PROCEDURE COVER SHEET NUCLEAR DEPARTMENT PROCEDURE
~O
~are A" CONTROL ROOM EVACUATION ON-100-009 Revision 3
Page 1 of 28 EFFECTIVE DATE:
PERIODIC REVIEW FREQUENCY:
PERIODIC REVIEW DUE DATE:
REVISED PERIODIC REVIEW DUE DATE:
PROCEDURE TYPE:
QA Program
(
YES
(
)
NO Plant Procedure
( ~YES
(
)
NO REVIEW METHOD:
(
) Alternate (~Expedited
(
)
(
)
ERC I'repared by Reviewed by Date Date Recommended Approved by Date Date
.Supervisor Date Functional Unit Manager PORC Committee Meeting No.
P)IA ERC Committee Meeting No.
FORM NDAP-QA-0002-1, Rev.
1, Page 1 of 1
9505260325
'p)50522 PDR ADOCK 05000387 F
PDR lllmmllllllHlHIIBIHIll8llllllllll IHIIIIIIHllltIMMEllll
ON-100-009 Revision 3
Page 2 of 28 1.0 SYMPTOMS AND OBSERVATIONS Conditions exist which require Control Room EVACUATION:
1.1 Dense
- SMOKE, 1.2 Extreme HEAT 1.3 Hazardous GAS which induces difficulty in breathing 1.4 Direction from Shift Supervision
- 2. 0 AUTOMATIC ACTIONS None 3.0 IMMEDIATE OPERATOR ACTIONS NOTE:
If Control Room evacuation is anticipated, NOTIFY Security to provide access to BOTH Units'emote Shutdown Panels.
- 3. 1 As time permits, PERFORM following prior to Control Room evacuation:
CONFIRM 3.1.1 3.1.2 3.1.3 3.1.4 3.1.5 3.1.6 3.1.7 3.1.8 3.1.9 ANNOUNCE twice over Plant PA System "Control Room evacuation in progress".
PLACE REACTOR MODE SWITCH HS-C72A-1SOl to SHUTDOWN.
ENSURE all Control Rods INSERTED.
CLOSE RFP A,B,&C DSCH ISO HV-10603A,B&C.
PLACE FW LOW LOAD LIC-C32-1R602 in AUTO.
OPEN HPCI TEST LINE ISO VLV HV-155-F011.
TAKE two (2) sets of security keys from Shift Supervisor key cabinet to gain entrance into Reactor Building.
(Unit Supervisor only)
3.2 EVACUATE Main Control Room.
ON-100-009 Revision 3
Page 3 of 28 CONFIRM NOTE:
Attachment D contains lists of all functions performed by placing transfer switches to EMERG position.
4.0 SUBSE UENT OPERATOR ACTIONS NOTE:
All indications and controls are from 1C201 unless otherwise indicated.
- 4. 1 If required'o establish communication between Remote Shutdown Panel and locations in the plant, REFER to Attachment C for sound powered phone location.
NOTE:
Unit Two Remote Shutdown Panel Room phone extension is 3823.
4.2 If Control Room evacuated prior to completing immediate operator actions, PERFORM locally:
4.2.1 OPEN following breakers to scram reactor and isolate Inboard and Outboard MSIV's and Main Steam Line Drains:
NOTE:
A screwdriver has been stored in Sound Powered Phone Headset Storage Box JP1203 by A RPS Panel, if needed to open RPS panels.
4.2.2 a.
1Y201A bkr CB2A in RPS power distribution Panel (27-749')
b.
1Y2018 bkr CBSB in RPS power distribution Panel (27-749')
~
'ANUALLY CLOSE following valves:
a.
RFP A Dsch Iso HV-10603A.
b.
RFP 8 Dsch Iso HV-106038.
c.
RFP C Dsch Iso HV-10603C.
ON-100-009 Revision 3
Page 4 of 28 CONFIRM 4.3 Upon arrival at Remote Shutdown
- Panel, PERFORM following to determine plant status:
4.3.1 Transfer control and instrumentation to Remote Shutdown Panel. as follows, OBSERVING green light ILLUMINATES for each transfer switch when placed in EMERG position:
a.
PLACE INSTR TRANSFER SWITCH A INSTR SET 1,2 HSS-14901A in EMERG position.
b.
Transfer CONTROL TRANSFER SWITCH A HSS-14902A as follows:
(1)
ENSURE BAROMETRIC CDSR COND PUMP 1P220 aligned to AUTO.
(2)
PLACE CONTROL TRANSFER SWITCH A HSS-14902A in EMERG position.
c.
Transfer CONTROL TRANSFER SWITCH M HSS-14902B as follows:
(1)
ENSURE TURB EXH TO SUPP POOL HV-149-F059 aligned to OPEN.
