ML20085F707

From kanterella
Jump to navigation Jump to search
Updated AO AO-74-11 Revising Analysis of Occurrence.Loss of Dc Control Power to Bus 1D Feeder Breaker 72-203 Results in Breaker Not Being Able to Operate If Equipment Malfunctions
ML20085F707
Person / Time
Site: Palisades 
Issue date: 09/19/1975
From: Sewell R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
Office of Nuclear Reactor Regulation
Shared Package
ML20085F712 List:
References
AO-74-11, NUDOCS 8308230145
Download: ML20085F707 (1)


Text

,

O O

Ox Consumers l (~ ;

(

Br QQ) por:

Campany ww General Officeas 212 West Michigan Avenue, Jackson. Micnigan 49201. Area Code 517 788 OSSO Septemb'ei-19,'1975 e

4 h.

j g.

2 SEP 2 21975

  • r

" TU,s'l$^" I Division of Reactor Licensing I-

"'5"""

US Nuclear Regulatory Commission Washington, DC 20555 d

m DOCKET 50-255, LICENSE DPR-20 PALISADES PLANT On August 28, 1974, we transmitted a final report regarding an abnormal occur-rence (Th-11) at the Palisades Plant. This abnormal occurrence involved a loss of d-c control power to Bus 1D feeder breaker, Breaker 72-203. The Safety and Audit Review Board subsequently reviewed this report and concluded that there were some related Ufects which vere not obvious that should have been explicitly described in the report. The purpose of this letter is to provide that explicit description.

Item 8, Analysis of Occurrence, is revised as follows to explicitly delineate the related affects:

The loss of d-c control power to Bus 1D feeder breaker results in the breakers not being able to operate in case of equipment malfunction. With no alarm resulting from loss of control power, the operator may not be aware of the i

situation.

In addition, high-pressure safety injection pumps P66A and P66C, LP safety ejection pump P67A and containment spray pump P5hA vould not have actuated automatically if required during this loss of d-c control power.

The redundant counterparts of this equipment, which are powered from different buses, were available for automatic actuation. The design of the plant is such that the remaining components capable of automatic actuation would be sufficient in the event of a Loss of Coolant Accident. Not withstanding the above, the plant was in a cold shutdown condition during this occurrence.

Thus, there was no risk to health and safety of the public, f

pfQ LLL Halp B. Sewell Nuclear Licensing Administrator O

CC: JGKeppler, USNRC File 1005'O 8308230145 750919 PDR ADOCK 05000255 g

PDR COPY SBNP REGION _-