O

'O' gs '#

e c

WU AGCY WHEA VEES 66(8921)(2-es7622C153)PD'87/92/75 8917 Opf N-[/jd')~<[

WUA 18s DL

!!A CDT TLX CONSPOWER JKN

, g,_

ZCZC.984 DLY JACKSON MICHIGAN gE2'-75 doMg joa PNS USNRC g

MR J G-KEPPLER 6s137 ( ' qg#

'j7g 799 ROOSEVELT RD GLEN ELLYN, IL THIS TVX IS TO CONFIRM OUR TELEPHONE CONVERSATION WITH K BAKER ON 7-1-75 IN RE0ARD (O AN ABNORMAL OCCURRENCE " FAILURE OF BUS 1D TO FAST TRANSFER FROM STATION TO START-UP POWER" AND AN UNUSUAL EVENT "9 INCH DEVIATION ON CONTROL ROD 38."

THESE REPORTS HAVE OUR CODE NUMBERS OF A0 75-14 AND UE 75-4 RESPECTIVELY.

THE LACK OF A FAST TRANSFER HAS BEEN IDENTIFIED TO BE A FAULTY AUXILIARY CONTACT ON AN INCOMING BUS BREAKER.

THE 9-INCH DEVIATION RESULTED FROM A SHORTED PHASE SHIFTING CAPACITOR IN THE MOTOR DRIVE CIRCUIT.

THE FORMAL REPORTS WILL FOLLOV FRON OUR GENERAL OFFICE.

CC RBSEVELL RLHAUETER J G LEWIS PALISADES NUCLEAR PLANT CONSUMERS POWER COMPANY ALL CH h$h0$$0h 050 0 s

3 WU MVN ILL es