(2)
ENSURE BAROMETRIC VACUUM PUMP 1P219 aligned to STOP.
(3)
PLACE CONTROL TRANSFER SWITCH M
HSS-14902B in EMERG position.
d.
Transfer CONTROL TRANSFER SWITCH B HSS-14903A as follows:
(1)
ENSURE VAC PP DSCH TO SUPP POOL HV-149-F060 aligned to OPEN.
(2)
PLACE CONTROL TRANSFER SWITCH B HSS-14903A in EMERG position.
e.
PLACE CONTROL TRANSFER SWITCH N HSS-14903B in EMERG position.
f.
PLACE CONTROL TRANSFER SWITCH C HSS-14904A in EMERG position.
ON-100-009 Revision 3
Page 5 of 28 CONFIRM PLACE CONTROL TRANSFER SWITCH D HSS-14905A in EHERG position.
PLACE INSTR TRANSFER SMITCH 8 INSTR SET 3,4 HSS-15110A in EHERG position.
Transfer CONTROL TRANSFER SWITCH R HSS-151118 as follows:
(1)
ENSURE INSTR GAS TO CONTN ISO SV-12651 aligned to OPEN.
(2)
PLACE CONTROL TRANSFER SMITCH R HSS-151118 in EHERG position.
PLACE CONTROL TRANSFER SMITCH F HSS-15112A in EHERG position.
PLACE CONTROL TRANSFER SMITCH S HSS-151128 in EHERG position.
PLACE CONTROL TRANSFER SMITCH G
HSS-15113A in EHERG position.
Transfer CONTROL TRANSFER SMITCH T HSS-151138 as follows:
(1)
ENSURE SHUTDOWN CLG SUCT HV-151-F0068 aligned to CLOSE.
(2)
ENSURE RHR LOOP 8 CROSSTIE HV-151-F0108 aligned to CLOSE.
(3)
PLACE CONTROL TRANSFER SMITCH T HSS-151138 in EHERG position.
NOTE:
Indication for RHR LOOP 8 CROSSTIE HV-151-F0108 will not illuminate due to supply breaker being open.
Transfer CONTROL TRANSFER SMITCH H HSS-15114A as follows:
(1)
ENSURE RHR PUMP 8 SUCT HV-151-F0048 aligned to OPEN.
ON-100-009 Revision 3
Page 6 of 28 CONFIRM (2)
PLACE CONTROL TRANSFER SMITCH H HSS-15114A in EHERG position.
o.
Transfer CONTROL TRANSFER SMITCH U HSS-15114B as follows:
(I)
ENSURE INSTR GAS CNP OB SUCT ISO SV-12605 aligned to OPEN.
(2)
PLACE CONTROL TRANSFER SWITCH U
HSS-151148 in EHERG position.
PLACE CONTROL TRANSFER SMITCH J HSS-15115A in EHERG position.
Transfer CONTROL TRANSFER SWITCH V HSS-15115B as follows:
(1)
ENSURE HX B SHELL SIDE INLET HV-151-F047B aligned to OPEN.
(2)
'LACE 'CONTROL TRANSFER SWITCH V HSS-15115B in EMERG position.
Transfer CONTROL TRANSFER SWITCH K HSS-15116A as follows:
(1)
ENSURE HX B SHELL SIDE OUTLET HV-151-F003B aligned to OPEN.
(2)
PLACE CONTROL TRANSFER SMITCH K HSS-15116A in ENERG position.
s.
PLACE CONTROL TRANSFER SWITCH W
HSS-15116B in ENERG position.
t.'LACE CONTROL TRANSFER SMITCH L HSS-15117A in EHERG position.
u.
PLACE CONTROL TRANSFER SMITCH X HSS-151178 in EHERG position.
ENSURE Main Steam Lines ISOLATED by either:
a.
OBSERVING IB HSIV's indicate CLOSED.
b.
LOCALLY OBSERVING OB MSIV's CLOSED.
4.3.3 4.3.4 ON-100-009 Revision 3
Page 7 of 28 MMFIRM MONITOR available parameters to determine plant status.
NOTIFY I&C to install:
a ~
b.
Temporary level indication in accordance with IC-180-004, Reactor Shutdown Range Level Measurement at Rack 1C005, LT-B21-1N027.
Temporary reactor coolant tempei ature indication in accordance with IC-149-005, Installation and Removal of Temporary RTD Readers for Local Monitoring of RHR Heat Exchanger B Inlet (TE-Ell-1N004B) and Outlet (TE-Ell-1N027B) Temperatures.
NOTE:
Transferring control switch Y HSS-14454 to EMERG will cause RWCU OB ISO HV-144-F004 to close.
Opening breaker 18 in 1Y219 will de-energize SV-14433 closing HV-144F033.
