ML070780372

From kanterella
Revision as of 17:44, 13 March 2020 by StriderTol (talk | contribs) (StriderTol Bot change)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
CR-PNP-1996-09593, Crack in Housing for MO-1001-34A
ML070780372
Person / Time
Site: Pilgrim
Issue date: 11/27/1996
From:
Entergy Corp
To:
Office of Nuclear Reactor Regulation, NRC/OGC, NRC Region 1
References
CR-PNP-1996-09593
Download: ML070780372 (5)


Text

I

~

Entergy CONDITION REPORT CR-PNP-199609593 Originator: CONVERTED DATA Originator Phone: 0 Originator Group: CONVERTED DATA Operability Required: N Reportability Required: N Supervisor Name: CONVERTED DATA Discovered Date: I 1/27/1996 0O:OO Initiated Date: 11/27/1996 0O:OO Condition

Description:

DURING SHOP WORK ON THE OLD MOV HOUSING FOR MO-1001-34A, A CRACK WAS FOUND ON ONE WPPER HOUSING FLANGE BOLT HOLE. THE ACTUATOR HOUSING WAS BEING REFURBISHED PER P2403876 FOR RE-USE AS MO-1201-85 IN RFO #I I.

Immediate Action

Description:

Suggested Action

Description:

EQUIPMENT:

Tag Name Tag Suffix Name Component Code Process System Code 99 REFERENCE ITEMS:

TvPe Code Description CONVERTED PR PR.96.9593

' I I I 1 ADMIN CR-PNP-1996-09593 Initiated Date: 11/27/1996 0:OO Owner Group :CA&A Staff Current

Contact:

WALKER, J.

Current Significance: D - ADMIN CLOSE Closed by: WALKER, J. 12/4/1996 0:OO I ~

Summary

Description:

DURING SHOP WORK ON THE OLD MOV HOUSING FOR MO-1001-34A9A CRACK WAS FOUND ON ONE UPPPER HOUSING FLANGE BOLT HOLE. THE ACTUATOR HOUSING WAS BEING REFURBISHED PER P2403876 FOR RE-USE AS MO-1201-85 IN RFO #11.

Remarks

Description:

MOV HOUSING MO-1001-34A P9403876 MO-1201-85 LIMITORQUE ACTUATOR Closure

Description:

EVALUATION COMPLIANCE REVIEW EVALUATION AND CORRECTIVE ACTION COMPLETE.

Entergy ASSIGNMENTS CR-PNP-1996-09593 Version: 1 Significance Code: D - ADMIN CLOSE Classification Code: NON-SIGNIFICm Owner Group: CA&A Staff Performed By: Shatas,Albert A 11/27/1996 0O:OO Assignment

Description:

SCREEN IAW NOP92A1

Enterrrv I CORRECTIVE ACTION I CR-PNP-1996-09593 CA Number: 1 I__

Group l__ __I ~

r-I

-- -- Name Assigned By: CA&A Staff SHATAS, A.

Assigned To: CA&A Staff Shatas,Albert A Subassigned To :

~

Originated By: SHATAS, A. 11/27/1996 0O:OO:OC Performed By: SHATAS, A. 11/27/19960O:OO:OC Subperformed By:

Approved By:

Closed By: SHATAS, A. 11/27/19960O:OO:OC Current Due Date: 12/04/1996 Initial Due Date: 12/04/1996 CA Type: GENERAL Plant Constraint: NONE CA

Description:

SCREEN IAW NOP92A1

Response

CONVERTED DATA Subresponse :

Closure Comments:

PAC APPROVED NOP92A1 EXHIBIT 3

CORRECTIVE ACTION I CR-PNP-1996-09593 CA Number: 2 r--- Name I Assigned By: Regulatory & Industry Affairs Staff KEENE, J.

Assigned To: Regulatory & Industry Affairs Staff Haladyna,Robert A Subassigned To :

Originated By: KEENE, J. 11/27/19960O:OO:OC Performed By: HALADYNA, R. 12/30/19960O:OO:OC Subperformed By:

Approved By:

Closed By: KEENE, J. 12/30/19960O:OO:OC Current Due Date: 12/10/1996 Initial Due Date: 12/10/1996 CA Type: GENERAL Plant Constraint: NONE CA

Description:

CONDUCT A 10CFR50.73 REVIEW FOR THE CONDITIONS IDENTIFIED IN THIS PROBLEM REPORT.

Response

CONVERTED DATA Subresponse :

Closure Comments:

COMPLETE 10CFR50.73REVIEW.

10 CFR 50.73 REPORTING APPLICABLE? NO BASIS: THE PROBLEM REPORT IS NOT REPORTABLE BECAUSE IT DID NOT MEET THE REPORTING THRESHOLD ESTABLISHED IN 10CFR50.73 AND IT IS NOT A REPEAT OCCURRENCE. THE PROBLEM WAS EVALUATED REGARDING POSIBLE OVERTHRUST OF VALVE MO- 1001-34A WHILE THE HOUSING OPERATOR WAS INSTALLED ON MO-1001-34A. IN

SUMMARY

, THE EVALUATION CONCLUDED THERE WAS NO ADVERSE IMPACT ON VALVE MO-1001-34A WHILE THE OPERATOR WAS INSTALLED ON MO-1001-34A.

(NCR 96-44 ALSO DOCUMENTED THE PROBLEM FOR MO-1201-85).