Proposed Tech Spec Changes Providing Editorial Correction to Previously Approved Change for Unit 1 & Supporting Mods Which Enhance Capability of Drywell Cooling Sys for Unit 2ML17146A311 |
Person / Time |
---|
Site: |
Susquehanna |
---|
Issue date: |
03/27/1986 |
---|
From: |
PENNSYLVANIA POWER & LIGHT CO. |
---|
To: |
|
---|
Shared Package |
---|
ML17146A310 |
List: |
---|
References |
---|
NUDOCS 8604020436 |
Download: ML17146A311 (8) |
|
|
---|
Category:TECHNICAL SPECIFICATIONS
MONTHYEARML18040B2891999-03-12012 March 1999 Proposed Tech Specs Including Rev 0 to EMF-1997(P)(A) Into TS Section 5.6.5 & Including Revised MCPR Safety Limits in TS Section 2.1.1.2 ML18040B2881999-01-12012 January 1999 Proposed Tech Specs Re ANFB-10 Critical Power Correlation & MCPR Safety Limits ML17164A6711998-07-0808 July 1998 Proposed Tech Specs,Implementing Improved Tech Specs of NUREG-1433.Page B3.8-1 of Incoming Submittal Not Included ML17159A3261998-05-12012 May 1998 Proposed Tech Specs Re Removal of Fire Protection Program ML18026A4711997-02-11011 February 1997 Proposed Tech Specs Requesting Improved TSs LCO 3.10.3 & LCO 3.10.4 Be Approved for Use During Susquehanna Ses Unit 2 Eighth Refueling & Insp Outage Scheduled for 970315 ML20129D7851996-09-23023 September 1996 Proposed Tech Specs Re MSIVs Leakage Testing ML20116K3491996-08-0909 August 1996 Proposed Tech Specs Re Battery Load Profiles ML17158B5581996-03-20020 March 1996 Proposed Tech Specs,Changing Open Logic for HPCI Suction Valve HV-155/255-F042 in Order to Eliminate HPCI Pump auto- Transfer on High Suppression Pool Level ML20115A8171996-02-29029 February 1996 Proposed Tech Specs,Relocating Spec 3/4.9.6, Refueling Platform to Document Which Is Controlled Under Requirements of 10CFR50.59 ML20115A8211996-02-29029 February 1996 Proposed Tech Specs,Removing Rod Block Monitor Requirements from TS by Reducing Number of Rod Movements During Power Maneuvers ML17158B1071996-02-12012 February 1996 Proposed Tech Specs to Implement 10CFR50,App J,Option B & Establish New Spec 6.8.5, Primary Containment Leakage Rate Testing Program. ML17164A5801995-02-10010 February 1995 Proposed Tech Specs for Aot/Sti Extensions ML17164A4351994-11-21021 November 1994 Proposed Tech Specs Increasing MSIV Leakage Rate & Deleting MSIV-LCS ML17158A5441994-10-28028 October 1994 Proposed Tech Specs,Incorporating Administrative Changes ML20058F8281993-11-24024 November 1993 Proposed Tech Specs Re Power Uprate W/Increased Flow ML17157C2741993-04-0202 April 1993 Proposed TS 3.4.1.1.2 Re LCO for Recirculation Loops,Single Loop Operation ML20082P1871991-09-0404 September 1991 Proposed Tech Specs for HPCI Sys Low Pressure Surveillance Test Acceptance Criteria ML17157A3371990-09-24024 September 1990 Proposed Tech Specs in Support of Facility Cycle 5 Reload ML17157A2441990-07-0202 July 1990 Proposed Tech Specs to Support Cycle 6 Reload ML19325D7491989-10-19019 October 1989 Proposed Tech Specs 3.2.2 Eliminating Certain Requirements on One Time Basis for 3 Months ML17156B1101989-04-14014 April 1989 Proposed Tech Specs,Making Changes to Emergency Svc Water Sys,Per 10CFR50,App R ML17156A7291988-08-10010 August 1988 Proposed Tech Specs,Extending Operation During Cycle 4 W/ One Recirculation Loop Out of Svc ML18040A8741988-04-0606 April 1988 Proposed Tech Specs Re Radiation Monitoring Instrumentation ML17146B0891987-12-23023 