ELECTRICAL POWER SYSTEMS SURVEILLAHCE RE IRENENTS Continued 5) 6)

7) 8)

Channel "A" battery 20612:

338 amperes for 60 seconds 112 amperes for'he remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.

Channel "8" battery 20622:

346 amperes for 60 seconds 121 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.

Channel "C" battery 20632:

326 amperes for 60 seconds 107 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.

Channel "0" battery 20642:

326 amperes for 60 seconds 107 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.

9)

Channel "H" battery 00595:

aug 486 amperes for the first 60 seconds 8-minutes

'7~MS amperes for the Ws4-aRy4e. of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.

P 6'~~n&Cp c)

For 250-volt batteries:

1)

Battery bank 10650:

1120 amperes for 60.0 seconds 599 amperes for 29.0 minutes 99 amperes for 120.0 minutes 27 amperes for 90.0 minutes 2)

Battery bank 887 amperes 396 amperes 366 amperes 325 aiperes 187 amp eres 229 aIperes 10660:

for 60.0 seconds for 9.0 minutes for 20.0 minutes for 90.0 minutes for 119. 0 minutes for 60.0 seconds e.

At least once per 60 months by verifying that the battery capacity is at least 8GX of the manufacturer's rating when subjected to a performance discharge test.

Once per 60 month interval, this per-formance discharge test may be performed in lieu of the battery service test.

f.

Annual performance discharge tests of battery capacity shall be given to any battery that shows signs of degradation or has reached 85% of the service life expected for the application.

Oegradation is indicated when'he battery capacity drops more than 10K of rated capacity from its average on previous performance tests, or is below 90K of the manufacturer's rating.

SUS(UEHAHHA - UHIT 1 8904200367 S904i4 PDR ADOCK 05000337 PDC 3/4 8-13 Amen~nt Ho.

86

TABLE 3. 8. 4.'2. 1-1 MOTOR OPERATEO VALVES THERMAL OVERLOAO PROTECTION -

CONTINUOUS VALVE NUMBER HV"01222A HV-012228

HV-01224A1 HV-01224Bl HV-01224A2 HV-0122482 SYSTEM(S)

AFFECTED RHRSW RHRSW RHRSW RHRSW RHRSW RHRSW HV-08693A HV-086938 HV-01201Al.

HV-01201A2 HV"0120181 HV-01201B2 HV-11210A HV-11210B HV-11215A HV-112158

.HV-15766 HV-15768 HV-12603 HV-11345 HV"11313 HY-11346 HV-11314 HV-E11-1r 009 W-ESW ESW RHRSW RHRSW RHRSW RHRSW RHRSW RHRSW RHRSW RHRSW Cont.

Cont.

Cont.

Cont.

Cont.

Cont.

Cont.

RHR Isol.

Iso 1.

Isol.

Iso l.

Isol.

Isoi.

Isol.

SUS(UEHANNA - UNIT 1 3/4 8-29 Amendment No. "-1

TABLE 3.8.4

~ 2.2-1 MOTOR OPERATED VALVES THERMAL OVERLOAD PROTECTION - AUTOMATIC VALVE NUMBER HV-01110 E HV-01120E

~y-ofiiia' Y-oozed E'.

SYSTEN(S)

AFFECTEQ SUSQUEHANNA - UNIT 1, 3/4 8-32b Amendment No. 53 4Ai.

c '==,

ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREHENTS Continued 7)

Channel "C" battery 2D632:

326 amperes for 60 seconds 107 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test 8)

Channel "D" battery 2D642:

326 amperes for 60 seconds 107 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test 9) 1 "tl" 00595:

p 4

mper~s forthe-next-238-minutes,

~mperes-for-the-4a

'se-A'-She-4-hou c)

For 250-volt batteries:

gg ~y~ g~

p~ a ~ ~c J c's'p p.p~~gpg Jcp dg ~( +40>>

X csZ.

1)

Battery bank 2D650:

458 amperes for 60 seconds 251 amperes for 239 minutes 2)

Battery bank 2D660:

1119 amperes for 60 seconds 244 amperes for 239 minutes f.

Annual performance discharge tests of battery capacity shall be given to any battery that shows signs of degradation or has reached 85K of the service life expected for the application.

Degradation is indicated when the battery capacity drops more than 10K of rated capacity from its average on previous performance tests, or is below 90K of the manufacturer's rating.

e.

At least once per 60 months by verifying that the battery capacity is at least 80K of the manufacturer's rating when subjected to a per" formance discharge test.

Once per 60-month interval, this performance discharge test may be performed in lieu of the battery service test.

. SUSQUEHANNA - UNIT'2 3/4 8-13a Amendment No. 44

I

'I Wq

/

TABLE 3. 8. 4. 2. 1-1 MOTOR-OPERATEO VALVES THERMAL OVERLOAO PROTECTION CONTINUOUS VALVE NUMBER HV-01222A HV-01222B HV-01224A1 HV-01224B1 HV-01224A2 HV-01224B2 SYSTEM(S)

AFFECTED RHRSW RHRSW RHRSW RHRSW RHRSW RHRSW

~HV~O

~V-e~e HV-21144A, HV"211448 HV-08693A HV-086938 HV"01201A1 HV-01201A2 HV-0120181 HV"0120182 HV" 21210A'V-212108 HV"21215A HV-212158 HV"25766 HV"25768 HV-22603 W-W W-W-

WW-W W"

ESW ESW ESW ESW RHRSW RHRSW RHRSW RHRSW RHRSW RHRSW RHRSW RHRSW Cont. Isol.

Cont. Isol.

Cont.

Iso',.

SUSQUEHANNA - UNIT 2 3/4 8"31 Amendment No.

32

TABLE 3. 8. 4. 2. 2-1 MOTOR

.OPERATED VALVES THERMAL OVERLOAD PROTECTION - AUTOMATIC Valve Number HV-01110E HV"01120E System(s)

Affected ESW ESM Hv-o iiiZe A V- 0 ll24 E r std E

SUSQUEHANNA - UNIT 2 3/4 8"34b Amendment No.