ML17156B139
ML17156B139 | |
Person / Time | |
---|---|
Site: | Susquehanna |
Issue date: | 02/22/1989 |
From: | PENNSYLVANIA POWER & LIGHT CO. |
To: | |
Shared Package | |
ML17156B140 | List: |
References | |
EO-100-009, EO-100-9, NUDOCS 8905080174 | |
Download: ML17156B139 (72) | |
Text
PROCEDURE COVER SHEET PENNSYLVANIA POWER 8( LIGHT CO.
SUSQUEHANNA STEAM ELECTRIC STATION EO-100" 009 PLANT SHUTDOWN FROM OUTSIDE CONTROL ROOM Revision 12 Page 1 of 43 EFFECTIVE DATE PERIODIC REVIEW FREQUENCY AND EXPIRATION DATE (check one):
( ) Procedure exempt from periodic review;, Procedure will not expire.
{~) Periodic Review Frequency is:
Expiration Date: C So 9O Revised Expiration Dates:
r
. PROCEDURE TYPE {check one): (~) PORC { ) NON-PORC REVIEW TYPE (check one):
( X) Expedited Review. PORC Review not required.
( ) Alternate Review. PORC Review not required.
( ) PORC Review. PORC Meeting No.
Prepared by, Date Z / Io Reviewed by Date Responsible S rvi r Recommended A Date 2- >2- 8 Section ad/Manager Approved by Date 2-'22..
NORM AO-QA-101-1, Rev. 5, Page 1 of 1 85'05080174 890428 PDR ADOCK 05000387 PDC
~a ~
1
$P
EO-100-009 Revision 12 Page 2 of 43 1.0 SYMPTOMS AND OBSERVATIONS I
Conditions exist which require Control Room EVACUATION:
1.1 Dense SMOKE 1.2 Extreme HEAT 1.3 Hazardous GAS which induces difficulty in breathing 1.4 Direction from Shift. Supervision 2.0 AUTOMATIC ACTIONS None 3.0 IMMEDIATE OPERATOR ACTIONS I CONFIRM 3.1 As time permits, PERFORM following prior to Control Room evacuation: .
3.1. 1 ANNOUNCE twice over Plant PA System "Control Room Evacuation in* Progress".
3.1.2 PLACE MODE SWITCH to SHUTDOWN.
3.1.3 ENSURE all Control Rods INSERTED.
I 3.1.5 CLOSE MSIV's and MSL drains HV-141-F016 and HV-141" F019.
3.1.7 PLACE FW LOW LOAD LIC-C32-1R602 in AUTO.
3.1.8 OPEN HPCI TEST LINE ISO VLV HV"155"F011.
3.1.9 TAKE two (2) security access 2A keys from Shift Supervisor key cabinet to gain entrance into Reactor Building . (Unit Supervisor only) 3.2 EVACUATE Main Control Room.
I
'l I
li
EO-100-009 Revision 12 Page 3 of 43 3.3 If Control Room evacuated prior to scramming, PERFORM locally:
(') 3.3. 1 OPEN following breakers to Scram Reactor and isolate Inboard and Outboard MSIV's and Main Steam Line Drains:
- a. 1Y201A (CB2A) on RPS power distribution panel 1Y201A
- b. 1Y2018 (CBSB) on RPS power distribution panel 1Y2018 3.3.2 MANUALLY CLOSE following valves:
- a. RFP A Discharge Iso HV-10603A
- b. RFP B Discharge Iso HV-106038
- c. RFP C Discharge Iso HV-10603C 4.0 SUBSE UENT OPERATOR ACTIONS CAUT'ION IF REACTOR FEED PUMP DISCHARGE VALVES CANNOT BE CLOSED AND REACTOR PRESSURE IS REDUCED BELOW 650 PSIG, CONDENSATE PUMPS MUST BE TRIPPED TO PREVENT OVER FEEDING REACTOR VESSEL.
CAUTION RANSFER OF RHR TO REMOTE SHUTDOWN PANEL DEFEATS AUTOMATIC INITIATION OF BOTH RHR LOOPS IN LPCI MODE.
NOTE LL INDICATIONS AND CONTROLS ARE FROM 1C201A/B UNLESS OTHERWISE INDICATED.
4.1 Upon arrival at Remote Shutdown Panel, immediately PERFORM following to deter mine plant status:
4.F 1 TRANSFER following Instrumentation Transfer Switches from NORM to EMERG positions and OBSERVE green indicating light ILLUMINATED.
.a. INSTR TRANSFER SW A INSTR SET 1,2 HSS-14901A.
- b. INSTR TRANSFER SW B INSTR SET 3,4 HSS-15110A.
1 ~
\I
EO-100"009 Revision 12 Page 4 of 43 4.).2 ENSURE Main Steam Lines ISOLATED by either:
- b. MN STM LINE A,B,C,D OB ISO HV"141-F028A,B,C,D OBSERVED CLOSED in Main Steam Tunnel if indication of Inboard MSIV's not functional.
- 4. 1.3 MONITOR available parameters to determine plant status.
4.2 As necessary to stabilize plant conditions, ENTER following steps CONCURRENTLY:
4.2.1 To establish and/or maintain Reactor level > +18",
PERFORM section 4.6, RCIC operation.
4.2.2 To establish and maintain Reactor pressure < 1000 psig, PERFORM section 4.7, Reactor Pressure Control.
4.2.3 To maintain Suppression Pool Temperature < 90'F; PERFORM section 4.8, Suppression Pool Cooling.
NOTE COMMUNICATIONS BETWEEN REMOTE SHUTDOWN PANEL AND PERSONNEL ON ELEVATION 749'HOULD BE ESTABLISHED WHEN TIME AND PERSONNEL ARE AVAILABLE FOR VERIFICATION OF LEVEL AND'RESSURE INSTRUMENTATION.
4.3 If Control Room evacuation was because of fire, PERFORM following:
4.3.1 When personnel become available, CHECK Battery Room area -and RESTART Battery Room Exhaust Fans as necessary in accordance with MT-TY-OIO, Emergency Start of Fans In The Event of a Control Room Fire.
4.3.2 Within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, NOTIFY Electrical Maintenance to stop
.any equalizing battery charges in progress.
.ensure proper operation of Balance of Plant equipment, 4.4 To PERFORM section 4 '.
EO" 100-009 Revision 12 Page 5 of 43 4.5 If necessary, OBSERYE pater level instrumentation on local instrument racks 1C004 and 1C005 at 27-749'.'
Ij I l
EO-100-009 Revision 12 Page 6 of 43 4.6 OPERATE RCIC for level.and/or pressure control as follows:
NOTE RCIC HIGH LEVEL TRIP AT LEVEL 8 IS BYPASSED WHEN CONTROLLED FROM REMOTE SHUTDOWN PANEL.
NOTE THE FOLLOWING MAJOR INTERLOCKS ARE DEFEATED FOR RCIC WHEN CONTROLLED FROM REMOTE SHUTDOWN PANEL:
- 1) ISOLATIONS FOR HV-149-F007 and HV-149-F008
- 2) ALL TURBINE TRIPS EXCEPT OVERSPEED (110 4 125K) AND MANUAL
- LINE
- 3) EXHAUST VACUUM BREAKER ISOLATIONS
- 4) RCIC AUTO INITIATIONS
- 5) RCIC TURBINE SHUTDOWN ON HIGH LEVEL (LEVEL 8)
- 6) MIN FLOW TO SUPP POOL +V-149-F019 OPERATION ON HI/LOW FLOW
RCIC SYSTEM IS USED TO CONTROL RPV LEVEL AND/OR PRESSURE. IN LEVEL CONTROL, FLOWPATH IS FROM CST TO RPV. PRESSURE CONTROL FLOW PATH IS FROM CST TO CST.