December 1987 Proposed Tech Specs Index & Sections 3/4.2.1,3/4.2.2, 3/4.2.3,3/4.2.4,3/4.3.6,3/4.4.1,B 2.1,B 3/4.2.1,B 3/4.2.2, B 3/4.2.3 & B 3/4.4.1,to Support Cycle 3 Reload ML18040A8421987-06-10010 June 1987 Proposed Tech Specs,Increasing Load Profile for Batteries 1D612 & 1D622 ML18040A8341987-04-16016 April 1987 Proposed Tech Spec 4.1.3.1.4(a) Changing Requirements for Surveillance of Scram Discharge Vol Vent & Drain Valves ML18040A8261987-02-0909 February 1987 Proposed Tech Specs,Allowing Alternate Method of post-accident Drywell Gaseous Sampling & Providing Relief for Unnecessarily Restrictive Action Statement on Drywell Oxygen Analyzer ML20215C1291986-12-0909 December 1986 Proposed Tech Spec Tables 3.6.3-1 & 3.8.4.2-1,supporting Mods to Improve Containment Isolation Function & Testability of Feedwater Sys ML17146A4811986-08-0505 August 1986 Proposed Administrative Changes to Tech Specs ML20206J9471986-06-23023 June 1986 Proposed Tech Specs Changing Main Steam Line Radiation High Setpoint from Three Times Background to Seven Times Background ML17146A4161986-06-19019 June 1986 Proposed Tech Specs Re Cycle 2 Reload.Nshc Encl ML17146A3111986-03-27027 March 1986 Proposed Tech Spec Changes Providing Editorial Correction to Previously Approved Change for Unit 1 & Supporting Mods Which Enhance Capability of Drywell Cooling Sys for Unit 2 ML20141C9281986-03-27027 March 1986 Proposed Tech Specs Re Recirculation Sys W/One & Two Loop Operation,Supporting Operation W/One Recirculation Loop Out of Svc ML17146A2681986-02-10010 February 1986 Proposed Tech Specs,Reflecting Incorporation of Fifth Diesel Generator Into Plant Design ML20137G5781985-11-26026 November 1985 Proposed Tech Specs,Deleting Requirement for Operability of Refueling Floor Wall & High Exhaust Ducts & Railroad Access Exhaust Duct Radiation Monitoring Sys for Conditions 1,2 & 3 ML17156A1261985-04-11011 April 1985 Proposed Tech Spec Changes Re Single Loop Operation Requirement ML18040A7701985-02-11011 February 1985 Proposed Tech Specs Re Util Review Committee Membership ML17139C7431984-12-0606 December 1984 Proposed Tech Specs Separating Unit 1 from Unit 2 Battery Loads to Avoid Forced Shutdown of Unit 2 During Unit 1 Refueling Outage ML18040A7421984-09-24024 September 1984 Proposed Tech Specs,Revising Table 3.3.7.1-1, Radiation Monitoring Instrumentation. ML18040A7411984-09-0707 September 1984 Proposed Tech Specs Re Primary Containment Isolation Valves & Containment Sys Limiting Condition for Operation & Bases ML20078M6531983-10-20020 October 1983 Proposed Changes to Tech Spec Table 4.8.1.1.2-2 Re Settings for Emergency Svc Water Pump Timers ML17139B3301983-02-0303 February 1983 Proposed Tech Specs 2.2.1.1,3.2.2,4.2.2 & 3.3.6-2 Re Reactor Protection Sys Instrumentation,Average Power Range Monitor & Control Rod Block Instrumentation Setpoints ML17139B3311983-02-0303 February 1983 Proposed Tech Specs 3.4.3 & 4.4.3 Re RCS Leakage Detection Sys ML18031A4031982-10-19019 October 1982 Proposed Changes to Tech Spec Table 3.8.4.1-1 to Include More Conservative Type 2 Molded Case Circuit Breakers & to Add Previously Omitted Type 3 Molded Case Circuit Breakers 1999-03-12
[Table view] Category:TECHNICAL SPECIFICATIONS & TEST REPORTS
