ML20086E346

From kanterella
Revision as of 15:22, 15 April 2020 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
AO 75-03:on 750204,spray Sys Pump Discharge Pressure Sensor PS-14-44A Actuated at 82 Psig,Below Tech Spec Min. Sensor Replaced & Calibr
ML20086E346
Person / Time
Site: Vermont Yankee Entergy icon.png
Issue date: 02/05/1975
From: Riley B
VERMONT YANKEE NUCLEAR POWER CORP.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20086E261 List:
References
AO-75-03, AO-75-3, VYV-3642, NUDOCS 8312060464
Download: ML20086E346 (1)


Text

v ,

~

O n v

N..m VERMONT YANKMM NUCLEAR POWER CORI?OR ATION

'\K SCVENTY SCVEN OROVC STRCCT RUTLAND, VP.ICMONT 05701 VYV-3642 P.O. BOX 157

- .VCRNON, VCRMONT oS354 February95, 1{ 7.5C.

2 % x/

D), (\O

,~

$ s'h \k $ $

Director ~ gg ';{/5 > ;S Directorate of Regulatory Operations, Region I t'

. h .

United States Atomic Energy Commission 1

, " EM Nt' "

631 Park Avenue *

, g {'.l, g /

King of Prussia, Pennsylvania 19406, A -

v,

'. ~

b' W

h. .

REFERENCE:

Operating License DPR-28 .

Docket No. 50-271

~

- Abnormal Occurrence No. A0-75-03 (24 Hour Report)

Dear Sir:

? .

f - As defined by Technical Specifications for the Vermont Yankee Nuc1 car vnuar n e n H . .n . nc,tfon 6.7. we are reporting the following Abuormal

. Occurrence as A0-75-03 and confirming our telephone conversation with l .,your office.

At approximately 0930 on February 4, 1975, while performing a monthly.

. functional tcat on the Core Spray System, the-Core Spray System Pump Discharge Pressure sensor PS-14-44A actuated at 82 psig. Table 3.2.1 of

- the Technical Specifications requires that the trip level setting of tiiis censor be set at >100 psig.

Failure of this sensor to actuate at the  :

specified trip level setting resulted in fewer operable instrument channels-

- per trip system than that required by Tabic 3.2.1 cf the Technical Specifications. Functionally, this sensor operates as a pressure permissive

]

. in the Automatic Depressurization System indicating the fact that a core {

spray pump is running. ,

j The sensor was immediately replaced and the trip icvel setting adjusted ~

'to,110 +5 psig which precluded the necessity of performing the ' action

[. specified in Note 2 of Tabic 3.2.1 of the Technical-Specifications. The e

plant was operating at full power at the time of the discovery of this .

. . occurrence. .

Very truly yours, 8312060464 750214 r aoo"

. g.g 9 , pf,q Bradford W. Riley .. c -

3 (

Plant Superintendent T.

' HE/kbd

.. 11913

-_ ' myy aggr REMON - - ~_

[ m a_

_