NOTE PLACING CONTROL TRANSFER SWITCH A HSS-14902A TO EMERG POSITION WILL CAUSE RCIC TURB L-0 IN VLV HV"150F046 TO AUTO OPEN. THIS VALVE POSITION MUST BE CHECKED LOCALLY TO ASSURE CORRECT. POSITION SINCE POSITION IS NOT INDICATED ON REMOTE SHUTDOWN PANEL.
EO" 100-009 Revision 12 Page 7 of 43 CAUTION IF RED LIGHT FOR RCIC TOPAZ INVERTER NOT ILLUMINATING, 00 NOT START RCIC TURBINE BECAUSE INVERTER SUPPLIES RCIC SPEED CONTROL. IF STARTED, RCIC TURBINE WILL HAVE NO SPEED CONTROL RESULTING IN OVERSPEED TRIP ON STARTUP.
4.6.1 If RCIC INJECTING into Reactor Vessel, PERFORM following:
- a. PLACE RCIC TURBINE FLOW CONTROLLER FIC-14903 in MANUAL at minimum setting.
- b. PLACE following transfer switches to EMERG position:
(1) CONTROL TRANSFER SWITCH A HSS-14902A (2) CONTROL TRANSFER SWITCH M HSS-14902B (3) CONTROL TRANSFER SWITCH B HSS-14903A (4) CONTROL TRANSFER SWITCH N HSS-14903B
{5) CONTROL TRANSFER SWITCH C HSS-14904A (6) CONTROL TRANSFER SWITCH O'SS-14905A c ~ RESTART RCIC BARD CDSR VACUUM PP 1P219.
CAUTION PERATION OF RCIC AT LOW FLOW {' 300 GPM) IN AUTO COULD CAUSE FLOW OSCILLATIONS.
- d. After nulling, TRANSFER RCIC TURBINE FLOW CONTROLLER FIC-14903 to AUTO and ADJUST for desired flowrate.
- e. CONFIRM RCIC continues to operate by observing flow on FIC-14903 panel 1C201A.
- f. PROCEED to step 4.6.3.
~ ~
EO-100" 009 Revision 12 Page 8 of 43 4.6.2 If RCIC NOT INJECTING into RPV, PERFORM following:
- a. PLACE following transfer switches to EMERG position:
(1) CONTROL TRANSFER SWITCH A HSS-14902A
{2) CONTROL'RANSFER SWITCH M HSS-14902B (3) CONTROL TRANSFER SWITCH B HSS-14903A
{4) CONTROL TRANSFER SWITCH N HSS-14903B (5) CONTROL TRANSFER SWITCH C HSS-14904A (6) CONTROL TRANSFER SWITCH D HSS-14905A OBSERVE indicated position/status. of following RCIC and Reactor Recirculation components:
PLANT NORMAL ATERNATE CFM COMPONENT LOCATION LOCATION POSITION POSITION BY
- 2. TURBINE TRIP AND 1C201A 25-670 OPEN HV-15012
'HROTTLING
- 4. STEAM SUPPLY OB 1C201A 25"670 OPEN ISO HV-149-F008
- 6. PUMP SUCT(FROM 1C201A CLOSED SUPP POOL HV"149-F031 25"670'C201A
- 8. MIN FLOW TO 1C201A 25-670 CLOSED SUPP POOL HV-149-F019
- 13. RCIC BARO CDSR 25" STOPPED VACUUM PP 1P219 670'C201A
- 14. VAC PP DSCH TO 25"670 OPEN SUPP POOL HV-149-F060
~ ~
EO"100-009 12'evision Page 9 of 43 PLANT NORMAL ATERNATE CFM COMPONENT LOCATION LOCATION POSITION POSITION BY
- 17. TURB EÃH IB 1C201A 25-670 OPEN VAC BKR HV"149-F084 IF RCIC HAS TRIPPED, VALVE MUST BE FULLY CLOSED, THEN FULLY OPENED FOR VALVE TO ACTUALLY OPEN. IF MECHANICAL OVERSPEED TRIP HAS OCCURRED, VALVE MUST BE LOCALLY RESET.
CLOSING VALVE WILL TRIP "B" RECIRCULATION PUMP.
"*" PUMP CYCLES TO MAINTAIN BAROMETRIC CONDENSER LEVEL.
- c. PLACE RCIC in oper ation as follows:
(1) SET RCIC TURBINE FLOW CONTROLLER FIC-14903 to minimum value and place in~MANUAL.
(2) START RCIC BARO CDSR VACUUM PP 1P219.
CAUTION MIN FLOW TO SUPP POOL FV-149"F019 WILL NOT AUTO OPEN OR AUTO CLOSE.
(3) Simultaneously OPEN:
(a) STEAM TO RCIC TURBINE HV-150-F045 (b) MIN FLOW TO SUPP POOL FV"149"F019 NOTE RCIC BARO CDSR COND 5'P 1P220 AUTO STARTS ON HIGH TANK LEVEL (4) INCREASE. flow demand using RCIC TURBINE FLOW CONTROLLER FIC-14903 until turbine speed >
2200 rpm.
(5) OPEN RCIC INJECTION VALVE HV"149-F013.
~ >
I 4~'f
EO-100-009 Revision 12 Page 10 of 43 CAUTION MAINTAIN TURBINE SPEED GREATER THAN 2200 RPM TO ASSURE PROPER BEARING LUBRICATION.'AUTION OPERATION OF RCIC AT LOW FLOW (- 300 GPM) IN AUTO COULD CAUSE FLOW OSCILLATIONS.
(6) INCREASE flow using RCIC TURBINE FLOW CONTROLLER FIC-14903 until desired flowrate obtained.
1 (7) NULL RCIC TURBINE FLOW CONTROLLER FIC-14903 and PLACE in AUTO.
(8) CLOSE MIN FLOW TO SUPP POOL~ HV-149-F019 when flow > 250 gpm on FI-14903.
CAUTION IN FLOW TO SUPP POOL FV-149-F019 SHOULD-BE MANUALLY OPENED WHEN FLOW IS LESS THAN 150 GPM TO PROTECT PUMP.
4.6.3 CONTROL Reactor Vessel Level between 20 and 40 inches.
4.6.4 If RCIC fails to start, PROCEED to step 4.10.
START ESW PUMP OP504A8C at Unit 2 panel 2C201B to provide cooling water for RCIC room coolers.
4.6.6 At 2C201B, OBSERVE SPRAY POND LOOP A BYPS HV-01222A indicates OPEN in approximately 120 seconds.
4.6.7 ALIGN Spray Pond Spray Networks in accordance with OP,"116-001.
CAUTION' RCIC ROOM TEMPERATURE SHOULD BE MAINTAINED BELOW 150PF TO PREVENT POSSIBLE DAMAGE TO RCIC CONTROL ELECTRONICS.
V
,e fk
EO-100 "009 Revision 12 Page 11 of 43 4.6.8 As time and personnel become available, PERFORM following locally:
- a. ENSURE RCIC room cooling fan RUNNING.
- b. ENSURE RCIC Lube Oil Cooling Water Valve HV150F046 OPEN.
4.6.9 If RCIC turbine. speed decreases < 2200 rpm and RPV level being maintained and it is desired to continue RPV heat removal using RCIC as heat sink, OPEN MIN FLOW TO SUPP POOL FV-149-F019.
4.6.10 If increased heat removal rate required, PERFORM following:
a ~ RAISE RPV Level with RCIC until approximately 45 inches indicated.
- b. OPEN or CHECK OPEN MIN FLOW TO SUPP POOL HV-149-F019.