4.4 If there is indication of RWCU piping leak or indication of flow being diverted to condenser or Radwaste through RWCU PERFORM following:
4.4.1 PLACE control transfer switch Y HSS-14454 to EMERG ~ND 4.4.2 OBSERVE green light ILLUMINATED.
4.4.3 OPEN breaker lY219-018 (29-719').
4.5 If Control Room evacuation was because of fire:
4.5.1 4.5.2 PERFORM the following within 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />s:
a.
OPERATE Control Structure HVAC in accordance with ON-030-001, Local Operation of Control Structure HVAC.
b.
SECURE any battery equalizing charges in progress.
PERFORM DC-OP-001, Post Fire Recovery Actions within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.
CAUTION ON-100-009 Revision 3
Page 8 of 28 CONFIRM If RHR Pump 1P202A must be tripped, PERFORM the following at lA20102:
a.
PLACE Lateral Control Switch to HANDLE OUT position.
b.
PLACE Lateral Control Switch to OPEN.
4.6 To control reactor pressure PERFORM following:
RHR PUMP 1P202A MAY SPURIOUSLY START PREVENTING UNIT 2 FROM RUNNING RHR PUMP 2P202A WHEN REQUIRED.
(')
4.5.3 NOTE:
4.6.1 Relief mode for SRV<s A, B, and C, will not auto initiate when applicable Control Transfer Switches are in EMERG position, however, safety function is always operable.
Also, when SRV Transfer Switches are in EMERG spurious auto actuation is prevented due to a Control Room fire.
ENSURE following valves OPEN:
a.
INSTR GAS TO CONTN ISO SV-12651.
b.
INSTR GAS CMP OB SUCT ISO SV-12605.
CAUTION LEVEL 1 (-129")
OR HIGH DRYWELL PRESSURE (1.72 PSIG)
LOCA ISOLATION SIGNAL IS DEFEATED FOR CIG VALVES WHEN CONTROLLED FROM THE REMOTE SHUTDOWN PANEL.
NOTE:
Placing Transfer Switch U, HSS-15114B, in EMERG causes instr gas cmp OB suction to cycle possibly tripping CIG compressors on low suction pressure.
4.6.2 If CIG Compressors
- tripped, RESET as follows at 1C239:
a.
DEPRESS Logic Reset Push button.
b.
ENSURE CIG Compressor STARTS.
4.6.3 OPERATE SRV's as'follows:
CAUTION 1
ON-100-009 Revision 3
Page 9 of 28 CONFIRM IF RPV PRESSURE DROPS BELOW 650
~CII TIIIN 2
WIDE RANGE LEVEL INDICATION BECOMES LESS ACCURATE AS RPV PRESSURE DECREASES.
a.
OPEN SRV's A,B, and C as needed.
NOTE:
b.
Keys to operate SRVs are located in sealed Pink sound powered phone storage box, labeled "JP1207,
- JP1402, JP2201",
inside the Remote Shutdown Panel Room.
If pneumatic supply to SRV's A, B, and C not available, OPERATE SRV's G, J, K,
L, M, or N (ADS valves) individually from upper(lower) relay room Panel 1C631 (1C628) using keylock switches.
4.6.4 c.
REFER to Attachment A for RPV Pressure/Temperature Correlation.
PLOT cooldown in accordance with Attachment A
and B.
CAUTION RCIC WILL NOT TRIP ON HIGH VESSEL LEVEL +54".
a ~
b.
When desired to place shutdown cooling in service, RAISE RPV water level to 90 - 100 inches.
WHEN reactor pressure
< 98 psig, ALIGN RHR System Loop B for Shutdown Cooling in accordance with OP-149-002, RHR Operation in Shutdown Cooling Mode.
4.7 Diesel Generator Local Start ON-100-009 Revision 3
Page 10 of 28 CONFIRM 4.7.1 4.7.2 4.7.3 If required, PERFORM ON-104-001 Unit 1
Response
to Loss of All Offsite Power.
If B Loop of ESW not available or cannot be placed in service, place A Loop ESW in service from Unit 2 Remote Shutdown Panel 2C201 in accordance with OP-054-001, Emergency Service Water System (ESW).
If required, START Diesel Generators A(B)(C)(D)(E) locally at OC521A(B)(C)(D)(E) in accordance with OP-024-001, Diesel Generators.
4.8 Re-ener gizing a 4.16KV ESS bus 4.8.1 If the Diesel Generator breaker to the 4. 16KV ESS bus fails to close, PERFORM following at 1A20104(1A20204)(1A20304)(1A20404):
'a ~
b.
ENSURE breaker control power in breaker cubicle available by CLOSING DC Ctl Power knife switch in lA20104(lA20204) (lA20304)
(1A20404)
ENSURE effects of breaker operation and associated interlocks have been evaluated.
c.