MONTHYEARML18040B2891999-03-12012 March 1999 Proposed Tech Specs Including Rev 0 to EMF-1997(P)(A) Into TS Section 5.6.5 & Including Revised MCPR Safety Limits in TS Section 2.1.1.2 ML18040B2881999-01-12012 January 1999 Proposed Tech Specs Re ANFB-10 Critical Power Correlation & MCPR Safety Limits ML17164A6711998-07-0808 July 1998 Proposed Tech Specs,Implementing Improved Tech Specs of NUREG-1433.Page B3.8-1 of Incoming Submittal Not Included ML17159A3261998-05-12012 May 1998 Proposed Tech Specs Re Removal of Fire Protection Program ML20199C8741997-10-22022 October 1997 Rev 0 to NASI-00-507, Corrective Action Process Effectiveness Assessment ML18026A4711997-02-11011 February 1997 Proposed Tech Specs Requesting Improved TSs LCO 3.10.3 & LCO 3.10.4 Be Approved for Use During Susquehanna Ses Unit 2 Eighth Refueling & Insp Outage Scheduled for 970315 ML17158C0321997-01-0808 January 1997 Rev 4, Solid Radwaste Pcp. ML20129D7851996-09-23023 September 1996 Proposed Tech Specs Re MSIVs Leakage Testing ML20116K3491996-08-0909 August 1996 Proposed Tech Specs Re Battery Load Profiles ML17158B5581996-03-20020 March 1996 Proposed Tech Specs,Changing Open Logic for HPCI Suction Valve HV-155/255-F042 in Order to Eliminate HPCI Pump auto- Transfer on High Suppression Pool Level ML20115A8211996-02-29029 February 1996 Proposed Tech Specs,Removing Rod Block Monitor Requirements from TS by Reducing Number of Rod Movements During Power Maneuvers ML20115A8171996-02-29029 February 1996 Proposed Tech Specs,Relocating Spec 3/4.9.6, Refueling Platform to Document Which Is Controlled Under Requirements of 10CFR50.59 ML17158B1071996-02-12012 February 1996 Proposed Tech Specs to Implement 10CFR50,App J,Option B & Establish New Spec 6.8.5, Primary Containment Leakage Rate Testing Program. ML17158A6821995-04-26026 April 1995 Rev 3 to Nuclear Dept Procedure ON-100-009, Control Room Evacuation. ML17158A6841995-04-13013 April 1995 Rev 3 to Nuclear Dept Procedure ON-200-009, Control Room Evacuation. ML20081L9151995-03-14014 March 1995 Rev 1 to NS-ST-002, Security Training & Crucial Security Task Certification ML17164A5801995-02-10010 February 1995 Proposed Tech Specs for Aot/Sti Extensions ML17164A5891995-01-20020 January 1995 Rev 2 to PP&L SSES Odcm. ML17164A4351994-11-21021 November 1994 Proposed Tech Specs Increasing MSIV Leakage Rate & Deleting MSIV-LCS ML17158A5441994-10-28028 October 1994 Proposed Tech Specs,Incorporating Administrative Changes ML20058F8281993-11-24024 November 1993 Proposed Tech Specs Re Power Uprate W/Increased Flow ML17157C3881993-05-31031 May 1993 Rev 8 to ISI-T-100.0, ISI Program Plan for Pump & Valve Operational Testing. ML17157C3901993-05-31031 May 1993 Rev 5 to ISI-T-200.0, ISI Program Plan for Pump & Valve Operational Testing. ML18017A2671993-04-20020 April 1993 Exercise Manual. ML17157C2741993-04-0202 April 1993 Proposed TS 3.4.1.1.2 Re LCO for Recirculation Loops,Single Loop Operation ML18017A2631992-05-0606 May 1992 Emergency Exercise Std for Conduct in Performance of 920219 NRC Graded Exercise ML20113G9881992-02-19019 February 1992 Package Providing Basis for Conduct of Simulated Radiological Accident at Plant ML17157B0081991-12-31031 December 1991 Rev 7 to ISI-T-100.0, Sses,Unit 1,ISI Program Plan for Pump & Valve Operational Testing, Per Generic Ltr 89-04 ML17157B0101991-12-31031 December 1991 Rev 4 to ISI-T-200.0, Sses,Unit 2,ISI Program Plan for Pump & Valve Operational Testing, Per Generic Ltr 89-04 ML18017A2591991-10-16016 October 