ML17146A268

From kanterella
Revision as of 16:46, 4 February 2020 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Proposed Tech Specs,Reflecting Incorporation of Fifth Diesel Generator Into Plant Design
ML17146A268
Person / Time
Site: Susquehanna  Talen Energy icon.png
Issue date: 02/10/1986
From:
PENNSYLVANIA POWER & LIGHT CO.
To:
Shared Package
ML17146A267 List:
References
NUDOCS 8602140058
Download: ML17146A268 (203)


Text

ATTACHMENT 2 8602240058 8602%0

'PDR ADOCK 05000387 .

P . . PDR

INSTRUMENTATION FIRE DETECTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION 3.3.7.9 As a minimum, the fire detection instrumentation for each fire detection zone shown. in Table 3.3.7.9-1 shall be OPERABLE.,

APPLICABILITY: Whenever equipment protected by the fire detection instrument is required to be OPERABLE.

ACTION:

With the number of OPERABLE fire detection instruments less than the Minimum Instruments OPERABLE requirement of Table 3.3.7.9-1:

a. Within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, establish a'fire watch patrol to inspect the zone(s) with the inoperable instrument(s) at least once per hour, unless the instrument(s) is located inside an inaccessible zone, then inspect the area surrounding the inaccessible zone at least once per hour.
b. The pr ovisions of Specifications 3. 0.3 and 3. 0. 4 are not applicable.

SURVEILLANCE RE UIREMENTS 4.3.7.9. 1 Each of the above required fire detection instruments which are accessible during unit operation shall be demonstrated OPERABLE at least once per 6 months by performance of. a CHANNEL FUNCTIONAL TEST. Fire detectors which are not accessible during unit operation shall be demonstrated OPERABLE by the performance of a CHANNEL FUNCTIONAL TEST during each COLD SHUTDOWN exceeding 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> unless performed in the previous 6 months.

4.3.7.9.2 The supervised circuits supervision associated with the detector alarms of each of the above required fire detection instruments shall be demonstrated OPERABLE at least once per 6 months.

SU.".,~UFHANtlA " UNIT 1 3/4 3"77 Amendment No. 26

TABLE 3.3.7 '-1 FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCATION INSTRUMENTS OPERABLE PHOTO-FIRE ZONE 0-24D 0-240 C~ ROOM OR AREA ntrol Buildin Lower Relay PGCC Room E EY.

698'"1" 698'-1'I HEAT TOTAL iMIN.

4, 54 2

27 IONIZATION TOTAL MIN.

4 30 2

15 ELECTRIC TOTAL MIN.

NA NA HA HA 0-25E Lower Cable Spreading Rm. 714'-0" 26 13 6 3 NA HA 0"25A Lower Cable Spreading Rm. 714'-0" 20 10 6 3 NA iVA 0-26H Control Rm.

'5 (Under Flr. Unit 1)" 729 '1" NA NA 18 9 NA NA 0-26H Control Room (Under Flr. Unit 2)" 729'"1" NA NA 8 ,A ,A I 0-26H Control Room 729'-1" NA NA 10 5 HA NA 0-26H Control Rm. (Above Clg)" 729'-1" NA NA. 9 ,5 NA NA 0-27C Upper Cable Spreading Rm. 753'-0" 29 15 NA NA 0-27B Upper Cable Spreading Rm. 753i Qll 28 14 5 3 NA NA 0-27E Upper Relay Room 754'-1" 4 2 2 1 NA HA 0-2?E PGCC 754'-1" 55 28 30 15 HA iVA 0-28K Battery Room 7711 Qll NA NA 1 1 HA NA 0;28L Battery Room 771'0 NA HA 1 1 NA NA 0-28M Battery Room 771'-0" NA NA 1 1 NA NA 0"28N Battery Room 771'-O'I NA NA 1 1 NA NA 0-28I Battery Room 771'-0" HA NA 1 1 HA NA 0-28J Battery Room 771'"0" NA NA 1 1 HA NA 0-28G Battery Room 771'-0" NA HA 1 1 NA HA 0-28F Battery Room 771'0" NA NA 1 1 NA NA 0-28E Battery Room 771'-0" NA NA 1 1 HA NA 0-28C Battery Room 771'-0" NA NA 1 1 NA NA 0-28D Battery Room 7711 Oil NA NA 1 1 NA NA 0"28T Battery Room 771'-0" NA NA 1 1 HA NA SUS(UEMANNA " UNIT 1 3/4 3-78 Amendment No. 36

TABLE 3.3.7.9-1 (Continued)

FIRE OETECTION INSTRUMENTATION INSTRUMENT LOCATION 'NSTRUMENTS OPERABLE PHOTO-FIRE HEAT ION IZATION ELECTRIC ZOHE ROOM OR AREA ELEV. TOTAL MIN. TOTAL MIN. TOTAL MIN.

0-22A Filter Area 687'8" HA HA 11 6 NA HA 0-268 South Cable Chase 729'-1" HA HA 1 1 NA HA 0-,26C Center Cable Chase 729'-1" NA NA 1 1 NA NA 0-260 North Cable Chase 729'-1" NA HA 1 1 NA NA 0-26F Vestibule 729'1" PA HA 1 1 NA NA 0-26G Shift Office 729'1" NA NA 1 1 NA NA 0-26J Vestibule 729'1" NA NA 1 1 NA HA 0-26M 'offit 729'1" HA HA 4 2 NA NA 0-26H Control Soffit 7293 "1'I 0-26P Control

=Room Room Soffit 729'-1" NA NA 'A NA 2 2

1 1

NA NA NA NA 0"26R Soffit 729'1" . NA NA 4 2 NA NA 0"26S South Cable Chase 729'-1" 1 1 NA HA NA NA 0-26T Center Cable Chase 729'-1" 1 1 HA HA HA NA 0-26V Horth Cable Chase 729'1" 1 1 NA HA NA -

NA 0-27F South Cable Chase 754'1" 1 1 NA NA NA NA 0-27G Center Cable Chase 754'-1" 1 .1 NA NA NA NA 0-27H Horth Cable Chase 754'-1" 1 1 NA HA NA NA 0-28A Equipment Room 771'"0" NA NA 2 NA NA 0-288 'Equipment Room ?71'-0" NA NA 2 NA HA 0-28H Repair Shop 771'-0" NA NA 2 1 NA NA 0-28P South Cable Chase 771'-0" 1 1 NA HA NA NA 0-28R North Cable Chase 771'-0" 1 1 NA HA NA NA 0"29B HBV Equipment Room 783'"0" NA 'NA 10 5 0-30A HVAC Equipment Room 8063-0" NA NA 20 10 NA NA 0"25B South Cable Chase 714'-0" 1 1 NA HA NA NA 0-25C Center Cable Chase ?14'-0" 1 1 NA NA NA HA 0-250 North Cable Chase 714'-0", 1 1 NA HA NA NA 0-28Q Center Cable Chase 771'-0" 1 1 NA HA NA NA 0-26I Operational Support Center 729 I ill NA NA 1 1 NA NA SUSQUEHANNA " UNIT 1 3/4 3"78$ Amendment No.36

0 TABLE 3. 3. 7. 9-1 (Continued)

FIRE OETECTION INSTRUMENTATION INSTRUMENT LOCATION INSTRUMENTS OPERABLE PHOTO-FIRE HEAT IONIZATION I ELECTR C.

ZONE ROOM OR AREA ELEV. TOTAL MIN. TOTAL MIN. TOTAL MIN.

.~ll 8 l1 1-18 Core Spray Pump Room 645'-0" NA NA 5 3 NA NA 1" 1A Core Spray Pump Room 645'-0" NA NA 7 4 NA NA 1-1E RHR Pump Room 645'-0" HA HA NA NA 13  ?

1-1F RHR Pump Room OII HA NA NA NA 15 8 1-10 RCIC Pump Room 645'-0" 2 1 NA NA 5 3 1-1C HPCI Pump Room 645'-0" 2 1 HA NA 7 4 1" 1G Sump Room 645 I OII NA HA 2 1 NA NA 1-28 I II Access Area 670 0 NA NA 7 4 NA NA 1-5A Fuel Pool Pumps and-Heat Exchangers 749 I

] II HA NA 22 ll 1-20 Remote Shutdown Panel Rm. 670'-0" HA NA 2 1 NA NA 1"4C Swi'tchgear Room 719'-0" HA 'A 2 NA HA 1-40 Switchgear Room 719'-0" NA NA 2 1 NA NA 1" 4A Containment Access Area 719'-0" NA NA 27 14' 2.

1-5F Load Center Room 749'-1" NA NA 1 NA NA 1"5G Load Center Room 749'-1" NA NA 2 1 NA NA 1-2A Access Area 670'-0" NA NA 7 4 NA NA 1-3A Access Area 683'-0" NA NA 7 4 NA NA 1-38 Access Area 683'-0" NA NA 12 6 NA NA 1"3C I Oll Access Area 83 HA NA NA NA 13 7 1-48 Pipe Penetration Room 719'-1" .NA NA 1 1 NA NA 1-4G I Main Steam Pip'ing 719 11I NA NA HA NA 6 3 1"58 Valve Access Area 761'-10" NA NA NA NA 2 1 1-50 RMCU Pumps 8 Heat Exchangers 749'-1" NA NA NA NA 12 6 1-5E Penetration Room 749'"1" NA NA NA NA 2 1 1-6A Access Area 77g I 1II NA NA 9 5 NA NA 1-6I Fuel Pooling Holding Pump Room 779'-1 NA . NA NA SUS(UEHAHNA - UNIT 1 3l4 3"79 < Amendment No. 36

TABLE 3 3. 7.

~ 9-1 (Continued)

FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCATION INSTRUMENTS OPERABLE PHOTO-FIRE HEAT IONIZATION EI ECTRIC ZONE ROOM OR AREA ELEV. TOTAL MIN. TOTAL MIN. TOTAL MIN.

Reactor Bui 1 din Continued) 1-60 H&V Equipment Room 779'1" NA NA 12 6 NA NA 1-6E Recirculation Fans Area 779'1" NA NA 2 1 NA NA 0"6G Surge Tank Vau1t 779'"4" NA NA 2 1 NA NA 1-7A H&V Fan and Filter Rooms 799'-1" 24 12 15 8 NA NA 0"8A Refueling Floor. 818'1" NA NA NA NA 59 30

~EWIIP h 0-51 '

Pump Room 685'"6" NA NA 6 NA NA 0" 52 Pump Room 685'"6" NA NA 6 3 NA NA-INFRA-RED (FLAME)

TOTAL MIN.

d. Diesel Generator Buildin 0" 41A Diesel Generator Rooms 660'-0" N

and 677'"0" 22 11 2 1 15 8 0" 41C Diesel Generator Rooms 660'-0" and 677'-0" 22 11 2 1 15 8 0-41B Diesel Generator Rooms 660'-0" and 677I Oll 23 12 2 1 15 8 0-41D Diesel Generator Rooms 6600"0" and 677'-0" 22 11 2 1 15 8 Q,egal G,e,~~a~ E QviLding Xgt4-W~

fhXQ o-'ii,E.. Yi<+mi &me>>a4>> gem s. I iS and ~ZS -4 Nh M1 3 and 70/'-0' Ah i"P 4, "Not accessible.

\

SUS(UEHANNA - UNIT 1 3/4 3-80 Amendment No.36

SPRAY ANO SPRINKLER SYSTEMS LINVINC CONDITION FOR OPERATION 3.7.6.2 The followfng spray and sprinkler systems shall be OPERABLE:

RCIC Pump Room, Unft 1

b. HPCI Pump Room, Unit 1 Upper Cable Spreadfng Room, Unft 1 Lower Cable Spreading Room, Unft 1 ee Ofesel'enerator A Roea Diesel Generator 8 Ro'om .

ge Ofesel Generator C Rool

b. Dfesel Generator 0 Room Ffre Zones 1-3A and 1-38 Fire Zone 1-4A
k. Ffre Zone 1-5A Fire Zone 1-28 Fire Zone 0-298 S86 ne Fire Zone 0-,30A N~f

~yq ct ~

h w APPLICABILITY: Whenever equfpment protected by the spray and/or sprfnkler I 1 PEIMBLE.

ACT'fbii:

a.: With one or more of the above required spray and/or sprinkier systems inoparab1e, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> astabiish a continuous tire watch with backup i'ire suppression aquipmant d'or those areas in which redundant systems or components could be damaged; for other areas, establish an hourly fire watch patrol. l>>

b. The provfsfons of Specfffcatfon 3.0.3 and 3.0.4 are not applfcable.

rusmnr A Ci, ~~SQ QeitCraker P Phuslhin9 >

Hrr. ~ 0- fl<

SUS)UEHANNA - UNIT 1 3/4 7-19 Amendment No. 36

SURVEILLANCE RE UIREHENTS 4.7.6.2, Each oP the above required sPray and sPrfnkler systems shall be demonstrated

'f."least OPERABLE:

a. once pir 31 days by verifyfng that each valve, manual powe~ operated or automatic, fn the flow path fs in its correct position.
b. At least once per L2 months by cycling each testable valve in the flow path through at least one complete cycle of full. travel.
c. At least once per M months:
l. . By performing a system functfonel test which includes sfmulated automatic actuation of the system, and:

a) Verffyfng that the automatic valves fn the flow'path actuate to their correct positions on a test signal, and.

b) Cyclfng each valve fn the flow path that fs not testable durfng plant operation through at least one complete cycle of full .travel.

2- By a visual inspection of the dry pipe spray and sprfnkler headers to verify their fntegrfty, and

3. By a visual fnspectfon of each deluge nozzle's spray area to verify that the spray pattern fs not obstructed.
d. At least once per 3 years by performfng an afr or water f1ow test through each open head spray and sprfnkler header and verffyfng each open head spray and sprfnkler nozzle fs unobstructed.

SUSQUEHANNA - UNIT l 3/4 7-20 Amendment No- 36

FIRE HOSE STATIONS LIMITING CONOITION FOR OPERATION 3.7.6.$ The.ffre hose stations shown in Table 3.7.6.5-1 shall be OPERABLE.

APPLICABILITY: Whenever equipment fn the areas protected by the fire hose I EIIE I.E.

ACTION:

85th one or more of the fire hose stations shown fn Table 3.7.6.5-1 inoperable, route an additional fire hose of equal or greater diameter to the unprotected area(s) from an OPERABLE hose station wfthfn 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> .

ff the inoperable fire hose fs the primary means of fire suppression; otherwfse, route the additional hose within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

~

b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE RE UIRENENTS 4.7.6.5 Each of the fire hose stations shown. in Table 3.7.6.5-1 shall be demonstrated OPERABLE:

a. At least once per 31 days by a visual inspection of the fire hose stations accessible during plant operation to assure all required equipment is at the station.
b. At least once per 18 months by:

E

l. Visual fnspectfon of the fire hose stations not accessible during plant operation to assure all required equipment fs at the station.
2. Removing ths hoes nor fnensction end re-rocking for ell f$ re hoes ikg stations, and
3. Inspecting all gaskets and replacing any degraded gaskets in fz9 the couplfngs. for all fire hose stations.

Ce At least once per 3 years by:

1. Partially opening each hose station valve to verify valve

'PERABILITY and no flow blockage.

2. Conductfng a hose hydrostatic test at a pressure of 150 psig or at least 50 psfg above the maximum fire main operating pressure, whichever's greater.

SUSQUEHANNA - UNIT 1 3/4 7-23 Amendment No.36

TABLE 3.7.6.5"I FIRE HOSE STATIONS HOSE RACK LOCATIONS COLUMN NUMBER Control Structure El. 697'-0" L-26 IHR"171 El. 697'-0" . L-32 2HR" 171 El. 714 I Pll L-26 IHR"162 El. 714 I Oll L-31 2HR-162 El. 729'-0" L"25. 9 IHR-158 El. 729'-0" L-32. 1 2HR" 158 El. 754'-0" L-26 IHR-136 El. 754'-0" L"32 2HR" 136 El. 771'-0" L-26 IHR-125 El. 771 I Oll L-31 2HR"125

b. Rea ctoi Building El. 645'-OI'45'-0" R-29 IHR-271 El. P-20. 6 IHR-272 El. 645'-0" U-22 IHR-273 El. 645'-0" R" 37. 4 2HR-271

'l.

El.

El.

645'-0" 645I-Oll 670'-0"

.U-30. 5 R-30 0-27.5 2HR" 272 2HR" 273 IHR-261 El. 670'-0" Q-29 1HR-262 El. 670I'-Oll T-22 IHR-263 El. 683'-0" Q-2?.5 1HR"251 El. 683I-O'I Q" 20. 6 IHR"252 El. 683I Oll T-22 IHR" 253 El. 719I-I'I Q"27.5 IHR"241 El. 719'-I" S"27.5 IHR" 242 El. 719'-'I" .Q-20.6 IHR"243 El. 719'-1" T"20.6 IHR"244 El. 719l-I" T-23.5 IHR-245 El. 749'-I" S-27. 5 IHR-231 El. 749'-I" S" 27. 5 IHR-231 El. 749I-I'I Q" 20. 6 IHR"232 El. 749I-Ill T-20. 6 IHR"233 El. 7?9'-1" P" 26. 5 IHR"221 El. 779I-I'I S-26. 5 IHR-222 El. 779'-1 Q-22 IHR-223 El. 779'-1" U-20. 6 IHR-224 El. 779'-1" T-23. 3 IHR-211 El. 818'"I" P-26. 5 IHR-201 El. 818'-1" U-26.5 IHR-202 El. 818'-I" Q"20.6 IHR"203

~. easel Cvene~abr ~

BRi!~in) el l Hotif sld~~~ OHa-el. (o5b -6" h l. (p5&

lb'-(p"

-6'y

+~/

uaPg SIMIOl ~RvE i 5f7fjgNA oHR- 8C

>HR- gZ]

C l.

S I.

El. '708 -0"

