ML20085F523

From kanterella
Revision as of 21:54, 16 April 2020 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
AO AO-75-1:on 741206,allowable Leak Rate Exceeded on Purge Air Supply Valve CV-1808 During Test.Caused by Lack of Sufficient Lubricant Aggravated by Unusual Svc Condition. Packing Properly Greased & Leakage Reduced
ML20085F523
Person / Time
Site: Palisades Entergy icon.png
Issue date: 01/31/1975
From: Sewell R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
Office of Nuclear Reactor Regulation
Shared Package
ML20085F525 List:
References
AO-75-1, NUDOCS 8308220168
Download: ML20085F523 (3)


Text

. _ -_-_ . _ _ - - - - - - - _ _ - - _

- - A o V V COnSum8lS Power k

%%# 4 Company (hhbi V 4 General Offices. 212 West unchegan Airpr')ve J o Machigan 492Oi . Area Code 517 7H8-0550

$ January 31, 1975

'M ,

gElldl) ['\,\

~ . ,? I .' ., .

'I La , .2

\A i

.)

k':,L:. 'l

-[.I Re: Docket 50-255 Division of Reactor Licensing License DPR-20 US Nuclear Regulatory Commission Palisades Plant Washington, DC 205h5 A0-75-1 Gentlemen:

The first abnormal occurrence report for 1975 is attached and covers a containment penetration local leak rate test.

Yours very truly, Ralph B. Sewell (Signed)

WGF/ map Ralph B. Sewell Nuclear Licensing ."i-inistrator CC: JGKeppler, USNRC i

l 8308220168 750131 l PDRADOCK05000g S

l 1179

1 O O _

i ABNORMAL OCCURRENf'E Palisades Plant 255

1. Report Number: A0-75-1 2a. Report Date: January 31, 1975 2b. Occurrence Date: December 6, 1974 (Classified as an A0 on January 20, 1975) 3 Facility: Palisades Plant, Covert, Michigan
4. Identification of Occurrence: lowable local leak rate exceeded on purge air supply valve (CV-1808),during test on December 6, 1974 and inadequacies in associated procedures.

5 Conditions Prior to Occurrence: Plant in cold shutdown.

6. Description of Occurrence: During a local leak rate test of Control Valve 1808, the operator measured a leak rate of 3 psi / minute around the packing and noted it at the bottom of the test data sheet. The leak was corrected by the operator and retested using the same data sheet. Upon completion of the test, a Test Engineer used the final (retest) results, which were acceptable, and did not observe the operator's note indicating the before-maintenance leakage.

On January 20, 1975, the Test Engineer received the test data and observed the before-maintenance note. A resultant calculation showed the leak rate to be unacceptable.

7 Designation of Apparent Cause of Occurrence: Lack of sufficient lubricant aggravated by unusual service condition.

8. Analysis of Occurrence: The Test Engineer, upon reviewing the tests on January 20, 1975, discovered the operator's note and recalculated the leak rate. The new calculation yielded a before-maintenance leak
rate of 283,421 cc/ minute which exceeded the leak rate limit. The after-maintenance data resulted in a leak rate of 509 cc/ minute after the packing was greased and reinstalled.

i l 9 Corrective Action: The following corrective action has or is being l taken:

a. The packing was properly 6reased and the leakage reduced to an acceptable level.
b. The Local Leak Rate Testing Procedure will be modified to identify "before-maintenance" and "after-maintenance" leak rate data.

l

O O ,

. ABNORMAL OCCURRENCE Palisades Plant 255-(Contd) 9 Corrective Action: (Contd) l c. The Penetration Testing Procedure will contain a leak rate guide-line to indicate whether or not the recorded data approaches or exceeds a predetermined limit.

d. A preventative maintenance program has been established to deter-mine an appropriate greasing schedule for valves susceptible to this type of problem.