ENSURE Closing Spring Charging Motor operates.
d.
When closing spring is charged, OPERATE breaker as desired, using lateral control switch.
4.9 DISPATCH Operators to ENSURE following:
4.9.1 4.9.2 4.9.3 Main Turbine TRIPPED.
Generator TRIPPED by observing output breaker OPEN.
At 13.8 KV Switchgear, auxiliary buses transferred to Startup Bus 10 indicated by Breakers 1A10101 8 lA10201 OPEN and Breakers 1A10104 8 lA10204 CLOSED and voltage on bus.
4.9.4 4.9.5 4.9.6 4.9.7 4.9.8 ON-100-009 Revision 3
Page ll of 28 CONFIRM Hain Suction Pump and Turning Gear Oil Pump auto START.
Lift pumps auto START.
Turning Gear ENGAGES Hain Turbine.
Reactor Feed Pump Turbines TRIP.
Reactor Recirculation Pumps 1P401A 8
1P401B remain at minimum speed at Servo Controller 1S137A(B) as follows:
NOTE:
a a b.
Reactor Recirculation Pumps lAS1B should be at Limiter No.
1 (30X) due to low feedwater flow at this point.
REMOVE top cover.
PLACE control power switch to OFF.
4.10 When Control Room becomes available, PROCEED to OP-100-001 to return control to Control Room from Remote Shutdown Pane%.
5.0 REFERENCES
5.1 FSAR 7.4.1.4 5.2 E-153 Sh 4, 9-18, 20, 24, 36-41, 44 5.3 E-185 Sh 5, 10-13 5.4 J-451 Sh 1-3
(')
5.5 Susquehanna Fire Protection Review Report (a) 5.6 PLI-74583,App R HOT SHORTS Procedure Change Request 5.7 E-690 Appendix "R" Safe Shutdown Manual Actions List
ON-100-009 Revision 3
Page 12 of 28 6.0 DISCUSSION This procedure assumes EOPs are entered and providing directions for parameter control and is designed to shut down the plant from outside the Control Room by using the Remote Shutdown Panel and manual operations in the plant.
Since the Control Room will be evacuated, Unit 2 will be implementing ON-200-009 at the same time.
Transfer of control to the Remote Shutdown Panel bypasses Main Control Room devices and transfers component's control power to alternate supply.
The operation of systems and equipment needed for safe shutdown are those systems necessary to perform the following functions:
a.
REACTIVITY CONTROL:
RPS manual SCRAM from Control Room.
b.
REACTOR COOLANT MAKEUP:
c ~
REACTOR DEPRESSURIZATION and HEAT REMOVAL: Operating one of three specific SRV's from Remote Shutdown Panel or-ADS SRV's locally in Relay Rooms.
Shutdown Cooling and Suppression Pool Cooling are used for heat removal.
d.
- SUPPORT, FUNCTIONS:
RHR Service Water which removes heat from the Suppression Pool in the Suppression Pool Cooling Mode or the Reactor Loop through the Heat Exchanger in Shutdown Cooling.
2.
Emergency Service Water which provides cooling for equipment through the appropriate Room Coolers.
3.
Control Structure HVAC which is utilized to cool the Control Structure.
4.
'Diesel Generators and batteries which supply power to the various components with the AC and DC distribution system.
Evacuation of the main Control Room should only occur after reasonable efforts have been utilized including use of respiratory equipment.
Prior to leaving the Control Room, attempts are made to scram the reactor and close MSIV's and drains.
If Control Room actions cannot be performed, all functions can be performed outside the Control Room.
ON-100-009 Revi si on 3
Page 13 of 28 I8C is notified to install temporary remote level and temperature indication.
Wide range level instrumentation is increasingly less accurate as pressure decreases.
At approximately 200 psig, wide range level instrument indicates
+60" when actual level is 0".
Temperature indication is not available at the shutdown panel to monitor reactor coolant temperature.
While the reactor is pressurized, coolant temperature is derived from RPV pressure using the saturation curve on Attachment A.
Once the reactor is depressurized, coolant temperature is unavailable at the remote shutdown panel.
This procedure, and in conjunction with appropriate EOP's, ON's, OP's, etc., will:
a.
Achieve and maintain subcritical reactivity conditions.
b.
Maintain Reactor coolant inventory.
c.
Achieve Hot Shutdown.
d.
Achieve and maintain Cold Shutdown.
Transfer switches are wired very differently in Unit 1
RSP as compared to Unit 2 RSP.
This requires procedure steps to be implemented differently on each unit.
