WSES-FSAR-UNIT-3 7.6-1 Revision 305 (11/11) 7.6 ALL OTHER INSTRUMENTATION SYSTEMS REOUIRED FOR SAFETY
7.
6.1 DESCRIPTION
This section includes a description of those instrumentation systems required for safety which have not been discussed in Sections 7.2 through 7.5.
These systems include instrumentat ion to prevent overpressurizati on of low pressure systems.
7.6.1.1 Shutdown Coo ling System Interlocks
7.6.1.1.1 Description
Cooling of the Reactor Coolant System (RCS) is accomplished by heat removal via the steam generators down to approximately 350 F and by the Shutdown Cooling System (SDCS) below this temperature.
(EC-935, R302; EC-14765, R305)
The SDCS described in Subsection 9.3.6 is not designed to accept RCS operating pressure since it is a low pressure system. It is put into operation onl y at reduced temperature and pressure conditions. Overpressure protection is assured by providing two motor-operated isolation valves (one in each line) and two pneumatic operated isolation valves (one in each line) installed in series in the two shutdown
cooling suction lines inside the containment vessel.
Each of the two pneumatic operated valves has a solenoid operated bypass fill valve used to reduce potentia l voids in the downstream piping. Each line is also provided with a motor operated isolation valve outside the containment with manual control (no
automatic operation) at the main control room. T he SDCS instrumentation and controls are discussed in Section 7.4. To assure proper operation and hence prevent inadvertent pressurization of the low pressure portion of the SDCS, each of the valves inside the containment is interlocked by one of four independent pressurizer pressure measurement channels to pr event opening when RCS pressure exceeds 377 psig. The pressure setpoint for the interlocks (at CP-25, CP-26, CP-27, CP-28) is selected such that the design
pressure of the SDCS is not exceeded. (EC-935, R302)
Each measurement channel provides a permissive si gnal to one of the four main and two bypass fill isolation valves to allow opening that valve when the pr essurizer pressure is below 377 psig. An alarm is sounded in the main control room in case the RCS pressure higher than 392 psia, and its associated valve is not fully closed. The alarm is used to i ndicate an LTOP transient or possible lifting of the shutdown cooling relief valves. The design of the inte rlock is such that loss of electric power to a permissive channel would leave the valves in it s set position and would render inoperative the open permissive feature. However, if the valve is open, it can be manually closed, but if the valve is closed, it cannot be manually opened. Keylocked switches are prov ided in the control room (RTGB-CP8) to allow opening of the isolation valves (V 1501B with bypass fill valve, V1502B , V1503A with bypass fill valve, V1504A) when the permissive signal is present.
Four independent power sources (two 480V ac and two 125V dc) are provided to keep the four main and two bypass fill isolation valves, in two shutdown lines, operable. A single failure of any power source will adversely affect only one shutdown line. (EC-14765, R305)
For a list of control wiring diagrams see Section 1.7.
WSES-FSAR-UNIT-37.6-2Revision 10 (10/99)7.6.1.1.2Design Basis InformationThe design basis for the shutdown cooling interlocks is to prevent an equipment fault or an operator actionfrom producing an unsafe condition. The interlocks have no protective function as defined in IEEE Standard 279-1971. However, using Section 3 of IEEE Standard 279-1971 as a guideline, the followingparagraphs respond to the provisions identified in IEEE Standard 279-1971 Section 3 insofar as they areapplicable:Item 1The interlocks shall function to prevent opening the shutdown cooling lineisolation valves whenever pressurizer pressure exceeds a preset value.Item 2Pressurizer pressure shall be monitored to provide the required function.Item 3Four separate, physically independent sensors located on separate pressurizernozzles are provided. Each of these sensors provide interlock/permissive signals to a separate isolation valve. A maximum of three out of four of these sensors need to operate to perform the required system function.Item 4Operating procedures, administrative controls, and the interlocks all serve toensure that, the isolation valves are not open when pressure in the RCS is greater thanthe design pressure of the shutdown cool suction lines.7.6.1.2Safety Injection Tank (SIT) Isolation Valve Interlocks 7.6.1.2.1DescriptionFour SITs are used to flood the reactor core with borated water following RCS depressurization as a resultof a LOCA. During normal plant operation, each SIT is isolated from the RCS by a check valve. The SITsautomatically discharge their contents into the RCS, if RCS pressure decreases below the SIT pressureduring power opemtion.Safety injection tank motor-operated isolation valves are provided to allow isolation of the SITs when RCSpressure is below 400 psig. The isolation valves are normally open and interlocked with pressurizerpressure measurement channels (PIC-103, -104). The SIT motor-operated isolation valves are provided with the following interlocks:a)The SIT isolation valves cannot be shut unfil RCS pmasure is 400 psig. Section 6.3 describedprocedures for depressurizing the RCS.b)The valves will open automatically when the RCS pressure is > 500 psig. This interlock assuresthe availability of the fluid in the tanks after the SDCS isolation valves have been closed during plant heatup.Since it is essential that the isolation valves on the safety injection tanks be open whenever the RCS is atpressure, the fail-as-is valves are locked open and the valve motor circuit breaker handle is padlocked in the open position. A safety injection actuation signal (SIAS) "open" signal is provided to each valve, even though the valves are locked open and the breakers padlocked. Position indicating lights are provided in the main control room for each valve. An audible alarm is actuated whenever the RCS pressure is >500psig and the valve is not fully open and whenever the RCS pressure is < 400 psig and the WSES-FSAR-UNIT-37.6-3Revision 10 (10/99)valve is not fully closed. The position indication and audible alarm are independent of the motor controlcenter power.For a list of control wiring diagrams see Section 1.7.