C. CLOSE RCIC INJECTION VLV HV"149-F013.
- d. MANUALLY OPEN HPCI Test Line Iso Vlv HV155F011 if not opened prior to Control Room evacuation.
CLOSE MIN FLOW TO SUPP POOL FV-149"F019 when flow
> 250 gpm on FI-14903.
CAUTION MIN FLOW TO SUPP POOL FV-149-F019 SHOULD BE MANUALLY OPENED WHEN FLOW IS LESS THAN 150 GPM TO PROTECT PUMP.
0 REPEAT preceding steps as required to increase heat removal rate.
When reject to CST no longer needed, CLOSE TEST LINE ISO TO CST HV-149-F022 MANUALLY CLOSE HPCI Test Line Iso Vlv HV155F011.
EO-100-009 Revision 12 Page 12 of 43 Periodically MONITOR CST level locally to assure adequate supply.
If CST level drops below approximately 85, corresponding .to approximately 4 feet, TRANSFER RCIC suction to Suppression Pool as follows:
- a. OPEN PUMP SUCT FROM SUPP POOL HV-149-F031.
I
- b. When PUMP SUCT FROM SUPP POOL HV-149-F031 reaches fully OPEN position, CLOSE PUMP SUCT VLV FROM CST HV-149-F010.
Periodically MONITOR Suppression Pool on LI-15776B2 to assure level maintained between 22 and 24 feet.
~ ~
4g I a
Pt XY
~. ~
EO-100-009 Revision 12 Page 13 of 43 4.7 Reactor Pressure Control NOTE REACTOR PRESSURE SHOULD BE MAINTAINED BELOW 1000 PSIG BY CYCLING SAFETY RELIEF VALVES PSV-141-F013A,B, AND C IN SEQUENTIAL ORDER TO PREVENT EXCEEDING LOCAL HEAT LOADING OF THE SUPPRESSION POOL.
CAUTION THE FOLLOWING STEPS WILL REMOVE AUTO INITIATION CAPABILITIES FOR BOTH RHR LOOPS.
TO RE-ESTABLISH AUTO INITIATION OF LPCI, PLACE CONTROL TRANSFER SWITCHES TO NORM.
CAUTION WITH TRANSFER SWITCHES IN EMERG POSITION, THE fOLLOWING..CONDITIONS EXIST:
NSSSS ISOLATION SIGNALS TO RHR VALVES 1F008, IF009, IF01~5B, 1F040, 1F049, 1F022, 5 1F023 ARE DEFEATED; HIGH REACTOR PRESSURE VESSEL PRESSURE SIGNALS TO RHR VALVES 1F008 and 1F009 ARE OPERABLE.
NOTE RELIEF MODE OF SRV's A, B, AND C DOES NOT AUTO INITIATE WHEN APPLICABLE ONTROL TRANSFER SWITCHES ARE IN EMERG POSITION.
NOTE URING PERIODS OF LOW DECAY HEAT, RCIC SYSTEM CAN BE USED FOR PRESSURE ONTROL.
EO-100-009 Revision 12 Page 14 of 43 4.7.1 TRANSFER following Control Transfer Switches from NORM to EMERG position:
NOTE THE BELOW LISTED TRANSFER SWITCHES WILL AUTO INTERLOCK CLOSED FOLLOWING VALVES WHEN THE TRANSFER SWITCHES ARE PLACED IN EMERG:
- 1) HSS-15111A: HV-151-F048A, HV-151-F017A
- 2) HSS" 15111B: HV-151" F016A
- 3) HSS" 15112A: HV-151-F003A
- 4) HSS-15112B: HV-151-F006A&C, HV"151-F028A
- 6) HSS-15113B: HV"151-F016B, HV-151-F006D THIS ENSURES ALL RHR LOOP B FLOW IS CONTROLLED FROM REMOTE SHUTDOWN PANEL AND ENABLES HEAD SPRAY OPERATION IF NEEDED.
- a. CONTROL TRANSFER SWITCH- E HSS-15111A b., CONTROL TRANSFER SWITCH R HSS-15111B C. .CONTROL TRANSFER SWITCH F HSS" 15112A
- d. CONTROL TRANSFER SWITCH S HSS-15112B
- e. CONTROL TRANSFER SWITCH G HSS-15113A
- f. CONTROL TRANSFER SWITCH T HSS-15113B CONTROL TRANSFER SWITCH H HSS-15114A h
- j. CONTROL TRANSFER SWITCH V HSS-15115B
- k. CONTROL TRANSFER SWITCH K HSS-15116A
- 1. CONTROL'RANSFER SWITCH W HSS-15116B
I ~
1 g
~ ~
EO-100" 009 Revision 12 Page 15 of 43
- m. CONTROL TRANSFER SWITCH L HSS-15117A
- n. CONTROL TRANSFER SWITCH X HSS-15117B 4.7.2 OBSERVE indicated position/status of components per step 4.8.2.
4.7.3 If Containment Instrument Gas Tripped or Isolated, PERFORM following:
NOTE CONTAINMENT INSTRUMENT GAS LEVEL 1 LOCA ISOLATION SIGNAL IS DEFEATED FOR BELOW VALVES WHEN CONTROLLED FROM THE REMOTE SHUTDOWN PANEL.
- a. OPEN following valves from Remote Shutdown Panel:
1 (1) INSTR GAS TO CONTN ISO SV"'12651 (2) INSTR GAS CMP IB SUCT ISO HV"12603 (3) INSTR GAS CMP OB SUCT ISO HV-12605 NOTE THE FOLLOWING STEPS ARE PERFORMED AT LOCAL PANEL 1C239 ~
,h
- b. PLACE Mode Selector Switch for Instrument Gas Compressor 1K205A to OFF/RESET.
- c. PLACE Mode Selector Switch for Instrument Gas Compressor 1K205A to AUTO.
- d. PLACE Mode Selector Switch for Instrument Gas Compressor 1K205B to OFF/RESET.
- e. PLACE Mode Selector .Switch for Instrument Gas Compressor 1K205B to AUTO.
EO-100-009 Revision 12 Page 16 of 43 CAUTION DO NOT EXCEED 100 F/HOUR RPV COOLDOWN RATE. REFER TO ATTACHMENT A FOR RPV PRESSURE TEMPERATURE CORRELATION AND ATTACHMENT B FOR PLOTTING TEMPERATURE DECREASE.
CAUTION IF RPV PRESSURE DROPS BELOW 600 PSIG, CONDENSATE PUMPS WILL INJECT WITH RPV LEVEL 18 INCHES IF FW LOW LOAD LIC-C32"1R602 IN AUTO SET FOR 18 INCHES.
4.7.4 If Reactor Pressure fluctuating due to SRV's cycling, REDUCE RPV pressure between 700 and 920 PSIG by opening SRV's fn alphabetical order on Remote Shutdown Panel as needed.
4.7..5 If continuous pneumatic supply NOT AVAILABLE, OPERATE SRV's G, J, K, L, M, or N (ADS valves) individuaTly from upper (lower) relay room Panel 1C631 (1C628) using keylock switches.
4.7.6 If SRV's NOT AVAILABLE, OPERATE RCIC System per section 4.6 to control pressure.
~ ~ I ti
'I
EO-100-009 Revision 12 Page 17 of 43 4.8 Suppression Pool Cooling NOTE SUPPRESSION POOL TEMPERATURE SHOULD BE MAINTAINED BELOW 90 F USING RHR SUPPRESSION POOL COOLING.
CAUTION FOLLOWING STEPS WILL REMOVE AUTO INITIATION CAPABILITIES FOR BOTH RHR LOOPS. TO RE-ESTABLISH AUTO INITIATION OF LPCI, PLACE CONTROL TRANSFER SWITCHES TO NORM POSITION.