+~ syver

~~~ ~II<~

OHR- FZL oHR, 1p$ (

708'" hip~ sou al Sr'~<<< @Hi - i8t.

CI.

SUSQUEHANNA - UNIT I 3/4 7"24 Amendment No. BB

(

3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8. 1 A.C. SOURCES A.C. SOURCES - OPERATING LIMITING CONDITION FOR OPERATION 3.8. 1. 1 As a minimum, the following A.C. electrical power sources shall be OPERABLE:

Two physically independent circuits between the offsite transmission network and the onsite Class lE distribution system, and

b. Four separate and independent diesel generators", each with:

oP+4c Qvg Separate engine mounted day fuel tanks containing a minimum of 325 gallons of fuel,

2. A separate fuel storage system containing a minimum of 47,570 gal1one of fuel~and
3. A separate fuel transfer pump. &r dl~a 9en~A f a, ~~a APPLICABILITY: OPERATIONAL CONDITIONS 1, 2, and 3.

genggrabf C ACTION:

~ 445, Claws ~ dm~aleqnlg 45reag reassn atbeHbam bud dlcsel e: csNWp a0 With either one offsite circuit or one diesel gene ator of the above required A.C. electrical power sources inoperable demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirements 4.8. l.l.l.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and 4.8. 1. 1.2.a.4, for generator at a time, within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> and at least once per one'iesel 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> therafter; restore at least two offsite circuits and four diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

With one offsite circuit and one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Require" ments 4;8.1.1. l.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and 4.8. l. 1.2.a.4, for one diesel generator at a time, within 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> and at least'once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the inoperable A.C. sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Restore at least two offsite circuits and four diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss. or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in'COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Shared with Unit 2.

SUSQUEHANNA - UNIT 1 3/4 8-1 Amendment No. 51

Prior to but within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of removing any diesel generator from service in order to do work associated with tyiag in the additional diesel generator, Surveillance Requirement 4.8.1.1.2.a.4 shall be performed on the diesel generators which are to remain in service.

0 When any diesel generator is removed from service in order to do work asso-c ciated with tying in the additional diesel generator, the ACTIONS shall read as follows:

a4 With one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C.

sources by performing Surveillance Requirements 4.8. 1. l. I.a 'within one hour and 4.8.1. 1.2.a.4, within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> and at least. once per 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> thereafter; restore at least four diesel genarators to OPERABLE status within 60 days of accumulated tie-in outage time for all four diesels or be in at least HOT SHUTDOWN within the'next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. The provisions of Specification 3.0.4 are not applicable.

b. With one offsite circuit and one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A. C. sources by performing Surveillance Requirements 4.8. 1. 1. l.a within one hour and 4.8. 1. 1.2.a.4, within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and at least once per 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> thereafter; restore at least two offsite circuits to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. With the two offsite circuits restored to OPERABLF status, follow ACTION a.
c. With one diesel generator of the above required A.C. electrical power sources inoperable, in addition to ACTION a or b, above, verify within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> that all required systems, subsystems, trains, components and devices that 'depend on the remaining diesel generators as a sour ce of emergency power are also OPERABLE except as noted io Specification 3.7.1. 2; otherwise, be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
d. With two of the above requi'red offsite circuits inoperable, demonstrate the OPERABILITY of four diesel generators by performing Surveillance Requirement 4.8. 1.1.2.a.4, for one diesel generator at a time, within four hours and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter, unless the diesel generators are already operating; restore at least one of the inoperable offsite circuits to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. With on'iy one offsite circuit restored to OPERABLE status, restore at least two offsite circuits to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
e. With two or more of the above required diesel generators inoperable, demon-strate the OPERABILITY of the remaining A.C. sources by performing Sur-veillance Requirement 4.8. l. l. l.a within one hour and 4.8. 1. 1.2.a.4, for one diesel generator at a time, within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />; restore at least three of the diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. With three diesel generators restored to OPERABLE status,. follow ACTION a.

SUS(UEHANNA - UNIT 1 3/4 8-1a l.

LIMITING CONDITION FOR OPERATION Continued ACTION (ContInued) g e gras ne.gunneglgninI unng gennnnnnn n + ngeO4ss KE d gn gegnnngstennn

c. With one diesel gen ator of the above required A.C. electrical power sources inoperable< in addition to ACTION a or b, above, verify within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> that all required systems, subsystems, trains, components and devices that depend on the remaining diesel generators as a source of emergency power are also OPERABLE; otherwise, be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLO SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

E

d. With two of the above required offsite circuits inoperable, demonstrate the OPERABILITY of four diesel generators by performing Surveillance Requirement 4.8. l. 1.2. a.4, for one diesel generator at a time, within four hours and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter, unless the diesel generators are already operating; restore at least one of the inoper-able offsite circuits to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. With only one offsite circuit restored to OPERABLE status, restore at least two offsite circuits to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLO SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
e. With two or more of the above required diesel generators inoperable, demonstrate the OPERABILITY of the remajning A.C. sources by performing Surveillance Requirement 4.8. l. l. l. a within one hour and 4.8. 1. 1.2.a.4, for one diesel generator at a time, within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, and at. least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least three of the diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT SHUTDOWN within the next 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> s and in COLO SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. Restore four diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLO SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

SUS(UEHANNA - UNIT 1 3/4 8"2

ELECTRICAL POWER SYSTEMS SURVEIl LANCE RE UIREMENTS

4. 8. 1. 1. 1 Each of the above required independent circuits between the offsite transmission network and the onsite Class lE distribution system shall be:

Determined .OPERABLE at least once per 7 days by verifying correct breaker alignments and indicated power availability, and

b. Demonstrated OPERABLE at least once per 18 months during shutdown by transferring, manually and au'tomatically, unit power supply from the normal circuit to the alternate circuit.

4.8.1.1. 2 Each of the above required diesel generators shall be demonstrated OPERABLE:

a. In accordance with the frequency specified in Table 4.8.1.1.2-1 on a

~ STAGGERED TEST BASIS by:

1.. Verifying the fuel level in the engine-mounted day fuel tank.

2. Verifying the fuel level in the fuel storage tank.
3. Verifying the fuel transfer pump starts and transfers fuel from the storage system to the engine-mounted day fuel tank.
4. Verifying the diesel starts. from amtHent condition and accel-erates to at least 600 rpm in less than or equal to 10 seconds.

The generator voltage and frequency shall be 4160 + 400 volts and 60 't 3.0 Hz within 10 seconds after the start. signal. The diesel generator shall be started for this test by using one of the following signals:

a) ,Manual.

b) Simulated loss of offsite power by itself.

c) Simulated loss of offsite power in conjunction with an ESF actuation test signal.

d) An ESF actuation test signal by itself.

5. Verifying the diesel generator is synchronized, loaded to greater than or equal to 4000 kw in less than or equal to 90 seconds,

. and operates with, this load for at least 60 minutes.

6. Vey ifying the diesel generator. is aligned to provide standby power to the associated emergency busses.
7. Verifying the pressure in all diesel generator air start receivers to be greater than or equal to 240 psig.
b. At least once per 31 days and after each operation of the diesel ~here the period of operation was greater than or equal to 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> by checking for and removing accumulated water. from the engine-mounted day fuel tanks.

SUSQUEHANNA -'NIT 1 3/4 8"3

ELECTRICAL POMER SYSTEMS SURVEILLANCE RE UIREMENTS Continued

c. At least once per 92 days and from new fuel oil prior to addition to the storage tanks by verifying that a sample obtained in accordance with ASTM-D270-1975 has a water and sediment content of less than or

.equal to .05 volume percent and a kinematic viscosity 8 40'C of greater than or equal to 1.3 but less than or equal to 2.4 for 1D oil or >1.9 but <4. 1 for 2D oil when tested 'in accordance with ASTM-09?5-7?, and an impurity level of less than 2 mg. of insolubles per 100 ml. when tested in accordance with ASTM-02274-70.

d. At least once per 18 months by:

Subjecting the diesel'o an inspection in accordance with procedures prepared in conjunction with its manufacturer's recommendations for this class of standby service.

2. Verifying the diesel generator capability to reject a load of
  • greater than or equal to 1425 kw while maintaining voltage at 4160 t 400 volts and frequency at 60 k 3.0 Hz.
3. Verifying the diesel generator capability to reject a load of 4000 kw without tripping. The generator voltage shall not exceed volts during and foll'owing the load rejection.

f64y 0

4. Simulat~ g a loss of offsite power by itself, and:

a) Verifying deenergization of thd emergency busses and load shedding from the emergency busses. ~

b) Verifying the diesel generator starts on the auto-start signal, energizes the emergency busses with permanently

'onnected loads within 10 seconds and operates for greater than or equal to 5 minutes while its generator is loaded with the shutdown loads. After energization, the steady be maintained at 4160 this test.

+~

~Boo volts and 60 + ~

-state voltage and frequency of the emergency busses shall

~8.o Hz during

5. Verifying that on an ECCS actuation test signal, without loss of offsite power, the diesel generator starts on the auto-start signaI and operates on standby for greater than or equal to 5 minutes.

-266 volts and 60 a ~

The generator voltage and frequency shall be 4160 +

Hz within 10 seconds after the auto-start sig al; the steady state generator voltage and frequency shall.

be aintained with n these limits during this test.

3;0 SUSQUEHANNA - UNIT 1 3/4 8-4 Amendment No. 36

ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREMENTS Continued)

6. Simulating a loss-of-offsite power in conjunction with an ECCS actuation test signal, and:

a) Verifying deenergization of the emergency busses and load shedding from the, emergency busses.

b) Verifying the diesel generator starts on the auto-start signal, energizes the emergency busses with permanently connected loads within 10 seconds, energizes the auto- .

connected 1'oads through the load timers and operates for greater than or equal to 5 minutes while its generator is loaded with the emergency loads. After energization, the steady state voltage and frequency of the emergency busses shall be maintained at 4160 2 400 volts and 60 + 3.0 Hz during th'is. test; c) Verifying that all automatic diesel generator trips, except engine overspeed, generator differential and engine low lube oil pressure, are automatically bypassed upon loss of voltage on the emergency bus concurrent with an ECCS actuation signal.

7. Verifying the diesel generator operates for at least 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

During the first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of this test, the diesel generator shall be loaded to greater than or equal to 4700 kW and during the remaining 22 hours2.546296e-4 days <br />0.00611 hours <br />3.637566e-5 weeks <br />8.371e-6 months <br /> of this test, the diesel generator shall be loaded to 4000 kW. The generator voltage and frequency shall be 4160 + 400 volts and 60 + 3.0 Hz within 10 seconds after the start signal; the steady state generator voltage and frequency.

shall be maintained within these limits during this test. Within 5 minutes after completing this 24-hour test, perform Surveillance Requirement 4.8.1.1.2.d.4.b}.~

8. Verifying that the 'auto-connected loads to each diesel generator krdiesel gener d4TS A)Sb<dbf'old do not exceed the 2000-hour rating of 4700 kW,

+be ~+inuC VS Wki lkgb ek SOeek~4 duvet Verifying the diesel generator' capability to:

9enera,4T- 5. a) Synchronize with the offsite power source while the generator is loaded with its emergency loads upon a simulated restor'ation of offsite power, b) Transfer its loads to the offsite power source, and c) Be restored to its standby status.

If Surveillance Requirement 4.8. 1; 1.2.d.4.b) is not satisfactorily completed, it is not necessary to repeat the preceding 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> test. Rather, the diesel generator may be operated at 4000 kW for 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or until operating temperature 9 has stabilized.

SUS(UEHANNA - UNIT 1 3!4 8-5 Amendment No. 36

0 ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREMENTS (Continued)

10. Verifying that with the diesel generator operating in a test mode and connected to its bus, a simulated ECCS actuation signal overrides the test mode by (1) returning the diesel generator to standby operation, .and (2) automatically energizes the emergency loads with offsite power.

tls Verifying that each diesel generator loading sequence timer shown in Table 4.8. 1. 1.2-2 is OPERABLE with its setpoint within 2 10K of. its design setpoint.

lg,s Verifying that the following diesel generator lockout features prevent diesel generator starting and/or operation only when required:

a) Engine overspeed.

b) Generator differential.

c) Engine low lube oil pressure.

e. At least once per 10 years or after any modifications which could affect diesel generator interdependence by starting all diesel generators simultaneously, during shutdown, and verifying that all diesel generators accelerate to at least 600 rpm in less than or equal to 10 seconds. l
f. At least o'ce per 10 years by:

Draining each fuel oil storage tank, removing the accumulated sediment and cleaning the tank using a sodium hypochlorite or equivalent solution, and

2. Performing a pressure test of those portions of the diesel fuel oil system designed to Section III, subsection ND of the ASME Code in accordance with ASME Code Section XI Article IWD-5000.

dI s&v I s I s aI

~Re orts

- All diesel generator failures, valid or non-valid, shall be reported to the Commission in a Special Report pursuant to Specification 9.9.2 ~3,e wsthsn 30 days. Reports of diesel generator failures shall include the snforma-tion recommended in Regulatory Position C.3.b of Regu atory Guide 1.108, Revi-sion 1, August 1977. If the number of failures in th last 100 valid tests, on a per nuclear 'unit basis, is greater than or equal to 7, the report shall be supplemented to include the additional information re ommended in Regulatory Position C.3.b of Regulatory Guide 1. 108, Revision 1, August 1977.

Of.+'jie raus~ d~l gener v

SUSQUEHANNA " UNIT 1 3/4 8-6 Amendment No. 36

TABLE 4. 8. 1. 1. 2-1 OIESEL GENERATOR TEST SCHEDULE Number of Failures in Last 100 Valid Tests*($

At least once per 31 days At least once per 14 days 3 At .least once per 7 days At 'least once per 3 days Criteria for determining number of failures and gumber of valid.

tests shall be in accordance wi'th Regulatory Position C.2.e of Regulatory Guide 1. 108, Revision 1, August 1977, where the last 100 tests are determined on a per nuclear unit basis. For the purposes of this test schedule, only valid tests conducted after the OL issuance date shall be included in the computation of the "last 100 valid tests." Entry into this test schedule shall be made at the 31 day test frequency.

+ gkgv, d~ geoecde~ 6 is eeV a>tyed 4c +q~ Cla ~ L.< Chk~ihu4~ zp4e )

gite,ke>4~8~ ~ill A+ bc Cv'Hi4ed +o ~e ~W'( 4>(vces 4f JQNQvqh>A~l1)

@<QVSYlM3 0~ 8~ Cfl~d g~A++d4N'5 gggul fM W 4C 01 ERABLl SUSQUEHANNA - UNIT 1 3/4 8-7

TAB LE 4. 8. l. l. 2" 2 UNIT 1 UNIT 2 EIE E CEHWI I I EEE OEVICE TAG TINE NO. SYSTFM LOCATION SETTING 62A"20102 RHR Pump 1A 1A201 3 sec 62A-20202 RHR Pump 18 lA202 3 sec 62A-20302 RHR Pump 1C 1A203 3 sec 62A-20402 RHR Pump 1D 1A204 3 sec 62A-20102 RHR Pump 2A 2A201 3 sec 62A"20202 RHR Pump 28 2A202 3 sec 62A-20302 RHR Pump 2C 2A203 3 sec 62A-20402 RHR Pump 20 2A204 3 sec K116A CS pp 1A 1C626 10.5 sec K1168 CS pp 18 1C627 10.5 sec K125A CS pp lc 1C626 10.5 sec'0.5 K1258 CS pp 10 1C627 sec K116A CS pp 2A 2C626 10.5 sec K1168 CS pp 28 2C627 10.5 sec K125A CS pp 2C 2C626 10.5 sec K125B CS pp 20 2C627 10.5 sec 62AX2"20108 Emergency Service Mater (ESM) lA201 40 sec 62AX2"20208 Emergency Service Mater (ESM) lA202 40 sec 62AX2-20303 Emergency Service Mater (ESW) 1A203 44 sec 62AX2-20403 Emergency Service Mater (ESM} 1A204 48 sec 62X3-20304 Contro1 Structure OC877A 60 sec Chil1ed Mater System 62X3-20404 Contro1 Structure OC8778 60 sec Chilled Mater System 62X"20104 Emergency Switchgear Rm. OC877A 60 sec Cooler A &

RHR SM pp H&V

~

Fan A SUSQUEHANNA " UNIT 1 3/4 8-8 Amendment No. 36

TABLE 4.8. 1. 1.2-2 (Continued)

UNIT 1 AND UNIT 2 DIESEL GENERATOR LOADING TINERS DEVICE TAG TINE NO. SYSTEM LOCATION SETTING

62X"20204 Emergency Switchgear Rm OC8778 60 sec h

Cooler 8 &

RHR SM pp H&V Fan 8 262X"20104 Emergency Switchgear Rm OC877A 120 sec Cooler A 262X"20204 Emergency Switchgear Rm OC8778 120 sec Cooler 8 62X-516 DG Rm Exh Fan A 08516 2 min

+ 62X-526 DG Rm Exh Fan 8 08526 2 min

+ 62X~536 DG, Rm Exh Fan C 08536 2 min 62X-546 DG Rm Exh Fan 0 08546 2 m'fn asm 62X1-20304 Control Structure OC877A 3 llllfl Chilled Mater System 62X1-20404 Control Structure OC8778 3 min Chilled Water System 62X1-20340 Control Structure OC876A 3 fllin Chilled Water System 62X2"20410 Control Structure OC8768 3 min Chilled Mater System 62X2-20304 Control Structure OC877A 3;5 min Chilled Water System 62X2-20404 Control Structure OC8778 3.5 min Chilled Mater System 62X"K11AB Emergency Switchgear 2CB250A 260 sec .

Rm Cooling Compressor A 62X" K1188 'Emergency Switchgear 2C82508 260 sec Rm Cooling Compressor 8

~~+ <

Cg.g-z4,sz A a.R.x-WSZ A 5g ~~

Rcow 5~ppl y fjord C 2 s<pii.Y FM CZ o95(,5 2. lrii win.

im bst DSSl 5 Z

$ 7x 5453A gC RoO~i gx<m+ Fl < 6 > OR SfoG 3 llht 'A ++

(,Z,y-s(552 A pc~ Room E'xH~< FW +4 ossr.s pirited C4W UEHANNA - UNIT 3/4 8-Ba Amendment Nn. 36

~ 4~~+~ ~t~l+eiiereW~ is decried OPGqAe,LC

) nltnuM ~c,Y: G2 G)eii+s

] re'iiiu4e aAer Bl w~W

INSERT A 4.8.1.1.3

~ ~ ~ ~ When substituting diesel generator E for diesel generator A,B,C or D, diesel generator E shall be demonstrated OPERABLE by:

a. Verifying diesel generator E energizes the appropriate emergency bus.
b. Verifying that at least once within the previous 31 days the following have been verified:
1. The fuel level in the engine-mounted day fuel tank.
2. The fuel level in the fuel storage tank.
3. The fuel transfer pump started and transferred fuel from the storage system to the engine-mounted day fuel tank.
4. The diesel manually started from ambient condition and accelerates to at least 600 rpm in less than or equal to 10 seconds. The generator voltage and frequency were 4160 + 400 volts and 60 + 3.0 Hz within 10 seconds after the start signal.
5. The diesel generator was synchronized, loaded to greater than or equal to 4000 kw in less than or equal to 90 seconds, and operated with this load for at least 60 minutes.
6. The pressure in the diesel generator air start receivers to be greater than or equal to 240 psig.

c~ Verifying that at least once within the previous 31 days and after each operation of the diesel, within the previous 31 days, where the period of operation was greater than or equal to 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> that a check was made for accumulated water from the engine-mounted day fuel tanks.

d. Verifying that at least once within the previous 92 days and from new fuel oil prior to addition to the storage tanks that a sample obtained in accordance with ASTM-D270-1975 has a water and sediment content of less than or equal to .05 volume percent and a kinematic viscosity 8 40'C of greater than or equal to 1.3 but less than or equal to 2.4 for 1D oil or 1.9 but 4.1 for 2D oil when tested in accordance with ASTM-D975-77, and an impurity level of less than 2 mg. of insolubles per 100 ml. when tested in accordance with ASTM-D2274-70.
e. Verifying that at least once within the previous 18 months if specification 4.8.1.1.2.d has not been performed:
1. An inspection in accordance with procedures prepared in conjunction with its manufacturer's recommendations for this class of standby service was performed.
2. The diesel generators capability to reject a load of greater than or equal to 1425 kw while maintaining voltage at 4160 + 400 volts and frequency at 60 + 3.0 Hz was tested.

A' I'(

C k

N I E

3. The diesel generators capability to reject a load of 4000 kw without tripping. The generator voltage shall not exceed 4360 volts during and following the load rejection was tested.
4. The diesel generator operated for at least 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. During the first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of this test, the diesel generator was loaded to greater than or equal to 4700 kW and during the remaining 22 hours2.546296e-4 days <br />0.00611 hours <br />3.637566e-5 weeks <br />8.371e-6 months <br /> of this test, the diesel generator was be loaded to 4000 kW. The generator voltage and frequency shall be 4160 + 400 volts and 60 + 3.0 Hz within 10 seconds after the start signal; the steady state generator voltage and frequency were maintained within these limits during this test.
5. The following diesel generator lockout features prevented diesel generator starting and/or operation only when required:

a) Engine overspeed.

b) Generator differential.

c) Engine low lube oil pressure.

6. Either:

a) That on a rotational basis, diesel generator E was substituted for diesel generator A, B, C, or D and a loss-of-offsite power was simulated in con)unction with an ECCS actuation test signal and:

i) Diesel generator E started on the auto start signal, energized the emergency busses with permanently connected loads within 10 seconds, energized the auto>>connected loads through the load timers and operated for greater than or equal to 5 minutes while its generator is loaded with the emergency loads.

After energization, the steady state voltage and frequency of, the emergency busses were maintained at 4160 + 400 volts and 60 + 30 Hz during this test, and ii) With the diesel generator operating in a test mode and connected to i,ts bus, a simulated ECCS actuation signal overrode the test mode by (1) returning the diesel generator to standby operation, and (2) automatically energizes the emergency loads with off-site power; or b) That by simulating a loss-of-offsite power in conjunction with an ECCS actuation test signal and:

i) Diesel generator E started on the auto start signal, energized the simulated emergency bus with simulated permanently connected loads within 10 seconds, energized the simulated auto-connected loads and operated for greater than or equal to 5 minutes while

IW ~, I 'h ht

'4 1 I

H ht jj r 4

I 4 I'<<1 gh

'"S I I I I' I P 4 E

~ hr rr rt 1 I' 11 h r- ~ P,t hr h

~ r. r I I', I ~

)

~ 1 $ 1 I P 1

~ yrj S) >St j L I, tjh~j p'j S I 'I 'I

,r V

r Hh' ~ 'I tf'>>I II ~ g WCI r<<p IP P

t ~

I I S I Wrtk P '

h I

I 1 h *~

tt ~ j'* H j' "g

1 4~

1 P 'f

its generator is loaded with the simulated emergency loads. After energization, the steady state voltage and frequency of the emergency busses were maintained at 4160 + 400 volts and 60 + 3.0 Hz during this test, and ii) On a rotational basis, diesel generator E was substituted for diesel generator A, B, C, or D and verify that diesel generator E energized the appropriate emergency bus.

e. Verifying that once per 10 years if Specification 4.8.1.1.2f has not been performed:

1

/