1991 Exercise Manual, Approved by Util as Std for Conduct in Performance of 911016 NRC Graded Exercise ML20082P1871991-09-0404 September 1991 Proposed Tech Specs for HPCI Sys Low Pressure Surveillance Test Acceptance Criteria ML17157A3381990-09-30030 September 1990 Cycle 5 Reload Summary Rept. ML17157A3371990-09-24024 September 1990 Proposed Tech Specs in Support of Facility Cycle 5 Reload ML17157A2441990-07-0202 July 1990 Proposed Tech Specs to Support Cycle 6 Reload ML17157A0891990-03-19019 March 1990 Rev 0 to Procedure MT-024-024, Diesel Engine Analysis & Load Balancing. ML17157A0871990-03-19019 March 1990 Rev 0 to Procedure TP-024-087, Data Collection for E Diesel Generator Combustion Intake Air Temp Test. ML20127B4271990-01-19019 January 1990 Rev 8 to Procedure MT-GE-008, 480 Volt & Under Circuit Breaker High Current Testing ML19325D7491989-10-19019 October 1989 Proposed Tech Specs 3.2.2 Eliminating Certain Requirements on One Time Basis for 3 Months ML20082C4101989-08-16016 August 1989 Spec Change Notice 7 to Rev 4 to TS F1000, TS for Design & Installation of Electrical Raceway Fire Barriers ML17156B1101989-04-14014 April 1989 Proposed Tech Specs,Making Changes to Emergency Svc Water Sys,Per 10CFR50,App R ML17156B0671989-03-31031 March 1989 Rev 3 to ISI-T-200.0, Pump & Valve Inservice Insp Testing Program. ML17156B0651989-03-31031 March 1989 Rev 6 to ISI-T-100.0, Pump & Valve Inservice Insp Testing Program. ML20082C4071989-03-23023 March 1989 Spec Change Notice 6 to Rev 4 to F1000, TS for Design & Installation of Electrical Raceway Fire Barriers ML17156B1391989-02-22022 February 1989 Rev 12 to EO-100-009, Plant Shutdown from Outside Control Room. ML20082B2771989-01-0404 January 1989 Rev 4 to TS F1000, TS for Design & Installation of Electrical Raceway Fire Barriers ML20082C3731988-11-0707 November 1988 Spec Change Notice 5 to Rev 3 to TS F1000, TS for Design & Installation of Electrical Raceway Fire Barriers ML20082C3711988-11-0101 November 1988 Spec Change Notice 4 to Rev 3 to TS F1000, TS for Design & Installation of Electrical Raceway Fire Barriers ML20082C3641988-10-14014 October 1988 Spec Change Notice 3 to Rev 3 to TS F1000, TS for Design & Installation of Electrical Raceway Fire Barriers ML17156A7291988-08-10010 August 1988 Proposed Tech Specs,Extending Operation During Cycle 4 W/ One Recirculation Loop Out of Svc ML20082B2911988-07-11011 July 1988 Rev 3 to TS F1000, TS for Design & Installation of Electrical Raceway Fire Barriers 1999-03-12
[Table view] |
Text
CONTAINMENT SYSTEMS ORYWELL AIR FLOW SYSTEM LIMITING CONDITION FOR OPERATION 3.6.6.3 Orywell unit cool'er fans 1V414 A&B, lV416 A&B and recirculation fans 1V418 A&8 shall be OPERABLE at low speed.
APPLICABILITY: OPERATIONAL CONDITIONS 1 and 2.
ACTION:
c one .o ore of t above fans
'in oper able t low speed, estore e inop able f s) to OP BLE status 30 s or be in least T SHUTOO within next 1 urs.
SURVEILLANCE RE UIREMENTS 4.6.6.3 Each of the fans required above shall be demonstrated OFERABi least once per 92. days by:
- a. Starting each fan at low speed from the control room, and
- b. Verifying that each fan operates for at least 15 minutes.
pig one. f0h Ln one. ol fhofc o( QQQ, gQve, popes (ho~efo4(e. ot toW $ (eecf, M5'kfe +4< inoftera4'te, /ah(s) +o 0<g,ARE StataS wiles,c~ 30 dayS Or be 'IW G.t'eaSi- Hog CRQfb~glJ gqgg,~ +LAC, Vle.yf l2 4o~s .