CAUTION WITH TRANSFER SWITCHES IN EMERG POSITION, THE FOLLOWING'CONDITIONS EXIST: NSSSS SIGNALS TO'HR VALVES 1F008, 1F009, 1F015B,. 1F040, 1F049, 1F022 Bc 1F023 'SOLATION ARE DEFEATED; HIGH REACTOR PRESSURE VESSEL PRESSURE SIGNALS TO RHR VALVES 1F008 and 1F009 ARE OPERABLE..
4.8.1 TRANSFER following Control Transfer Switches from NORM to EMERG:
NOTE BELOW LISTED TRANSFER SWITCHES WILL AUTO AND INTERLOCK CLOSED FOLLOWING VALVES WHEN TRANSFER SWITCHES ARE PLACED IN EMERG:
- 2) HSS-15111B: HV"151" F016A
- 3) HSS-15112A: HV-151-F003A
- 4) HSS" 15112B: HV-151" F006AELC, HV-151" F028A
- 6) HSS-15113B'. HV-151" F016B, HV-151-F006D .
THIS ENSURES ALL RHR LOOP B FLOW IS CONTROLLED FROM REMOTE SHUTDOWN PANEL AND ENABLES HEAD SPRAY OPERATION IF NEEDED.
I 4 l
~ ~
Sp EO-100-009 Revision 12 Page 18 of 43
- a. CONTROL TRANSFER SWITCH E HSS-15111A
- b. CONTROL TRANSFER SMITCH R HSS-15111B
- c. CONTROL TRANSFER SWITCH F HSS-15112A
- d. CONTROL TRANSFER SWITCH S HSS-15112B
- e. CONTROL TRANSFER SWITCH G HSS-15113A
- f. CONTROL TRANSFER SWITCH T HSS-15113B
- g. CONTROL TRANSFER SWITCH H HSS-15114A
- h. CONTROL TRANSFER SMITCH U HSS-15114B
- i. CONTROL TRANSFER SWITCH J HSS"15115A CONTROL TRANSFER SWITCH V HSS-15115B k: CONTROL TRANSFER SMITCH K HSS"15116A
- 1. CONTROL TRANSFER SWITCH W HSS-15116B
- m. CONTROL TRANSFER SWITCH L HSS-15117A
- n. CONTROL TRANSFER SWITCH X HSS-'15117B
~ ~
EO-100-009 Revision 12 Page 19 of 43 4.8.2 OBSERVE indicated position/status of following:
PLANT NORMAL ALTERNATE CFM 1.
COMPONENT HEAD SPRAY LOCATION 1C 2018 '5" LOCATION 670 POSITION OPEN POSITION BY SHUTOFF HV-15112
- 5. SHUTDOWN CLG 1C2018 25-670 CLOSED SUCT HV-151-F0068
- 6. RHR PUMP 8 1C 2018 25" 670 OPEN SUCT HV-151-F0048
- 8. RHR PUMP 8/D MIN 1C 2018 25-670 OPEN FLOW HV-151" F0078 HX 8 SHELL SIDE 1C 2018 25" 670 OPEN BYPS HV-151-F0488 RHR INJ OB 1C2018 25-670 CLOSED ISO HV"151-F0158
- 20. RHR INJ FLOW 1C201B 25"670 OPEN CTL HV"151-F0178 Valves HV-1F010A88 breakers are normally racked o ut with valves in closed p'osition during reactor operation above 212'F and should only be racked in for flushing to LRW or head spray operation.
~ ~
J N
tl
~ ~
EO-100-009 Revision 12 Page 20 of 43 PLANT NORMAL ALTERNATE CFM COMPONENT LOCATION LOCATION POSITION POSITION BY
- 21. TEST LINE CTL 1CZ018 25"670 CLOSED HV-151-F0248
- 22. SUPP CHMBR SPRY TEST 1C2018 25."670 CLOSED SHUTOFF HV-151-F0288
- 25. SPRAY POND LOOP.B 1C2018 25-670 CLOSED BPYS HV-012228
- 27. ESW PUMP 1C 2018 25" 670 STOPPED OP504D
- 29. INSTR GAS CMP 1C2018 25-670 OPEN OB SUCT ISO SV-12605 HX 8 VENT 1C2018 C.LOS ED HV-151" F1038 25-670'C2018 HX 8 VENT 25"670 CLOSED HV"151" F1048
- 32. SPRAY POND NETWORK 1C 2018 25-670 CLOSED 81 HV-0122481
- 33. SPRAY POND NETWORK 1C2018 25 "670 CLOSED 82 HV-0122482
~ ~
I
~ ~
s EO-100-009 Revision 12 Page 21 of 43 4.8.3 If RHR System Loop 8 and RHR Service Water System Loop 8 AVAILABLE, PLACE Suppression Pool Cooling in service as follows:
- b. PLACE RHR Service Water System Loop 8 in service as follows:
(1) OPEN RHRSW HX 8 OUTLET HV-112158.
(2) CRACK OPEN RHRSW HX 8 INLET HV-112108.
(3) START RHRSW PUMP 1P5068.
(4) OBSERVE SPRAY PONQ LOOP 8 BYPS HV-012228 OPENS approximately 120 seconds after ESW started.
(5) OPEN RHRSW HX 8 INLET HV-112108 until flow on FI-112078 reaches 9000 gpm.
(6) ALIGN Spray Pond Spray Netw'orks in accordance wi th OP-.116-001
- c. CHECK RHR System Loop 8 FILLED and VENTED in accordance with OP-149-001.
- d. START RHR PUMP 1P2028.
- e. OPEN SUPP CHMBR SPRY TEST SHUTOFF HV-151-F0288.
- f. THROTTLE TEST LINE CTL HV"151-F0248 until flow on RHR SYSTEM FLOW indicator FI-15105 < 10,000 gpm.
CAUTION RHR PP 8/D MIN FLOW HV"1F0078 WILL NOT AUTO OPEN OR CLOSE. THIS VALVE WILL BE LEFT OPEN TO PROVIDE PUMP PROTECTION.
I'.
READJUST flow.to < 10,000 gpm usi'ng TEST LINE 'CTL HV-151- F0248.
1 ~ MONITOR suppression pool water temperature on SUPPRESSION POOL WATER TEMP indicator TI-15752 (TI-15751) at Panel 1C2018(A).
When time and personnel permit, ENSURE RHR Room Cooler 18 STARTED.
~ ~
'I EO-100-009 Revi'sion 12 Page 22 of 43 4.8.4 If RHR System Loop B or RHR Service Water System Loop B NOT AVAILABLE, PLACE Suppression Pool Cooling in service using RHR Loop A and RHR Service Water Loop 'A as follows:
NOTE RHR SYSTEM LOOP A AND RHR SERVICE WATER SYSTEM LOOP A CANNOT BE CONTROLLED FROM REMOTE SHUTDOWN PANEL. ALL ACTIONS ARE PERFORMED LOCALLY OR AS INDICATED. THIS IS NOT A NORMAL ROUTINE EVOLUTION AND WOULD ONLY BE PERFORMED IF THE LOOPS CONTROLLED FROM REMOTE SHUTDOWN PANEL WERE NOT AVAILABLE.
- a. If not in service, PLACE ESW System Loop A in service by starting ESW Pump OP504A&C at Unit 2 Panel 2C201B.
- b. PLACE RHR .Service Water System Loop A in service as follows:
(1) OPEN RHRSW Hx A Outlet HV-11215A locally..
(2) CRACK OPEN RHRSW Hx A Inlet HV-11210A locally.
(3) At lA20308, elevation 749', PLACE RHR Service Water Pump 1P506A lateral contrr1 switch to HANDLE OUT position.
(4) START RHR Service Water Pump 1P506A placing lateral control switch to CLOSE.