1. The fuel oil storage tank'has been drained, removing the accumulated sediment and cleaned using a sodium I

hypochlorite or equivalent solution, and

2. A pressure test of those portions of the diesel fuel oil system designed to Section III, subsection ND of the ASME Code in accordance with ASME Code Section II Article IWD-5000 has been performed.

dew/msa202345i

Nl'

~ ~

b t t E

E

ELECTRICAL POWER SYSTEMS A.C.

~ ~ SOURCES " SHUTDOWN LIMITING CONDITION FOR OPERATION 3.8.'1.2 As a minimum, the following A.C. electrical power sources shall be OPERABLE:

aO One circuit between the offsite transmission network and the onsite Class 1E distribution s stem, and I

each of<k A've. Two diesel generators with:

sc'pard+ bnd INJ

1. An engine mounted da fuel tank containing a minimum of 325 gallons of fuel C dwells A,b,ctbjd 4(u0,980~(0~5 rd'~4'~fengrdM+,
2. A fuel storage system containing a minimum of 47,570 gallons of fue.l.
3. A fuel transfer pump.

APPI ICABILITY: OPERATIONAL CONDITIONS 4, 5 and ".

I I

With less than the above required A.C. electrical power sources OPERABLE, suspend CORE ALTERATIONS, handling of irradiated fuel in the secondary containment, operations with a potential for draini'ng the reactor vessel and crane operations over the spent fuel pool when fuel assemblies are sto'red therein. In addition, when in OPERATIONAL CONDITION 5 with the water level less than 22 feet above the reactor pressure vessel flange, immediately initiate .corrective action to restore the required power sources to OPERABLE status as soon as practical.

b. The provisions of Specification 3.0.3 are not applicable.

SURVEILLANCE RE UIREMENTS 4.8. 1.2 At least the above required A.C. electrical power .sources shall be demonstrated OPERABLE per Surveillance Requirements 4.8. l. 1. 1, 4.8. l. 1.2 and

, except for the requirement of 4.8. l. 1.2.a.5.

When handling irradiated-fuel in the secondary containment.

SUSQUEHANNA - UNIT 1 3/4 8-9

0 3/4.8.2 0.C. SOURCES O.C. SdURCKS - OPERATING LIMITING CONDITION FOR OPERATION 3.8.2.1 As a minimum, the following O.C. electrical power sources shall be OPERABLE:

a. Division I, consisting of:
1. Load group Channel "A" power source consisting of:

a) 125 volt OC battery bank 10610, 20610>>

b) Full capacity charger 10613, 20613"

2. Load group Channel "C" power source consisting of:

a) I25 volt DC battery bank 106305 20630" b) Full capacity charger 10633,2 0633"

3. Load group "I" power source consisting of:

a) 250 volt OC battery 10650 b) Half-capacity chargers I0653A 106538

4. Load group "I" power source consisting of:

a) 0 24 volt OC battery bank 10670 b) Two half-capacity chargers 10673, ID674

b. Division II, consisting of:

I. Lhad group Channel "B" power source consisting of:

a) 125 volt OC battery bank 10620, 2D620" b) Full capacity charger 10623, 20623"

2. Load group Channel "0" power source consisting of:

a) 125 volt DC battery bank 10640, 2D640" b) Full capacity charger 10643, 20643*

~

,3. Load group "II" power source consisting of:

a) 250 volt OC battery bank 10660 b) Full capacity charger 10663 Load group "II" power source consisting of:

'I I 4.

a) 4 24 volt OC battery bank 10680 b) Two half-capacity chargers. 10683, 10684 APPLICABILITY: OPERATIONAL CONDITIONS I, 2, and 3 ACTION:

a. Nlth one or the above reqvlred Unit 1 125 volt or 250 volt OC load grove I battery banks inoperable, restore the inoperable battery barik to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLO SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

b.

satisfied.

SUSQUEHANNA - UNIT I I <>

Otherwise, declare the Unit 1 and common loads aligned to the inoper-able Unit 2 battery bank(s) inoperable and take the ACTION required by the applicable Specification(s).

C. With the Unit 1 loads associated with one or more of the above required Unit 1 125-volt DC load group battery bank(s) aligned to the corre-sponding Unit 2 load group battery bank(s), realign the Unit 1 loads to the Unit 1 battery bank(s) within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> after restoring the Unit 1 battery bank(s) to OPERABLE status; otherwise, declare the Unit 1 loads aligned to the Unit 2 battery bank(s) inoperable and take the ACTION required by the applicable Specification(s).

d. Nith one of the above required t 24 vo1t OC 1oad group battery banks declare the associated equipment inoperable and take p'noperable, D/Vtatbgt24< DIV>+~+ the ACTION required by the applicable Specification(s).
e. With one of the above required chargers inoperable, demonstrate the OPERABILITY of its associated battery bank by performing Surveillance Requirement 4.8.2.1.a.l within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least 1~1 once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If any Category A limit in Table 4.8.2.1-1 is not met, declare the battery inoperable.

.l v SURVEILLANCE RE UIREMENTS 4.8.2.1 Each of the above required k 24-volt, 125-volt and 250-volt batteries and chargers shall be demonstrated OPERABLE:

a. At least once per 7 days by verifying that:
1. The parameters in Table 4.8.2.1-1 meet the Category A limits, and
2. There is correct breaker alignment to the battery chargers, and total battery terminal voltage is greater than or equal to 26, 129, 258-volts on float charge.
b. At least once per 92 days and within 7 days after a battery discharge with battery terminal voltage below 22, 110 or 220 volts, as applicable, or battery overcharge with battery terminal voltage above 30, 150 or 300 volts, as applicable, by verifying that:
1. The parameters in Table 4.8.2. 1-1 meet the Category B limits,

'2. There is no visibie corrosion at either terminals or connectors,~<<

or the connection resistance of these items is less than 150 x 10-e ohm, and

3. The average electrolyte temperature of 4, 10 or 20, as applicable, of connected cells for the 24, 125 and 250 volt batteries is above 60 F.

SUS(UEHANNA - UNIT 1 3/4 8-11 Amendment No.

Insert B

f. With the above required diesel generator E 125 volt DC load group battery bank inoperable and diesel generator E not aligned to the Class lE distribution system, restore the battery bank to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or verify that all ESW valves associated with diesel generator E are closed and diesel generator E is 'not running within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. The provisions of Specification 3.0.4 are not applicable.
g. With the above required diesel generator E 125 volt DC load group battery bank inoperable and diesel generator E aligned to the Class 1E distribution system, restore the battery bank to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or declare diesel generator E inoperable and take the ACTION required by specification 3.8.1.1.
h. With the above required diesel generator E 125 volt DC charger inoperable and diesel generator E aligned to the Class lE distribution system, demonstrate the OPERABILITY of the associated battery bank by performing Surveillance Requirement 4.8.2.1.a.l within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If any Category A limit in Table 4.8.2.1-1 is not met, declare diesel generator E inoperable and take the ACTION required by specification 3.8.1.1.
i. With the above required diesel generator E charger inoperable and diesel generator E not aligned to the Class lE distribution system, demonstrate the OPERABILITY of its associated battery bank by performing Surveillance Requirement 4.8.2.1.a.l within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If any Category A limit in Table 4.8.2.1-1 is not met, declare the battery inoperable, and take the ACTION required by specification 3.8.2.1.f. The provisions of Specification 3.0.4 are not applicable.

I ~ I P

~ V P ~ V E

~ E ~

'I II

~ ~

E V E ~

ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREMENTS (Continued)

c. At least once per 18 months by verifying that:

The cells, cell plates and battery racks show no visual indication of physical damage or abnormal deterioration,

2. The cell-to-cell and, terminal connections are clean, tight, free of corrosion and coated with anti-corrosion material,
3. The resistance of each cell-to-cell and terminal connection of each 125-volt and 250-volt battery is less than or equal to 150 x 10-ohm, and The battery charger, for at least 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, will supply at least:

d} kr Alt 125-vo 1k g8AenhlN dhesJ 8'e68Nies, aspects aka,e,t ntmum

~ a) For the +

25.7 volts.

24-volt batteries, 25 amperes at a minimum of g f3768 volts b) For the 125-volt batteries, 100 amperes at a minimum of 127.8 volts.

c) For the 250-volt batteries, 300 amperes at a minimum of 255.6 va1ts.

d. At least once per l8 months by verifying that either:

The battery capacity is adequate to supply and maintain in OPERABLE status all of the actual emergency loads for the design duty cycle when the battery is subjected to a battery service test, or

2. The battery capacity is adequate to supply a dummy, load of the following profile, which is verified to be greater than the actual emergency loads, while maintaining the battery terminal voltage greater than or equal to + 21, 105 or 210 volts, as applicable.

a) For + 24-volt battery banks 10670, 10670-1, 10680 and 10685-1, 9.37 amperes for the entire 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.

b) For 125-volt batteries:

1) Channel A battery 10612:

325 amperes for 60 seconds 107 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test

2) Channel "B" battery 10622:

323 amperes for 60 seconds 105 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test

3) Channel "C" battery 10632:

340 amperes for 60 seconds 121 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test

4) Channel "D" battery 10642:

323 amperes for 60 seconds 104 amperes for the remainder of the 4 hour test.

SUSQUEHANNA " UNIT 1 3/4 8-12 Amendment No.* 36

SURVEILLANCE RE UIREMENTS Continued

5) Channel "A" battery 20612:

328 amperes fov 60 seconds 112 amperes fov the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.

Channel "B" battery 20622::

q)C4meL "ii" i ii~ o0<<~: 326 amperes for 60 seconds 110 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.

2848 ~cS qg ~~.f0'54 i 55'cy+85 Gx~ oevk?38m'iiiiL4s )

Mihii40~ Hl Channel "C" battery 20632:

343 8mperes for 60 seconds 128 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.

8) Channel "0" battery 20642:

326 amperes for 60 seconds 111 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.

c) For 250-volt batteries:

Battery bank 10650:

1091 amperes for 60 seconds 567 amperes for 29.0 minutes 113 amperes for 60.0 minutes 24 amperes for 150.0 minutes

2) Battery bank 1D660:

1314 amperes for'. 60 seconds 465 amperes for 60 seconds 365 amperes for 28.0 minutes 323 amperes for 15.0 minutes 185 amperes for 195.0 minutes

e. At least once per 60 months by verifying that the battery capacity is at least 80K of the manufacturer's rating when subjected to a performance discharge test. Once per 60 month interval, this per-formance discharge test may be performed in lieu of the battery servi,ce test.
f. Annual performance discharge tests of battery capacity shall be given to any battery that shows signs of degradation or has reached 85K of the service life expected for the application. Oegradation is indicated when the battery capacity drops move than 10K of rated capacity from its average on previous performance tests, or is below 90K of the manufacturer's rating.

SUSQUEHANNA " UNIT 1 3/4 8"13 ( Amendment No. 36

TABLE 4.8.2.1-1 BATTERY SURVEILLANCE RE UIREMENTS CATEGORY A CATEGORY 8(2) ar ameter Limits for each Lfsfts for each Allowable( )

designated pilot connected cell value for each

~ cel 1 connected cell 1 ectrolyte >Mfnfmus level >Hfnfsua level Above top of Level indication mark, indication mark, plates, and < V'bove and < V'bove and not maximum level maxfsua level overflowing indication mark fndfcatfon sark Float Voltage > 2.I3 volts > 2.07 volts Not more than

.020 below. the average of all con'nected cell Specfffg I.2OO(b)

Gravity' ) Average yf all Average of all connect~))cells . connect~))cell

> 1.205 > I.I95 (a) Corrected for electrolyte temperature an'd level.

(b) Or. battery charging current fs less than 0.01, 0.1 and 0.25 amperes for the &4, I25 and 250 volt batteries, respectively, when on float charge.

(c) May be corrected for average electrolyte temperature.

(I) For any Category A paraneter(s) outside the limit(s) shown the battery may be considered OPERABLE provided that within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> all the Category 8 measurements are taken and found to be within their allowable values, and provided all Category A and 8 parameter(s) are restored to within limits wfthfn the next 6 days.

(2) For any Category 8 parameter(s) outside the limit(s) shown, the battery may be considered OPERABLE provided that the Category 8 parameters are within their allowable values and provfded the Category 8 parameter(s) are restored to within Ifmfts within 7 days.

(3) Any Category 8 parameter not within its allowable value indicates an inoperable battery.

SUS)UEHANNA - UNIT I 3/4 8-14

0.C. SOURCES SHUTDOWN LINTING CONOITION FOR OPERATION 3.8.2.2 As a minimum, Division I or Division II of the D.C. electrical power sources shall be OPERABLE with:

a. Division I consisting of:
1. Load group Channel "A" power source, consisting of:

a) 125 volt DC battery bank M610, 20610>>

b) Full capacity charger 10613)2 0613>>

2. Load group Channel "C" power source, consisting of:

a) 125 volt DC battery bank 10630, 20630"*

b) Full capacity charger 10633, 20633""

3. Load group "I" power source, consisting of:

a) 250 volt DC battery bank 10650 b) Half-capacity chargers ID653A, 106538

4. "I" power source, consisting of:

a) i Load group 24 volt OC battery bank Two half-capacity chargers

')

10670 10673, M674

b. Division II consisting of:
1. Load group Channel "B" power source, consisting of:

a) 125 volt DC battery bank 1D620, 20620>>

b) Full capacity charger 10623, 2D623""

2. Load group Channel "0" power source, consisting of:

a) 125 volt OC battery bank 1D640, 20640>>

b) Full capacity charger 10643, 20643""

3. Load group "II" power source, consisting of:

a). 250 volt DC battery bank 10660 b) Full capacity charger 10663

4. group "II" power source, consisting of:

Load a) b)

i 24 volt DC battery bank Two half-capacity chargers 10680 10683, 10684 SSS'N5EILT h

APPLICABILITY: OPERATIONAL CONDITIONS 4, 5, and ".

ACTNN: givtaionK~~or 5tviaion K E~~

a. Nth less than the above requir'ed Unit 1 125 volt and/or 250 volt DC load group battery banks OPERABLE, suspend CORE ALTERATIONS, handling of irradiated fuel in the secondary containment and operations with a potential for draining the reactor vessel.
b. Nth less. than the above required Unit 2 125-volt DC load group battery banks OPERABLE, either:

hen hand ng irradiated fuel in the secondary containment.

  • "Not required to be OPERABLE when the requirements of ACTION b have been satisfied.

SUSQUEHANNA - UNIT 1 3/4 8-15 Amendment No. 3l

Insert A c.

~ Diesel Generator E 1.~ Load group power source, consisting of:

a) 125 volt DC battery bank OD595 b) Full capacity charger OD596

4 I

I t

LIMITING CONDITION FOR OPERATION Conti nued ACTIOII: (Contfaued)

I. Suspend CORE ALTERATIONS, handling of irradiated fuel fn the secondary containment and operations with a potential i'or drafn-fng the reactor vessel, or

2. I Transfer the Unft and coaaon loads alfgned to the inoperable Unit 2 battery bank(s) to the corresponding Unit 1 battery bank(s).

Otherwfse, declare the Unit 1 and comon loads aligned to the fnoper able Unit 2 battery bank(s) inoperable and take the ACTION required by the applicable Specfffcatfon(s).

C, Nth the Unit 1 loads associated with one or more of the above required Unft 1 125-volt DC load group battery bank(s) aligned to the corre-sponding Unit 2 load group battery bank(s), realign the Unit 1 loads to the Unft 1 battery bank(s) within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> after restoring the Unit 1 battery bank to OPERA8LE status; otherwise, declare the Unit 1 loads aligned to the Unit 2 battery bank(s) inoperable and take the ACTION required by the applicable Specfffcatfon(s).

d. i Nth the above required 24 volt D.C. load group battery banks inoperable, declare the assocfated equipment inoperable and take i0iVisio~ Z~~+.r the ACTION re ufred b the applfcable Specftfcatfon(s).

Qivi5toh K~~W eo Nth the above required charger(s) inoperable, demonstrate the OPERABILITY of the associated battery by performing Surveillance Requfrement 4.8.2.1.a.l within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If any Category A limit fn Table 4.8.2.1-1 fs not met, declare the battery inoperable.

f. The provisions of, Specfffcatfon 3.0.3 are not applfcable.

9r

~~ 5 SURVEILLANCE RE UIREMENTS 4.8.2.2 At least the above required battery and charger shall be demonstrated OPERABLE per Surveillance Requirement 4.8.2.1.

SUSQUEHANNA - UNIT 1 3/4 8-16 Amendment No. 31

Insert B

g. With the above required diesel generator E 125 volt DC load group battery bank inoperable and diesel generator E not aligned to the Class lE distribution system, restore the battery bank to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or verify that all ESW valves associated with diesel generator E are closed and diesel generator E is not running within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. The provisions of Specification 3.0.4 are not applicable.
h. With the above required diesel generator E 125 volt DC load group battery bank inoperable and diesel generator E aligned to the Class 1E distribution system, restore the battery bank to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />'r declare diesel generator E inoperable and take the ACTION required by specification 3.8.1.2.

With the above required diesel generator E 125 volt DC charger inoperable and diesel generator E aligned to the Class 1E distribution system, demonstrate the OPERABILITY of the associated battery bank by performing Surveillance Requirement 4.8.2.l.a.l within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If any Category A limit in Table 4.8.2.1-1 is not met, declare diesel E inoperable and take t'e ACTION required by specification 3.8.1.2.

With the above diesel generator E charger inoperable and diesel generator E not aligned to the Class lE distribution system, demonstrate the OPERABILITY of the associated battery by performing Surveillance Requirement 4.8.2.1.a.l within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If any Category A limit in Table 4.8.2.1-1 is not met, declare the battery inoperable, and take the ACTION required by specification 3.8.2.2.g. The, provisions of Specification 3.0.4 are not applicable.

WI I P P

~ M ~

IE

=

IE ~

W 4 I W II ~

I I~ I IE M ~ ~

M' 'I Y I ~

t ,

'I O'

o I~ E n

3/4.8. 3 ONSITE POWER OISTRIBUTION SYSTENS OISTRIBllTIN OPERATING LIMITS% CQOITIQN FOR OPERATION 3.8.3. 1 The following power distribution system divisions shall be energized with tie breakers open both between redundant buses within the unit and between units at the same station:

a. A. C. power distribution:
1. Oivfsion I, consisting of:

a) Load group Channel ."A", consisting of:

1) 4160 volt A.C. switchgear bus 1A201
2) 480 volt A.C. load canter 18210
3) 480 volt A.C. motor control canter 08516 b) Load group Channel "C", consisting of:
1) 4160 volt A.C. switchgear bus 1A203
2) 480 volt A.C. load canter 1B230
3) 480 volt A.C. motor control canter OB536 e) Isolated 480 volt A.C. swing bus, including:

25( 1) Prefer~ed power source gg +pys%1 AV~~~~ 2) Preferred power source MG set

&70 3) Alternate power source C 4) Automatic transfer switch C. 2. Oivision II, consisting of:

a) Load group Channel"B", consisting of;

1) 4160 volt A.C. switchgear bus 1A202
2) 480 volt A.C. load center 1B220
3) 480 volt A.C. motor control canter OB526 b) Load group Channel "0", consisting of:
1) 4160 volt A.C. switchgear bus ih204
2) 480 volt A.C. load center 13240
3) 480 volt. A.C. motor control center OB546 e) Isolated 480 volt A.C. swing bus, including: tB229
1) Preferred power source
2) Preferred power source HG set
3) Alternate power source a) Auteaatic tranerer ewttca

.C. power distribution:

Oivision I, consisting of:

a) Load group Channel "A", consisting of:

1) 125 volt OC buses H)612 20612,>>

10614, 20614>>

2) Fuse box 10611, 20611" l E IO I

SUSQUEHANNA - UNIT 1 3/4 8-17 . Amendment Ho. 48

INSERT A

a. A.C. power distribution:
1. Division I, consisting of:

a) Load group Channel "A", consisting of:

1) 4160 volt A.C. switchgear bus 1A201~ gA5lOA
2) 480 volt A.C. load center 1B210
3) 480 volt A.C. motor control centers OB5 16 > OB517 1B216, 1B217
4) 208/120 volt A.C. instrument panels 1Y216 b) Load group Channel "C", consisting of:
1) 4160 volt A.C. switchgear bus 1A203, oAsloc-
2) 480 volt A.C. load center 1B230
3) 480 volt A.C. motor control centers OB536, OB136 1B236$ 1B237
4) 208/120 volt A.C. instrument panels 1Y236 c) Isolated 480 volt A.C. swing bus, including: 1B219
1) Preferred power source
2) Preferred power source MG set
3) Alternate power source
4) Automatic transfer switch
2. Division II, consisting of:

a) Load group Channel "B", consisting of:

1) 4160 volt A.C. switchgear bus 1A202 ) Oh<>>>
2) 480 volt A.C. load center 1B220
3) 480 volt A.C. motor control centers OB526I OB527 1B226, 1B227
4) 208/120 volt A.C. instrument panels 1Y226 b) Load group Channel "D", consisting of:
1) 4160 volt A.C. switchgear bus 1A204 oA<N'4
2) 480 volt A.C. load center 1B240
3) 480 volt A.C. motor control centers OB546, OB146 1B246I 1B247
4) 208/120 volt A.C. instrument panels 1Y246 c) Isolated 480 volt A.C. swing bus, including: 1B229
1) Preferred po~er source
2) Preferred power source MG set
3) Alternate power source
4) Automatic transfer switch

Insert B

3. Diesel Generator E, when aligned to the Class 1E system a) Load group consisting of:
1) 4160 volt A.C. switchgear bus OA510E
2) 480 volt A.C. motor control center OB565

I

/>

i e+

,,~a I

H'

ELECTRICAL POWER SYSTBIS LIMITING CONOITION FOR OPERATION Conti nued D.C. power distribution: (Continued) I h) Load group Channel "C", consisting of:

1) 125 volt OC buses M632, 20632~

M634, 20634

2) Fuse box M631, 20631~

c) Load group "I", consisting of:

1) 250 volt OC buses 10652, 10254
2) Fuse box M651 d) Load group "I", consisting of:
1) c 24 volt OC buses 10672
2) Fuse box 1067'1
2. Division II, cansfstfng of:

a) Load group Channel "8" consisting of:

1) 125 volt OC buses M622, 20622" 10624, 20624~
2) Fuse box M621, 20621" b) Load group Channel "0" consisting of:
1) 125 volt OC buses 10642, 20642" 10644, 20644"
2) Fuse box 1D641, 20641" c) Load group "II" consisting of:
1) 250 volt OC buses 10662, M264, 10274
2) Fuse box M661 d) Load group "II" consisting of:
1) x 24 volt OC buses M682
2) Fuse box 10681 a

APPLICABILITY: OPERATIONAL CONDITIONS 1, 2 and 3.

v Lr'svbrlA W sb~ 3)'awo'son aCTvgh JZ'.

usth one of the above required A.c. dsstributkon system load groves not energized, re-energize the load group within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or be in at least HOT SHUTDOWN within he next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLO SHUTDOWN within the i'0 1OWing 24 haurS 1 ~ ~'sulsblssst~Odhgvrbltm~

b. With one of the above required Unit 1 D.C. distr.'bution system load groups not energized, re-energize the toad group within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at .

least HOT SHUTDOWN within the next-12 hours and in COLO SHUTDOWN within the i'ollawing 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

c. With one or rsore of the above required Unit 2 O.C. dfstribution system load groups not energized, within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> either:
1. Reenergfze the load group(s), or
2. Transfer the Unit 1 and canaan loads aligned to the deenergfzed Unit 2 load group(s) to the corresponding Unit 1 laad graup(s).

"Not required to be OPERABLE when the requirements af ACTION c have been satisfied.

SUSqUEHANNA - UNIT' 3/4 8 18 Amendlent No. 48

Insert C

3. Diesel Generator E a) Load, group consisting of:
1) 125 volt D.C. bus OD 597

I II I

ELECTRICAL POMER SYSTBIS LINITIN CQgmON FOR OPERATION Continued ACTIOll (Cant< nusd)

Otherwise, declare the Unit 1 and eamon loads aligned to the deenergized Unit 2 lqad gloup(s) fnoperable and take the ACTION required by the appli-cable Speci ff catf on(s).

d. Nth the Unit 1 loads associated with one or more of the above required Unit 1 ]25-volt O.C. load group(s) aligned to the corresponding Unit, 2 1 t 1 t oad group(s), r eal f gn the Uni 1 oads to the Uni 1 oad group(s) 1 within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> after restoring the Unit 1 load group(s) to OpERABLE status; otherwfse, declare the Unit 1 loads aligned to the Unit 2 load group(s) inoperable and take the ACTION required by the applicable Specification(s).

fifth one or both of the isolated 480 volt A.C. swing busses inoperable, declare the associated LPCI loop inoperable (see Specfffcatfon 3.5. 1).

9 ~

SURVEiLLANCE RE UIREMENTS 4.8.3. L.1 Each of the above required, power distribution system load groups shall be determined energized at least once per 7 days by verifying correct breaker alignment and voltage on the busses/MCCs/panels.