7.6.1.2.2Design Basis Information The design basis for the SIT isolation valve pressure interlocks is to provide a means of assuring that thesafety injection tanks are not isolated from the RCS when the system pressure exceeds a preset value.
The interlocks have no protective function as defined in IEEE Standard 2791971. However, using Section3 of IEEE Standard 279-1971 as a guideline, the following discussion responds to the provisions identified in Section 3, insofar as they are applicable.IEEE Standard279-1971, Section 3DiscussionItem 1The pressure interlocks shall function to open the SIT isolation valveswhenever pressurizer pressure exceeds a preset value.Item 2Pressurizer pressure shall be monitored to provide the required function.Item 3Two separate, physically independent sensors on separate pressurizer nozzlesare provided, either of which will perform the required function.Item 4Operating procedures, administrative controls and the interlocks all serve toensure that the isolation valves are open when pressure in the RCS is greater than a preset value.Item 5No protective action is required. When system pressure exceeds the setpoint,the interlock functions to open the valves.The design of the control circuits for the SIT isolation valves incorporates the following features:
a)Automatic opening of the valves when either the RCS pressure exceeds a preselected value or asafety injection signal has been initiated. Both signals are provided to the valves.b)In the event of loss of power supply, pressurizer pressure measurement channel output relaysand also the SIAS group relays fail to the "safe" position generating a "valve open" commandsignal.c)Visible indication of the open or closed status of the valves, actuated by sensors on the valve isprovided in the control room. The indication is independent of the valve power supply on 120V AC.d)An audible and visible alarm is provided, actuated by a sensor on the valves when the valves arenot in the fully open position and pressurizer pressure is > 500 psig.
WSES-FSAR-UNIT-37.6-4Revision 10 (10/99)e)A SIAS is provided to open the valves. There are no overrides or bypasses that would inhibit theSIAS and prevent the valves from opening when required.7.6.1.3Refueling InterlocksRefueling interlocks which are non-safety are described in Section 9.1.
7.6.1.4Spent Fuel Pool Cooling and Cleanup SystemSpent fuel pool cooling and cleanup are described in Subsection 9.1.3.
7.6.1.5Containment Purge Isolation Signal7.6.1.5.1DescriptionThe Containment Purge System and its isolation valves are described in Subsection 9.4.5. TheContainment Purge Isolation Signal (CPIS) is generated by the use of three local radiation monitors in each of the safety channels A & B. The signal is generated separately and independently from the engineered safety actuation signals. The analog signal from the radiation monitors are fed into bistables located in the radiation monitor panels. One out-of-three logic in each channel provides the purgeisolation signal, which acts as a permissive input for manual opening and automatic closing of the valves.Control switches for the isolation valves as well as provisions for testing the circuit operation are located in the main control room. Testing will be performed periodically as outlined in the Technical Specifications.For a list of control wiring diagrams see Section 1.7.7.6.1.5.2Design Basis InformationThe CPIS as described above, acts as a permissive to allow manual opening of the valves when radiationlevels are acceptable. Removal of the permissive signal at any state of operation will cause the valves to shut automatically. This condition is alarmed in the main control room. Closing of the valves will prevent purging the containment when radiation levels are unacceptable. The CPIS has no protective function as defined in IEEE Standard 279-1971. However, using Section 3 of IEEE Standard 279-1971 as a guideline, the following discussion responds to the provisions identified in Section 3, insofar as they are applicable.IEEE Standard279-1971 Section 3DiscussionItem 1The CPIS shall function to prevent opening or shut if open the containmentpurge isolation valves whenever containment radiation exceeds a preset value.Item 2Containment and plant stack radiation shall be monitored to provide therequired function.
