Telecopy Ro:On 830811,safety Injection Tank Boron Found Below Tech Spec Limits for Tanks T-82D & T-82B.No Cause Stated.Both Tanks Inoperable at Same Time for 1 Minute
ML20076C567
Person / Time
Site: Palisades Entergy icon.png
Issue date: 08/12/1983
From: Krich R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8308230085
Download: ML20076C567 (1)


Text

ei - --

'} R, in o ,. )

^ ^

-3, a PMBNAB BRID C7 O

1-012051C224 08/12/83 gg

, ICS IPMMVIJ MVN q) 04241 08-12 0215P CDT MVIH O ICS IPMDDGS 312 932 2500 NUCLEAR REGULATORY COMMISSION

() 1-OO9349C224 08/12/83 O TLX CONSPOWER JKN e 246 CONSUMERS POWER JACKSON MI 13:40 EDT 08-12 y

=

O PMS NUCLEAR REGULATORY COMMISSION g q% 5506 E

PALISADES PLANT SECT CHIEF E.

1 799 ROOSEVELT AVENUE y GLEN ELLEN IL 60137 O MSG

  • CeW134 VDEST: PALISADES MSGID:NRC MESSAGE O DEST: MSG CENTER MICH AVE TO:U S NUCLEAR REGULATORY COMMISSION FROM:R M KRICH O

TO: U S NUCLEAR REGULATORY COMMISSION g 799 ROOSEVELT AVENUE 'E O GLEN ELLYN, ILLINOIS [f

} ATTN: d'ALISADES PLANT SECTION CHIEF ii; F

'f ' FROM: R M KRICH, PALISADES $ L.)

CC: R B DEWITT, P-26-1178, JACKSON

](

D J VANDEWALLE, P-24-614B, JACKSON )

'l 4 THIS CONFIRMS PROMPT NOTIFICATION OF TWO OCCURRENCES REPORTABLE PER O T. S. 6.9.2.A(2). ON AUGUST 11, 1983. AT 1842, A SAMPLE FROM T-82D 0 (D SAFETY INJECTION TANK) SHOWED BORON CONCENTRATION TO BE 1719 PPM WHICH IS BELOW THE T.S. LIMIT OF 1720 PPM BORON. T-82D DORON O CONCENTRATION COLILD NOT BE RESTORED WITHIN THE ONE HOUR LIMIT OF O

) T.S. 3.3.2.A. AT 2030, AUGUST 11, 1983, SIT T-92D WAS RESTORED TO ,g OPERABILITY WITH A BORON CONCENTRATION OF 1734 PPM. g y O E.

1 ON AUGUST 11, 1983, AT 2049, WITH THE T-82D SAFETY INJECTION (SI) 3

} TANK INOPERABLE DUE TO FILL AND DRAIN EVOLUTIONS, AN ADDITIONAL E

O SI THNP- T-92B, BECAME INOPERABLE DUE TO LOW LEVEL. THIS OCCURRENCE
I OF TWO INOFERABLE SI TANKS AT THE SAME TIME LASTED FOR APPROXIMATELY ONE MINUTE AT WHICH TIME T-828 WAS RESTORED TO CPERABILITY PER O T.S. 3.3.' >

INITIAL REPOPT WAS MADE VIA THE NRL POT LINE AT 2035 FOR THE FIRST M O EVENT, AND 2106 FOR THE SECOND EVENT, ON AUGUST 11, 1983. NOTIFICAT ION TO THE NRC RESIDENT INSPECTOR WAS MADE ON AUGUST 11, 1 ": .

O c

.e c

CBW s 4O E m

1413 EST g 1425 EST J 8308230085 830812

/ PDR ADOCK 05000255 PDR gip J

IPMBNAB BRID S ~

' 7 _ _ . _ _ _ _ . _ _ _ _ - . _ _ lium 9 a swm 4_ '