Proposed Tech Specs,Making Changes to Emergency Svc Water Sys,Per 10CFR50,App R
ML17156B110
Person / Time
Site: Susquehanna  Talen Energy icon.png
Issue date: 04/14/1989
From:
PENNSYLVANIA POWER & LIGHT CO.
To:
Shared Package
ML17156B109 List:
References
NUDOCS 8904200367
Download: ML17156B110 (8)


Text

ELECTRICAL POWER SYSTEMS SURVEILLAHCE RE IRENENTS Continued

5) Channel "A" battery 20612:

338 amperes for 60 seconds 112 amperes for'he remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.

6) Channel "8" battery 20622:

346 amperes for 60 seconds 121 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.

7) Channel "C" battery 20632:

326 amperes for 60 seconds 107 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.

8) Channel "0" battery 20642:

326 amperes for 60 seconds 107 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.

9) Channel "H" battery 00595:

aug 486 amperes for the first 60 seconds 8-minutes

'7~MS amperes for the Ws4-aRy4e. of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test.

P 6'~~n&Cp c) For 250-volt batteries:

1) Battery bank 10650:

1120 amperes for 60.0 seconds 599 amperes for 29.0 minutes 99 amperes for 120.0 minutes 27 amperes for 90.0 minutes

2) Battery bank 10660:

887 amperes for 60.0 seconds 396 amperes for 9.0 minutes 366 amperes for 20.0 minutes 325 aiperes for 90.0 minutes 187 amp eres for 119. 0 minutes 229 aIperes for 60.0 seconds

e. At least once per 60 months by verifying that the battery capacity is at least 8GX of the manufacturer's rating when subjected to a performance discharge test. Once per 60 month interval, this per-formance discharge test may be performed in lieu of the battery service test.
f. Annual performance discharge tests of battery capacity shall be given to any battery that shows signs of degradation or has reached 85% of the service life expected for the application. Oegradation is indicated when'he battery capacity drops more than 10K of rated capacity from its average on previous performance tests, or is below 90K of the manufacturer's rating.

SUS(UEHAHHA - UHIT 1 3/4 8-13 Amen~nt Ho. 86 8904200367 S904i4 PDR ADOCK 05000337 PDC

TABLE 3. 8. 4.'2. 1-1 MOTOR OPERATEO VALVES THERMAL OVERLOAO PROTECTION - CONTINUOUS SYSTEM(S)

VALVE NUMBER AFFECTED HV"01222A RHRSW HV-012228 RHRSW HV-01224A1 RHRSW HV-01224Bl RHRSW HV-01224A2 RHRSW HV-0122482 RHRSW W-HV-08693A ESW HV-086938 ESW HV-01201Al. RHRSW HV-01201A2 RHRSW HV"0120181 RHRSW HV-01201B2 RHRSW HV-11210A RHRSW HV-11210B RHRSW HV-11215A RHRSW HV-112158 RHRSW

.HV-15766 Cont. Isol.

HV-15768 Cont. I so 1.

HV-12603 Cont. Isol.

HV-11345 Cont. Iso l.

HV"11313 Cont. Isol.

HY-11346 Cont. Isoi.

HV-11314 Cont. Isol.

HV- E11-1r 009 RHR SUS(UEHANNA - UNIT 1 3/4 8-29 Amendment No. "-1

TABLE 3.8.4 2.2-1

~

MOTOR OPERATED VALVES THERMAL OVERLOAD PROTECTION - AUTOMATIC SYSTEN(S)

VALVE NUMBER AFFECTEQ HV-01110 E HV-01120E

~y-of i iia' Y-oozed E'.

SUSQUEHANNA - UNIT 1, 3/4 8-32b Amendment No. 53 4Ai. c '==,

ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREHENTS Continued

7) Channel "C" battery 2D632: 326 amperes for 60 seconds 107 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test
8) Channel "D" battery 2D642: 326 amperes for 60 seconds 107 amperes for the remainder of the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> test
9) 1 "tl" 00595: p 4 mper~s forthe-next-238-minutes,

~mperes-for-the-4a 'se-A'-She-4-hou c) For 250-volt batteries:

gg ~y~ g~ p~ a ~ ~c J c's'p

1) Battery bank 2D650: p.p~~gpg Jcp dg ~( +40>>

458 amperes for 60 seconds 251 amperes for 239 minutes X csZ.

2) Battery bank 2D660:

1119 amperes for 60 seconds 244 amperes for 239 minutes

e. At least once per 60 months by verifying that the battery capacity is at least 80K of the manufacturer's rating when subjected to a per" formance discharge test. Once per 60-month interval, this performance discharge test may be performed in lieu of the battery service test.
f. Annual performance discharge tests of battery capacity shall be given to any battery that shows signs of degradation or has reached 85K of the service life expected for the application. Degradation is indicated when the battery capacity drops more than 10K of rated capacity from its average on previous performance tests, or is below 90K of the manufacturer's rating.

. SUSQUEHANNA - UNIT'2 3/4 8-13a Amendment No. 44

I

'I Wq

/

TABLE 3. 8. 4. 2. 1-1 MOTOR-OPERATEO VALVES THERMAL OVERLOAO PROTECTION CONTINUOUS SYSTEM(S)

VALVE NUMBER AFFECTED HV-01222A RHRSW HV-01222B RHRSW HV-01224A1 RHRSW HV-01224B1 RHRSW HV-01224A2 RHRSW HV-01224B2 RHRSW

~HV~O W-

~V-e~e W W-W-

W W-W W"

HV-21144A, ESW HV"211448 ESW HV-08693A ESW HV-086938 ESW HV"01201A1 RHRSW HV-01201A2 RHRSW HV-0120181 RHRSW HV"0120182 RHRSW HV" RHRSW 21210A'V-212108 RHRSW HV"21215A RHRSW HV-212158 RHRSW HV"25766 Cont. Isol.

HV"25768 Cont. Isol.

HV-22603 Cont. Iso',.

SUSQUEHANNA - UNIT 2 3/4 8"31 Amendment No. 32

TABLE 3. 8. 4. 2. 2-1 MOTOR .OPERATED VALVES THERMAL OVERLOAD PROTECTION - AUTOMATIC System(s)

Valve Number Affected HV-01110E ESW HV"01120E ESM Hv-o iiiZe A V- 0 ll24 E r std E

SUSQUEHANNA - UNIT 2 3/4 8"34b Amendment No. 32 BAR;6 Ig87