired, THEN press the "D COPY/S COPY" key while the screen is displayed.
3. lE. a particular termin-al malfunctions, THEN dose projections can be made from any one of the other terminals.
4. lE. a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.

- I

~* l

)

NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 6 PAGE 21 of 21 STEP ACTtON/EXPECTED RESPONSE RESPONSE NOT OBTAINED

~~ 16 DISENGAGE SYSTEM:

a) Touch EXIT twice on the ACCIDENT RUN MENU SELECTION screen b) Press "CTRL" and "Z" keys simultaneously c) WHEN "Local>" appears, THEN type LO d) Press RETURN e) Ensure "LOGGED OFF" message appears on screen f) Press START/STOP button (the top button near the lower right front of terminal) g) Ensure START/STOP button -

DISENGAGED

~~ 17 TERMINATE EPIP-4.30:

  • Give completed EPIP-4.30, forms and other applicable records to the Radiological Assessment Director/Coordinator
  • By:

Date:

Time:

-END-

CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:

  • MIDAS screens have* selection boxes that may include RESET. CONFIRM and EXIT. The RESET box is used to clear any data that was entered ..

before initiating a run. or to return to a previous screen. When all information on the screen is correct. the CONFIRM bcx i~

selected to continue model processing. The EXIT box exits the modeling process. Selection touch screens include:

  • ACCIDENT RUN MENU SELECTION (CONFIRM, EXIT. RESET)
  • MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
  • RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
  • RELEASE OPTION SELECTION (CONFIRM, RESET)
  • OBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
  • RELEASE TIMING SELECTION (CONFIRM, RESET)
  • WEATHER SELECTION (CONFIRM, RESET)
  • MORE REPORTS SELECTION (CONFIRM, EXIT)
  • Surry release points are assigned as follows:
  • Release Point 1: Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+OO" based on no containment release.)
  • Release Point 2: Process Vent
1. 1£ the touch screen feature is activated. THEN use the touch screen to make entries IF a "mouse" is connected to the terminal. THEN do the following when instructed to touch the screen during performance of this procedure:

a) b)

Do not touch the screen when prompted to do so by the procedure.

Use the "mouse" to position cross-hairs at desired location on screen.

c) Click the "mouse" after cross-hairs are properly positioned.

NOTE: Copying may take over two minutes. Using the CONTROL key with the D COPY/S COPY key will produce light text on a black background (reverse image). which may improve the resolution of maps/isopleths.

2. WHEN a print of an individual screen is desired. THEN press the "D COPY/S COPY" key while the screen is displayed.
3. 1£ a particular terminal malfunctions. THEN dose projections can be made from any one of the other terminals.
4. 1£ a terminal lock-up occurs. THEN refer to Attachment 1 for response actions.
  • NUMBER ATTACHMENT TITLE REVISION I

EPIP-4.30 6 ATTACHMENT RESPONSE TO TERMINAL LOCK-UP PAGE 1 1 of 1 Perform the following actions. in sequence. to recover from terminal or sy'stem lock-up. The user may return to the procedure upon recovery (i.e. it is not necessary to complete the entire sequence if operation is restored).

1. Enter the letter "E" AND press RETURN.

l£. system accepts commands, THEN RETURN TO procedure.

2. Enter "CTRL Y".

l£. system accepts commands, THEN RETURN TO procedure.

3. Press "RESET" on terminal.

l£. system accepts commands. THEN RETURN TO procedure.

4. Enter "CTRL Y".

l£. system accepts commands. THEN RETURN TO procedure.

5. Turn terminal power OFF and back ON again.

l£. system accepts commands, THEN RETURN TO procedure.

6. Enter "CTRL Y" .

l£. system accepts commands, THEN RETURN TO procedure.

NOTE: The HP and CEOF terminals are normally connected to Server "A".

TSC and LEOF terminals are normally connected to Server "B".

7. Reset the MIDAS terminal servers as follows:

a) Have all users exit MIDAS.

b) Have the power cord for the affected terminal unplugged from the MIDAS terminal server (located in TSC Computer Room MIDAS Cabinet).

c) Plug the power cord back in to the MIDAS terminal server.

d) Wait for approximately 2 minutes while the server loads files from MIDAS and restarts operation. MIDAS will be out of service on at least two terminals during this time.

e) l£. system accepts commands. THEN RETURN TO procedure.