4.8.3. 1.2 The isolated 480 volt A.C. swing bus automatic transfer switcnes shall be demonstrated OPERABLE at least once per 31 days by actuating the load test switch or by disconnecting the preferred power source to the transfer switch and verifying that swing bus automatic transfer is accomplished.

3/4 8- IBa Amendment No.48 SUSQUEHANNA.- UNIT 1

Insert D

f. With the above required diesel generator E A.C. distribution system load group not energized and diesel generator E aligned to the Class lE distribution system, re-energize the load group within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN'within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
g. With the above required diesel generator E 125 volt D.C. distribution system load group not energized and diesel generator E not aligned to the Class 1E distribution system, re-energize the load group within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or shutdown diesel generator E and close all ESW valves associated with diesel generator E within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. The provisions of Specification 3.0.4 are not applicable.
h. With the above required diesel generator E 125 volt D.C. distribution system load group not energized and 'diesel generator E aligned'o the Class lE distribution system, re-energize the load group within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or declare diesel generator E inoperable and take the ACTION required by specification 3.8.1.1.

N th N,K'KKhh I ~

K I tN Nn ,h t jfh tK 1 Krjj .

~

)(K l'

t

I K K

OISTRIBUTION - SHUTOOWN LINITIl CSOITION FOR OPERATION 3.8.3.2 ~ a <nial, the following power dfstrfbutfon systai divisions shall be energfnd:

a. For A.C. power distribution, Ofvfsfon I or Ofvisfon II with:
l. Ofvisfan I consisting of:

a) Load group Channel "A", consisting of:

1) 4160 volt A.C. swftchgear bus IA201
2) 480 volt A.C. load center 1B210
3) 480 volt A.C. Iotor control center OB516 b) Load group Channel "C", consistfng of:
1) 4160 volt A.C. switchgear bus 1A203
2) 480 volt A.C. load center 1B230
3) 480 volt A.C. motor control center 08536 Revloos PEA- 25 e4np,'ub

Aed undec as p~psed A~mes, 5eG e) Isolated 480 volt A.C. swing bus, including: 1B 219"

1) Preferred power source

~SE< 2) Preferred power source MG set

3) Alternate power source 4g Automatic transfer switch
2. Oivision II consisting of:

a) Load group Channel"B", consisting of:

l) 4160 volt A.C. switchgear bus 1A202

2) 480 volt A.C. load center 1B220
3) 480 volt A.C. motor control center OB526 b) Load group Channel "0", consisting of:
1) 4160 volt A.C. switchgear bus IA204
2) 480 volt A.C. load center 1B240
3) 480 volt A.C. motor control center 08546 e) Isolated 480 volt A.C. swing bus, includfng: lB229~
1) Preferred power source
2) Preferred power source HG set
3) Alternate power source
4) Autamatic transfer s~itch sea 3.

gyseM 6 "The swing bus shall be, OPERABLE ff the Division I LPCI subsystem alone is fulfilling the requirements of Speciffcatfon 3.5.2.

" The swing bus shall be OPERABLE if the Ofvisfon II LPCI subsystem alone is fulfilling the requirements of Specification 3.5.2.

SUSQUEHANNA - UNIT 1 3/4 8-19 Amendment No. 48

pg~ cu~gg INSERT A and cfi~l gener~rE,

a. For A.C. power distribution, Division I or Division II with:
1. Division I consisting of:

a) Load group Channel "A", consisting of:

1) 4160 volt A.C. switchgear bus 1A201, opsioa
2) 480 volt A.C. load center 1B210
3) 480 volt A.C. motor control centers OB516 OB517 1B216I 1B217
4) 208/120-volt A.C. instrument panels 1Y216 b) Load group Channel "C", consisting of: Meal
1) 4160 volt A.C. switchgear bus 1A203 1A203, OA5(oC. c~e~
2) 480 volt A.C. load center 1B230
3) 480 volt A.C. motor control centers')

OB536, OB136 1B236, 1B237 208/120 volt A.C. instrument panels 1Y236 c) Isolated 480 volt A.C. swing bus, including: 1B 219*

1) Preferred power source
2) Preferred power source MG set
3) Alternate power source
4) Automatic transfer switch
2. Division II consisting of:

a) Load group Channel "B", consisting of: aJ

1) 4160 volt A.C. switchgear bus 1A20 2 > oA6(oB ~~yg
2) 480 volt A.C. load center 1B220
3) 480 volt A.C.. motor control centers OB526, OB527 1B226J 1B227
4) 208/120-volt A.C. instrument panels 1Y226 b) Load group Channel "D", consisting of:
1) 4160 volt A.C. switchgear bus 1A204, bp,sloD ~~g
2) 480 volt A.C. load center 1B240
3) 480 volt A.C. motor control centers OB546, OB146 1B246, 1B247
4) 208/120 volt A.C. instrument panels 1Y246 c) Isolated 480 volt A.C. swing bus, including: 1B229**
1) Preferred power source
2) Preferred power source MG set
3) Alternate power source
4) Automatic transfer switch

Insert B

3. Diesel Generator E a) Load Group, consisting of:
1) 4160 volt A.C. svitchgear bus OA510E
2) 480 volt A.C. motor control center OB565

r P

C I \

ELECTRICAL POSER SYSTEHS CSOITION FOR OPERATION Cont f nued

b. FOr O.C. peter d4strfbutfon, Ofvfsfon I or Ofvfsfon II, with:
l. Oivfsion I conifstfng of:

a) Load group Channel "A", consisting of:

1) 125 volt OC buses 10612 29612<<

M614 20614>>>>

2) Fuse box 10611, 29611>>>>

b) Load group Channel "C", consfstfng of:

1) 125 volt OC buses 19632, 20632>>>>

M634, 20634>>>>

2) Fuse box M631, 20631>>>>

c) Load group "I", consfstfng of: It

1) 250 volt OC buses 10652, 10254 Z) Fuse box 10651 d) Load group "I", consisting of;
1) x 24 volt OC buses 10672
2) Fuse box 10671
2. Oivision II consisting of:

a) Load group Channel "8", consisting of;

1) 12S volt OC buses 10622, 20622>>>>

10624, 206Z4>>>>

2) Fuse box M621, 20621 P

b) Load group Channel "0", consisting of:

1) t

?25 vo 1 OC buses ~J)642, 20642>>>>

10644, 20644>>>>

2) Fus& box 10641. 29641>>>>

c) Load group "II", consisting of:

1) 250 volt OC buses 19662, 'OZ64, 10274
2) Fuse box 10661 Load group "II", consisting of:

~~e. ~ ~

APPLICABIL'!:

1) 2)

e 24 volt Fuse box OC buses

'OPERATIONAL CONOITIONS 4, 5 and ".

U)682 10681 When handling irradfated fuel in the secondary containment.

""Not required to be OPERABLE when the requirerrrents of ACTION c have been satisfied.

SUSQUEHANNA - UNIT 1 3/4 8-20 Amendment No. 48

Insert C

3. Diesel Generator E a) Load group consisting of:
1) 125 volt D.C. bus OD 597

LIMITIHG CONOITION FOR OPERATION Continued ACTION:

a. Wfth less than the Ofvision I or Oivfsion II load groups of the abave required A. C. dfstrfbutfon system energfzed, suspend CORE ALTERATIOHS, handling of irradiated fuel fn the secondary containment and ope~ations with a potential f'r draining the reactor vessel.
b. With less than the Ofvfsfon I or Ofvfsfon II load groups of the abave required Vnft 1 O. C. distribution system energized, suspend CORE ALTERATIONS, handling or frradfated fuel in the secondary containment and operations with a potential for drafning the reactar vessel.
c. With less than Oivfsfon I or Ofvision II of the above required Unit 2 O.C. distribution system energized, either:
1. Suspend CORE ALTERATIONS, handling of ir~adiated fuel in the secondary containment, and operations with a potential far drain-ing the reactor vessel, or
2. Transfer the Unit 1 and coaeon loads alfgned to the deenergfzed Unit 2 laad group(s) to the corresponding Unit 1 load group(s).

Otherwise, dec!are the Unft 1 and caaeon loads aligned to the deener-gized Unit 2 load group(s) inoperable and take the ACTION required by the applicable Specification(s).

With the Unit 1 loads aligned to one or more of the above required Unit '25-volt O.C. load group(s) aligned to the correspondfng Unit 2 load group(s), realign the Unit 1 loads to the Unit 1'load group(s) within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> after restoring the Unit 1 load group(s) to OPERASLE status; otherwise, declare the Unit, 1 loads aligned to the Unit 2

'load group(s) inoperable and take the ACTIOH required by the appli-cable Specification(s).

e. With one or both of the isolated 480 volt A.C. swing busses inoperable, declare the asscociated LPCI loop inoperable (see Specification 3.5.2).

The provisions of Speciffcation 3.0.3 are not applicabl ~ .

SURV LLANCE RE UIREMEHTS 4.8.3.2.1 At least the above required power distribution system divisions shall be determined energized at least once per 7 days by verifying correct breaker alignment and voltage an the busses/MCCs/panels.

4.8.3.2.2 The isolated 480-volt A.C. swing bue automatic transfer switch shall be demonstrated OPERASLE at least ance per 31 days by actuatfng the load test s~itch or by dfscannectfng the preferred power'ource to the transfer switch and verifying that swing bus automatic transfer .is accomplished.

SUStlUEHANNA - UNIT 1 3/4 8-21 Amendment No. 48

e, Insert D

g. With the above required diesel generator E A.C. distribution system load group not energized and diesel generator E aligned to the Class 1E distribution system, suspend CORE ALTERATIONS, handling of irradiated fuel in the secondary containment and operations with a potential for draining the reactor vessel.
h. With the above required diesel generator E 125 volt D.C. distribution system load group not energized and diesel generator E not aligned to the Class 1E distribution system, re-energize the load group within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or verify that all ESW valves associated with diesel generator E are closed and diesel generator E is not running within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. The provisions of Specification 3.0.4 are not applicable.

With the above required diesel generator E 125 volt D.C. distribution system load group not energized and diesel generator E aligned to the Class 1E distribution system, re-energize the load group within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or declare diesel generator E inoperable and take the ACTION required by specification 3.8.1.2.

C F

D I y~

P

ELECTRICAL POWER SYSTEMS MOTOR OPERATED VALVES THERMAL OVERLOAO PROTECTION - dog~uou~

LIMITING CONDITION FOR OPERATION

~,s.4.z,i g, QAiz.l - 'I The thermal overload protection of each valve shown in Table shall be bypassed continuously by an OPERABLE bypass device integral with the motor s arter.

APPLICABILITY: whenever the motor operated valve is required to be OPERABLE nless oHewise epci6 ed.

a. Nth thermal overload protection for one or more of the above required valves not bypassed continuously by an OPERABLE integral bypass device, take administrative action to continuously bypass the thermal overload within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or declare the affected valve(s) inoperable and apply the appropriate ACTION statement(s) for the affected system(s).
b. The provisions of Specification 3. 0. 4 are not applicable.

SURVEILLANCE RE UIREMENTS Qg,A z,j,I The thermal overload protection for the above required valves shall be verified to be bypassed continuously by an OPERABLE integral bypass device by verifying that the thermal overload protection is bypassed:

a. At least once per 18 months, and
b. Following maintenance on the motor starter.

2 8.4 z.~.z.

The thermal overload protection shall be verified to be bypassed fo'llowing activities during which the thermal overload protection was temporarily placed in force.

,SUSQUEHANNA - UNIT 1 3/4 8-28 Amendment No. 36

TABLE +-8. ~

'3.8.4~z<~- ~

MOTOR OPERATED VALVES THERMAL OVERLOAD PROTECTION - QDA'rrÃU0W SYSTEM(S)

VALVE. NUMBER AFFECTED HV-01222A RHRSW HY-012228 RHRSW HV-01224AI RHRSW HV-0122481 RHRSW HV-01224A2 RHRSW HV-0122482 RHRSW 4 HV-01112A ESW

+ HV-011128 ESW 4'V-01122A ESW

~ HV-011228 ESW.

+ HV-01112C ESW HV"01112D ESW

> HV-01122C ESW

+ HV-'01122D ESW HV"01110A ESW

+ HV-011108 ESW

> HY-01120A ESW HV-011208 ESW HY-01110C ESW HV"01110D ESW HV-01120C c vv-otiioe ESW HV-01120D + HV-o imam ESW ewe HV-08693A + Hv->>'i ze ESW HV-086938 + gv-a <iz,zc ESW HV-0120IAI RHRSW HV-0120IA2 RHRSW HV"0120181 RHRSW HV-0120182 RHRSW HV-11210A RHRSW HV-112108 RHRSW HV-11215A RHRSW HV-112158 RHRSW HV-15766. Cont. Isol.

HV-15768 Cont. Isol.

HY-12603 Cont. Isol.

HY-11345 Cant. Isol.

HV-11313 Cont. Isol.

HV-11346 Cont. Isol.

HV-11314 Cont. Isol.

HV-Ell-1F009 RHR HV-Ell-1F040 RHR HV-G33-IFOOI RWCU HV-Ell-IF103A RHR HY-Ell-IF075A RHRSW HV"Ell-IF048A RHR HV-Ell"IFOOSC RHR SUSQUEHANNA - UNIT I 3/4 8-29 Amendment No. 52 b~~ o+ ~o

+' ~ ~~ + ~~~ + ~~ ~+ ./~~~~A

0

'I p

TABLE 3. 8.4. 2-1 (Continued)

MOTOR OPERATED VALVES THERMAL OVERLOAD PROTECTION SYSTEM(S)

VALVE NUMBER AFFECTEO HV- Ell-1F004C RHR HV- Ell-1F015A RHR HV-Ell-1F024A RHR HV-E21-1F015A CS HV-E41-1F002 HPCI HV-B21-1F016 NSSS HV-Ell"IF022 RHR HV-Ell-1F010A RHR HV-E11-1FOllA RHR HV-Ell-1F004A RHR HV-Ell-1F006A RHR HV-Ell-1F027A RHR HV-Ell-1F007A RHR HV-Ell-1F104A RHR HV"Ell-1F026A RHR HV- Ell-1F028A RHR HV-Ell"1F047A RHR HV-Ell-1F073A RHRSW HV-Ell-IF003A RHR HV-E11-.1F017A RHR HV"E21-1F001A CS HV-E21" 1F031A CS HV-E21"1F004A CS HV-E21" CS 1F005A'V-Ell-1F021A RHR HV-Ell-1F016A RHR HV-15112 RHR HV"E51" 1F007 RCIC

. HV-E51-1F084 RCIC .

HV"Ell-1F027B RHR HV-Ell-1F048B "

RHR HV"Ell-1F015B RHR HV-Ell-1F006B RHR HV-Ell-1F021B RHR HV-Ell-1F0108 RHR HV-Ell"1F011B RHR HV-Ell-1F004B RHR HV"Ell-1F007B RHR HV"Ell-1F104B RHR HV"Ell-1F026B RHR SUSQUEHANNA " UNIT 1 3/4 8-30 Amendment No. g)

TABLE 3.8.4.2-.1 (Continued)

MOTOR OPERATED VALVES THERMAL OVERLOAD PROTECTION SYSTEM(S)

VALVE NUMBER AFFECTED HV-Ell-1F028B RHR HV"Ell-1F047B RHR HV- Ell-1F016B RHR HV- Ell-1F003B RHR HV"Ell-1F017B RHR HV- E21" 1F031B CS HV"E21-1F001B CS HV-Ell"1F103B RHR HV"Ell-1F075B RHRSW HV- Ell-1F073B RHRSW HV"Ell-1F006D RHR HV" Ell" 1F0040 RHR HV"Ell-1F024B RHR HV-E21-1F015B CS HV-E21-1F004B CS HV"E21-1F005B CS HV"E32" 1F001K MSIV HV"E32" 1F002K MSIV HV-E32"1F003K MSIV HV-E32-1F001P MSIV HV"E32-1F002P MSIV HV"E32-1F003P MSIV HV"E32" 1F001B MSIV HV-E32-1F002B MSIV HV-E32-1F003B MSIV HV"E32-lFOOlF MSIV HV"E32-1F002F MSIV HV-E32"1F003F MSIV HV"E32-1F006 MSIV HV- E32-1F007 MSIV HV-E32"1F008 MSIV HV-E32-1F009 MSIV ~

I lb HV- E51-1F045 RCIC HV- E51" 1F012 RCIC HV"E51-1F013 RCIC HV-15012 RCIC HV"E51-1F046 RCIC HV"E51-1F008- RCIC HV- E51-1F031 RCIC HV- E51" 1F010 RCIC SUSQUEHANNA - UNIT 1 3/4 8-31 Amendment No. 2g

TABLE 3. 8. 4. 2-1 (Continued)

MOTOR OPERATED VALVES THERMAL OVERLOAD PROTECTION SYSTEM(S)

VALVE NUMBER AFFECTED HV- E51-1F019 RCIC HV- E51-1F060 RCIC HV- E51" 1F059 RCIC HV- E51-1F022 RCIC .

HV- E51-1F062 RCIC HV- E41" 1F012 HPCI HV- E41-1F001 HPCI HV"E41-1F011 HPCI HV- E41-1F006 HPCI HV- E41" 1F079 HPCI HV"E41-1F059 HPCI HV"E41" 1F004 HPCI HV- E41-1F003 HPCI HV"E41-1F042 HPCI HV"E41-1F075 HPCI HV-E41-1F008 HPCI HV"E41-1F007 HPCI HV"E41-1F066 HPCI HV-G33-1F004

'RWCU HV-B21-1F019 NSSS HV- E11" 1F008 RHR HV- Ell-1F023 RHR HV-Ell-lF049 RHR HV"B31" 1F032A RX RECIRC HV-B31-1F032BB RX ',RECIRC HV"B3%-1F031A RX 'RECIRC HV-B31-1F031B RX RECIRC

';O'OUEHAt/ttA - UNIT 1 3/4 8-32 Amendment No. 16

ELECTRICAL POWER SYSTEMS MOTOR OPERATED VALVES THERMAL OVERLOAD PROTECTION AUTOMATIC LIMITING CONDITION FOR OPERATION 3.8.4.2.2 The thermal overload protection of each valve shown in Table 3.8.4.2.2-1 shall be bypassed automatically by an OPERABLE bypass device integral with the motor starter.,

APPLICABILITY: When diesel generator E is not aligned to the 'Class lE distribution system.

ACTION:

a. With thermal overload protection automatic bypass inoperable for one or more valves listed above, take administrative action to continuously bypass the thermal overload within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, or verify that all diesel generator E ESW valves are closed and diesel generator E is not running within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.
b. The provision of Specification 3.0.4 are not applicable.

SURVEILLANCE RE UIREMENTS 4.8.4.2.2.1 The automatic bypass of thermal overload protection for those valves listed above shall be demonstrated OPERABLE at least once per 18 months.

TABLE 3.8.4.2.2-1 MOTOR OPERATED VALVES THERMAL OVERLOAD PROTECTION AUTOMATIC System(s)

Valve Number Affected HV-01110E ESW HV-01120E ESW HV-01112E ESW HV-01122E ESW

3/4. 8 ELECTRICAL POWER SYSTEMS BASES 3/4.8.1 3/4.8.2 and 3/4.8.3 A.C. SOURCES O.C. SOURCES and ONSITE POWER OIS U ON YS S The OPERABILITY of the A.C. and O.C. power sources and associated distribution systems during operation ensures that sufficient power will be available to supply the safety related equipment required for (1) the safe shutdown of the facility and (2) the mitigation and control of accident conditions within the facility. The minimum specified independent and redundant A.C. and D. C. power sources and distribution systems satisfy the requirements of General Design Crfterfa 17 of Appendix "A" to 10 CFR 50.

The ACTION requirements specified for the levels of degradation of the power sources provide restrictfon upon continued facility operation commensurate with the level of degradation. The OPERABILITY of the power sources are con-sistent with the initial condition assumptions of the accident analyses and are based upon maintaining at least three of the onsite A.C. and the corre-sponding D.C. power sources and assocfated distribution systems OPERABLE during accident conditions coincident with an as e 'loss of offsite power and single failure of one other onsite A. C. source. +~ss~A The A.C. and D.C. source allowable out-of-service times are based on Regulatory Guide 1.93, "Availability of Electrical Power Sources," December 1974. When one diesel generator is inoperable, there is an additional ACTION requirement to verify that all required systems, subsystems, trains, components and devices, that depend on the remaining OPERABLE diesel generator as a source of emergency power, are also OPERABLE. This requfrement is intended to provide assurance that a loss of offsite power event will not result in a complete loss of safety function of critical systems during the period one of the diesel generators is inoperable. The term verify as used in this context means to admfnfstratfvely check by examining logs or other fnformation to determine if certain components are out-of-service for maintenance or other r'easons. It does not mean'o perform the surveillance requirements needed to demonstrate the OPERABILITY of the component.

The OPERABILITY of the minimum specified A.C. and D.C. power sources and associated distribution systems during shutdown and refueling ensures that...

(1) the facfltty can be maintained fn the shutdown 'or refueling condition for extended time periods and (2) sufficient instrumentation and control capability is available for monitoring and maintaining the unit status.

The surveillance requirements for demonstrating the OPERABILITY of the diesel generators are in accordance wfth the recomaendatfons of Regulatory Guide 1.9, "Selection of Diesel Generator Set Capacity for Standby Power Supplies", March 10, 1971, Regulatory Guide 1. 108, "Periodic Testing of Diesel Generator Units Used as Onsfte Electric Power Systems at Nuclear Power Plants",

Revision 1, August 1977 and Regulatory Guide 1.137 "Fuel-Oil Systems for Standby Diesel Generators", Revision 1, October 1979.

SUSQUEHANNA - UNIT 1 B 3/4 8-1 cfkur&~el genes&-48 <<~ -<~~>~ A'A d~

'L

~p~~ ~pg~g~g'+~~gpff ~~ pf ~ p~v ~p +/~cp~~c~

0 ELECTRICAL POWER SYSTEMS BASES'.C.

SOURCES O.C. SOURCES and ONSITE POWER OISTRIBUTION SYSTEMS (Continued)

The. surveillance requirements for demonstrating the OPERABILITY of the unit batteries are fn accordance with* the recommendations of Regulatory Guide I. 129, "Maintenance Testing and Replacement of Large Lead Storage Batteries for Nuclear Power Plants", February 1978, and IEEE Std 450-1980, "IEEE Recom-mended Practica for Maintenance, Testing, and Replacement of Large Lead Storage Batteries for Generating Stations and Substations."

Verffyfng average electrolyte temperature above the minimum for which the battery was sized, total battery terminal voltage onfloat charge, connection resistance values and the performance of battery service and. discharge tests ensures the effectiveness of the charging system, the ability to handle high discharge rates and compares tha battery capacity at that time with the rated capacity.

Table 4.8.2.1-1 specifies the normal limits for each designated pi lot cell and each connected cell for electrolyte level, float voltage and specific gravity. The limits for the designated pilot cells float voltage and specific gravity, greater than 2. 13 volts and .015 below the manufactUFer's full charge specfffc gravity or a battery charger current that had stabilized at a Iow value, fs characteristfc of a charged .cell. with adequate capacity. The normal limits for each connected cell for float voltage and specific gravity, greater than 2.13 volts and not mora than .020 below the manufacturer' full charge specific gravity with an average specific gravity of all the connected .cells not more than .010 below the manufacturer ' ful I charge specific gravity, ensures the OPERABILITY and capability of the battery.

Operation with a battery cell's parameter outside the normal limit but within the allowable value specified in Table 4.8.2. 1-1 is permitted for up to 7 days. Ouring this 7 day period: (1) the allowable values for electrolyte level ensures no physical damage to the plates with an adequate electron transfer capability; (2) the allowable value for the average specific gravity of all the cells, not more than .020 below tha manufacturer's recommended full charge specific gravity, ensures that the decrease in rating will be less than the safety margfn provided in sizing; (3) the allowable value for an individual cell's specific gravity ensu'res that an individual cell's specific gravity will not be more than .040 below the manufacturer's full charge specific gravity and that the overall capability of the battery will be maintained within an acceptable, limit; and (4) the allowable value for an individual cell's float voltage, greater than 2.07 volts, ensures the battery' capability to perform fts design function.

fl SUS)UEHANNA - UNIT 1 B 3/4 8-2

ELECTRICAL POWER SYSTEMS BASES 3/4.8.4 ELECTRICAL E UIPMENT PROTECTIVE DEVICES Primary containment electrical penetrations and penetration conductors are protected by either de-energizing circuits not required during reactor operation or demonstrating the OPERABILITY of primary and backup overcurrent protection circuit breakers by periodic surveillance.

The surveillance requirements applicable to lower voltage circuit breakers and fuses provides assurance of breaker and fuse reliability by testing at least one representative sample of each manufacturers brand of circuit breaker and/or fuse. Each manufacturer's molded case and metal case circuit breakers and/or fuses are grouped into representative samples which are than tested on a rotating basis to ensure that all breakers and/or fuses are tested. If a wide variety exists within any manufacturer's brand of circuit breakers and/or fuses, it is necessary to divide that manufacturer's breakers and/or fuses into groups and treat each group as a separate type of breaker or fuses for surveillance purposes.

The bypassing of the motor operated valve thermal overload protection continuously by integral bypass devices ensures that the thermal overload protection will not prevent .safety related valves from performing their func-tion. The surveillance requirements for demonstrating the bypassing of the thermal overload protection continuously are in accordance with Regulatory Guide 1. 106 "Thermal Overload Protection for Electric Motors on Motor Operated Valves", Revision 1, March 1977.

SUSQUEHANNA - UNIT 1 .B 3/4 8-3

INST RUHENTATION FIRE DETECTION INSTRUMENTATION LIHITIHG CONDITION FOR OPERATION 3.3.7.9 As a minimum, the fire detection instrumentation for each fire detection zone shown in Table 3.3.7.9-1 shall be OPERABLE.

fire

~q APPLICABILITY: Whenever equipment 0 EHlliL protected by the detection instrument ACTION:

With the number of OPERABLE fire detection instruments less than the Hinimum Instruments OPERABLE requirement of Table 3.3.7.9-1:

a. Within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />., establish a fire watch patrol to inspect the zone(s}

with the inoperabla instrument(s) at least once per hour, unless the instrument(s) is located inside an inaccessible zone, then inspect the area surrounding the inaccessible zone at least once per hour.

b. The provisions or Specitications 3.0.3 and 3.0.4 are not app'licahle.

SURVEILLANCE RE UIREMENTS 4.3.7.9. 1 Each of the above required fire detection instruments which are accessible during unit operation shall be demonstrated OPERABLE at least once per 6 months by performance of a CHANNEL FUNCTIONAL TEST. Fire detectors which are not accessible during unit operation shall be demonstrated OPERABLE by the performance of a CHANNEL FUNCTIONAL TEST during each COLD SHUTDOWN exceeding 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> unless performed in the previous 6 months.

4.3.7.9.2 The supervised circuits supervision associated with the detector alarms of each of the above required fire detection instruments shall be demonstrated OPERABLE at least once per 6 months.

SUSQUEHANNA - UNIT 2 3/4 3-77 l Amendment No. 8 a

TABLE 3. 3.7.9-1 FIRE OETECTION INSTRUMENTATION INSTRUMENT LOCATION INSTRUMENTS OPERABLE PHOTO-FIRE HEAT IONIZATION ELECTRIC ZONE ROOM OR AREA ELEV. TOTAL NIH. TOTAL NIH. TOTAL NIH.

~MN

a. Cont 0-22A Filter Area 687'-8¹ NA HA 'l 6 HA NA 0-240 Lower Relay Room 698'1" 4 2 4 2 HA NA 0-24G Lower Relay Room 698'14 4 2 ,4 2 NA NA 0-24G PGCC 698'-I" 54 27 30 15 HA HA 0-25A Lower Cable Spreading Rm. 714'-0 20 10 6 3 0-25B South Cable Chase 714'-0¹ 1 1 HA NA 0-25C Center Cable Chase 714'-OIE 1 1 HA NA 0-25D North Cable Chase 714'-0¹ 1 1 . NA NA 0-25E Lower Cable Spreading Rm. 714'-0¹ 26 13 6 3 HA NA 0-26B South Cable Chase 729'-1" NA HA 1 1 HA HA 0-26C Center Cable Chase 729'-1" NA HA 1 1' NA NA 0-260 ~