< - .
1'/4 8604020436 860327 PDR ADOCN, 05000387 P RDR SUSQUEHANNA - UNIT 6-38 Amendment N'o. 46
CONTAINMENT SYSTEMS DRYWELL AIR FLOW SYSTEM LIMITING CONDITION FOR OPERATION c
3.6.6.2 Three independent drywell air flow unit cooler subsystems (2V414A,B, 2V415A,B, and 2V416A,B) shall be OPERABLE at low speed with each subsystem con-sisting of two unit cooler fans.
APPLICABILITY: OPERATIONAL CONDITIONS 1 and 2.
"ACTION:
W ne fan of one more unit coo subsystems inop ble at low eed, restore least HOT inoperable WN within t s) to OPERABL atus within 30 s or be i t SH - ext 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
SURVEILLANCE RE UIREMENTS 4.6.6.2 Each drywell air flow unit cobler subsystem required above shall be demonstrated OPERABLE at least once per 92 days by:
- a. Starting each fan at low speed from the control room, arid
- b. Verifying that each fan operates for at least 15 minytes.
I ec O ~ IJiih oee fee ce oee or morc. of ~c eicocc [o,rs of $es j~~qq4te a4 toe s)cQ,. fes4ore 4'4 ~noperah~ fcu (c)+o OPERA&~ <fakers Qi+iA & dR)$ of ke ln ak (east. ROT ',
SHQTbo4M lpA+4in 4'kc g~i'2 404cl s ~
Idion 4th ~ous 'u csee oeir inoceroiNe st (ow
'foIIosS Age rqu rcmcces of S~cc,(;c e,'I o g SUSQUEHANNA - UNIT 2 3/4 6-40
TABLE 3.8.4.1-1 (Continued)
PRIMARY CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES
RESPONSE
TIME TRIP (Milli CIRCUIT BREAKER FRAME . SET POINT seconds/ SYSTEMS OR LOCATION TYPE" RATING/UL ~Ae eres ~Cc1 ee E UIPMENT POWERED T e 2 Molded Case Circuit Breakerst (Continued)
- 29. 28246112 HFB-M 150/3 10 NA HV8212F002 - Reactor Head Vent Val ve
- 30. 28246113 HFB-M 150/3 10 NA .HV8212F005 " Reactor Heat Vent Ve "'.
- 31. 28246062 HFB-M 150/3 15 NA HV21346 - RBCCW Containment Iso. Vlv.
- 32. 28246012 HFB-M 150/3 15 NA HV21345 - RBY'"W Containment I;n.
- 33. 28253063 HFB-M 150/5 20 2P402A - Orywel 1 Floor Drain Su.ttp "A" Pump "A"
- 34. 28253053 HFB-M 150/5 20 NA HVG332F102 - Li;le Suction Inside Contr ol Valve
- 35. 28263043 HFB-M 150/3 10 NA HVG332F100 - RWCU Loop "A" Suction
- 36. 28263053 HFB-M 150/3 10 HVG332F106 - RWCU Loop "8" Suction
- 37. 28263081 HFB-M 150/3 10 NA HVG332F101 " RWCU Sys Vessel Drain Line Recirc.
- 38. 28263071 HFB-M 150/5 20 NA 2P4028 - Drywell Floor Drain Sump ttAtt Pump ttBtt
- 39. 28253043 HFB-M 150/5 20 NA 2P403A - Drywel 1 Floor Drain Sump ttBtt Pump
- 40. 28263072 'HFB-M 150/5 20 2P4038 - Drywell Floor Drain Sump ttBtt Pump ttBtt 41; 28253021 HFB-M 150/50 400 HV8212F011A Feedwater'nlet Shutoff Valve 4 28263023 HFB-M 150/50 400 HV8212F0118 - Feed-
~les~ 4 water Valve Inlet Shutoff "HFB-M - Westinghouse Type HFB, magnetic only SEach location number represents two breakers in series.