8. Connect to backup (alternate) MIDAS system:

a) Reset terminal by turning terminal power OFF and then back ON again.

b) Press CTRL K keys.

c) WHEN the "Local>" prompt appears, THEN type "C NMIDAS". Make sure to put a space between "C" and "NMIDAS".

d) Return to procedure Step 2.a)l and continue procedure using manually entered monitor and meteorological data.

9. Notify the MIDAS System Manager or Code Authority and the RAD or RAC .

NUMBER ATTACHMENT TITLE REVISION EPIP-4.30 DESIGN BASIS ACCIDENT TECHNICAL OVERVIEW 6

  • ATTACHMENT I PAGE 2 1 of 3
1. MAIN STEAM LINE BREAK:
  • Release duration: 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />. with all activity released in first 1/2 hour.
  • Release from faulted line: 2.15E+5 lb-mass/hr.
  • Release from unaffected steam lines: 0 - 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />s= 38.924 lb-mass/hr per line: 2 - 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />s= 41.296 lb-mass/hr per line.
  • Primary and secondary side activity: Technical Specification limits at onset of event.
  • Primary to secondary leak rate: Technical Specification limit, 500 gpd in affected generator. and 1440 gpd (1 gpm) total for all 3 steam generators.
  • Iodine partition factors: Faulted S/G = 1: Intact S/Gs = 0.10.
  • Condenser is assumed unavailable and the following release points apply:

Broken steam line, intact steam line relief valves, and AFWPT.

  • Activity released from broken steam line is distributed among the other 3 remaining release paths: 2 intact reliefs and AFWPT.
  • Concurrent Iodine spike is 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> in duration.
  • 10% of total activity is released via AFWPT. Steam flow to AFWPT: 40.5*

lbs/hr per horsepower. Rated power= 710 horsepower. AFWPT total steam flow= 28.755 lbs/hr.

2. STEAM GENERATOR TUBE RUPTURE:
  • Release duration: 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.
  • Tubes in the affected steam generator are uncovered at 5 minutes from event initiation, and remain uncovered for 10 minutes.
  • Iodine Partition Factor: 1.0 in affected steam generator: 0.01 in
  • unaffected generators.
  • Primary and secondary side activity: Technical Specification limits at onset of event. .
  • Primary to secondary leak rate: Technical Specific~tion limit, 500 gpd in affected generator, and 1440 gpd (1 gpm) total for all 3 steam generators.
  • Primary coolant release to affected steam generator: 108.381 lbs (0 - 30 minutes).
  • Steam release from affected steam generator: 107,395 lbs from O - 30 minutes. or 2.15E+5 lb-mass/hr.

o Steam release from intact steam generators: 0 - 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />s= 38,924 lb-mass/hr per generator: 2 - 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />s= 41.296 lb-mass/hr per generator.

  • Condenser is assumed unavailable and the following release points apply:

faulted generator relief valves. intact steam line relief valves, AFWPT.

If condenser is available, release points are as follows: steam line relief valves (3), AFWPT, Vent Vent 1. and Air Ejector. The Unit 1 Air Ejector vents through Vent Vent 1. The Unit 2 Air Ejector vents via an independent stack.

  • All activity released is distributed among the 3 main steam reliefs and AFWPT.
  • Concurrent Iodine spike is 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> in duration.
  • 10% of total activity is released via AFWPT. Steam flow to AFWPT: 40.5 lbs/hr per horsepower. Rated power = 710 horsepower. AFWPT total steam flow= 28,755 lbs/hr .

r

'NUMBER ATTACHMENT TITLE REVIS ION EPIP-4.30 DESIGN "BASIS ACCIDENT TECHNICAL OVERVIEW 6 ATTACHMENT PAGE 2 2 of 3

3. FUEL HANDLING ACCIDENT (in Fuel Building):
  • Release duration assumed for 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.
  • Fuel Pool effective Iodine partition factor of 100.
  • Release is through tbe charcoal filtration system. The filters through which the fuel building is exhausted are assumed to be 95% efficient for all species of Iodine.
  • Fuel is not moved until 150 hours0.00174 days <br />0.0417 hours <br />2.480159e-4 weeks <br />5.7075e-5 months <br /> post shutdown(= decay time).
4. WASTE GAS DECAY TANK RUPTURE:
  • Release duration assumed for 15 minutes.
  • Entire contents of tank released at 100% Technical Spe~ification limit (25.000 Ci D.E. Xe-133).
  • 1/2 of release occurs via Process Vent.
  • 1/2 of release occurs via Vent Vent.
5. LOSS OF COOLANT ACCIDENT - MELT:
  • Release duration: 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.
  • Release paths: Containment (Containment leakage) and Vent Vent 2 (ECCS leakage).
  • Containment airborne source term: 100% core Noble Gases. 25% core Iodines. *
  • Spray removal: 10 hr-1 for elemental Iodine.
  • Containment leak rate: 0.1% per day, 0 to 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> (1.3 cfm).
  • ECCS leakage: 0 gpm. 0 to 5 min.; 964 cc/hour 5 min. to 20 min.;

4800 cc/h~ 20 min to 30 days.