North Cable Chase 729'-1¹ NA NA 1 HA NA 0-26F Vestibule 729'-1¹ HA HA 1 1 HA NA

'-26G Shift Office 729'-1¹ NA NA 1 1 NA NA" 0-26H Control Rm.

{Vnder Flr. Unit 1)" 729'1¹ HA HA 18 9 NA NA 0-26H Control Room (Under Flr. Unit 2)" 729'-1¹ HA HA 15 8 NA NA 0-26H Control Room 729'-1¹ HA HA 10 5 HA NA 0-26H Control Rm. {Above Clg)" 729'1¹ HA NA 6 3 NA HA 0-26I Operational Support 729'-1¹ HA HA 1 1 HA NA Center 0"26J Vestibule 729'-1¹ HA NA 1 1 NA NA 0-26M 'offit 729'-1¹ NA ~ NA 4 2 HA NA 0-26N Control Roam Soffit 729 ( -1¹ HA HA 2 '1 HA NA 0-26P Control Room Soffit 729'-1'I HA HA 2 1 HA HA 0-26R Soffit 729 I -1¹ HA NA 4 NA HA (

0-26S South Cable Chase 729'-1¹ 1 1 NA HA NA NA SVS(UEHAHHA - UNIT 2 3/4 3-78

TABLE 3.3.7.9-1 (Continued)

FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCATION INSTRUMEHTS OPERABLE PHOTO-FIRE HEAT IONIZATION ELECTRIC ZONE ROOM OR AREA ELEV. TOTAL MIN. TOTAL MIN. TOTAL MIN.

a. C 0<<26T Center Cable Chase 729 I -1N 1 1 NA NA NA NA 0-26V North Cable Chase 729'-lu 1 1 NA HA NA NA 0-27A Upper Relay Room 754'1" 2 1 2 1 NA NA 0"27A PGCC 754'-1" 55 28 30 15 . NA HA 0-27B 'pper Cable Spreading Rm. 753'-Ou 24 12 5 2 NA NA 0<<27C Upper Cable Spreading Rm. 753'-0" 25 13 6 3 NA NA 0-27E Upper Relay Room 754 I <<ill 4 2 2 1 NA NA 0-27F South Cable Chase 754'-1" 1 1 NA NA HA NA 0-27G Cable Chase 'enter 754 I <<ill 1 1 NA NA NA NA 0-27H North Cable Chase 754'-V 1 1 NA NA HA HA 0-28A Equipment Room 771'<<0" HA NA 4 2 NA NA 0-28B Equipment Room 771'<<0" NA NA 4 2 NA NA 0-28C Battery Room 771'<<0" NA NA 1 1 HA NA
0-'28D Battery Room 771'-0" NA NA 1 1 NA NA 0-28E Battery Room 771I

-OI'71'-04 NA N 1 1 HA NA 0-28F Battery Room NA NA 1 1 NA NA 0-28G Battery Room 771'-0" NA N 1 1 NA NA 0-28H Repair Shop 771'-04 NA NA 2 1 NA NA 0-28I Battery Room 771'0" NA NA 1 1 NA N 0-28J Battery Room 771'-04 NA NA 1 1 NA NA 0"28K Battery Room m'-0" NA NA 1 1 HA NA 0-28L Battery Room 771'<<0" NA NA 1 1 NA NA 0-28M Battery Room 771'-0" HA NA 1 1 NA N 0-28N Battery Room 771'<<0" NA NA 1 1 NA NA 0-28P South Cable Chase 771'<<0" 1 .1 HA NA NA NA 0"28Q Center Cable Chase 771'<<0" 1 1 NA NA NA NA 0-28R North Cable Chase 771'0" 1 1 NA NA HA NA SUSQUEHANNA - UNIT 2 3/4 3<<79

TABLE 3.3.7.9-1 (Contfnued)

FIRE. OETECTION INSTRUMENTATION.

INSTRUMENT LOCATION INSTRUMENTS OPERABLE PHOTO-FIRE HEAT IONIZATION "ELECTRIC ROOM OR AREA ELEV. TOTAL MIH. TOTAL MIN. TOTAL MIN.

ZONE *

"'R( 771'04 0-28T Batte~ Room NA NA 1 1 NA NA 0-29B M>V Equipment Room 783'"0" NA HA 10 5 NA NA 0-30A 806'"0"

"*"9 HVAC Equipment Room NA HA 20 10 NA HA 2-18 Core Spray Pump Room 645'-0" NA NA 6 3 NA NA 2-1A Core Spray Pump Room 645'-0" NA NA 8 4 NA NA 2-1E RHR Pump Room 645'-0" NA NA NA HA 13 7 2-1F RHR Pump Room 645 '0" NA HA NA HA 15 8 2-K RCIC Pump Room 645'-0" 2 1 NA NA 5 3 2"1C HPCI Pump Room 645'w 2 NA HA 7 4 2-1G Sump Room 645'-0" NA NA 2 1 NA NA 2-2B Core Spray Pump Room 670'-0" NA NA 11 6 NA NA 2-4C Switchgear Room 719'0" NA NA 2 1 NA NA 2-4D . Switchgear Room 719'0" NA NA 2 1 NA NA 2-4A Containment Access Area 719'-0" HA NA 26 13 3 2 2-5F Load Center Room 749'-1" NA NA 2 1 NA NA 2-5G Load Center Room 749'-V .HA NA 2 1 NA NA 2-2A Access Area and Remote 670'-0" HA NA 3 NA NA Shutdown Panel Room 2-3A Access Area 683'-0" NA HA 4 2 NA HA 2-38 Access Area 683 '0" HA HA 14 ,7 NA NA 2-3C Access Area 683'-Ou HA . NA NA NA 13 7 I ~ 1II 2-48 Pipe Penetration Room 719 HA HA 1 1 HA NA 2-4G Main Steam Piping 719'-1" NA, HA NA NA 4 2 2-5A Fuel Pool Pumps and Heat Exchangers 749'" NA HA 21 11 7 4 2-5B Valve. Access Area 761'10" HA NA NA NA 2 .1 2-5C RWCU Backwash Tank 749'-1" NA NA 1 1 2 1 SUSQUEHANNA - UNIT 2 3/4 3-80

TABLE 3.3.7. 9-1 (Continued)

FIRE DETECTION INSTRUMENTATION I

INSTRUMENT LOCATION INSTRUMENTS OPERABLE I

PHOTO-FIRE HEAT IONIZATION ELECTRIC ZONE ROOM OR AREA ELEV. TOTAL MIN. TOTAL MIN. TOTAL MIN.

b. Reactor Buildin Continued 2-5D RWCU Pumps 4 Heat Exchangers 749'-1" NA NA NA NA 10 5 2-5E Penetration Room 749'-1II NA NA NA NA 2 1 2-5H Instrument Repai~ Room 749 I ill NA NA 2 1 NA NA 2-6A Access Area 779 I 1II NA NA 10 5 NA NA 2-6B Load Cente~ Room 779 I ~ II

] NA NA 4 2 NA NA 2-6C Electric Equipment Room 779'-1" NA NA 2 1 NA NA 2-6E Hatch and Laydown Area 779'-1 NA NA 2 1 NA NA 2-6O H4V 'Equipment Room 779I 1II NA NA . 12 6 NA NA 0-6G Surge Tank Vault 779'-4" NA NA 2 1 NA NA 2-7A HLV Fan and '4 Filte~ Rooms 799'1II 24 12 7 NA NA 0-8A Refueling Floor 818'-1" NA NA- NA NA 59 30 J

0-51 P'ump Room 685'-6" NA NA 6 3 NA NA 0-52 Pump Room 685'-6" NA NA 6 3 NA NA INFRA-REO (FLAME)

TOTAL MIN.

d. Diesel Generator Buildin 0-41A Diesel Generator Rooms 660'-0" and 677'-0" 22 ll 2 1 15 8 0-41C Diesel Generato~ Rooms 660'-0" and 677'-0" 22 11 2 1 15 8 0-41B Diesel.Generator Rooms 660'-0" and 677'-0" 23 12 2 1 15 8 0-410 Diesel Generator Rooms 660'-0" i and 6771-0" 22 11 2 1 15 8 "Not accessible.

SUSQUEHANNA - UNIT 2 3/4 3-81 Q~~t GerIsr6&v G SLMQIh) g~~Q Q~maAoz Roo&s t 64 "4, < u 4 uA

.~d... ~g g +I. NA..MA

~

go@'.o~'JA

~

JJA 2

PLANT SYSTEMS SPRAY AND SPRINKLER SYSTEMS I IMITING CONDITION FOR OPERATION 3.7.6.2 The following spray and sprinkler systems shall be OPERABLE:-

a. RCIC Pump Room, Unit 2
b. HPCI Pump Room, Unit 2 C. Upper Cable Spreading Room, Unit 2
d. Lower Cable Spreading Room, Unit 2
e. Diesel Generator A Room
f. Diesel Generator B Room
g. Diesel Generator C Room
h. Diesel Generator D Room
i. Fire Zone 2-3B
j. Fire Zones 2-4A and 2-48
k. Fire Zone 2-5A
1. Fire Zone 0-29B
m. Fire Zone 0"30A APPLICABILITY: Whenever equipment protected by the spray and/or sprinkler systems is requi~ed to be OPERABLE.

ACTION:

a. With one or more of the above required spray and/or sprinkler systems inoperable, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> establish a continuous fire watch with backup fire suppression equipment for those areas in which redundant systems or components could be damaged; for other areas, establish, an hourly fire watch patrol.
b. The provisions of Specification 3.0.3 and 3.0.4 are not applicable.

SUS(UEHANNA - UNIT 2 3/4 7-Za

PLANT SYSTEMS SURVEILLANCE'E UIREHENTS 4.7.6.2 Each of the above required spray and sprinkler systems shall be demonstrated OPERABLE;

a. At least once per 31 days by verifying that each valve, manMal, power operated or automatic, in the flow path is in its correct position.
b. At least once per Z2 months by cycling each testable valve in the flow path through at least. one complete cycle of full travel.
c. At least once per 18 months:

L. By performing a system functional test which includes simulated automatic actuation of the system, and:

a) Verifying that the automatic valves in the flow path actuate to their correct positions on a test signal, and b) Cycling each valve in the flow path that is not testable during plant operation through at least one complete cycle of full travel.

2. By a visual inspection of the dry pipe spray and sprinkler headers to verify their integrity, and
3. By a visual inspection of each deluge nozzle's spray area to verify that the spray pattern is not obstructed.

d.. At least once per 3 years by performing an air or water flow test through each open head spray and sprinkler header and verifying each open head spray and sprinkler nozzle is unobstructed.

SUSQUEHANNA - UNIT 2 3/4 7-22

PLANT SYSTEMS FIRE HOSE STATIONS LIMITING CONOITION FOR OPERATION 3.7.6.5 The fire hose stations shown in Table 3.7. 6.5-1 shall be OPERABLE.

~O APPLICABILITY: Whenever equipment in the boreas protected by the fire hose LR.

ACTION:

a. With one or more of the fire hose stations shown in Table 3.7.6.5-1 inoperable, route an additional fire hose of equal or greater diameter to the unprotected area(s)'rom an OPERABLE hose station within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> if the inoperable fire hose is the primary means of fire suppression; otherwise, route the additional hose within 24'hours.
b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE RE UIREMENTS 4.7.6.5 Each of the. fire hose stations shown in Table 3.7.6.5-1 shall be demonstrated OPERABLE:

a. At least once per 31 days by a visual inspection of the fire hose stations accessible during plant operation to assure all required equipment is at the station.
b. At least once per L8 months by:
1. Visual inspection of the fire hose stations not accessible during plant operation to assure all required equipment is at the. station.
2. Removing the hose for inspection and re-racking for all fire hose stations, and
3. Inspecting all gaskets and replacing any degraded gaskets in the couplings for all fire hose stations.
c. At least once per 3 years by:
1. Partially opening each hose station valve to verify valve

, OPERABILITY and no flow blockage.

2. Conducting a hose hydrostatic test at a pressure of HO psig or at least 50 psig above the maximum fire main operating pressure, whichever is gr'eater.

SUS(UEHANNA - UNIT 2 3/4 7-25

TABLE 3. 7. 6. 5-1 FIRE HOSE STATIONS HOSE RACK LOCATIONS COLUMN NUMBER

a. Control Structure El. 697'-0<< L-26 1HR-01 El. 697I-0<< L-32 2HR-171 El. 714I-0<< L-26 1HR-162 El. 714'-0<< L-31 2HR-162 El. 729I-0 L-25.9 1HR"158 El. 729'-0<< L-32. 1 2HR-158 El. 754'-0<< L-26 1HR-136 El. 754'-0<< L-32 2HR"136 El. 771 I 0<< L-26-- 1HR-125 El. 771'-0<< L-31 2HR-125
b. Reac tor Building El. 645'-0<< R-37. 4 2HR" 271 EI. 645'-0<< U-30. 5 2HR-272 El. 645'-0<< R-30 2HR-273 El. 670'"0<< Q-36 ZHR-261 El. 670'0<< P-30. 3 2HR-262 El. 670'"0<< S-29 683'-0<< 2HR-263 El. Q-36 2HR-251 El . 683'-0<< Q-29 683'-0<< 2HR"252 El. Y-29 2HR"253 El. 719'-1<< Q-36 2HR-241 El. 719 I ~] << S-36 2HR-242 El . 719'"1<< Q-29 2HR"243 El. 719'1<< T-29 2HR"244 El . . 719'1<< 5-30.5 2HR-245 El. 749I~]<< S-36 2HR"231 El. 749'1<< Q-30.5 2HR-232 El. 749'1<< T-29 2HR-233 EL. 779'-1<< Q-36 2HR-221 EL. 779 I <<] << S-34.5 2HR-222 EL. 779'1<< Q-31. 5 2HR-Q3 EL. 779'-1<< U-29 2HR-224 EL. 779 I -1'I T-33 2HR-211 EL. 818'-1<< R-33 2HR-201 EL 818'-1<< U-33 2HR-2)2 0, t &~<mr C, Bu'liCh Og PLo as~'<< /~g <o.e S~~li~al .

yVR- 8(I BL. ~ ggI g<< we~< &~ <<a'i~'ri oHk-8IZ FL.. (y7Cr G

" rJerhR Alod Skaircuefl PAI'R 8II I Ei ~ (7C 6" S&Bree(f pe-FZ2.

H.. 7o8' jJ~fk +Q,traced pgR-SSI

'S'0" MErho@ ~ oHR-Q2 SUSQUEHANNA - UNIT 2 3/4 7"26

3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8. 1 A. C. SOURCES A.C. SOURCES - OPERATING LIMITING CONDITION FOR OPERATION 3.8.1.1 As a minimum, the following A.C. electrical power sources shall be

, OPERABLE:

aO Two physically independent circuits between the offsite transmission network and the onsite Class 1E distribution system, and

b. Four separate and independent diesel generators", each with:

Separate engine mounted day fuel tanks containing a minimum of 325 gallons of fuel,

2. A separate fuel storage system containing a minimum of 47,570 gallons of fuel 3; A separate fuel transfer pump 9>lice> ke<ierAgene~we b)@ed APPLICABILITY: OPERATIONAL CONDITIONS 1, 2, and 3.

ACTION: 8

+ Qr te~~v~

6 6 an~ alqo~g dt~l)A

++g~~ g>grig>K0n ~sic'

~

'a 0 With either one offsite circuit or one diesel gen rator of the above required A.C. electrical power sources inoperable~ demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirements 4.8. l. l. l.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and 4.8. l. 1.2.a.4, for one diesel generator at a time, within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least two offsite circuits and four diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLO SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

b. With one offsite circuit and one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Require-ments 4.8. l.l. l.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and 4.8.1. 1.2.a.4, for one diesel generator at a time, within 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the inoperable A.C. sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN wi'thin the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Restore at least two offsite circuits and four diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLO SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

  • Shared with Unit 1.

SUSQUEHANNA " UNIT 2 3/4 8-1 Amendment No. 19

Prior to but within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of removing any diesel generator from service in order to do work associated with tying in the additional diesel generator, Surveillance Requirement 4.8. 1. 1.2.a.4 shall be performed on the diesel generators which are to remain in service.

When any diesel generator is removed from service in order to do work asso-ciated with tying in the additional diesel generator, the ACTIONS shall read as follows: I With one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C.

sources by performing Surveillance Requirements 4.8. 1.1.l.a within one hour and 4.8. 1. 1.2.a.4, within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> and at least once per, 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> thereafter; restore at least four diesel generators to OPERABLE status within 60 days of accumulated tie-in outage time for all four diesels or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. The provisions of Specification 3.0.4 are not applicable.

b. With one offsite circuit and one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirements 4.8.1.1.1.a within one hour and 4.8.1.1.2.a.4, within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and at least once per 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> thereafter; restore at least two offsite circuits to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. With the two offsite circuits restored to OPERABLE status, follow ACTION a.
c. With one'iesel generator of the above required A.C, electrical power sources inoperable, in addition to ACTION a or b, above, verify within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> that all required systems, subsystems, trains, components and devices that 'depend on the remainihg diesel generators as a source of emergency power are also OPERABLE except as noted in Specification 3.7. 1. 2; otherwise, be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
d. With two of the above required offsite circuits inoperable, demonstrate the OPERABILITY of four diesel generators by performing Surveillance

. Requirement 4.8.1.1.2.a.4, for one diesel generator at a time, within four hours and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter, unless the diesel

. generators are already operating; restore at least one of the inoperable offsite circuits to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. With only one offsite circuit restored to OPERABLE status, restore at least two offsite circuits to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.,

e. With two or more of the above required diesel generators inoperable, demon-strate the OPERABILITY of the remaining A.C. sources by performing Sur-veillance Requirement 4.8.1. l. l.a within one hour and 4.8. 1. 1.2.a.4, for one diesel generator at a time, within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />; restore at least three of the diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the fol-lowing 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. With three diesel generators restored to OPE RABLE status, follow ACTION a.

I'I SUS(UEHANNA UNIT 2 3/4 8"la Amendment No.19; 1

k ELECTRICAL POWER SYSTEMS LIMITING CONDITION FOR OPERATION Continued ACTION (Continued)

Qt Piiy P~TI ~ r 4bWI dth )ittrt9 d~ QCAGfO, itTI 8 ++LC'Cl~ M C. With one diesel gen rator of the above required A.C. electrical power sources inoperable< in addition to ACTION a or b, above, verify within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> that all required systems, subsystems, trains, components and devices that depend on the remaining diesel generators as a source of emergency power are also OPERABLE; otherwise, be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

d. With two of the above required offsite circuits inoperable, demonstrate the OPERABILITY of four diesel generators by performing Surveillance Requirement 4.8. 1. 1. 2. a.4, for one diesel generator at a time, within four hours and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter, unless the diesel generators are already operating; restore at least one of the inoper-able offsite circuits to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. With only one offsite circuit restored to OPERABLE status, restore at least two offsite circuits to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />,
e. With two or more of the above required diesel generators inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirement 4. 8. l. l. l. a within one hour and 4.8. 1. 1.2.a.4, for one diesel generator at a time, within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least three of the die'sel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. Restore four diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

SUS(UEHANNA " UNIT 2 3!4 8-2

ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREHENTS 4.8. 1. 1. 1 Each of the above required independent circuits between the offsite transmission network and the onsite Class 1E distribution system shall be:

aO Determined OPERABLE at least once per 7 days by verifying correct breaker alignments and indicated power availability, and

b. Demonstrated OPERABLE at least once per 18 months during shutdown by transferring, manual.ly and automatically, unit power supply from the normal circuit to the alternate circuit.

4.8.1.1.2 Each of the above required diesel generators shall be demonstrated OPERABLE:

In accordance with the frequency specified in Table 4.8.1.1.2-1 on a STAGGERED TEST BASIS by:

l. Verifying the fuel level in the engine-mounted day fuel tank.
2. Verifying the fuel level in the fuel storage tank. .
3. Verifying the fuel transfer pump starts and transfers. fuel from the storage system to the engine-mounted .day fuel tank.
4. Verifying the diesel starts from ambient condition and accel-erates to at least 600 rpm in less than or equal to 10 seconds.

The generator voltage and frequency shall be 4160 a 400 volts and 60 R 3.0 Hz within 10 seconds after the start signal. The diesel generator shall be started for this test by using one of the following signals:

a) Manual.

b) Simulated loss of offsite power by itself.

c) Simulated loss of offsite power in conjunction with an ESF actuation test signal.

An ESF actuation test signal by itself.

5. Verifying the diesel generator is synchronized, loaded to greater than or:equal to 4000 kw in. less than or equal to 90 seconds, and operates with this load for at least 60 minutes.
6. Verifying the diesel generator is aligned to provide standby

,power to the associated emergency busses.

7. Verifying the pressure in all diesel generator air start receivers to be greater than or equal to 240 psig.
b. At least once per 31 days and after each operation of the diesel where the period of operation was greater than or equal to 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> by checking for and removing accumulated water from the engine-mounted day fuel tanks.

SUSQUEMANNA - UNIT 2 3/4 8-3

ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREMENTS Continued C. At least once per 92 days and from new fuel oil prior to.addition to the storage tanks by verifying that a sample obtained in accordance with ASTM-0270-1975 has a water and sediment content of less than or equal to 0.05 volume percent and a kinematic viscosity 8 40 C of greater than or equal to 1.3 but less than or equal to 2.4 for 10 oil ot >1.9 but <4.1 for 2D oil when tested in accordance with ASTM-0975-77, and an impurity level of less than 2 mg of .insolubles per .100 mL when tested in accordance with ASTM-02274-70.

d. At least once per 18 months by:
1. Subjecting the diesel to an inspection in accordance with procedures prepared in conjunction with its manufacturer's recommendations for this class of standby service.
2. Verifying the diesel generator capability to reject a load of greater than or equal to 1425 kW while maintaining voltage at 4160 t 400 volts and frequency at 60 ~ 3.0 Hz.
3. Verifying the diesel generator capability to reject a load of 4000 kW without tripping. The generator voltage shall not exceed 4560 volts during and following the load, rejection.
4. Simulating a loss-of-offsite power by itself, and:

a) Verifying deenergization of the emergency busses and load shedding from the emergency busses.

b) Verifying the diesel generator starts on the auto-start signal, energizes the emergency busses with permanently connected loads within 10 seconds and operates for greater than or equal to 5 minutes while its generator is loaded with the shutdown loads. After energization, the steady state'oltage and frequency of the emergency busses shall be maintained at 4160 t 400 volts and 60 t 3.0 HzAuring this test.

5.. Verifying that on an ECCS actuation test signal, without loss-of-offsite power, the diesel generator starts on the auto-start .

signal and operates on standby for'reater than or equal to 5 minutes. The generator voltage and frequency shall be 4160 t 400 volts and 60 t 3.0. Hz within, 10 seconds after the auto-start signal; the steady state generator voltage and frequency shall be maintained within these limits during this test.

SUS(UEHANNA - UNIT 2 3/4 8-4

ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREMENTS Continued

6. Simulating a loss-of-offsite power in conjunction with an ECCS actuation test signal, and:

a) Verifying deenergization of the emergency busses and load shedding from the emergency busses.

b) Verifying the diesel'enerator starts on the auto-start signal, energizes the emergency busses with permanently connected loads within 10 seconds, ene~gizes the auto-connected loads through the load timers and operates for greater than'r equal to 5 minutes while its generator is loaded with the emergency loads. After energization, the steady state voltage and frequency of the emergency busses shall be maintained at 4160 a 400 volts and 60 a 3.0 Hz during this test.

c) Verifying that all automatic diesel generator trips, except engine overspeed, generator differential and engine low lube oil pressure, are automatically bypassed upon loss of voltage on the emergency bus concurrent with an ECCS actuation signal.

7.. Verifying the diesel generator operates for at least 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Ouring the first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of this test~ the diesel generator shall be loaded to greater than or equal to 4700 kw and during the remaining 22 hours2.546296e-4 days <br />0.00611 hours <br />3.637566e-5 weeks <br />8.371e-6 months <br /> of this t6st, the diesel generator shall be loaded to 4000 kW. The generator voltage and frequency shall be 4160 4 400 volts and 60 k 3.0 Hz within 10 seconds after the start"signal; the steady state generator voltage and frequency shall be maintained within these limits during this test. Within 5 minutes after completing this 24-hour test, perform Surveillance Requirement 4.8.1.1.2.d.4.b)."

8. Verifying that the auto-connected loads to each diesel generator j hard>i~l @naca~ do.not exceed the 2000-hour rating of 4700 kW~

Ap,c. 4b an4 Wc eneMnuoo a re+i ng H soco gu) 0 c 9. Verifying thediesel generator's capability to:

gi~i qeeceke~ 6-a) Synchronize with the offsite power source while the

. generator is loaded with its emergency loads upon a simulated restoration of offsite power,,

b) Transfer its loads to the offsite power source, and c) 'e restored to its standby status.

"If Surveillance Requirement 4.8.1.1.2.d.4.b) is not satisfactorily completed, it is not necessary. to repeat the preceding 24-hour test. Rather, the diesel generator may be operated at 4000 kW for 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or until operating temperature has stabilized.

SUSQUEHANNA - UNIT 2 3/4 '8-5

ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREMENTS Continued

.10. Verifying that with the diesel generator 'operating in a test mode and connected to its bus, a simulated ECCS actuation signal overrides the test mode by (3.) returning the diesel generator to standby operation, and (2) automatically energizes the emergency loads with offsite power.

4ucA-,sewerage-tan Verifying that each diesel generator loading sequence timer shown in Table 4.8.1.1.2-2 is OPERABLE with its setpoint within t 10K of its design setpoint.

(Zs i Verifying that the following diesel generator lockout features prevent diesel generator starting and/or operation only when I required:

I a) Engine overspeed.

b) Generator differential.

c) Engine low lube oil pressure.

e. At. least once per 10 years or after any modifications which could affect diesel generator interdependence by starting all diesel generators simultaneously, during shutdown, and verifying that all diesel generators accelerate to at least 600 rpm in less than or equal to 10 seconds.

f; "At least once per 10 years by: .

1. Oraining each fuel oil storage tank, removing the accumulated sediment and cleaning the tank using a sodium hypochlorite or equivalent solution, and
2. Performing a pressure test of those portions of the diesel fuel

~sea' oil system designed to Section III, subsection ND of the ASME Code in accordance with ASME Code Section XI Article IN"5000.

