- l n

n

$h 'b' s

/

e;;=%4 Consumers q fnf. pJ s t

p un11975 = d i4bQ~.- / Com r Power (v) q

,A,

(% (W,*twet, anA,g" "

[,n.y D

V Generas omce.

sacason, u.chegan 4 9201. A*f 3 Code 517 7 HH-OSSO 2t I

March 27, 1975 Division of Reactor Licensing Re: Docket 50-255 US Nuclear Regulatory Commission License DPR-20 Washington, DC 20555 Palisades Plant A0 h-75 Gentlemen:

On March 17, 1975 Consumers Power Company submitted A0 4-75 concerning seiefe restraints on viving syste=3 at the Palisades Plant.

Since submittal of that report, the review of safety-related and shut-down cooling systems has been completed. The installation and/or modi-fication of restraints will be completed this evening (March 27,1975).

This letter is written to update the March 17, 1975 report to reflect action taken during the past ten days.

Item 8, " Analysis of Occurrence," is revised to read as follows:

(3 O

"8.

Analysis of Occurrence:

It has been determined that 102 new restraints, 12 restraint replacements and 74 restraint modifications were required or added for additional conservatism.

Of the 188 total, 66 were on lines 2-1/2" and larger, and 122 on lines 2" and smaller.

The systems (complete or portions of) studied are as follows:

a.

High-and low-pressure safety injection systems both inside and outside containment.

b.

Critical service water system both inside and outside contain-ment through isolable branch connections.

c.

Component cooling vater outside containment.

d.

Chcrging system.

e.

Concentrated boric acid system.

f.

Air room purge and containment air purge outside containment.

g.

Containment spray.

/

h.

CVCS letdown system through flow control valves.

(

)

1.

Fuel oil to the emergency diesels.

3390 8220111 750624 p

ADDCK 05000g55 J0'[(gf PDR

'W

'h COPY SENT REGION-

O O

Division of Rezctor Licensing 2

Palisades Plant March 27, 1975 l

"j. Connections to the primary loop through the isolation valves.

k.

Auxiliary feed-water system.

1.

Gas decay tank connections.

m.

Diesel generator auxiliary systems.

j n.

High-pressure air to the safeguard valves.

" Based on the review performed, it is our judgment that opera-tion without these restraints would not have resulted in a loss of functional integrity of the shutdown cooling system or ESS systems during a seismic occurrence."

Item 9, " Corrective Action," is revised to read as follows:

i "9

Corrective Action: Each of the safety-related and shutdown cooling systems (see Item 8) have been reviewed. New restraints and modifications to existing restraints identified will be in-stalled prior to resuming reactor critical operations.

i i

"The Plant Review Committee has reviewed the work effort involved j

in correcting this abnormal occurrence including the logic of selection of systems for detailed review. Based on this review, they concluded that the systems required for shutdown of the plant l

will operate as designed."

Yours very truly, j

Ralph B. Sewell (Signed)

I RBS/mel Ralph B. Sewell CC: JGKeppler, USNRC l

l t

i 1

l l

L