  • Iodine released in building atmosphere from ECCS leakage: 10%.
  • Filter efficiency for safeguards exhaust: 90% elemental Iodine.
6. LOSS OF COOLANT ACCIDENT - PC:
  • RCS concentration assumed at Technical Specification limits.
  • Safeguards filter efficiency: 90% Elemental Iodine.
  • Release duration: 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.
7. LOSS OF COOLANT ACCIDENT - GAP:
  • 3% core Noble Gases and 2% core Iodines assumed in gap.
  • Safeguards filter efficiency: 90% Elemental Iodine.
  • Release duration: 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.
8. LOCKED ROTOR:
  • Total release duration: 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.
  • Iodine Partition Factor of 100 is assumed for the condenser.
  • Steam flow to AFWPT = 40.5 lbs/hr per horsepower. Rated power 710 horsepower. AFWPT steam flow= 28.755 lbs/hr.
  • Release duration: 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.

1

. Nt!MBER ATTACHMENT TIT~E REVISION

' - EPIP-4.30 DESIGN BASIS ACCIDENT TECHNICAL OVERVIEW 6

  • ATTACHMENT PAGE

. 2 3 of 3

9. MISCELLANEOUS GENERAL ASSUMPTIONS:
  • Vent Vent: Auxiliary Building, Air Ejector(s). Safeguards (filtered).

Fuel Building (filtered). Containment Purge (filtered). Waste Gas Decay Tank area.

  • Process Vent: Waste Gas Decay Tanks, Containment Vacuum.
  • Containment leakage: MIDAS uses the higher of the two CHRRMS monitors to calculate the release.
  • Air Ejector Monitors: MIDAS adds the Air Ejector release to the associated vent vent release. *
  • Main Steam and AFWPT: MIDAS adds the flows from each "open" and "status unknown" valve to calculate the total flow for a particular steam line.

MIDAS sums the releases from all three steam lines and AFWPT to calculate the total release.

  • For Vent Vents and Process Vents. MIDAS uses the highest radiation monitor indication on the affected pathway to calculate dose projections. *
  • For "Quick Dose" defaults: Unidentified mix. ground level. all release points active. and noble gas and iodine.
  • SPS MIDAS FLOW RATES:

PATHWAY FLOW RATES VENT VENT STACK 2: Flow as indicated by FT-VS-116 (for VG-110, VG-131)

ERFCS unknown/bad Oata: o scfm MIDAS default: l. 72 E+5 scfm PROCESS VENT: Flow indicated by FT-GW-100 (for GW-130, GW-102)

ERFCS unknown/bad data:. 0 scfm MIDAS default flow: 300 scfm AIR EJECTOR: TV-SV-103 (-203) open: 25 scfm TV-SV-103 (-203) closed: O scfm TV-SV-103 (-203) ERFCS unknown/bad data: 25 scfm MIDAS default: 25 scfm CONTAINMENT: -containment pressure< 14.7 psia: 0 scfm Containment pressure> 14.7 osia: 1.3 scfm ERFCS unknown/oaa aata: C s:f~

MIDAS aefault: 1.30 scfm MAIN STEAM: The flaw for a:* valves associated witn a specific line'are summed to aetermine the rei-ease rate associated with the radiation monitor for that pathway.

SAFETY VALVES: Valve ooen or ERFCS unknown/bad data: 838,739 lb-mass/hr Valve closeo: o ATMOSPHERIC RELIEFS: Valve open or ERFCS unknown/bad data: 370.618 lb-mass/hr Valve closed: O MIDAS DEFAULT TOTAL: 3.73 E+6 lbs-mass/hr per steam line AFWPT: Flow indicated by FT-MS-100 (-200)

ERFCS unknown/bad data: 0 MIDAS default: 3.7 E+5 lb-mass/hr I