3;e,i. i.<

<Wh+A-.3. ~ge orts - A1'I dfese1 generator ra) lures'valid,or nonvalfd, sha11 be reported.to the Commission in a Special Report pursuant to Specification 6.9.2 within 30 days; Reports of diesel generator failures shall include the informa-tion recommended in Regulatory Position C.3.b of Regulatory Guide 3..108, Revis-ion I, August 2977. If the number of failures in the last 100 valid tests, on a per nuclear unit basis, is greater than or e ual to 7, the report shall be supplemented to include the additional informa ion recommended in Regulatory Position C.3.b of Regulatory Guide 1.108, Revi ion 1, August 1977.

4~ aogo<red de~i 9~ .

SUS)UEHANNA - UNIT 2 3/4 8-6

C TABLE 4.8.1.1.2-1 DIESEL GENERATOR TEST SCHEDULE Number of Failures in Last 100 Valid -Tests" C6 Test Fre uen At least once per 31 days At least once per 14 days At least once per 7 days

> 4 At least once per 3 days "Criteria for determining number of failures and number of valid tests shall be in accordance with Regulatory Position C.2.e of Regulatory Guide 1. 108, Revision 1, August 1977, where the last 100 tests are determined on a per nuclear unit basis. For the purposes of this test schedule, only valid tests conducted after the OL issuance date shall be included in the computation ap)cwind of the "last 100 valid tests." Entry into this test schedule shall be made at the 31 day test frequency.

e

~4r 6 no)eflyM ~Ac /4M gE'is c'ihukon )

Qh~ii cfires f

+ b ~'~ ~ ~~~f~f i0 gglQves fbi d~wiiiio) ltd A<~

keg,uemu) of hce diesel gwerakers <~O><~ ~ b~ ~~~"

SUS(UEHANNA - UNIT 2 3/4 8-7

TABLE 4.8.1.1.2-2 UNIT I AND UNIT 2 DIESEL GENERATOR LOADING TIMERS DEVICE TAG TIME NO. SYSTEM LOCATION SETTING 62A-20102 RHR Pump IA IA201 3 sec 62A-20202 RHR Pump IB IAZOZ 3 sec 62A-20302 -

RHR Pump IC IA203 3 sec 62A-20402 RHR Pump ID IAZ04 3 sec 62A"20102 RHR Pump 2A 2A201 3 sec 62A"20202 RHR Pump ZB 2A202 3 sec 62A-20302 RHR Pump 2C 2A203 3 sec 62A"20402 RHR Pump 2D 2A204 3 sec K116A CS pp IA IC626 10.5 sec K116B CS pp IB IC627 10..5 sec K125A CS pp IC IC626 10.5 sec K125B CS pp. ID IC627 10.5 sec K116A CS pp 2A 2C626 10.5 sec K116B CS pp 2B 2C627 10.5 sec K125A CS pp 2C 2C626 10;5 sec K125B CS pp 2D ZC627 10.5 sec 62AX2-20108 Emergency Service Water (ESW) IA201 40 sec 62AX2-20208 Emergency Service (ESW) IA202 40 sec 62AX2-20303 Service Water Water'mergency (ESW) IA203 44 sec 62AXZ"20403 Emergency Service Water (ESW) IA204 M sec 62X3-20304 Control Structure OC877A 60 sec Chilled Water System 62X3-20404 Control Structure OC877B 60 sec Chilled Water System 62X"20104 Emergency Switchgear*Rm OC877A 60 sec Cooler A 8 RHR SW pp H4V Fan A SUSQUEHANNA - UNIT 2 3/4 '8-8

TABLE 4.8.1.1.2-2 (Continued).

UNIT 1 AND UNIT 2 DIESEL GENERATOR LOADING TIMERS DEVICE TAG TIME NO. SYSTEM LOCATION SETTING 62X-20204 Emergency Switchgear Rm OC877B 60 sec Cooler B 8 RHR SW pp SkV'an 8

262X-20104 Emergency Switchgear Rm 0C877A 120 sec Cooler A 262X-20204 Emergency Switchgear Rm OC8778 120 sec Cooler B f 62X-516 OG Rm Exh Fan A OB516 2 IlllA 4 62X"526 DG Rm Exh Fan B OB526 2 min 4 62X-536 OG Rm Exh Fan C OB536 2 AllA

~ 62X-546 OG Rm Exh Fan 0 OB546 2 miA

~S+g7 62X1-20304 Control Structure OC877A 3 min Chilled Water System 62X1"20404 Control Structure OC877B 3 mlA Chilled Water System 62X2-20310 Control Structure OC876A 3 min Chilled Water System 62X2-20410 Control Structure OC876B 3 min Chilled Water System'ontrol 62X2-20304 Structure OC877A 3.5 min Chilled Water System 62X2-20404 Control Structure OC877B 3.5 min

'hilled Water System 62X-K11AB Emergency Switchgear 2CB250A 260 sec Rm Cooling Compressor A 62X-K11BB Emergency Switchgear 'm 2CB250B 260 sec Cooling Compressor B ~

~

lE C@-5~2.A CRg- 5lESZA k tE2X-5g65A 0 ts2%- sl,55~A

~

P4 gEM

~~

'ROOn MPqy

%VV' ROOn 8'XWVSV Fm GS l-~

RiEE 9,ooln 8xwAsm Fan 8'l CX 0$ 545 OB<b<

a&54 5',

0 55'&5 IYlln 3 colin

+4+

%k'lain

+ gheq asoou~wd d<m<l general'd~>s+

SUS(UEHANNA - UNIT 2 3/4 8-9 OPemam Qg, K4Ms

~~Y C~ e~

INSERT A 4.8.1.1.3 When substituting diesel generator E for diesel generator A,B,C or D, diesel generator E shall be demonstrated OPERABLE by:

a. Verifying diesel generator E energizes the appropriate emergency bus.
b. Verifying that at least once within the previous 31 days the following have been verified:
1. The fuel level in the engine-mounted day fuel tank.
2. The fuel level in the fuel storage tank.
3. The fuel transfer pump started and transferred fuel from the storage system to the engine-mounted day fuel tank.
4. The diesel manually started from ambient condition and accelerates to at least 600 rpm in less than or equal to 10 seconds. The generator voltage and frequency were 4160 + 400 volts and 60 + 3.0 Hz within 10 seconds after the start signal.
5. The diesel generator was synchronized, loaded to greater than or equal to 4000 kw in less than or equal to 90 seconds, and operated with this load for at least 60 minutes.
6. The pressure in the diesel generator air start receivers to be greater than or equal to 240 psig.

c~ Verifying that at least once within the previous 31 days and after each operation of the diesel, within the previous 31 days, where the period of operation was greater than or equal to 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> that a check was made for accumulated water from the engine-mounted day fuel tanks.,

d. Verifying that at least once within the previous 92 days and from new fuel oil prior to addition to the storage tanks that a sample obtained in accordance with ASTM-D270-1975 has a water and sediment content .,of'ess than or equal to .05 volume percent and a kinematic viscosity 8 40'C of greater than or equal to 1.3 but less than or equal to 2.4 for 1D oil or 1.9 but 4.1 for 2D oil when tested in accordance with ASTM-D975-77, and an impurity level of less than 2 mg. of insolubles per 100 ml. when tested in accordance with ASTM-D2274-70.
e. Verifying that at least once within the previous 18 months if specification 4.8.1.1.2.d has not been performed:

An inspection in accordance with procedures prepared in conjunction with its manufacturer's recommendations for this class of standby service was performed.

I

2. The diesel generators capability to reject a load of greater than or equal to 1425 kw while maintaining voltage at 4160 + 400 volts and frequency at 60 + 3.0 Hz was tested.

F v l1 'I' h h rd I 'h h

~ Ik I

v I' ~ I, h v f h

~

II). I'.e r h

~ h k

~ I ~ J ~

I h h h

li I'h 'l

~

'I h,h,kl h F h

3. The diesel generators capability to reject a load of 4000 kw without tripping. The generator voltage shall not exceed 4360 volts during and following the load rejection was tested.
4. The diesel generator operated for at least 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. During the first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of this test, the diesel generator was loaded to greater than or equal to 4700 kW and during the remaining 22 hours2.546296e-4 days <br />0.00611 hours <br />3.637566e-5 weeks <br />8.371e-6 months <br /> of this test, the diesel generator was be loaded to 4000 kW. The generator voltage and frequency shall be 4160 + 400 volts and 60 + 3.0 Hz within 10 seconds after the start signal; the steady state generator voltage and frequency were maintained within these limits during this test.
5. The following diesel generator lockout features prevented diesel generator starting and/or operation only when required:

a) Engine overspeed.

b) 'Generator differential.

'ngine low lube oil pressure. ')

6. Either:

'hat E

"a) on a rotational basis, diesel generator E was substituted for diesel generator A, B, C, or D and a .

loss-of-offsite power was simulated in conjunction with an ECCS actuation test signal and:

i) Diesel generator E started on the auto start signal, energized the emergency busses with permanently connected loads within 10 seconds, energized the auto-connected loads through the load timers and operated for greater than or equal to 5 minutes while its generator is loaded with the emergency loads.

After energization, the steady state voltage and frequency of the emergency busses were maintained at 4160 + 400 volts and 60 + 30 Hz during this test, and ii) With the diesel generator operating in a test mode and connected to its bus, a simulated ECCS actuation signal overrode the test mode by (1) returning the diesel generator to standby operation, and (2) automatically energizes the emergency loads with off-site power; or b) That by simulating a loss-of-offsite power in conjunction with an ECCS actuation test signal and:

i) Diesel generator E started on the auto start signal, energized the simulated emergency bus with simulated permanently connected loads within 10 seconds, energized the simulated auto-connected loads and operated for greater than or equal to 5 minutes while

Ig l 1

S t

s I '

its generator is'oaded with the simulated emergency loads. After energization, the steady state voltage and frequency of the emergency busses were maintained at 4160 + 400 volts and 60 + 3.0 Hz during this test, and ii) On a rotational basis, diesel generator E was substituted for diesel generator A, B, C, or D and verify that diesel generator E energized the appropriate emergency bus.

e. Verifying that once per 10 years if Specification 4.8.1.1.2f has not been performed:
1. The fuel oil storage tank has been drained, removing the accumulated sediment and cleaned using a sodium hypochlorite or equivalent solution, and
2. A pressure test of those portions of the diesel fuel oil system designed to Section III, subsection ND of the ASME Code in accordance with ASME Code Section II Article IWD-5000 has been performed.

dew/msa202345i

>>I h II 3~

31

>>I >>P>>

<<3 '

III 43, ),>>

I>> I

ELECTRICAL POWER SYSTEMS A.C. SOURCES - SHUTDOWN LIMITING CONOITION FOR OPERATION 3.8.1.2 As a minimum, the following A.C. electrical power sources shy]1 be OPERABLE:

a. One circuit between the offsite transmission network and the onsite Class 1E distribution s stem, and g.sc,h othe Ave sepelge. b. Two diesel generators with:
l. An engine mounted da fuel tank containing a minimum of 325 gallons of fue ~d~i9 ~~b~ga,l..~o;>~qo,q~~l~so4&elk>>dI~l ~~~W>> <,
2. A fuel storage system containing a minimum of 47,570 gallons of fuel.
3. A fuel transfer pump.

APPLICABILITY: OPERATIONAL CONDITIONS 4, 5 and ".

ACTION:

ao With less than the above required A.C. electrical power sources OPERABLE, suspend CORE ALTERATIONS, handling of irradiated fuel in the secondary containment,'perations with a potential for draining the reactor vessel and crane operations over the

'spent fuel pool when fuel assemblies are stored therein. In addition, when in OPERATIONAL CONOITION 5 with the water level less than 22 feet above the reactor pressure vessel flange, immediately initiate corrective action to restore the required power sources to OPERABLE status as soon as practi'cal.

b. The provisions of Specification 3.0.3 are not applicable.

SURVEILLANCE RE UIREMENTS 4.8.1.2 At least the above required A.C. electrical power sources shall be demonstrated OPERABLE per Surveillance Requirements 4.8.1.1.1, 4.8.1.1.2 and

, except for the requirement of 4.8.1.1.2.a.5.

4 e.),l 4 hen handling srradiated fuel in the secondary containment..

SUS)UEHANNA - UNIT 2 3/4 8-10

ELECTRICAL POWER SYSTEMS 3/4.8.2 D.C. SOURCES D.C. SOURCES - OPERATING LIMITING CONDITION FOR OPERATION

. 3.8.2.1 As a minimum, the following D.C. electrical power sources shall be OPERABLE:

a. Division I, consisting of:

Load group Channel "A" power source consisting of:

a) 125-volt D.C. battery bank 10610", 20610 b) Full capacity charger 1D613", 20613

2. Load group Channel "C" power source consisting of:

'a) 125-volt D.C. battery bank ~

10630", 20630 b) Full capacity charger 10633", 2D633

3. Load .group "I" power source .consisting of:

a) 250-volt D.C. battery 2D650 b) Half-capacity chargers 20653A, 20653B

4. Load group "I" power source consisting of:

a)

.b)'wo t 24-volt D.C. battery bank 2D670 half-capacity chargers 20673, 20674

b. Division II, consisting of:

Load group Channel "B" power source consisting of:

a) 125-volt D.C. battery bank 10620", 20620 b) Full capacity cha'rger 10623", 20623

2. Load group Channel "0" power source consisting of:

a) 125-volt 0. C. battery bank 1D640", 20640 b) Full capacity charger 10643", 2D643

3. Load group "II" power source consisting of:

a) 250-volt D.C. battery bank 2D660 b) Full capacity charger 2D663

4. Load group "II" power source consisting of:

a) a 24-volt D.C. battery bank 20680 b) Two half-capacity chargers 20683, 2D684 APPLICABILITY: OPERATIONAL CONDITIONS 1, 2, and 3

. ACTION:

With one of .the above required Unit 2 125-volt or 250-volt D.C. load group battery banks inoperable, restore the inoperable battery bank to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

  • Not required to be OPERABLE when the requirements of ACTION b have been satisfied.

SUSQUEHANNA - UNIT 2 3/4 8-11 Amendment No. 7

Insert A c.

~ Diesel Generator E 1.~ Load group power source, consisting of:

a) 125 volt DC battery bank OD595 b) Full capacity charger OD596

ELECTRICAL POWER SYSTEMS LIMITING CONOITION FOR OPERATION Continued ACTION: (Continued}

b. With one or more of the above required Unit 1 125-volt O.C. load group battery banks inoperable, within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> either:
1. Restore the inoperable battery bank(s) to OPERABLE status, or
2. Transfer the common loads aligned to the inoperable Unit 1 battery bank(s) to the corresponding Unit 2 battery bank(s).

Otherwise, declare the comnon loads aligned to the inoperable Unit 1 battery bank(s) inoper'able and take the ACTION required by the applicable, Specification(s).

C. Nlth one of the above required m 24-volt D.C. load group battery banks inoperable, declare the associated equipment inoperable and take the ACTION required by the applicable Specification(s).

QtvEEbl~~ or QvisimXC With one of the above required chargers inoperable, demonstrate the 58K gpsmtr sb ~ e, g

l1 ~

OPERABILITY of its associated battery bank by performing Surveillance Requirement 4.8.2. 1a.l. within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If any Category A limit in Table 4.8.2.1-1 is not met, declare the battery inoperable.

SURVEILLANCE RE UIREHENTS 4.8.2.1 Each of the above required and chargers shall be demonstrated OPERABLE:

i 24-volt, 125-volt, and 250-volt batteries

a. At least once per 7 days by verifying that:
1. The parameters in Table 4.8.2. 1-1 meet the Category A limits, and
2. There is correct breaker alignment to the battery chargers, and total battery terminal voltage is greater than or equal =to 26, 129, 258 volts on float charge.

k

b. At least once per 92 days and within 7 days after a battery discharge with battery terminal voltage below 22, 110, or 220 volts, as applic-able, or battery overcharge with battery terminal voltage above 30, 150 or 300 volts, as applicable, by verifying that:

I. The parameters in Table 4.8.2.1-1 meet the Category B limits,

2. There is no visible corrosion at either terminals or connectors, or the connection resistance of these items is less than 150 x 10-6 ohm, and
3. The average electrolyte temperature of 4, 10, or 20, as applicable, of connected cells for the 24, 125, and 250 volt batteries is above 600F.

SUS(UEHANNA - UNIT 2 3/4 8"12 Amendment No. 7

Insert B

'ith the above required diesel generator E 125 volt DC load group battery bank inoperable and diesel generator E not aligned to the Class 1E distribution system, restore the battery bank to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or verify that all ESW valves associated with diesel generator E are closed and diesel generator E is not running within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. The provisions of Specification 3.0.4 are not applicable.

With the above required diesel generator E 125 volt DC load group battery bank inoperable and diesel generator E aligned to the Class 1E distribution system, restore the battery bank to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or declare diesel generator E inoperable and take the ACTION required by specification 3.8.1.1.

With the above required diesel generator E 125 volt DC charger inoperable and diesel generator E aligned to the Class lE distribution system, demonstrate the OPERABILITY of the associated battery bank by performing Surveillance Requirement 4.8.2.l.a.l within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If any Category A limit in Table 4.8.2.1-1 is not met, declare diesel generator E inoperable and take the ACTION required by specification 3.8.1.1.

With the above required diesel generator E charger inoperable and diesel generator E not aligned to the Class 1E distribution system, demonstrate the OPERABILITY of its associated battery bank by performing Surveillance Requirement 4.8.2.1.a.l within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If any Category A limit in Table 4.8.2.1-1 is not, met, declare the battery inop'erable, and take the ACTION required by specification 3.8.2.1.8.':'he~ provisions of Specification 3.0.4 are not applicable.

~'

~ I' dy 1

Id

~ ~

I'

~ ~

I ~

E le I I E

,r. )t

~ >> I"

~ f E F ~

dd ~ ~

~/0 F I

~" I ll t >Ft II

ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREMENTS Continued C. At least once per 18 months by verifying that:

1. The cells, cell plates, and battery racks show no visual indica-tion of physical damage or abnormal deterioratiog,
2. The cell-to-cell and terminal connections are clean, tight, free of corrosion, and coated with anticorrosion material, 3.'he resistance of each cell-to-cell and terminal connection of each 125-volt and 250-volt battery is less than or equal to 150 x 10-e ohm, and
4. The battery charger, for at least 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, will supply at least:

a) For the + 24-volt batteries, 25 amperes at a minimum ofi dj sos Uss itduoil. dLssel 25.7 volts.

genera 6 0nWm) b) For the 125-volt batteries, 100 amperes at a minimum of g60arnperes 4 amtat~ue 127.8 volts.

$ A. l 8 vol&. c) For the 250"volt batteries, 300'amperes at a minimum of 255.6 volts.

d. At least once per 18 months by verifying that either:
1. The battery capacity is adequate to supply and maintain in OPERABLE status all of the actual emergency loads for the design duty cycle when the battery is subjected to a battery service test, or
2. The battery capacity is adequate to supply a dummy load of the following profile, which is verified to be greater than the actual emergency loads, while maintaining the battery terminal voltage greater than or equal to + 21, 105 or 210 volts, as applicable.

a) For + 24"volt battery banks 20670, 20670-1, 2D680, and 20685-1, 9.37 amperes'or the entire 4-hour test.

b) For 125-volt batteries:

1) Channel "A" battery 10612: 325 amperes for 60 seconds 107 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test
2) Channel "8" battery 10622: 323 amperes for 60 seconds l) Ceasel"N bakrfdbPlm: . 105 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test
3) Channel "C" battery 1D632: 340 amperes for 60 seconds 2et'+pe~ kc %~~tel bbaecedi 121 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test 85awpees +~+4~62Nnii>~+ 4) Channel "0" battery 1D642: 323 amperes for 60 seconds l55aeqO~ &4O leak ~i'm@ 4 104 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.
5) Channel "A" battery 20612: 328 amperes for 60 seconds 112 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test
6) Channel "8" battery 20622: 326 amperes for 60 seconds 110 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test
7) Channel "C" battery 2D632: 343 amperes for 60 seconds 128 ampers for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test
8) Channel "0" battery 2D642: 326 amperes for 60 seconds 111 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test

'l SUS(jUEHANNA - UNIT 2 3/4 8"13 Amendment No.

ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREMENTS Continued c) For 250-volt batteries:

1) Battery bank 20650:

458 amperes for 60 seconds 251 amperes for 239 minutes

') Battery bank 1119 amperes 2D660:

for 60 seconds 244 amperes for 239 minutes

e. At least once per 60 months by verifying that the battery capacity is at least 80K of the manufacturer's rating when subjected to a per-formance discharge test. Once per 60-month interval, this performance discharge test may be performed in lieu of the battery service test.
f. Annual performance discharge tests of battery capacity shall be given to any battery that shows signs of degradation or has reached 85X of the service life expected for the application. Degradation is indicated when the battery capacity drops more than 10K of rated capacity from its average on previous performance tests, or is below 90'f the manufacturer's rating.

SUS(UEHANNA - UNIT 2 3/4 8-14

TABLE 4.8.2.1-1 BATTERY SURVEILLANCE RE UIREMENTS CATEGORY A(1) CATEGORY B~ )

arameter Limits for each Limits for each Allowable designated pilot connected cell value for each cell connected cell lectrolyte >Minimum level >Minimum level Above top of evel indication mark, indication mark, plates, and < 4" above and < 4" above and not maximum level maximum level overflowing indication mark indication mark loat Voltage > 2.13 volts > 2.13 volts > 2.07 volts Not more than 0.020 below th average of all connected cell ravity'verage pecifig )

connected of all cells Average connected of all

(')

cell

> Z.205( )

(a) Corrected for electrolyte temperature and level.

(b) Or battery charging current is less than 0.01, 0.1 and 0.25 amperes for .

the a24, 125 and 250 volt batteries respectively, when on float cha~ge.

(c) May be corrected for average electrolyte temperature.

(1) For any Category A parameter(s) outside the limit(s) shown, the battery may be considered OPERABLE provided that within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> all the Category B measurements are taken and found to be within their allowable values, and provided all Category A and B parameter(s) are restored to within limits within the next 6 days.

(2) For any Category B parameter(s) outside the limit(s) shown, the battery may be considered OPERABLE provided that the Category B parameters are within their allowable values and provided the Category B parameter(s) are restored to within limits within 7 days.

(3) Any Category B parameter not within its allowable value indicates an inoperable battery.

SUS(UEHANNA - UNIT 2 3/4 8-15

ELECTRICAL POWER SYSTEMS O.C. SOURCES - SHUTDOWN LIMITING CONDITION FOR OPERATION 3.8.2.2 As a minimum, Division I or Division II of the D.C. electrical power sources .shall be OPERABLE with: and di diesel el 9cnara4ar E

'n

a. Division I consisting of:
1. Load group Channel "A" power source, consisting of:

a) 125-volt D.C. battery bank 10610"", 20610 b) Full capacity charger 10613"", 20613

2. Load group Channel "C" power source, consisting of:

a) 125-volt D.C. battery bank 10630"", 2D630 b) Full capacity charger 1D633"", 20633

3. Load group "I" power source, consisting of:

a) 250-volt D.C. battery bank 2D650 b) Half-capacity chargers 2D653A, 20653B

4. Load 'group "I" power source, consisting of:

a) k 24-volt O.C. battery bank 20670 b) Two half-capacity chargers 20673, 20674

b. Division II consisting of:
1. Load group Channel "B".power source, consisting of:

a) 125-volt O.C. battery bank 10620"", 20620 b) Full capacity charger 10623"", 20623

2. Load group Channel "0" power source, consisting of:

a), 125-volt O.C: battery bank 10640"*, 20640 b). Full capacity charger 10643"", 2D643

3. Load group "II" power source, consisting of:

a) 250-volt D.C. battery bank 20660 b) Full capacity charger 20663

4. Load group "II" power source, consisting of:

%88 a) i 24-volt D.C. battery bank 20680

~sacr i4 +-Q. b) Two half-capacity chargers 2D683, 20684 APPLICAB ILITY: OPERATIONAL CONDITIONS 4, 5, and ".

ACTION: - Division%.(~~ o~ 5ivisim K,(8argb~)

a~ With less than the above required Unit 2 125-volt and/or 250-volt D.C.

load group battery banks OPERABLE, suspend CORE ALTERATIONS, handling of irradiated fuel in the secondary containment and operations with a potential for draining the reactor vessel.

"When handling irradiated fuel in the secondary containment.

  • "Not required to be OPERABLE when the requirements of ACTION b have been satisfied.

SUSQUEHANNA - UNIT 2 3/4 8-16 Amendment No. 7

Insert A c.

~ Diesel Generator E 1.~ Load group power source, consisting of:

a) 125 volt DC battery bank E

OD595 b) Full capacity charger ' OD596

0 1

) ~ I fg

ELECTRICAL POMER SYSTEHS LIHITING CONDITION FOR OPERATION Conti nued ACTION: ICnnttnnnd)

b. Wth less than the above required Unit 1 125-volt O.C. load group battery banks OPERABLE, either:
1. Suspend CORE ALTERATIONS, handling of irradiated fuel in the secondary containment and operations with a potential for drain-ing the reactor vessel, or
2. Transfer the coilaon loads alfgned to the inoperable Unit 1 battery bank(s) to'the corresponding Unit 2 battery bank(s).

Otherwise, declare the coaeon loads aligned to the inoperable Unit 1 battery bank(s) inoperable and take the ACTION required by the applfcabli Specfffcatfon(s).

c Nth the above required 0 24-volt D.C. load group battery banks inoperable, declare the associated equipment inoperable and take Dtvisio T (~Tetst) <It the ACTION required by the applicable Specification(s).