(5) Locally OPEN RHRSW Hx A Inlet HV-11210A to approximately 80% open which corresponds to approximately 9000 gpm flow.
(6) OBSERVE SPRAY POND LOOP A BYPS HV"01222A indicates OPEN on Unit 2 Panel 2C201B.
(7) ALIGN Spray Pond Spray Newton ks in accordance with OP-116-001.
PLACE RHR System in service. using.RHR Pump 1A(1C) as follows:
(1) OPEN breakers for following valves:
(a) HV151F003A )B216053 (b) HV151F024A 1B237024 (c) HV151F028A - 1B216044
~ /
I 0
EO-100 "009 Revision 12 Page 23 of 43 (d) HV151F007A " 1B219031 (e) 'HY151F047A - 1B216052 (f) HV151F048A - 18237034 (g) HV151F004A 18216032 (h) HV151F004C - 1B237033 (i) HV151F027A - 1B236022
( j) HV151F017A - 1B216082 (IG) HV151F016A - 1B217032 (2) ENSURE following valves OPEN:
(a) RHR Pump Suet Frm Supp Pool HV155F004A OR
'RHR Pump Suet Frm Supp Pool HV155F004C (b) RHR Min Flow To Supp Pool HV155F007A (c) RHR Pump Dsch To RHR Heat Exch HV155F047A (3) ENSURE following valves CLOSED:
(a) Supp Chmbr Spray Vlv HV151F027A (b) RHR Heat Exch Bypass HV151F048A (c) RHR Dsch To Supp Pool Inbd HV151F024A (d) RHR Dsch To Supp Pool Outbd MV151F028A (e) RHR LPCI Outbd Valve HV151F017A (f) Drwl Spry Ob HV151F016A
y r
~ ~
( EO-100-009 Revision Page 24 of 12 43 (4) MANUALLY OPEN fol lowing valves:
(a) RHR Heat Exch Outlet HV151F003A (b) RHR Dsch To Supp Pool Outbd HV151F028A NOTE PL'ACING LATERAL CONTROL SWITCHES TO HANDLE OUT POSITION DEFEATS AUTO FEATURES OF THE PUMPS.
(5) If RHR 'Pump 1A to be placed in service, PERFORM following at lA20102 elevation 749':
(a) PLACE RHR Pump 1P202A lateral control switch to HANDLE OUT position.
(b) START RHR Pump 1P202A placing lateral control switch to CLOSE.
(6) If RHR Pump 1C to be placed in service, PERFORM following at 1A20302 elevation 719':
(a) PLACE RHR Pump 1P202C lateral control switch to HANDLE OUT position.
(b) START RHR Pump 1P202C placing lateral control switch to CLOSE.
NOTE THE FOLLOWING STEP TAKES TWO OPERATORS IN CONTACT WITH EACH OTHER BY RADIO, ONE AT VALVE AND ONE AT FLOW INDICATOR.
(7) MANUALLY OPEN RHR Discharge To Supp Pool Inbd HV151F024A to obtain flowrate of 10,000 gpm, as indicated on FI-'15105B located at 29-683'E corner RBCCW Heat Exchangers.
(8) MONITOR Suppression Pool water temperature. on SUPPRESSION POOL WATER TEMP indicator TI-15751 (TI-15752) panel 1C201A(B).
(9) ENSURE RHR Room Cooler A(C) STARTED.
~ ~
I
~ ~
P EO" 100 "009 Revision 12 Page 25 of 43 4.9 ENSURE proper operation of Balance of Plant equipment, performing following:
4.9. 1 Dispatch Operators to locally ASSURE following:
- a. Main Turbine TRIPPED.
- b. Generator TRIPPED by observing output breaker OPEN.
- c. At 13.8 KV Switchgear, ASSURE auxiliary buses to Startup Bus 10 indicated by Breakers 'ransferred 1A10101 & lA10201 OPEN and breakers 1A10104 & 1A10204 CLOSED.
- d. Main Suction Pump and Turning Gear Oil Pump AUTO START.
- e. Lift pumps AUTO START.
- f. Turning Gear ENGAGES Main Turbine.
- g. ENSURE Reactor Feed Pump Turbines TRIPPED or TRIP Tocally.
- h. ENSURE Reactor Recirculation Pumps 1P401A & 1P401B remain at minimum speed by performing following for each pump:
NOTE REACTOR RECIRCULATION PUMPS 1A&1B SHOULD BE AT LIMITER NO ~ 1 (30%) DUE TO LOW FEEDWATER FLOW AT THIS POINT.
(1) OPEN top cover on Scoop Tube Positi oner...
(2) PLACE Control Power switch to OFF.
(3) PLACE handcrank on small wheel.
(4) ROTATE handcrank in clockwise direction until low speed mechanical stop position reached.
(5) RESTORE handcrank and CLOSE cover.
e
EO".100"009 Revision 12 Page 26 of 43 TRANSFER steam supply for Steam Jet Air Ejectors to Auxiliary Steam locally if required to maintain Main Condenser Vacuum as follows:
- a. MANUALLY'LOSE following valves (05-699'):
(1) Mn Stm Supply HV-10701A (2) Mn Stm Supply HV-10701B
- b. MANUALLY OPEN Aux Stm Supply HV-10752 (05-699').
p/
~
e 4.10 Operation of pumps, from 4.16KV Switchgear Rooms EO" 100-009 Revision 12 Page 27 of 43 to maintain Reactor Vessel level.
4.10.1 OPERATE fol,lowing pumps, as required, to provide makeup to Reactor Vessel by performing actions in step 4.10.2.
- a. CRD Pump 1P132A " 1A20107
- b. CRD Pump 1P132B " 1A20407 P
- c. Core Spray Pump 1P206A - 1A20105
- d. Core Spray Pump 1P206B - 1A20205
- e. Core Spray Pump 1P206C - 1A20305
- f. Core Spray Pump 1P206D 1A20405
- g. RHR Pump 1P202A - 1A20102
- h. RHR Pump 1P202C - 1A20302
- i. RHR Pump 1P202D - 1A20402
- 4. 10 ' 'ERFORM following steps to provide makeup .to Reactor Vessel.
- a. MANUALLY ALIGN system for injection to Reactor Vessel, as required, in accordance with following applicable Operating Procedure.
(1) OP-155-001, Control Rod Drive Hydraulic System (2) OP-151-001, Core Spray System (3) OP-149-001 RHR System NOTE PLACING LATERAL CONTROL SWITCHES TO HANDLE OUT POSITION. DEFEATS AUTO FEATURES OF THE PUMPS
- b. At 4. 16KV Switchgear, PLACE lateral control switch for pump to be started to HANDLE OUT position.
- c. START pump by placing lateral control switch to CLOSE.
~ ~
4 P EO-100-009 Revision 12 Page 28 of 43
- 4. 11 Cooldown CAUTION CONDENSATE PUMPS WILL INJECT WHEN RPV PRESSURE DROPS BELOW 600 PSIG WITH RPV LEVEL
<18 INCHES IF FW LOW LOAD LIC-C32-1R602 IN AUTO SET FOR 18 INCHES.
CAUTION DO NOT DEPRESSURIZE THE RPV BELOW 60 PSIG UNLESS MOTOR DRIVEN PUMPS SUFFICIENT TO MAINTAIN RPV WATER LEVEL ARE RUNNING AND AVAILABLE FOR INJECTION.
- 4. 11. 1 DEPRESSURIZE RPV at < 100'F/HR cooldown rate using SAFETY RELIEF VALVES PSV-141-F013A,B and C in sequential order to prevent exceeding local heat loading of suppression pool AND/OR using RCIC per section 4.6. Refer to ATTACHMENT A for RPV pressure/temperature correlation and plot decrease on ATTACHMENT B.