1600 PRESSURE VS TEMPERATURE FOR SATURATED STEAM Attachment A
ON-100-009 Rev1sion 3
Page 14 of 28 1500 1l00 1300 1200 C9 g) 1100 CL 1000 L1j S00 800 U)
LU
~00 600 500 300 100 1
Page 1 of 1
200 250 300 l00 l50 TEMPERATURE (F) 500 550 600
Attachnent 8
ON-100-009 Revision 3
Page 15 of 28 550 PV TEHPERATURE PLOT 500 450 400 REACTOR 350 COOLANT TEHPERATURE
('F) '00 250 200 150 100 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 TIHE (HOURS)
Page 1 of 1,
SOUND POWERED PHONE LOCATIONS Attachment C
ON-100-009 Revision 3
Page 16 of 28 Jack Plate Identification Loop 2 Remote Shtdwn (JP1201)
Loop 2 Remote Shtdwn (JP1202)
Loop 2 Remote Shtdwn (JP1203)
Loop 2 Remote Shtdwn (JP1204)
Loop 2 Remote Shtdwn (JP1205)
Loop 2 Remote Shtdwn (JP1206)
Loop 2 Remote Shtdwn (JP1207)
Loop 2 Remote Shtdwn (JP1208)
Loop 2 Remote Shtdwn (JP1209)
Loop 2 Remote Shtdwn (JP1210)
Loop 2 Remote Shtdwn (JP1211)
Loop 2 Remote Shtdwn (JP1212)
Loop 2 Remote Shtdwn (JP1213)
Loop 2 Remote Shtdwn (JP1214)
Loop 2 Remote Shtdwn (JP1215)
Loop 2 Remote Shtdwn (JP2201)
Loop 2 Remote Shtdwn (JP2205)
Location (Area/Elevation) lA201 4.16 KV Switchgear Room 1A202 4.16 KV Switchgear Room RPS H/G Set 1A203 4. 16 KV Switchgear Room lA204 4.16 KV Switchgear Room CS HVAC Local Panel (29/749)
(28/749)
(30/762)
(29/719)
(28/719)
(21/783)
Unit 1 Remote Shutdown Panel Room (25/670) 13.8 KV Switchgear 1A101/lA102 Lower Relay Room A D/G Room 8 D/G Room C D/G Room D D/G Room E D/G Room
( 8/699)
(12/698)
(44/677),
(44/677)
(43/677)
(43/677)
(43/677)
Unit 2 Remote Shutdown Panel Room (32/670)
Unit 1 Remote Shutdown Panel Room (25/670)
Unit 2 Remote Shutdown Panel Room (32/670)
Page 1 of 2
SOUND POWERED PHONE LOCATIONS General Notes:
1)
A maximum of 6 jack plates can be used at one time.
Attachment C
ON-100-009 Revision 3
Page 17 of 28 2)
Sound Powered Phone Headsets are located in a sealed box near the jack plate.
3)
Can establish communications between any 2 to 6 locations listed above.
4)
Jack Plates and Headset Storage Boxes are color coded pink.
5)
Communications between Unit 1
& Unit 2 Remote Shutdown Panels use either:
JP1215 to JP1207 JP2201 to JP2205 Page 2 of 2
1.
CONTROL TRANSFER SWITCH A HSS-14901A (INSTR SET 1, 2) a.
RCIC FLOW INDICATION b.
RCIC FLOW CONTROLLER c.
RCIC SPEED INDICATION d.
SUPP POOL WATER TEMP (PARTIAL) e.
INBOARD MSIV INDICATION 2.
CONTROL TRANSFER SWITCH B HSS-15110A (INSTR SET 3, 4)
Attachment D
ON-100-009 Revision 3
Page 18 of 28 3.
a.
FLOW c.
SUPP POOL LEVEL d.
CONTAINMENT PRESSURE e.
SUPP POOL WATER TEMP (PARTIAL) f.
CONTAINMENT TEMPERATURE g.
SUPP POOL AIR TEMP CONTROL TRANSFER SWITCH A HSS-14902A
'a ~
b.
1P220 RCIC BARO CONDENSER CONDENSATE PUMP (1)
CONTROL AND INDICATION (2)
PUMP WILL AUTO CYCLE WITH LEVEL HV-149-F031 RCIC PUMP SUCT FROM SUPP POOL E-154 SH 2
E-154 SH 10 Co (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO OPEN ON LOW CST LEVEL TRANSFERS POWER SOURCE TO RCIC FROM EMG TURB SPEED E-154 SH 39 CONTROL BOX Page 1 of ll
4.
d.
HV-149-F046 RCIC BARO CONDENSER SPRAY (1)
OPEN SIGNAL TO VALVE CONTROL TRANSFER SWITCH B HSS-14903A a.
HV-15012 RCIC TURBINE TRIP AND THROTTLING VLV (1)
CONTROL AND INDICATION (2)
NO FUNCTIONS BYPASSED I
b.
FV-149-F019 RCIC MIN FLOW TO SUPP POOL Attachment D
ON-100-009 Revision 3
Page 19 of 28 E-154 SH 9 E-154 SH 8 E-154 SH 12 5.