5> vision 0-t~~bl d. Nth the above required charger(s) inoperable,,demonstrate the OPERABILITY of the associated battery by performing Surveillance Requfrement 4.8.2. l.a.l within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If any Category A limit in Table 4.8.2.1-1 is not met, declare the battery inoperable.

The provisions of Specification 3.0.3 are not applicable.

S~ gt

~IS~ h A SURVEILLANCE RE UIREHENTS 4.8.2.2 At least the above required battery and charger shall be demonstrated OPERABLE per Surveillance'Requirement 4. 8.2. 1.

SUS(UEHANNA - UNIT 2 3/4 8-17 Amendment No. 7

Insert B

f. With the above required diesel generator E 125 volt DC load group battery bank inoperable and diesel generator E not aligned to the Class 1E distribution system, restore the battery bank to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or verify that all ESW valves associated with diesel generator E are closed .and diesel generator E is not running within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. The provisions of Specification 3.0.4 are not applicable.
g. With the above required diesel generator E 125 volt DC load group battery bank inoperable and diesel generator E aligned to the Class 1E distribution system, restore the battery bank to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or declare diesel generator E inoperable and take the ACTION required by specification 3.8.1.1.
h. With the above required diesel generator E 125 volt DC charger inoperable and diesel generator E aligned to the Class lE distribution system, demonstrate the OPERABILITY of the associated battery bank by performing Surveillance Requirement 4.8.2.l.a.l within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If any Category A limit in Table 4.8.2.1-1 is not met, declare diesel generator E inoperable and take the ACTION required by specification 3.8.1.1.

With the above required diesel generator E charger inoperable and diesel generator E not aligned to the Class 1E distribution system, demonstrate the OPERABILITY of its associated battery bank by performing Surveillance Requirement 4.8.2.l.a.l within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If any Category A limit in Table 4.8.2.1-1 is not met, declare the battery inoperable, and take the ACTION required by specification 3.8.2.1.f. The provisions of Specification 3.0.4 are not applicable.

<<<<. 'I x I 1 It I ~ g- R I'

V I, II I<<

'I I

<< I<<

I' 1 1 <<r II IX C I

I, I

1 1

I x I I \

<< I It I

'I I

ELECTRICAL POMER SYSTEMS 3/4.8.3 ONSITE PNER OISTRIBUTION SYSTEMS OISTRI1NTION - OPERATING LIMITINQ CQNmON FOR OPERATION 3.8.3. 1 The following power distribution systea divisions shall be energized with tfe breakers open both between redundant buses within the unit and between units at the sale station:

a. A.C. power dfstrfbutfon:
1. Ofvfsion I, consfsting of:

a) Load group Channel "A", consisting of:

1) 4160-volt A.C. swftchgear bus V201, 2A201
2) 480-volt A.C. load center 18210, 28210
3) 480-volt A.C. motor control center 08516 b) Load group Channel "C",, consisting of:
1) 4160-volt A.C. switchgear bus 1A203, 2A203
2) 480-volt A.C. load center 18230, 2B230
3) 480-volt A.C. motor control center OB536 HB&&

Arvioo~ ebaep: Sdnu8cd N<er h.a-zs~z as p op~ e) Isolated 480 volt A.C. swing bus, includfng: 2B219 4teadrnmk >yg 1) Preferred power source

2) Preferred power source HG set S EE 3) Alternate power source
4) Automatic transfer switch Zn/5ew7 2. Oivision II, consisting of:

a) Load group Channel"8", consisting of:

1) 4160-volt A.C. switchgear bus IA202, 2A202
2) 480-volt A.C. load center 18220, 28220
3) 480-volt A.C. motor control center 08526 b) Load group Channel "0", consisting of:
1) 4160-volt A.C. switchgear bus lA204, 2A204
2) 480-volt A.C. load center H240, 28240
3) 480-volt A.C. motor control center 08546 centers MR+7 N4M-.Bats.

e) Isolated 480 volt A.C. s~ing bus, including: 28229

1) Preferred gower sour ce
2) Preferred power source MG set
3) Alternate power source
4) Automatic transfer switch gg&

~cgRc C, +p SUS(UEHANNA - UNIT 2 3/4 8-18 Amendnent No. 14

INSERT A

a. A.C. power distribution:

Division I, consisting of:

a) Load group Channel "A", consisting of: Nlr~ CHA>ICg

1) 4160-volt A.C. switchgear bus 1A201, 2A201, O>A Sit>a
2) 480-volt A.C. load center 1B210, 2B210
3) 480-volt A.C. motor control centers OB516, OB517>

1B216, 2B216 1B217, 2B217

4) 208/120-vo'lt A.C. instrument panels 1Y216, 2Y216 Load group Channel "C", consisting of: ErA> eH>>At~
1) 4160-volt A.C. switchgear bus 1A203, 2A203 > oAeioc,
2) 480-volt A.C. load center 1B230, 2B230
3) 480-volt A.C. motor control centers OB536> OB136 1B236, 2B236 2B237
4) 208/120-volt A.C. instrument panels 1Y236, 2Y236 c) Isolated 480 volt A.C. swing bus, including: 2B219
1) ~ Preferred power source
2) Preferred power source MG set
3) Alternate power source
4) Automatic transfer switch

~ ~ D iv is ion II, cons is t ing o f:

a) Load group Channel "B", consisting of: @6'>>Aug'A202

1) 4160-volt A.C. switchgear bus 1A202, cAs ion
2) 480-volt A.C. load center 1B220, 2B220
3) 480-volt A.C. motor control centers OB526, OB527 1B226, 2B226 1B227, 2B227
4) 208/120-volt A.C. instrument panels 1Y226, 2Y226 b) Load group Channel "D", consisting of
1) 4160-volt A.C. switchgear bus 1A204, 2A204) oAslon
2) 480-volt A.C. load center 1B240, 2B240
3) 480-volt A.C. motor control centers OB546, OB146
4) 208/120-volt A.C. instrument panels 1Y246> 2Y246 e) Isolated 480 volt A.C. swing bus, including: 2B229
1) Preferred power source
2) Preferred power source MG set
3) Alternate power source
4) Automatic transfer switch

Insert C

3. Diesel Generator E, when aligned to the Class lE system a) Load group consisting of:
1) 4160 volt A.C. switchgear bus OA510E
2) 480 volt A.C. motor control center OB565

'1 fit +

1

ELECTRICAL POWER SYSTEMS LIMITINQ CONDITION FOR OPERATION Continued

b. D.C. power distribution:
l. Dfvfsfon I, consisting of:

a) Load'roup Channel "A", consisting of:

1) 125-volt O.C. buses 10614gg 20612, 20614
2) Fuse box 10611"~, 20611 b) Load group Channel "C", consfstfng of:
1) 125-volt D.C. buses 3'06341'R 20632, 20634
2) Fuse box 10631~,

c) Load group "14, consisting of: 20631'0652,

1) 250-volt O.C. buses 20254
2) Fuse box 20651, d) Load group "I", consisting of:
1) e 24-volt O.C. buses 2D672
2) Fuse box 20671
2. Ofvfsfon II, consisting of:

a) Load group Channel "8" consisting of:

1) 125-volt O.C. buses 10622~, 18624~,

20622, 2D624

2) Fuse box 10621~, 2D621 b) Load group Channel "0" consisting of:
1) 125-volt D.C. buses 10642"", 19644"",

20642 ZQ 644

2) Fuse box 10641~, 20641 c) Load group "II" consisting of:
1) 250-volt O.C. buses 2D662, 20264, 20274
2) Fuse box 20661 Load group "II" consTsting of:

~& 1)

+ Z4-volt 0. C. buses 20682 gg~< b w3. 2) Fuse box 20681 APPLICABILITY: OPERATIONAL CONDITIONS 1, 2, and 3.

ACTC QN:

Q>>) Q Qivi%4c Vl~ >~ lb ivia ieAK

+glOOS

a. With one of the above required A.C. distribution system load groups q not energized, reenergize the load group within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or be in at least HOT SHUTDOWN within the next 1? hours and in COLO SHUTDOWN f'g5fl(f ~ ~b C>.

within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. sinai>>~z,~.el~i>>~~ <<~

With one of the above required Unit 2 O.C. distribution system load groups not energized, reenergfze the load group within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLO SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

d

""Not required to be OPERABLE when the requirements of ACTION g have been satisfied.

SUS)UEHANNA - UNIT 2 3/4 8-19 'mendment No. 14

Insert D

3. Diesel Generator E a) Load group, consisting of:

i

1) 125 volt DC bus OD597

INSERT B

b. With one of the above required Unit 1 and common A.C.

distribution system load groups not energized, re-energize the load group within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

ELECTRICAL POWER SYSTEMS LIMITING CONOITION FOR OPERATION Continued ACTMN (Continued) fifth ane or mare of the above required Unit, 1 O.C. distribution system laad groups not energized, within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> either:

1. Reenergfze the load group(s), or
2. . Transfer the eamon loads aligned to the deenergized Unit 1 load group(s) to the corresponding Unit 2 load group(s).

Otherwise, declare the coaaon loads aligned to the deenergfzed Unit 1 load group(s) fnoperabl ~ and take the ACTION required by the applicable Specification(s).

8 With one or both of the isolated 480-volt A.C. swing busses inoperable,.

ge g.'+&

declare the associated LPCI loop inoperable (see Specification 3.5. 1).

QeÃl C SURVEILLANCE RE UIREMENTS

'.8.3. 1. 1 Each of the above required power distribution system load groups shall be determined energized at least onc! per 7 days by verifying correct breaker alignment and voltage on the busses/MCCs/panels.

4.8.3. 1.2 The isolated 480-volt A.C. s~ing bus aytomatic transfer s~itches shall be demonstrated OPERABLE at least once per 31 days by actuating the load test switch or by disconnecting the preferred power source to the transfer switch and verifying that swing bus automatic transfer is accomplished.

SUSQUEHANNA - UNIT 2 3/4 8-20 Amendment No.14

Insert E

f. With the above required diesel generator E A.C. distribution system load group not energized and diesel generator E aligned to the Class 1E distribution system, re-energize the load group within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
g. With the above required diesel generator E 125 volt D.C. distribution system load group not energized and diesel generator E not aligned to the Class 1E distribution system, re-energize the load group within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or shutdown diesel generator E and close all ESW valves associated with diesel generator E within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. The provisions of Specification 3.0.4 are not applicable. II
h. With the above required diesel generator E 125 volt D.C. distribution system load group not energized and diesel generator E aligned to the Class 1E distribution system, re-energize the load group within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or declare diesel generator E inoperable and take the ACTION r'equired by specification 3.8.1.1.

II 1

7) g P fg'EaI 4

'(Ljl' "~ f) ~ .J <<f, q' II, 7 f 'yi, p ~((i, 'F I P

ELECTRICAL POWER SYSTEMS DISTRIBUTION - SHUTDOWN LIMITINQ CQOmON FOR OPERATION 3.8.3.2 Aa a Ifnfmum, the following power distribution system divisions shall be energized:

a. For A.C. power dfstrfbutfon,'ivision I or Division II with:
1. Ofvfsfon I consisting of:

a) 'oad group Channel "A", consisting of:

1) 4160-volt A.C. switchgear bus IA201, 2A201
2) 480-volt A. C. load center 18210, 28210
3) 480-volt A.C. motor control center 08516 b) Load group Channel "C", consfstfng of:
1) 4160-volt A.C. swftchgear bus IA203, 2A203
2) 480-volt A.C. load center 18230, 28230
3) 480-volt A.C. motor control center 08536 wep Frances, clara. '+bee~ 1 unde~ RA- 2s42 as q~pccs~ Aeendm~ >j'0 e) Isolated 480 volt A.C. swing bus, including: 28219"
1) Preferred power source C 2) Preferred power source HG set
3) Alternate power source gAgeg 4) Automatic transfer switch
2. Division II consisting of:

a) Load group Channel "8", consisting of:

1) 4160-volt A.C. switchgear bus 1&202, 2A202
2) 480-volt A.C. load center M220, 28220
3) 480-volt A.C. motor control center 08526 b) Load group Channel "0", consisting of:
1) 4160-volt A.C. switchgear bus &204, 2A204
2) 480-volt A.C. load center '8240, c.8240
3) 480-volt A.C. motor control center 08546 "The swing bus shall be OPERABLE if the Division I LPCI subsystem alone is fulfilling the requirements of Specificatfon 3.5.2.

SVS(UEHANNA - UNIT 2 3/4 8-21 Amendment No.14

INSERT A k

a. Por A.C. power distribution, Division I or Division II with: an~ol~elyeneekr E
1. Division I consisting of:

"A", consisting of:

a) Load group Channel

1) 4160-volt A.C. switchgear bus 1A201 2A201, OA5lOA
2) 480-volt A.C. load center 1B210 2B210
3) 480-volt A.C. motor control centers OB516, OB517 1B216, 2B216 1B217, 2B217
4) 208/120-volt A.C. instrument panels 1Y216, 2Y216 b) Load group Channel "C", consisting of: ~6<0
1) 4160-volt A.C. switchgear bus 2A203 oP sioC 46'A203,
2) 480-volt A.C. load center 1B230, 2B230
3) 480-volt A.C. motor control centers OB536, OB136 1B236, 2B236 2B237
4) 208/120-volt A.C. instrument panels 1Y236, 2Y236 c) Isolated 480 volt A.C. swing bus, including: 2B219*
1) Preferred power source
2) Preferred power source MG set
3) Alternate power source
4) Automatic transfer switch
2. Division II consisting of:

a) Load group Channel "B", consisting of:

1) 4160-volt A.C. switchgear bus 1A202> 2A202, Mio e
2) 480-volt A.C. load center 1B220, 2B220
3) 480-volt A.C. motor control center OB526$ OB527 1B226 > 2B226 1B227, 2B227
4) 208/120-volt A.C. instrument panels . 1Y226, 2Y226 b) Load group Channel "D", consisting of:
1) 4160-volt A.C. switchgear bus 1A204, 2A204, o~ioD
2) 480-volt A.C. load center 1B240, 2B240
3) 480-volt A.C. motor control center OB546, OB146 1B246, 2B246 2B247
4) 208/120-volt A.C. instrument panels 1Y246, 2Y246

ELECTRICAL POWER SYSTEHS LIMITING CON)ITION FOR OPERATION Continued

~) Isolated 480 volt A.C. s~ing bus; fncludfng: 28229~

1) Preferred power source
2) Preferred power source HG set
3) 'Alternate power source Sc'E'seer

< 4) Autoaatfc transfer swf tch

b. For O.C. power dfstrfbutfon, Division I or Division II, with:

Division I consisting of:

a) Load group Channel "A", consisting of:

1) 125-volt O.C. buses 10614aaa l 20612, 20614
2) Fuse box 106I3.~~, 29611 l b) Load group Channel "C", consisting of:

10 634'g l

1) 125-volt O.C. buses 10632~

29632, 20634

2) Fuse box 10631~~, 2D631 c) Load group, "I", consisting of:
1) 250-volt D.C. 'buses 20652, 20254
2) Fuse box 20651 d) Load group "I", consistfng of:
1) e 24-volt O.C. buses 20672
2) Fuse box 20671
2. Division II consisting of:

a) Load group Channel "8", consisting of:

1) 125-volt O.C. buses 10622*M 10624'A %*

20622, 2D624

2) Fuse box 10621~~", 20621 b) Load group Channel "0", consisting of:
1) 125-volt O.C. buses +642%~

20642, 20644

2) Fuse box 10641""", 20641 .

c) Load group "II", consisting of:

1) 250-volt O.C. buses 20662, 20264, 2D274
2) Fuse box 20661 d) Load group "II", consisting of:

+8&

1) t 24 volt O.C. buses 20682 20681
2) Fuse box

~m- c. APPLICABILITY: OPERATIONAL CONDITIONS 4, 5, and "".

"The swing bus shall be OPERABLE if the Ofvfsfon II LPCI subsystem alone is fulfflling the requirements of Specfffcatfon 3.5.2.

""When handling irradiated fuel in the secondary containment.

Not required to be OPERABLE when the requfrements of ACTION c have been satf sfied.

SUS/UENANNA - UNIT 2 3/4 8-22 .Amendment No. 14 C

e Insert B

3. Diesel Generator E a) Load Group, consisting of:
1) 4160 volt A.C. switchgear bus OA510E
2) 480 volt A.C. motor control center OB565

Insert C

3. Diesel Generator E a) Load group, consisting of:
1) 125 volt DC bus OD597

ELECTRICAL PO'HER SYSTEMS OC LINITINQ CQSITION FOR OPERATION Contf nued ACTION:

a. fifth less than the Ofvfsf& I or Ofvfsfon II load groups of the above required A.C. distribution system energized,'uspend CORE ALTERATIONS, handling of irradiated fuel fn the secondary containment and operations whtn a nntant<al mr dralnlng tna raantnr vaaaal.
b. fifth less than the Ofvfsfon I or Ofvfsfan II load groups of the above required Unit 2 O.C. distrfbutfon system energized, suspend CORE ALTERATIONS, handling of irradiated fuel fn the secondary containment and operations with a poteiNal for draining the reactor vessel.

c a C. Nth less than Oivfsion I orf Ofvfsfon II of the above required Unit 1 O.C. dfstrfbutfan systea energfzed, either:

l. Suspend CORE ALTERATIONS", handling of frradfated fuel in the secondary containment RZ operations with a potential for drain-ing the reactor vessel;a'ar
2. Transfer the comaon loa8s aligned to the deenergized Unit 1 load .

group(s) ta the corresponding

)C Unit 2 load group(s).

Otherwise, declare the common loads aligned to the deenergiiad Unit 1 load group(s) inoperable and take the ACTION required by the applicable Specification(s). le@

d. With one or both of the i@lated 480 volt A. C. Swing busses inoperable, declare the assaciatad LPCI loop inoperable (see Specfffcatfon 3. 5. 2).

pe e. The provisions of Specific@fan 3. O. 3 are not applicable.

~nanr Drgh.

SURVEiLLANCE RE UIRBIENTS I

a

<.8.3.2.1 At least the above require% power distribution system divisians snail be determined energized at least once per 7 days by verifying correct breaker alfgnaant and voltage on the busses/MCCs/panels.

4.8.3.2.2 The isolated A.C. swing bus.eutamatfc transfer s~itches shall be demonstrated OPERABLE at least once ~r 31 days by actuating the load test switch or by dfsconnecting the preferred power source to the transfer switch and verifying that swing bus automatic transfer fs accomplished.

SUS)UEHANNA - UNIT 2 3/4 8-23 Amendment No. 14

Insert D

f. With the above required diesel generator E A.C. distribution system load group not energized and diesel generator E aligned to the Class lE distribution system, re-energize the load group within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
g. With the above required diesel generator E 125 volt D.C. distribution system load group not energized and diesel generator E not aligned to the Class 1E distribution system, re-energize the load group within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or shutdown diesel generator E and close all ESW valves associated with diesel generator E within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. The provisions of Specification 3.0.4 are not applicable.
h. With the above required diesel generator E 125 volt D.C. distribution system load group not energized and diesel generator E aligned to the Class lE distribution system, re-energize the load group within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or declare diesel generator E inoperable and take the ACTION required by specification 3.8.1.~

t V

P"

~ ~ '

'1 '1 V

'i t5' ~

1 V

~V PE li P

P*

P

~ n

~ ~

P. =

v '

~ ~

V 1' 1 P

~ ~ ~

ELECTRICAL POWER SYSTEMS I

I MOTOR OPERATED VALVES THERMAL OVERLOAD PROTECTION - CoNxNuo>>

LIMITING CONDITION FOR OPERATION 3 8.4 2eL ~ 3.8.4.t. I - I

~ ~ ~ The thermal overload protection of each valve shown in Table- .

shall be bypassed continuously by an OPERABLE bypass device integral with the motor starter.

APPLICABILITY: Whenever the motor operated valve is required to be OPERABLE un e~s O~evgjise. p8c PiM.

aO With thermal overload protection for one or more of the above required valves not bypassed continuously by an OPERABLE integral bypass device, take administrative action to continuously bypass the thermal overload within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or declare the affected valve(s) inoperable and apply the appropriate ACTION statement(s) for the affected system(s).

b. The provisions of Specification 3.0.4 are not applicable.

SURVEILLANCE RE UIREMENTS jS.)r2 J f The thermal overload protection for the above required valves shall be verified to be bypassed continuously by an OPERABLE integral bypass device by verifying that the thermal overloadI protection is bypassed:

a. At least once per 18 months, and
b. Following maintenance on the motor starter.

g e.4.~.i.z The thermal overload protection shall be verified to be bypassed following activities during which the thermal overload'protection was temporarily placed in force.

SUSQUEHANNA - UNIT 2 3/4 8-30

e MOTOR-OPERATED VALVES THERMAL OVERLOAD PROTECTION - Qg t-~gUgU~

SYSTEM(S)

VALVE NUMBER AFFECTED HV-01222A RHRSW HV-01222B RHRSW HY-01224AI RHRSW HV-0122481 RHRSW HV-01224A2 RHRSW HV-0122482 RHRSW

> HV-01112A ESW

~ HV-01112B ESW

~ HV-01122A ESW

+ HV-01122B ESW

+ HV-01112C ESW

+ HV.-011120 ESW 4 HV-01122C ESW

> HV-01122D ESW w HV-01110A ESW

~ HV-01110B ESW

~ HV-01120A ESW HV"01120B ESW

~ HV"01110C ESW HV"01110D ESW HV 01120C ~ ov-on<or ESW 8sd HV-01120D " H< ESW HV-21144A e 8't- 0 ESW HY-2II44B ESW~

HV"08693A ESW HY-08693B ESW HV-0120IAI RHRSW HV-01201A2 RHRSW HY-01201BI RHRSW HV-01201B2 RHRSW.

HV-21210A RHRSW HY-212108 RHRSW HV-21215A RHRSW HV-21215B RHRSW HV-25766 Cont. Isol.

'V-25768 Cont. Isol.

HV-22603 Cont. Isol.

HV-21345 Cont. Isol.

HV-21313 Cont. Isol.

HV-21346 Cont. Isol.

HV-21314 Cont. Isol.

HV-Ell-2F009 RHR HV-Ell"2F040 RHR HV-G33-2FOOI RWCU SUSQUEHANNA - UNIT 2 3/4 8-31 Amendment No. 20 Qcn4rvcvs gypss no> mqy'i~ ~hew ~,~pend:ng Qiesal c)energy~~ is q+ ~llgged + &e'5 s

0 I

e

TABLE 3.8.4.2-1 (Continued)

MOTOR"OPElMTED VALVES THERMAL OVERLOAD PROTECTION SYSTEM(S)

VALVE NUMBER AFFECTED HV- Ell-2F103A RHR HV-Ell-2F075A RHRSW 2F048A 'V-Ell" RHR HV-Ell-2F006C RHR HV-Ell-2F004C RHR HV"Ell-2F015A RHR HV-Ell-2F024A RHR HV-E21-2F015A CS HV-E41-2F002 HPCI HV-821-2F016 NSSS HV"Ell-2F022 RHR HV-Ell"2F010A RHR HV-Ell-2FOllA RHR HY-Ell-2F004A RHR HV-Ell-2F006A RHR HV"Ell-2F027A RHR

'V-Ell-2F007A RHR HY-E11"2F104A RHR HV"Ell"2F026A RHR HV-Ell-2F028A RHR HV-Ell-2F047A RHR HY"Ell-2F073A RHRSW HV"EII-2F003A RHR HV"Ell-2f017A RHR HV-E21-2F001A CS HV-E21" 2F031A CS HV-E21-2F004A CS HV-E21-2F005A CS HV"Ell-2F021A RHR HV-Ell"2F016A RHR HY-25112 RHR HV-E51-2F007 RCIC HV-E51-.2F084 RCIC HV-Ell-2F0278 RHR HV-Ell-2F0488 RHR HV-Ell-2F0158 RHR HV-Ell-2F0068 RHR HV-Ell-2F0218 RHR HY-Ell-2F0108 RHR HV-Ell-2F0118 RHR HV"Ell-2F0048 RHR HV-Ell"2F0078 RHR HV-Ell-2F1048 RHR HV-Ell"2F0268 RHR SUSgUFHANNA - UNIT 2 3/4 8"32 Amendment No.

TABLE 3.8.4.2-1 (Continued)

MOTOR-OPERATED VAI VES THERMAI OVERLOAD PROTECTION SYSTEM(S)

VALVE NUMBER AFFECTED HV-Ell-2F028B RHR HV-Ell-2F0478 RHR HV-Ell-2F016B RHR HV-Ell"2F003B RHR HV-Ell-2F0178 RHR HV-E21-2F0318 CS HV-E21-2F0018 CS HV-Ell-2F103B RHR HV-Ell-2F0758 RHRSW HV-Ell-2F0738 RHRSW HV"Ell"2F006D RHR HV-Ell-2F004D RHR HV-Ell-2F024B RHR HV-E21-2F0158 CS HV-E21-2F0048 CS HV-E21"2FOOSB CS HV-E32-2F001K MSIY HV-E32-2F002K MSIV HY-E32-2F003K MSIY HV-E32-2F001P MSIV HV"E32-2F002P MSIV HY-E32-2F003P MSIV HV-BR-2F0018 MSIV HV"E32-2F002B MSIV HV-E32-2F0038 MSIV HY-E32" 2F001F MSIV HV-E32"2F002F MSIV HV-E32-2F003F MSIY HV-E32-2F006 MSIV HV-E32-2F007 MSIV HY-E32-2F008 MSIV HV-E32-2F009 MSIV HV-E51 2F045 RCIC HV-E51-2F012 RCIC HV-E51-2F 013 RCIC HV-25012 RCIC HY"E51-2F046 RCIC HV-E51"2F008 RCIC HV"E51-2F031 RCIC HV-E51-2F010 'RCIC SUSQUEHANNA - UNIT 2 3/4 8-33

TABLE 3.8.4.2-1 (Continued)

MOTOR-OPERATED VALVES THERMAL OVERLOAD PROTECTION VALVE NUMBER SY~h) 'FFECTED HV-E51-ZF019 RCIC HV-E51-2F060 RCIC HV-E51"2F059 RCIC HV-E51-2F022 RCIC HV-E51-2F062 RCIC HV-E41-ZF012 HPCI HV-E41-2F001 HPCI HV-E41"2F011 HPCI HV-E41-ZF006 HPCI HV-E41-2F079 HPCI HV"E41-2F059 HPCI HV-E41"2F004 HPCI HV"E41"2F003 HPCI HV"E41-ZF042 HPCI HV"E41-2F075 HPCI HV-E41-ZF008 HPCI HV-E41-ZF007 HPCI HV-E41-2F066 HPCI HV-G33"ZF004 RMCU HV-B21-2F019 NSSS HV"Ell-2F008 RHR HV-Ell-2F023 RHR HV-Ell"2F049 RHR HV-B31"2F032A Rx Recirc HV"B31-2F032B Rx Recirc HV-B31-2F031A Rx Recirc HV-B31-2F031B Rx Recirc

~ ~

SUS)UEHANNA - UNIT 2 3/4 8-34

ELECTRICAL POWER SYSTEMS MOTOR OPERATED VALVES THERMAL OVERLOAD PROTECTION AUTOMATIC LIMITING CONDITION FOR OPERATION 3.8.4.2.2 The thermal overload protection of each valve shown in Table 3.8.4.2.2-1 shall be bypassed automatically by an OPERABLE bypass device integral with the motor starter.

APPLICABILITY: When diesel generator E is not aligned to the Class 1E distribution system.

ACTION:

a. With thermal overload protection automatic bypass inoperable for one or more valves listed above, take administrative action to continuously bypass the thermal overload within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, or verify that all diesel generator E ESW valves are closed and diesel generator E is not running within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.
b. The provision of Specification 3.0.4 are not applicable.

SURVEILLANCE RE UIREMENTS 4.8.4.2.2.1 The automatic bypass of thermal overload protection for those valves listed above shall be demonstrated OPERABLE at least once per 18 months.

TABLE 3.8.4.2.2-1 MOTOR OPERATED VALVES THERMAL OVERLOAD PROTECTION - AUTOMATIC System(s)

Valve Number Affected HV-01110E ESW HV-01120E ESW HV-01112E ESW HV-01122E ESW

3/4.8 ELECTRICAL POWER SYSTEMS BASES 3/4.8.1 3/4.8.2 and 3/4.8.3 A.C. SOURCES D.C. SOURCES and ONSITE POWER The OPERABILITY of the A.C. and D.C. power sources and associated distribution systems during operation ensures that sufficient power will be available to supply the safety related equipment required for (1) the safe shutdown of the facility and (2) the mitigation and control of accident conditions within the facility. The minimum specified independent and redundant A.C. and D.C. power sources and distribution systems satisfy the requirements of General Design Criteria 17 of Appendix "A" to 10 CFR 50.