, RELIEF MODE OF SRV's A, NOTE B AND C DOES NOT AUTO INITIATE WHEN CONTROL TRANSFER SWITCHES ARE IN EMERG POSITION.
APPLICABLE.
NOTE IF CONTINUOUS PNEUMATIC SUPPLY IS OR BECOMES UNAVAILABLE, SRV's G, J, K, L, M or N (ADS VALVES) CAN BE OPERATED FROM UPPER (PANEL 1C631) OR LOWER RELY ROOM (PANEL 1C628) USING KEYLOCK SWITCHES.
NOTE MANUAL CONTROL OF THE STARTUP LEVEL CONTROL VALVE SHOULD BE TAKEN IF FW LO LOAD DEMAND SIG IND NOT IN AUTO AND CONDENSATE PUMPS ARE RUNNING TO ALLOW MAKEUP FROM THE CONDENSATE SYSTEMS
EO-100-009 Revision 12 Page 29 of 43 If adequate makeup capacity available from motor driven pumps, TRIP RCIC pump as follows:
- a. OPEN MIN FLOW TO SUPP POOL FV-'149-F019.
- b. REDUCE RCIC TURBINE FLOW CONTROLLER FIC-14903 to minimum speed of approximately 2200 rpm.
- e. PUSH RCIC TURB TRIP HS-15012B2.
CLOSE STEAM TO RCIC TURBINE HV-150"F045.
- g. CLOSE MIN FLOW TO SUPP POOL FV-149-F019 when pump STOPS.
- h. CLOSE TURBINE TRIP ANO THROTTLING HV-149-F012.
OPEN 1D254081. RCIC Bar Cond Clg Wtr Sgp 150F046 to allow manual closing.
J ~ MANUALLY CLOSE RCIC Bar Cond Cl g Wtr Sup HV150F046 (at pump turbine).
- k. RUN RCIC BARD CDSR VACUUM PP 1P219 for approximately 15 minutes.
If RHR System Loop B and RHR Service Water System Loop B AVAILABLE, PLACE RHR System Loop B in Shutdown Cooling Mode with reactor pressure < 98 psig as follows:
- a. ENSURE Transfer Switches for RHR aligned in accordance
- b. 'fwith 4.8. 1 and 4.8.2.
in Suppression Pool Cooling Mode, PERFORM following:
(1) CLOSE TEST LINE CTL VLV HV.-151-F024B.
(2) STOP RHR PUMP 1P202B.
C. ESTABLISH following alignment:
(1) CLOSE RHR PUMP B/D MIN FLOW HV-151-F007B.
(2) OPEN 18229031 PP BD Min FLow Mov HV151F007B.
EO" 100" 009 Revision 12 Page 30 of 43 (3) CLOSE or CHECK CLOSED SUPP CHMBR SPRY TEST SHUTOFF HV-151-F028B.
(4) CLOSE RHR PUMP 8 SUCT HV-.151-F004B.
(5) CLOSE or CHECK CLOSED TEST LINE CTL HV-151-F024B.
(6) OPEN SHUTDOWN CLG SUCT VLV HV-151-F006B.
FILL RHR Shutdown Cooling piping as follows room): (683'enetration (1) UNLOCK and OPEN Shutdown Cooling Flush Vlv 151F084.
(2) OPEN S/D Cooling Ln Ib Vent Vlv 151F066.
(3) OPEN SHUTDOWN CLG SUCT OB ISO HV-151-F008 from Panel 1C201.
(4) OPEN Pp Suet From RX Flush Vlv 151F083.
(5) OPEN S/D Cooling Ln Ob Vent Vlv 151090.
(6) OBSERVE water flowing from S/D Cooling Ln Ob Vent Vlv 151090 with no air present.
(7) CLOSE S/D Cooling Ln Ob Vent Vlv 151090.
(8) CLOSE S/D Cooling Ln Ib Vent Vlv 151F066.
(9) CLOSE Pp Suet From Rx Flush Vlv 151F083.
(10) LOCK CLOSED Shutdown Cooling Flush Vlv 151F084.
COMPLETE following alignment:
(1) OPEN SHUTDOWN CLG SUCT IB ISO HV"151-F009.
(2) CLOSE RHR INJ FLOW CTL HV"151-F017B.
(3) OPEN RHR INJ OB ISO VLV HV-151-F015B ~
(4) FULLY OPEN HX B SHELL SIDE BYPS HV-151-F048B.
{5) CHECK OPEN HX B SHELL SIDE OUTLET HV-151"F003B.
{6) CHECK OPEN HX B SHELL SIDE INLET HV-151"F0478.
~ ~
I 0
EO-100-009 Revision 12 Page 31 of 43
- f. FLUSH RHR piping to Radwaste as follows:
T NOTE PERFORMANCE OF FLUSH IS AT DISCRETION OF SHIFT SUPERVISION.
(1) CHECK Radwaste ready to accept RHR waste water.
(2) CLOSE 18226064 for LOOP 8 CROSS TIE VLV HV-151-F0108.
(3) OPEN Liquid RW Iso Vlv 151088.
(4) CHECK CLOSED RADWASTE IB ISO VLV HV-151-F040.
(5) OPEN RADWASTE OB ISO VLV HV-151-F049.
(6) OPEN RHR LOOP 8 CROSS TIE VLV HV-151"F0108, (7) COMMENCE flush throttling open RADWASTE IB
'SO HV-I51-F040 while monitoring RPV level.
I NOTE IF CI"E11"1R006 UNAVAILABLE, USE CISH"E11"1R0018 ON INSTRUMENT RACK 1C021.
(8) CONTINUE flush until conductivity indicated on local Conductivity Indicator CI-Ell-1R006 on Instrument Rack 1C021 indicates < 2 umhos/cm'r on direction of Shift Supervision.
If not in service, PLACE ESW LOOP 8 in service starting ESW PUMP OP5048&D.
- h. If not in service, PLACE RHR Service Water Loop 8 in service as follows:
(1) OPEN RHRSW HX 8 OUTLET HV"112158.
(2) CRACK OPEN RHRSW HX 8 INLET HV-112108.
(3) START RHRSW PUMP 1P5068.
(4) OBSERVE SPRAY POND LOOP 8 BYPS HV-012228 OPENS approximately 120 seconds after ESW started.
EO-100-009 Revision 12 Page 32 of 43 (5) OPEN RHRSW HX 8 INLET HV-112108 until flow on RHR SERV WATER SYSTEM FLOW indicator FI-112078 reaches 9000 gpm.
(6) ALIGN Spray Pond Spray Networks in accordance with OP-116-001.
When RHR flush complete, PERFORM following:
(1) CLOSE RADWASTE IB ISO VLV HV-151-F040.
(2) CLOSE RADWASTE OB ISO VLV HV-151-F049.
(3) CLOSE RKR LOOP 8 CROSS TIE VLV HV-151-F0108.
(4) OPEN 18226064 Loop 8 Crosstie Vlv HV151F0108.
(5) CLOSE Liquid RW Iso Vlv 151088.
NOTE PERFORMING THE NEXT STEP WILL TRIP REACTOR RECIRC PUMP 18.
CLOSE RECIRC PUMP 8 SUCT VLV HV"143-F0238.
NOTE RHR SYSTEM IS NOW READY TO BE PLACED IN SHUTDOWN COOLING MODE.
REACTOR WATER LEVEL IS BEING MAINTAINED BY EITHER RCIC AND/ OR CONDENSATE OR CRD.
I
- k. PLACE RHR System Loop 8 in operation as follows:
CAUTION DO NOT EXCEED A FLOWRATE OF 10,000 GPM THROUGH THE HEAT EXCHANGER.