(1)
CONTROL AND INDICATION (2)
DEFEAT AUTO OPEN ON HIGH PRESS AND LOW FLOW (3)
DEFEAT AUTO CLOSE ON HIGH FLOW, STOP VLV CLOSURE, OR STEAH ADMISSION VLV CLOSURE c.
HV-149-F060 RCIC VAC PP DSCH TO SUPP POOL (1)
CONTROL AND INDICATION (2)
NO AUTO FUNCTIONS EXIST d.
HV-149-F062 RCIC TURB EXH OB VAC BKR (1)
INDICATION (2)
SEE HSS-14904A FOR BALANCE LOGIC CONTROL TRANSFER SWITCH C HSS-14904A a.
HV-149-F008 RCIC STEAM SUPPLY OB ISO (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO CLOSE ON ISOLATION SIGNAL E-154 SH 13 E-154 SH 17 E-154 SH 3 Page 2 of ll
b.
HV-149-F013 RCIC INJECTION (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO OPEN ON INITIATIONSIGNAL (3)
DEFEAT AUTO CLOSE ON +54 SHUTDOWN SIGNAL c.
HV-149-F062 RCIC TURB EXH OB VAC BKR Attachment D
ON-100-009 Revision 3
Page 20 of 28 E-154 SH 7 E-154 SH 17 6.
7.
(1)
CONTROL AND INDICATION (2)
DEFEAT AUTO CLOSE ON LOW VESSEL PRESS WITH HIGH CONTAINMENT PRESS (3)
SEE HSS-14903A FOR BALANCE OF LOGIC CONTROL TRANSFER SWITCH D HSS-14905A a.
HV-149-F007 RCIC STEAM SUPPLY IB ISO (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO CLOSE ON ISOLATION SIGNAL (3)
CAN BE OPENED WITH ISOLATION SIGNAL PRESENT b.
HV-143-F023B RECIRC PUMP B SUCT (1)
CONTROL AND INDICATION (2)
NO AUTO FUNCTIONS EXIST c.
HV-149-F084 RCIC TURB EXH IB VAC BKR (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO CLOSE ON LOW VESSEL PRESSURE
- WITH, HIGH CONTAINMENT PRESS CONTROL TRANSFER SWITCH M HSS-14902B a.
1P219 RCIC BARO CDSR VACUUM PP (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO START ON INITIATION SIGNAL b.
HV-149-F010 RCIC PUMP SUCT FROM CST E-154 SH 4 E-151 SH 8 E-154 SH 16 E-154 SH 1
E-154 SH 11 Page 3 of ll
(1)
CONTROL AND INDICATION Attachment D
ON-100-009 Revision 3
Page 21 of 28 8.
(2)
DEFEAT AUTO CLOSE ON HV-149-F031 FULL OPEN (3)
DEFEAT AUTO OPEN ON INITIATION SIGNAL AND HV-149-F031 NOT FULL OPEN c.
HV-149-F059 RCIC TURB EXH TO SUPP POOL (1)
CONTROL AND INDICATION (2)
NO AUTO FUNCTIONS EXIST d.
TRANSFERS POWER SOURCE TO RCIC TURB TRIP SOLENOID, HOWEVER, TRIP SIGNAL RELAY KS IS BYPASSED CONTROL TRANSFER SMITCH N HSS-14903B E-154 SH 14
'a ~
b.
C.
HV-149-F045 STEAM TO RCIC TURBINE (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO OPEN ON INITIATION SIGNAL (3)
DEFEAT AUTO CLOSE ON +54 INCH SHUTDOWN SIGNAL HV-149-F012 RCIC PUMP DISCH (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO OPEN ON INITIATIONSIGNAL HV-149-F022 RCIC TEST LINE ISO TO CST (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO CLOSE ON INITIATIONSIGNAL (3)
DEFEAT AUTO CLOSE ON HV-149-F031 OPEN (4)
HV-149-F013, RCIC INJECTION, MUST BE CLOSED TO OPEN VLV ALSO WILL CLOSE F022 IF F013 LEAVES FULL CLOSED POSITION E-154 SH 5
E-154 SH 6 E-154 SH 15 Page 4 of ll
9.
CONTROL TRANSFER SWITCH R HSS-15111B a.
PSV-1F013A A SRV (1)
CONTROL (NO INDICATION ON RSP)
(2)
DEFEAT RELIEF FUNCTION b.
SV-12651 INSTR GAS TO CONTN ISO Attachment D
ON-100-009 Revision 3
Page 22 of 28 E-180 SH 1
E-172 SH 5 (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO CLOSE ON CONTAINMENT ISOLATION (3)
VALVE MILL AUTO CLOSE DURING TRANSFER 10.