The ACTION requirements specified for the, levels of degradation of the power sources provide restriction upon continued facility operation commensurate with the level of degradation. The OPERABILITY of the power sources are con-sistent with the initial condition assumptions of the accident analyses and are based upon maintaining at least three of the onsite A.C. and the corre-sponding D.C. power sources and associated distribution systems OPERABLE during accident conditions coincident with an a umed loss of offsite power and single failure of one other onsite A.C. source +xusae'h The A.C. and D.C. source allowable out-of-service times are based on Regulatory Guide 1.93, "Availability of Electrical Power Sources," December 1974. When one diesel generator is inoperable, there is an additional ACTION requirement to verify that all required systems, subsystems, trains, components and devices, that depend on the remaining OPERABLE diesel generator as a source of emergency power, are also OPERABLE. This requirement is intended to provide assurance that a loss of offsite power event will not result in a complete loss of safety function of critical systems during the period one of the diesel generators is inoperable. The term verify as used in this context means to administratively check by examining logs or other information to determine if certain components are out-of-service for maintenancezr other reasons. It does not mean to perform the surveillance requirements needed to demonstrate the OPERABILITY of the component.

The OPERABILITY,of the minimum specified A.C. and D.C. power sources and associated distribution systems during shutdown and refueling ensures that (1) the facility can be maintained in the shutdown or refueling condition for extended time periods and (2) sufficient instrumentation and control capability is available for monitoring and maintaining the unit status.

The surveillance requirements for demonstrating the OPERABILITY of the diesel generators are in accordance with the recommendations of Regulatory Guide 1.9, 45election of Diesel Generator Set Capacity for Standby Power Supplies", March 10, 1971, Regulatory Guide 1. 108, Periodic Testing of Diesel Generator Units Used as Onsite Electric Power Systems at Nuclear Power Plants",

Revision 1, August 1977 and Regulatory Guide 1.137 "Full-Oil Systems for Standby Diesel Generators", Revision 1, October 1979.

SUSQUEHANNA - UNIT 2 B 3/ 8-1

~A: 'r4~ doHyuwm d~ oP 4rcr~parrerr=&w-ri~iA <> -~>sp~~c

6 4W ~~ P~

ELECTRICAL POWER SYSTB5 BASES A.C. SOURCES D.C. SOURCES and ONSITE POWER DISTRIBUTION SYSTEMS (Continued)

The surveillance, requirements for demonstrating the OPERABILITY of the unit batteries are in accordance with the recommendations of Regulatorjj Guide

1. 129, "Maintenance Testing and Replacement of Large Lead Storage Batteries for Nuclear Power Plants", February 1978, and IEEE Std 450-1980, "IEEE Recom-mended Practice for Paint@nance, Testing, and Replacement of Large Lead Storage Batteries for Generating Stations and Substations."

Verifying average electrolyte temperature above the minimum for which the battery was sized, total battery terminal voltage onfloat charge, connection resistance values and the performance. of battery service and discharge tests ensures the effectiveness of the charging system, the ability to handle high discharge rates and. compares the battery capacity at that time with the rated capacity.

Table 4.8.2.1-1 specifies the normal limits for each designated pilot cell and each connected cell for electrolyte level, float voltage and specific gravity. The limits for the designated pilot cells float voltage and specific gravity, greater than 2.13 volts and .OL5 below the manufacturer's full charge specific gravity or a battery charger current that had stabilized at a low value, is characteristic of a charged cell with adequate capacity. The normal limits for each connected cell for float voltage and specific gravity, greater than 2.H volts and not more than .020 below the manufacturer's full charge specific gravity with an average specific ' gravity of all the connected cells not more than . 010 below the manufacturer full charge specific gravity, ensures the OPERABILITY and capability of the battery.

Operation with a battery cell's parameter outside the normal limit but within the allowable value specified in Table 4.8.2.1-1 is permitted for up to 7 days. During this 7 day, period: (1) the allowable values for electrolyte level ensures no physical damage to the plates with an adequate electron transfer capability; (2) the allowable value for the average specific gravity of all the cells, nat more than .020 below the manufacturer's recoaxaended full charge specific gravity, ensures that the decrease in rating will be Cess than the safety margin provided in sizing; (3) the allowable value for an individual cell's specific gravity ensures that an individual cell's specific gravity will not ba more than .040 below the manufacturer's full charge specific gravity and that thi overall capability of the battery will be maintained within an acceptable limit; and (4) the allowable value for an individual cell's float voltage, greater than 2.07 volts, ensures the battery's capability to perform its design function.

SUS/UEHANNA - UNIT 2 B 3/4 8-2

4

'l

ELECTRICAL POWER- SYSTEMS BASES 3/4.8.4 ELECTRICAL E UIPMENT PROTECTIVE DEVICES Primary containment electrical penetrations and penetration conductors are protected by either de-energizing circuits not required during reactor operation or demonstrating the OPERABILITY of primary and backup overcurrent prbtection circuit breakers by periodic surveillance. ~

The surveillance requirements applicable to lower voltage circuit breakers and fuses provides assurance of breaker and fuse reliability by testing at least one representative sample of each manufacturers brand of circuit breaker and/or fuse. Each manufacturer's molded case and metal case circuit breakers and/ot fuses are grouped into representative samples which are than tested on a rotating basis to ensure that all breakers and/or fuses are tested. If a wide variety exists within any manufacturer's brand of circuit breakers and/or fuses, it is necessary to divide that manufacturer's breakers and/or fuses into groups and treat each group as a separate type of breaker or fuses for surveillance purposes.

The bypassing of the motor operated valve thermal overload protection continuously by integral bypass devices ensures that the thermal overload protection will not prevent safety related valves frem performing their func-tion. .The surveillance requirements for demonstrating the bypassing of the thermal overload protection continuously are in accordance with Regulatory Guide l. 106 "Thermal Overload Protection for Electric Motors on Motor Operated Valves", Revision 1, March &77.

SUS)UEHANNA - UNIT 2 B 3/4 8;3

ATTACHMENT 3

~Tech S ec ~Chen e Justification 3.3.7.9 Table 3.3.7.9-1 Incorporate fire detection Requiring the E diesel generator building instrumentation for the fifth spray and sprinkler system, fire hose diesel generator building. stations, and fire detection instrumentation to be OPERABLE does not impact safety but 3.7.6.2 Incorporate item TOT entitled ~~Diesel merely ensures adequate fire suppression Generator E Building (Fire Zone 0-41E)" capability is available to confine and extinguish fires occurring in the facility.

3.7.6.5 Table 3.7.6.5-1 Incorporate fire hose station location for the fifth diesel The fire protection system in the E building generator building meets the criteria delineated in FSAR Chapter 9.5.1; 10CFR50, Appendix R and; NFPA National Fire Codes.

The system gets its water from the Plant yard loop and is designed for a water supply from one 500 GPM at 125 PSI fire pump with the shortest route assumed to be unavailable. The fire standpipe system and hoses are located so that all interior sections can be reached per NFPA Class III requirements. The fire detection system is compatible and interfaces with the existing fire protection multiplexing system.

3.8.1.1 3.8.l.l.b Incorporate the phrase 'of the Tech Spec 3.8.1.1 delineates the minimum five'fter the word 'Four'. number of A.C. power sources which must be OPERABLE during operation to ensure sufficient power will be available to supply the safety related equipment required for (1)

Safe-Shutdown of the facility and (2) control and mitigation of accident conditions within the facility. Additionally, separate and independent diesel generators satisfy the requirements of General Design Criteria 17 to 10CFR50, Appendix A. The incorporation of a fifth diesel generator does not impact safety since FSAR analyses assume three diesel generators are required for safe-shutdown of the Plant. This section of Tech Specs is

I 0

t li

+I Ir I

r I

r 'I 8

r 't ~

r I

I I r r p

i r .I I

'I V

I I

r I

I'I e

I II I

~Tech S ec ~Chan a Justification being revised to reflect the fact that an additional diesel generator has been installed as part of the Plant configuration and can be utilized as a replacement for any one of the existing diesel generators.

3.8.l.l.b.2 Incorporate reference to the Diesel generator E is a higher rated machine diesel generator E fuel storage than the existing diesel's, primarily because system. it carries its own house loads. The 60,480 gallons is a calculated number-per the guidelines of Reg. Guide 1.137-which represents the amount of fuel necessary to run the diesel generator at full load for seven continuous days. Similarly,. the fuel oil tank for diesel generator E has an 80,000 gallon capacity as compared to 50,000 gallons for the existing diesel generators.

3.8.1.1 Action a Incorporated phrase Action statements a & c assume the loss of one Action c "for any reason other diesel generator or offsite circuit cause by than aligning diesel a failure therein. When substituting diesel generator E to the generator E it is necessary to remove an to the Class 1E existing diesel from service for a short distribution system" period of time ( 2 hrs.) Incorporation of the after the word proposed phrase would waive the requirement to

'inoperable'. enter into an LCO when substituting diesel generator E which is appropriate given the reason for removing the diesel from service and eliminate unnecessary testing of the other diesels.

4.8.1.1.2 4.8.1.1.2.d.3 Inserted new generator Administrative change to correct typographical 4.8.1.1.2.d.4.b voltages and frequencies. error made when NRC issued this page under 4.8. 1. 1. 2.d. 5 Amendment 36 to NPF-14. (Unit 1 change only) 4.8.1.1.2.d.8 Surveillance modified to Diesel generator E has a higher 2000 hour0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br /> reflect the E diesel rating because it carries its own house loads generator 2000 hour0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br /> when operating. These loads are auto-

I fl 4 I Lf 41 II ~ 5 ~

f I I

'V I~

I I h I II I

~

.J I I

g I I'>> l

~ t I 3 I ,

4 0 4 lt I I I

)

I

'I I J 4 I 4 yl 4 I I

' P fl I J

'I J I

'I <

> P I, I I '4 ~ I+ . ~ fl "I h I >> fl "I Ih II If C C I 4 I", fl I ~Tech S ec ~Chan e Justification rating of 5000KW connected and must be considered when performing the 18 month surveillance. This verification is in accordance with the recommendations of Reg. Guide 1.108. 4.8.1.1.2.d.ll Delete requirement to verify Reg. Guide 1.108 recommends this surveillance the fuel transfer pump if the practice is part of the normal transfers fuel from each operating procedures. At Susquehanna this tank to the engine mounted transferring is not part of normal day tank of each diesel operating procedures and should not -be generator. verified in Tech Specs. Fuel transfer from the fuel oil tank to the corresponding diesel generator day tank is tested for each diesel every 31 days. There is no impact to safety since credit is not taken for this capability in any safety analyses. 4.8.1.1.3 The purpose of establishing section (NEW) 4.8.1.1.3 is to delineate the testing requirements which will demonstrate the E diesel generator OPERABLE when it is substituted for diesel generator A, B, C or D. The requirements of this new section 4.8.1.1.3 are equivalent to existing surveillance testing except for those which would necessitate the E diesel be aligned to the Class 1E system. This alternate testing of the E diesel does not impact current testing programs. 4.8.1.1.3.a Equivalent to 4.8.1.1.2.ae6 4.8.1.1.3.b Modified to indicate testing The first series of testing will be performed will be done once per 31 days. once every 31 days. Under the existing Tech Specs 31 days is the maximum duration between tests and is appropriate when the E diesel generator is not aligned to the Class 1E system. Further, there is no need to test on a more frequent basis since there is no impact I V 1 II II' e ~Tech S ec ~Chan e Justification to safety if the E diesel fails the testing required under this surveillance. 4.8.1.1.3.b.1 Equivalent to 4.8.1.1.2.a.l 4.8.1.1.3.b.2 Equivalent to 4.8.1.1.2.a.2 4.8.1.1.3.b.3 Equivalent to 4.8.1.1.2.a.3 4.8.1.1.3.b.4 Modified to reflect the When diesel generator E is not aligned to the fact that this verification Class 1E system, starting from ambient can only be performed by condition can only be accomplished with a manually starting the diesel manual start signal. 4.8.1.1.3.b.5 Equivalent to 4.8.1.1.2.a.5 4.8.1.1.3.b.6 Equivalent to 4.8.1.1.2.a.7 4.8.1.1.3.c Equivalent to 4.8. 1. 1. 2. b 4.8.1.1.3.d Equivalent to 4.8.1.1.2.c 4.8.1.1.3.e. Statement reworded to take credit for any surveillances which may have been performed while diesel generator E was aligned to the Class 1E distribution system. 4.8. 1.1.3.e. 1 Equivalent to 4.8.1.1.2.d.l 4.8. l. 1.3.e. 2 Equivalent to 4.8.1.1.2.d.2 4.8. 1.1.3.e.3 Equivalent to 4.8.1.1.2.d.3 4.8. 1.1.3.e.4 Equivalent to 4.8.1.1.2.d.7 4.8. 1.1.3.e.5 Equivalent to 4.8.1.1.2.d.12 (4.8.1.1.2.d.ll per this change) 4.8.1.1.3.e.6 Modified to incorporate the This surveillance is equivalent to testing required under existing tech specs 4.8.1.1.2.d.4, existing Tech Spe'cs 4.8.1.1.2.d.5 and 4.8.1.1.2.d.6. The 4.8.1.1.2.d.4, 4.8.1.1.2.d.5, surveillance is comprised of two tests and 4.8.1.1.2.d.6. however only one is required to be performed. Existing tech specs require the diesel be tested under a simulated loss of offsite 0 ~ ~ A ~ ~ T S U I 1 11 ~Tech S ec ~Chan e Justification power, an ECCS actuation test signal, and a loss of offsite power in conjunction with an ECCS actuation test signal. The purpose of these tests is to demonstrate that the associated test signals cause a diesel start. The first part of this surveillance 14.8.1.1.3.4.6 combines these three tests into one on the basis that once the diesel has started via one of the test signals, it is only necessary to verify that the relays associated with the other test signals are working. The second part of this surveillance provides the option of performing the three tests utilizing a load. Existing surveillance 4.8.1.1.2.d.4 performs a diesel generator auto start on a simulated loss of offsite power. This requires a dead bus which is only available during outages. Technically, this surveillance checks bus undervoltage sensing devices and diesel generator capability. The bus undervoltage relays are part of the existing Plant and have not been affected by installation of a fifth diesel generator. Diesel generator E's ability to auto start and load is independent of where the load originates therefore a load bank is acceptable. Existing surveillance 4.8.1.1.2.d.6 performs a diesel generator auto start on a simulated LOCA/LOOP signal followed by diesel generator loading according to design sequencing. This surveillance is intended to check the automatic load sequence timers and diesel generator capability. -The sequence timers are not part of the bus or diesel logic but are part of the individual load control schemes. They function independent of whether diesel t F 1 I ~ 'I 4 I .) '3 .t 7 4 I 4~ I r -1 I Fr 4 I I~ lt 4 ub I I" -7 tp I r' I 1. 44 J 4. 1 1 1 I I 1>> 11 4 'll 1 4 11 I 1 'I ~ 7 I J 4 4 1 ) t I l 4 14 ~ ~ 4 4 .I1 I V,' ' t t F4 4 .t h ~ 4 kt IV

  • tr 4 ~

I4 ~ q t ~ y ~ 1 4 I ~ ~ 1 'I f I tr I ~, ~Tech S ec ~Chan e Justification generator A or E is powering the bus. The ability of diesel generator E to respond to load sequencing must be tested ho~ever the diesels ability to auto start and accept load sequencing is independent of the load source therefore a load bank can be utilized. 4.8.1.1.3.e Equivalent to 4.8.1.1.2.f, reworded to take credit for performing 4.8.1.1.2.f when Diesel generator was aligned to the Class lE system. The following existing surveillances have not been incorporated into this new surveillance 4.8.1.1.3! 4.8.1.1.2.d.8 This verification is a calculation, performed on each diesel every 18 months. As stated previously, this section has been expanded to include the 5th diesel generator and is a verification which can be done regardless of the status of diesel generator E. 4.8.1.1.2.de9 This verification cannot be performed when diesel generator E is not aligned to the Class 1E distribution system. 4.8.1.1.2.d.ll This surveillance will be performed once per 18 months regardless of the status of diesel generator E. 4.8.1.1.2.e This testing cannot be accomplished because all 5 diesel generators cannot be operated at the same time. 4.8.1.1.4 Insert the phrase 'on the All diesel generator failures, valid or required diesel generators'n non-valid, will continue to be reported to the last sentence after the the Commission. This section of Tech Specs word 'failures'. has been altered to reflect the fact that the p ~Tech S ec ~Chan e Justification report is only applicable to those diesels Table 4.8.1.1.2-1 Incorporated a new required for safe shutdown which could footnote which states include diesel generator E if it is aligned "When diesel generator E to the Class lE system. The basis for this is not aligned to the change is to eliminate the potential of Class 1E distribution placing diesel generators A, B, C, or D in a system, any failures will precarious position as a result of a failure not be credited to the on diesel E when it is not aligned. total failures for determining the test frequency of the diesel generators required to be OPERABLE" Table 4.8.1.1.2-2 Expanded to include the Including diesel generator E's loading timers diesel generator E ensures the E Building supply and exhaust fans loading timers. Also fans will be OPERABLE. The footnote has been a footnote has been added for clarity. There is no reason to added to reflect current verify for example the 'A'iesel design. generator Room exhaust fan is operable if diesel generator A is out of service. 3.8.1.2 3.8.1.2.b Incorporate the phrase 'of the Specification modified to reflect five separate and incorporation of a fifth diesel generator into the word 'Two', and the the Plant configuration and the fact that any independent'fter word 'each'fter 'generators'. two of those five diesels will meet the Tech 'pec requirement. 3.8.1.2.b.2 Incorporated the fuel The fifth diesel is a higher rated machine requirements for diesel primarily because it carries its own house generator E. loads and requires significantly more fuel to meet Reg. Guide 1.137 i.e. enough fuel to operate for 7 days continuous at full load. There is no impact to safety since this calculated number is per the guidance in the Reg. Guide and is consistent with existing tech specs. II 'I 0 ~Tech S ec ~Chan e Justification 4.8.1.2 Incorporated reference to The reference to 4.8.1.1.3 has been deleted 4.8.1.1.4 Reports, which was since it applies to diesel generator E, renumbered as a result of Diesel generator E will always be tested and incorporation of a new surveillance demonstrated OPERABLE since it is not Unit 4.8.1.1.3. Reference to 4.8.1.1.3 related. has been deleted. 3.8.2.1 3.8.2.1.C Incorporates the D.C. electrical The 125 volt D.C. system supplies d.c. power 3.8.2.2 3.8.2.2.C power sources for diesel for diesel controls, field flashing, tripping generator E. the 4.16KV switchgear in the E diesel generator building and to the ECCS isolation valves. The system was installed in accordance with the recommendations in Reg. Guide 1.128 and will be surveilled per the guidelines in Reg. Guide 1.129 and IEEE Standard 450-1980. 3.8.2.1 Action e. Incorporated the phrase This change is necessary to clarify that 3.8.2.2 Action a. 'Division I or Action e is only applicable to Division I or 3.8.2.2 Action e. Division II'fter the word 'required'. Division II which is appropriate because the battery bank and charger for diesel generator E have their own action statements. 3.8.2.1.f New Action statements to address The new Action statements address all 3.8.2.1.g the battery bank and charger for possible scenarios i.e. when diesel generator 3.8.2.1.h diesel generator'E. E is and is not aligned to the Class lE 3.8.2.l.i distribution system. The ACTION requirements specified provide restriction upon continued 3.8.2.2.g facility operation commensurate with the level 3.8.2.2.h of degradation. 3.8.2.2.i 3.8.2.2.j These new action statements are equivalent to the existing statements applicable to diesel generators A, B, C and D. 4.8.2.1.c.4.d Incorporated diesel Change is necessary to reflect unique changing E's battery charger. requirements for the 125-volt diesel generator E batteries. 2 .0 I 1 0 5 ~1 0 0 I yl P 0 2 I<< ,1 0 I 1 'I 4 I 1 01 2 'I e 1 l 10 0 ~ I~ yy 10'2 ~ I I 2 I 0> 51 1 ~ 0 ~ -2 I <<2 yf I ' 'I '0 1 1 1 I' ~0 ,0 I'

5) If 0

'0 'I -I t 01 I VI) 0 I 0 5 I 4 ~ 'I V 01 2 ~ ~ ~ ~ ~ 1 ~ 0 0 ) 0 ~ 0 1 e 0 ~ ~ e 0 ~Tech S ec ~Chan e Justification 4.8.2.l.d.2.b.(9 Incorporated the diesel Surveilling the battery and charger for diesel generator E batter load generator E enhances safety since it provides profile. assurance that the batteries can perform their intended function. This is equally important since these batteries provide power to the ESW valves. 3.8.3.1 3.8.3.l.a.l.a)l) Incorporate OA510 busses These busses provide a double break on the 3.8.3.2 3.8.3.1.a.l.b)l) 4 kv system and serve as the transfer points 3.8.3.1.a.2.a)1) for aligning the existing diesel generators 3.8.3.l.a.2.b)1) or diesel generator E to the Unit 1 or Unit 2 ESS busses. The OA510 busses have been 3.8.3.2.a. l.a) 1) installed under DCP's 83-812A, 83-812B and 3.8.3.2.a.l.b) 1) 83-812C (see attached safety evaluations). 3.8.3.2.a.2.a)l) 3.8.3.2.a.2.b)1) 3.8.3.1.a.3 Incorporate the power The OPERABILITY of the power distribution 3.8.3.2.a.3 distribution system associated system during operation ensures sufficient 3.8.3.1.b.3 with diesel generator E. power will be available. to supply the safety 3.8.3.2.b.3 related equipment required for (1) the safe shutdown of the Plant and -(2) the mitigation and control of accident conditions within the facility. The minimum specified distribution systems satisfies the requirement of GDC 17 to 10CFR50, Appendix A. The OPERABILITY of the power distribution system during shutdown and refueling ensures that (1) the facility can be maintained in the shutdown or refueling condition for extended time periods and (2) sufficient instrumentation and control capability is available for monitoring and maintaining the Unit status. 3.8.3.1 Actions a&b Incorporated the phrase This phrase has been incorporated to delineate 'Division I or the fact that ACTIONS a & b do not apply to 1 1 <<4 4 w v I ww l I 4 l 1 4 4 ~ 1 I I 1 I 4 w' 4 ~ 4 I ~ ~ ~ II 4 II ~ ~ I ' I 4 ~ 4 4 ~ 0 4 4 4 ~ ~ ~Tech S ec ~Chan e Justification Division II'. those power distribution systems associated with diesel generator E. Diesel generator E's power distribution system has its own specific ACTION statements. 3.8.3.1 Actions f, g and h These new action statements provide 3.8.3.2 Actions g, h and i restriction upon continued operation of the facility commensurate with the level of degradation. They are consistent with the existing ACTIONS for diesel generators A, B, C, and D. 3.8.4.2 Specification retitled to read "Motor The diesel generator E, ESW valves thermal Operated Valves Thermal Overload Protection- overload protection is in some instances Continuous" and renumbered as 3.8.4.2.1. bypassed continuously and in other Reference to Table 3.8.4.2-1 renumbered. instances automatically. This specification Surveillances,4.8.4.2.1 6 4.8.4.2.2 details the requirements for continuous renumber consi'stent with renumbering of bypass and a new specification 3.8.4.2.2 specification. addresses automatic bypass. Applicability Statement incorporated the This phrase has been added to clarify phrase 'unless otherwise specified'. changes to Table 3.8.4.2.1-1. Table 3.8.4.2.1-1 Renumbered, Incorporated Table renumbered for consistency. ESW valves associated with diesel generator E and When an existing diesel generator is not added an asterisk footnote connected to the Class lE distribution which states "Continuous system there is no reason to require bypass not required when thermal overload protection bypass of it' corresponding diesel associated ESW valves. Since under the generator is not aligned condition, the valves do not provide a to the Class 1E safety function. Bypass would be initiated distribution system". prior to returning the corresponding diesel generator to service. ~ 41 ~Tech S ec ~Chan e Justification 3.8.4.2.2 3.8.4.2.2 Actions A & B The ESW system cannot provide cooling to (NEW) 5 diesel generators. Therefore when diesel generator E is not aligned to the Class 1E distribution system in which case it can be operated for testing thus requiring ESW it is essential that adequate ESW be available to diesels A, B, C or D in the event one or all of them receive an actuation signal. To provide this margin of safety, thermal overload protection of the ESW valves associated with diesel generator E is automatically bypassed thus ensuring those valves will close should the existing diesel receive a start signal. $ .8.4.2 2.1 Consistent with existing technical specification. B 3/4.8 Added wording for clarity. Incorporated the current plant configuration i.e. five diesel generators. dew/exk202214c ll.~ H 0 0 II I 0 4