NOTE IF RHR PUMP 8 CANNOT BE STARTED, RHR PUMP D CAN BE STARTED FROM 1A20402D ELEVATION 749'Y PLACING LATERAL CONTROL SWITCH TO HANDLE OUT POSITION ND THEN TO CLOSE POSITION.
(1) START RHR PUMP 1P2028 AND
~ ~
'I 1t
')
~ ~
I 0
~
EO-100-009 Revision Page 33 12 of 43 (2) IMMEDIATELY OPEN RHR INJ FLOW CTL HV-151-F017B to achieve flowrate > 4,000 gpm on RHR SYSTEM FLOW indicator FI-15105 at Panel 1C201B.
(') . TRIP Reactor Rectrc Pump IA M.G. Set by pushing up on plunger marked "LIFT PLUNGER TO OPEN" at lA10110.
r
- n. PLOT RPV Cooldown Rate on Attachment B using Attachment A for pres'sure temperature relationship with RPV at pressure.
4.11.5 If RHR System Loop B or RHR Service Mater System Loop B NOT AVAILABLE, PLACE RHR System Loop A in Shutdown Cooling Mode of operation with reactor pressure ( 98 psig as follows:
NOTE
'HR SYSTEM LOOP A AND RHR SERVICE WATER SYSTEM LOOP A CANNOT BE CONTROLLED FROM REMOTE SHUTDOWN PANEL. ALL ACTIONS ARE PERFORMED LOCALLY OR AS INDICATED. THIS IS NOT A NORMAL ROUTINE EVOLUTION AND WOULD ONLY BE PERFORMED IF THE LOOPS CONTROLLED FROM REMOTE SHUTDOWN PANEL WERE NOT AVAILABLE.
- a. ENSURE Transfer Switches for RHR aligned in accordance with 4.8.1 and 4.8.2.
- b. If in Suppression Pool Cooling Mode with A Loop of RHR, PERFORM following:
(1) MANUALLY CLOSE RHR Discharge To Supp Pool Inbd HV-1F024A AND (2) At 1A20102, PLACE RHR Pump 1P202A lateral control switch to TRIP, OR (3) At lA20302, PLACE RHR Pump 1P202C lateral control switch to TRIP.
OPEN breakers for following valves:
(1) HV151F003A 1B216053 (2) HV151F028A 18216044 (3) HV151F007A " 1B219031
EO-100" 009 Revision 12 Page 34 of 43 (4) HV151F047A - 1B216052 (5) HV151F048A " 1B237034 (6) HV151F004A - 1B216032 (7) HV151F004C - 1B237033 (8) HV151F017A - 1B216082 (9) HV151F015A " 1B219011 (10) HV151F006A - 1B216033 (11) HV151F006C " 1B237032
{12) HV151F016A - 1B217032
- d. CHECK CLOSED or MANUALLY CLOSE following valves:
(1) RHR Pump Suction From Supp Pool HV151F004A (2) RHR Pump Suction From Supp Pool HV151F004C (3) RHR Min Flow To Supp Pool HV151F007A (4) RHR Dsch To Supp Pool Outbd HV151F028A (5) RHR LPCI Outbd Valve HV151F017A (6) Drw Spray Ob Vlv A HV151F016A.
- e. CHECK OPEN or MANUALLY OPEN following valves:
(1) RHR Pump Dsch To RHR Heat Exch HV151F047A (2) RHR LPCI Inbd Valve HV151F015A (3) RHR Heat Exch Outlet Valve
~ ~
HV151F003A (4) RHR Heat Exch Bypass Valve HV151F048A (5) RHR Pump'Suction From RPV HV151F006A OR
{6) RHR Pump Suction From RPV HV151F006C
EO-100-009 Revision 12 Page 35 of 43
- f. FILL RHR Shutdown Cooling piping as follows:
(1) OPEN SHUTDOWN CLG SUCT OB ISO HV-151-F008 from panel 1C201B.
(2) UNLOCK and OPEN Shutdown Cooling Flush Vlv 151F084.
(3) OPEN S/D Cooling Ln Ib Vent Vlv 151F066.
(4) OPEN PP Suet From R){ Flush Vlv 151F083.
(5) OPEN S/D Cooling Ln Ob Vent Vlv 151090.
(6) OBSERVE water flowing from S/D Cooling Ln Ob Vent Vlv 151090 with no air present.
(7) CLOSE S/D Cooling Ln Ob Vent Vlv 151090.
(8) CLOSE S/D Cooling Ln Ib Vent Vlv 151F066.
/
(9) CLOSE PP Suet From Rx Flush Vlv 151F084.
(10) LOCK CLOSED Shutdown Cooling Flush Vlv 151F084.
(11) OPEN SHUTDOWN CLG SUCT IB ISO HV-151-F009 from pane1 1C201.
- g. FLUSH RHR piping to Radwaste as follows:
NOTE PERFORMANCE OF FLUSH IS AT DISCRETION OF SHIFT SUPERVISION.
(1) CHECK Radwaste ready to accept RHR waste water.
(2) CLOSE 18216022 for LOOP A CROSS TIE VLV HV"1F010A.
(3) OPEN. Liquid RW Iso. Vlv 151088.
(4) CHECK CLOSED RADWASTE IB.ISO- VLV HV-151"F040.
(5) OPEN RADWASTE OB ISO VLV HV"151-F049.
(6) OPEN RHR LOOP A CROSS TIE HV"151-F010A ~
(7) COMMENCE flush by throttling open RADWASTg IB ISO VLV HV-151-F040 while monitoring RPV level.
~ I
EO-100-009 Revision 12 Page 36 of 43 NOTE IF CI-Ell"1R006 UNAVAIIABLE,'SE CISH"Ell 1R001A ON INSTRUMENT RACK 1C021.
(8) CONTINUE flush until conductivity indicated on local Conductivity Indicator CI-E11-1R006 on Instrument Rack 1C021 indicates < 2 umhos/cm~
or on direction of shift supervision.
If not in service, PLACE RHR Service Water System Loop A in service as follows:
(1) OPEN RHRSW Hx A Outlet HV-11215A locally.
(2) CRACK OPEN RHRSW Hx A Inlet HV-11210A locally.
(3) At lA20308, elevation 749', PLACE RHR Service Water Pump 1P506A lateral control switch to HANDLE OUT position.
(4) START RHR Service Water Pump 1P506A placing lateral control switch to CLOSE.
(5) OBSERVE SPRAY POND LOOP A BYPS HV"01222A indicates OPEN on Unit 2 Panel 2C201B.
(6) Locally OPEN RHRSW Hx A Inlet HV-11210A to approximately 80Fo open which corresponds to approximately 9000 gpm flow, (7) ALIGN Spray Pond Spray Networks in accordance with OP-116-001 When flush complete, PERFORM following:
(1) CLOSE RAOWASTE IB ISO VLV HV-151"F040.
(2) CLOSE RADWASTE OB ISO VLV HV-.151-F049.
(3) CLOSE RHR LOOP A CROSS TIE VLV HV-151-F010A.
(4) OPEN 1B216022 Loop A Crosstie Vlv HV151F010A.
(5) CLOSE Liquid RW Iso Vlv 151088.
~ I
EO-100" 009 Revision 12 Page 37 of 43
- k. TRIP Reactor Recirc Pump lA M.G. Set by pushing up on plunger marked "LIFT PLUNGER TO OPEN" at 1A10110.
- 1. CLOSE Recirc Pump Suet Vlv F023A from 18237043 as follows:
(1) OPEN breaker.
(2) OPEN breaker door.
(3) PLACE a jumper from 1F to SP1.
(4) CLOSE door.
NOTE THE FOLLOWING STEP WILL CAUSE VALVE TO CLOSE. TORQUE SWITCH WILL REMOVE POWER FROM VALVE.