SUS(UEHANNA - UNIT 2 3/4 8-28
TABLE 3.8.4.1-1 (Continued)
PRIMARY CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES
RESPONSE
TIME CIRCUIT BREAKER
'TRIP (Milli-
~
FRAME . SET POINT seconds/ SYSTNS OR LOCATION TYPE: RATING/UL ~Am ares ~Cc1 ms T e 2 Molded Case Circuit Breakerst (Continued)
.45 262M125 +~ HFB-we <6 o/zo zv g,l h /~weal I Cg,b gmeo Ce,ol<~
pcln .
44 2.8244 Q.l y+ HFP -TQ f50/Zo 2Q+lSQ, - p<yWell CRT Fan.
4~ cooli~g
>"HFB"TM-Westinghouse Type HFB, vHcRMAi zan,veal c cow~y HEach location number represints two breakers in series.
SUS(UEHANNA - UNIT 2
~ 0 TABLE 3.8.4.1-1 PRIMARY CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Circuit Breaker Deai nation 8 atea ui ment Povered
- 1. 2B237043 Rx Recirc/HV B31 2P023h 2+ 2B219022 Rx Recirc/HV-B31"ZE03lh 3 25219023 Rx Racirc/HV-b31-2P032h 4 25246011 Rx Recirc/HV>>531-2P023b 5~ . 2b229022 Rx Recirc/HV-B31-2P031B 6, 2B229023 Rx Recirc/HV-B31-2P032B 7~ 25236042 Dryvell Air Plov/2V41lh 8~ 2B236032 Dryvell hir Plov/2V41ZA 9o 2b236011 Dryvell Air Plov/2V413h
- 10. 25236033 Dryvell Air Plov/ZV414h
- 11. 25236082 Dryvell Air Plov/ZV415A
- 12. 25236043 Dryvell Air Plov/ZV416A 13'B236021 Dryvell Air Flov/ZV417h
+.1$ . ZB246091 Dryvell Air Plov/2V411B Jrf.+.25246103 Dryvell hir Plov/ZV412B Pf.17.25246102 Dryvell Air Plov/2V413B P.t8. 28246061 Dryve11 Air Plov/2V414B Pf. I). 2B246072 Dryvell Air Plov/2V415B PY.Za25246081 Dryvell Air Plov/2V416B gf.2I. 2B24605 Dryvell Air Plov/2V417B 1'Pf.23.2BZ36052 RHR/HV-Ell-2P009
~8.2B237073 RHR/HV-Ell 2P022 by~el( Ai Floa /ZVei8A g2; 2.S~IZ 1 Mell ~;r Flo~ l 2~~~8j3
Circuit Breaker Desi ation S stem/E ui ment Powered
+.2S. 2B237082 HPCI/HV-E41-2P002 P'.4.2B253021 NSSS/HV-B21-2PO1 lh Pf.27.2B263023 NSSS /HV-B21-2P011B
~4S2B253041 MSIV Hoist/TB0815 Qlf.2B263021 MSIV Hoist/TB0816 B. ~Ta HPB-M+
- 1. 2B236023 Cont. Inst. Gas/HV-22603
- 2. 2B246022 RCIC/HV-E51-2P007
- 3. 2B237072 NSSS/HV-B21-2P016 4~ 2B236102 NSSS/HV-B21-2F001
- 5. 2B246112 NSSS/HV-B21-2F002
- 6. 2B246113 NSSS/HV-B21-2F005
- 7. 2B236053 RWCU/HV-G33-2F001
- 8. 2B253053 RWCU/HV-G33-2F102
- 9. 2B263043 RWCU/HV-G33-2P100
- 10. 2B263053 RWCU/HV-G33-2F106
- 11. 2B263081 RWCU/HV-G33-2F101
- 12. 2B246062 RBCCW/HV-21346
- 13. 2B246012 RBCCW/HV-21345
- 14. 2B253063 Drywell Sump/2P402A
- 15. 2B263071 Drywell Sump/2P402B
- 16. 2B253043 Drywell Sump/2P403A
- 17. 2B263072 Drywell Sump/2P403B
Ia