CONTROL TRANSFER SMITCH F HSS-15112A a.
PSV-1F013C C SRV (1)
CONTROL (NO INDICATION ON RSP)
(2)
DEFEAT RELIEF FUNCTION b.
HV-151-F009 SHUTDOWN CLG SUCT IB ISO (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO CLOSE ON RHR NSSSS ISOLATION (3) 98 PSIG VESSEL HIGH PRESSURE MILL ISOLATE VLV, 125V DC
- POWER, DOES NOT RE(UIRE RESET c.
HY-12603 INSTR GAS CHP IB SUCT ISO (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO CLOSE ON ISOLATION SIGNAL
'l.
CONTROL TRANSFER SMITCH S HSS-15112B E-180 SH 1
E-153 SH 17 E-172 SH 2 a 0 b.
HV-151-F040 RADWASTE IB ISO (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO CLOSE ON NSSSS ISOLATION SIGNAL HV-151-F006A SHUTDOWN CLG SUCT (1)
CLOSE SIGNAL TO VALVE E-153 SH 40 E-153 SH 20 Page 5 of ll
c.
HV-151-F006C SHUTDOWN CLG SUCT (1)
CLOSE SIGNAL TO VALVE d.
PSV-1F013B B SRV (1)
CONTROL (NO INDICATION ON RSP)
(2)
DEFEAT RELIEF FUNCTION
'12.
CONTROL TRANSFER SWITCH G HSS-15113A a.
HV-151-F008 SHUTDOWN COOLING SUCT OB ISO Attachment D
ON-100-009 Revision 3
Page 23 of 28 E-153 SH 20 E-180 SH 1
E-153 SH 15 (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO CLOSE ON RHR NSSSS ISOLATION (3) 98 PSIG VESSEL HIGH PRESSURE WILL ISOLATE VLV, 125 V DC
- POWER, DOES NOT RE(UIRE RESET b.
HV-112-F073B RHR SM CROSS TIE (1) 'LOSE SIGNAL TO VALVE 13.
CONTROL TRANSFER SMITCH T HSS-15113B E-150 SH 29 a ~
b.
c ~
d.
Page 6 of ll HV-151-F006B SHUTDOWN CLG SUCT (1)
CONTROL AND INDICATION (2)
DEFEAT INTERLOCK THAT REQUIRES HV-151-F028A CLOSED TO OPEN VALVE (3)
STILL HAVE INTERLOCK THAT RE(UIRES HV-141-F004A CLOSED TO OPEN VALVE HV-151-F010B RHR LOOP B CROSS TIE (1)
CONTROL AND INDICATION (2)
NO AUTO FUNCTIONS EXIST HV-151-F006D SHUTDOWN CLG SUCT (1)
CLOSED SIGNAL TO VALVE HV-151-F016B RHR DRYWELL SPRAY OB ISO (1)
CLOSE SIGNAL TO VALVE E-153 SH 36 E-153 SH 112 E-153 'SH 20 E-153 SH 114
14.
CONTROL TRANSFER SWITCH H HSS-15114A a.
HV-151-F004B RHR PUMP B SUCT (1)
CONTROL AND INDICATION (2)
HV-151-F006B MUST BE CLOSED TO OPEN VALVE b.
HV-151-F017B RHR INJ FLOW CTL (1)
CONTROL AND INDICATION (2) 'EFEAT INTERLOCK WITH HV-151-F015B (3)
DEFEAT AUTO OPEN ON LOCA SIGNAL c.
HV-151-F049 RADWASTE OB ISO (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO CLOSE ON OB CONTAINMENT ISO (3)
CAN BE OPENED WITH ISO SIGNAL PRESENT 15.
CONTROL TRANSFER SWITCH U HSS-15114B Attachment D
ON-100-009 Revision 3
Page 24 of 28 E-153 SH 10 E-153 SH 14 E-153 SH 39 a ~
1P202B RHR PUMP 1B (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO START ON LOCA SIGNAL (3)
DEFEAT AUTO TRIP WITH NO SUCTION PATH ALIGNED (4)
DEFEAT LOCA/FALSE LOCA TRIP (5)
START DELAYED 3 SECONDS IF DG SUPPLYING BUS (6) 2B RHR PUMP MUST BE SHUTDOWN TO START E-153 SH 4 Page 7 of ll
b.
HV-151-F024B TEST LINE CTL (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO CLOSE ON LOCA SIGNAL c.
SV-12605 INSTR GAS CMP OB SUCT Attachment D
ON-100-009 Revision 3
Page 25 of 28 E-153 SH 13 E-172 SH 5 (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO CLOSE ON CONTAINMENT ISOLATION (3)
VALVE WILL CYCLE CLOSED DURING TRANSFER TRIPPING CIG COMPRESSORS 16.