(5) CLOSE breaker.
(6) After approximately 30 seconds, when main
.contactor releases, OPEN breaker.
(7) OPEN door.
(8) REMOVE jumper from 1F to 'SPl.
(9) CLOSE door.
(10) LEAVE breaker OPEN.
CHECK RHR System Loop A discharge piping filled and vented.
PLACE RHR System Loop A in operation as follows:
NOTE PLACING LATERAL CONTROL SWITCHES TO HANDLE OUT POSITION DEFEATS. AUTO FEATURES OF THE PUMPS.
( 1) If RHR Pump 1A to be placed in service, PERFORM
- following at lA20102 elevation 749':
(a) PLACE RHR Pump 1P202A lateral control switch to HANDLE OUT position.
C I"
EO-100-009 Revision 12 Page 38 of 43 (b) START RHR Pump 1P202A placing lateral control switch to CLOSE, AND OR (2) If RHR Pump 1C to be placed in service, PERFORM following at 1A20302 elevation 719':
(a) PLACE RHR Pump 1P202C lateral control switch to HANDLE OUT position.
(b) START RHR Pump 1P202C placing lateral control switch to CLOSE, AND NOTE HE FOLLOWING STEP TAKES TWO OPERATORS IN CONTACT WITH EACH OTHER BY RADIO, ONE AT VALVE AND ONE AT FLOW INDICATOR.
(3) IMMEDIATELY MANUALLY OPEN RHR LPCI Outbd Valve HV151F017A to achieve a flowrate > 4,000 gpm indicated on FI-15105A located at 29-683'y RBCCW Heat Exchangers.
- o. TRIP Reactor Recirc Pump 1B M.G. Set by pushing up on plunger marked "LIFT PLUNGER TO OPEN" at 1A10210.
- p. If cooldown desired to be controlled, MANUALLY THROTTLE RHR Heat Exch Bypass Vlv HV151F048A.
- q. PLOT RPV Cooldown Rate on Attachment 9 using Attachment A for pressure temperature relationship with RPV still at pressure from the Remote Shutdown Panel.
4.11.6 If RHR Shutdown Cooling NOT AVAILABLE for cooldown,
~ PERFORM ON-149-001 Loss of RHR Shutdown Cooling Mode.
NOTE HE REACTOR PLANT IS SHUTDOWN WITH SHUTDOWN COOLING IN SERVICE WITH VESSEL LEVEL BEING MAINTAINED BY CONDENSATE AND/OR CRD.
4.11.7 PROCEED to OP-100-001 to return control to Control Room
'Room from Remote Shutdown Panel when Control Room becomes available.
4 g l
EO-100-009 Revision 12 Page 39 of 43
5.0 REFERENCES
5.1 OP-149-001 Residual Heat Removal System 5.2 OP-125-001 Containment Instrument Gas System 5.3 OP-155-001 Control Orive Hydraulic System 5.4 OP-100-001 Remote Shutdown-Normal Plant Operating Lineup 5.5 OP-164-001 Reactor Recirculation System 5.6 OP-151-001 Core Spray System 5.7 OP-116-001 Residual Heat. Removal Service Water (RHRSW) 5.8 ON-149-001 Loss of RHR Shutdown Cooling Mode 5.9 J-451 Sh 1-3 5.10 E"185 Sh 5, 10"13 5.11 E"153 Sh 4, 9-18, 20, 24, 36-41, 44
.5.12 PLI-41155 5.13 MT-TY-010 Emergency Start of Fans in the Event of a Control Room Fire I (x) 514 NCR-87 0727 Procedural Action Required for Appendix R Compliance
(') 5.15 NCR-87-0729 Procedural Action'Required for Appendix R Compliance I
(2) 5 16 NCR-87-0748 Procedural Action Required for Appendix R Compliance
(') 5.17 NCR-87-0879 Procedural Action Required for Appendix R Compliance
~ J o
i4 I
EO-100-009 Revision 12 Page 40 of 43
- 6. 0 DISCUSSION This procedure is designed to shutdown the plant from outside the Control Room by using the Remote Shutdown Panel and/or manual operations in the plant. Activation of the Remote Shutdown Panel transfer switches bypass'the Main Control Room devices and transfer the components control power to alternate supply or thru new fuses. This transfer should be made prior to manual operation of system because most auto signals to these systems are bypassed.
Evacuation of the Main Control Room should only occur after reasonable efforts have been utilized including use of respiratory equipment. Upon leaving the Control Room, the Reactor shall be scrammed and the MSIVs and main steam line drains closed. All other functions shall take place outside the Control Room.
An Operator/STA should be stationed at the TSC to monitor plant parameter s on DCS/PMS and SPDS. He should be equipped to communicate with the Remote Shutdown Panels. If the TSC is also uninhabitable, he should go to the EOF and establish communications to the Remote Shutdown Panels.
/
RCIC system shall be utilized to control Reactor water level. If RCIC is unavailable HPCI should cycle a,utomatically to provide adequate core cooling.
Reactor pressure shall be controlled with the Safety/Relief Valves. As pressure increases to a relief set point, the valve will open with the exception of the three relief valves controlled from the Remote Shutdown, Panel. When these three valves are transferred to the EMERG position, their relief .function is bypassed. These valves will only auto open off their if safety setting. All other valves will. open off their safety setting only their relief function is inoperable. If pneumatic supply is unavailable to SRV's from Remote Shutdown Panel, ADS valves can be operated individually from Upper or Lower Relay Rooms .using keylock switches.
RHR Suppression Pool Cooling shall be used to maintain the suppression pool less than maximum design temperatures. The other loop of RHR can be manually operated if the loop normally controlled on the remote shutdown panel is unavailable.
Fire in the Control Room may result in the loss of both SPOTMOS channels at the Remote Shutdown Panel.. Should this occur, 'initiation of RHR Suppression Pool Cooling must be based on heat addition from Safety/Relief Valves, RCIC and/or HPCI operation.
In bringing the plant to cold shutaown, the three (3) Safety/Relief Valves on the Remote Shutdown Panel shall be used sequentially to distribute heat load (not exceeding 100 F/hr cooldown rate) until pressure is low enough to establish RHR Shutdown Cooling. If RHR Shutdown Cooling is unavailable, cooling can be accomplished using the alternate cooling method per ON-149-001 from outside the Control Room.
4 ~
( . i
/y (jl I C V Jy k
$ s 1
PRESSURE V EMPERATURE FOR SATURATED STEAM 1600 1500 1400 1300 1200 1100 CL 1000 LU eoO 800 700 LU CY 600 500
~~DlW eC)n 400 o cO ( I rt
~
lO v nn
~
C) D 300 ~0 I B C) 0 0 C)D aD rt 200 O 100 0
200 250 300 350 400 450 500 550 600 TEHPERATURE, (F)
<'u l
SSO 1'a.
100 W
EK I-lK UJ CL tel I-300 2:
<<C C3 CJ lK E3 I-CJ
~mme o eC)w I (~ DA aQ us I c+
DK p 0 I B
~ D SD 0 ~D LD rt h
N 0 0.5 1.0 i.5 2. ~ 2.% $ .0 3.5, 1.0 1,5 .S.P 5.5 1.0 I.S 7.0 7.$ e.'I T IHE/HRS ~
P, C
~ Al,>
p gi.f ~
'ttachment C EO-100-009 Revision 12 Page 43 of 43 APPROXIMATE INDICATED HATER LEVEL FOR COLQ
'EPRESSURIZFQ REACTOR VESSEL CONDITION CTUAL WIT 200 50
+100
> +50 +1 00 +1 IHO I CATEO LEVEL
-50
-100
-150 200 Page 1 of 1
f