CONTROL TRANSFER SWITCH J HSS-15115A a.
HV-151-F007B RHR PP B/D MIN FLOW (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO OPEN ON LOW FLOW (3)
DEFEAT AUTO CLOSE ON HIGH FLOW b.
HV-151-F028B SUPP CHMBR SPR TEST SHUTOFF (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO CLOSE ON LOCA SIGNAL 17.
CONTROL TRANSFER SWITCH V HSS-15115B E-153 SH 93 E-153 SH 12 a ~
b.
HV-151-F047B RHR HX B SHELL SIDE INLET (1)
CONTROL AND INDICATION (2)
NO AUTO FUNCTIONS EXIST HV-151-F103B RHR HX B VENT (1)
CONTROL AND INDICATION (2)
NO AUTO FUNCTIONS EXIST E-153 SH 107 E-153 SH 94 Page 8 of ll
c.
HV-151-F048B RHR HX B SHELL SIDE BYPS (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO OPEN ON LOCA SIGNAL d.
HV-151-F027B SUPP CHHBR SPRAY CTL (1)
CLOSE SIGNAL TO VALVE 18.
CONTROL TRANSFER SWITCH K HSS-15116A Attachment D
ON-100-009 Revision 3
Page 26 of 28 E-153 SH 9 E-153 SH 115
'a ~
b.
C.
HV-151-F003B RHR HX B SHELL SIDE OUTLET (1)
CONTROL AND INDICATION (2)
NO AUTO FUNCTIONS EXIST HV-151-F104B RHR HX B VENT (1)
CONTROL AND INDICATION (2)
NO AUTO FUNCTIONS EXIST HV-151-F015B RHR INJ OB ISO (1)
CONTROL AND INDICATION (2)
DEFEAT AUTO OPEN ON LOCA SIGNAL (3)
DEFEAT INTERLOCK WITH HV-151-F017A (4)
DEFEAT INTERLOCK WITH VESSEL HIGH PRESS (5)
DEFEAT AUTO CLOSE ON +13 INCH SDC ISOLATION E-153 SH 11 E-153 SH 94 E-153 SH 16 19.
CONTROL TRANSFER SMITCH-W HSS-15116B a.
HV-11215B RHRSM HX B OUTLET
. (1)
CONTROL AND INDICATION (2)
NO AUTO FUNCTIONS EXIST E-150 SH 12 Page 9 of ll
b.
HV 01222B SPRAY POND LOOP B BYPS (1)
CONTROL AND INDICATION (2)
VALVE WILL AUTO OPEN ON PUMP START OR ON LAST PUMP SHUTDOWN c.
1P506B 1B RHRSW PUMP Attachment D
ON-100-009 Revision 3
Page 27 of 28 E-150 SH 4 E-150 SH 13 (1)
CONTROL AND INDICATION (PARTIAL)
(2)
DEFEATS LOCA TRIP (3)
SEE HSS-15117B TRANSFERS REMAINING CONTROL AND INDICATION 20.
CONTROL TRANSFER SWITCH L HSS-15117A a ~
b.
C.
HV-01224B1 SPRAY POND NETWORK Bl (1)
CONTROL AND INDICATION (2)
NO AUTO FUNCTIONS EXIST OP504B B
ESW PUMP (1)
CONTROL AND INDICATION (2)
ENABLES INDICATION AT U2 RSP (3)
PUMP WILL START WITH D/G (4)
DEFEATS LOCA/LOOP RESET LOGIC HV-11210B RHRSW HX B INLET (1)
CONTROL AND INDICATION (2)
NO AUTO FUNCTIONS EXIST E-150 SH 8 E-146 SH 3
- 8. 4 E-150 SH 11 Page 10 of ll
21.
CONTROL TRANSFER SWITCH X HSS-15117B a.
HV-01224B2 SPRAY POND NETWORK B2 (1)
CONTROL AND INDICATION (2)
NO AUTO FUNCTIONS EXIST b.
OP504D D
ESW PUMP (1)
CONTROL AND INDICATION (2)
ENABLES INDICATION AT U2 RSP (3)
PUMP WILL START WITH D/G (4)
DEFEATS LOCA/LOOP RESET LOGIC c.
1P506B 1B RHRSW PUMP (1)
CONTROL AND INDICATION (PARTIAL)
Attachment D
ON-100-009 Revision 3
Page 28 of 28 E-150 SH 8 E-146 SH 7
- 8. 8 E-150 SH 2
(2)
SEE HSS-15116B TRANSFERS REMAINING CONTROL AND INDICATION 22.
CONTROL TRANSFER SWITCH Y HSS-14454 a.
CLOSE SIGNAL TO VALVE (2)
THERMAL OVERLOADS BYPASSED E-165 SH 7
Page ll of ll