WSES-FSAR-UNIT-37.6-5Revision 10 (10/99)Item 3Three separate, physically independent sensors for each of the safety channels(A & B), shall be provided. Each of these sensors provides the permissive signal by a one-out-of-three logic to operate the isolation valves.Item 4Operating procedures, administrative controls, and the permissive signal fromthe radiation monitoring panel will ensure that the isolation valves are closed when purging is not permitted.Item 5Protective action is required during containment purge. When radiation levelsexceeds the setpoint, the signal functions to shut the valves.7.6.1.6Reactor Coolant System Leak Detection SystemThe RCS Leak Detection System and its instrumentation is described in Subsection 5.2.5.
7.6.1.7Area and Process Radiation Monitoring,Area radiation monitoring is described in Section 12.3. The process radiation monitoring is described inSection 11.5.7.6.1.8Contaimment Vacuum Relief SystemThe Containment Vacuum Relief System and its instrumentation is described as part of the containmentfunctional design in Subsection 3.8.2.3.7.6.1.9Low Temperature Overpressure Protection (LTOP)LTOP provides narrow range (100-750 psia) pressure indication from four channels. It is used duringheatup, cooldown and cold shutdown in conjunction with the Shutdown Cooling System (SDCS) interlocks discussed in Subsection 7.6.1.1.Low temperature overpressure protection during heatup, cooldown and cold shutdown is addressed inAppendix 5.2B.7.6.2ANALYSIS 7.6.2.1Shutdown Cooling System InterlocksThere are no specific NRC Regulatory Guides or General Design Criteria which apply to theseinterlocks.The requirements of Standard 279-1971 are written expressly for protection systems, and as such, theyare not directly applicable to these interlocks. A discussion of the extent to which these interlocks apply tothis Standard is provided below.
WSES-FSAR-UNIT-3 7.6-6 Revision 305 (11/11)
The following discussion refers to the requirements set fo rth in the respective items of Section 4 of IEEE Standard 279-1971:
IEEE Standard
279-1971
Section 4 Discussion
Item 1 The interlocks are designed to m eet the requirements of quality, seismic and environmental Class 1E electrical equipment as described in Sections 3.10 and 3.11.
(EC-14756, R305)
Item 2 Single failure criteria are met in that no single interlock failure in the six valve arrangement can remove the pressure boundary between the RCS and the Shutdown Cooling System nor prevent SDCS operating when inquired. (EC-14765, R305)
Item 3 The sensors for these interlocks m eet the same quality requirements that are imposed on protective syst em instrumentation.
Item 4 Type tests are performed on the instrumentation that will ensure their operation during expected conditions of seismic activity.
Item 5 The interlocks are designed to ma intain functional capability in the normal plant operating environment and to maintain functional capability under accident
conditions including the design bases LOCA or MSLB-
Item 6 The pressure transmitters are located on separate pressurizer nozzles and separation is between channels.
Item 8 Direct measurement of pressurize r pressure is used as the signal for these interlocks.
Item 9 The operational availability of the four pressure sensing channels can be determined by comparing their outputs.
Item 10 Testing will be performed during nor mal plant shutdown periods using standard test devices and approved procedures.
Item 11 Not applicable.
(EC-23616, R305; EC-14765, R305)
Item 12 Bypass switches are installed for SI
-401B, SI-405B and SI-4052B allowing the plant through 14 operator to override the RCS pressu re interlock and open the valves during an Appendix R fire event. Adequate RCS pressure is adm inistratively verified prior to opening the valves. (EC-23616, R305; EC-14765, R305)
Item 15 Multiple setpoints are not used.
WSES-FSAR-UNIT-37.6-7Revision 10 (10/99)Item 17A key-locked control switch is provided in the control room which enables theoperator to close the isolation valves at any time, or to open the isolation valves if permissive conditions are met.Item 18Administrative controls are provided for access to setpoint adjustment andcalibration controls.Item 19Completion of the isolation function is identified by the valve positionindication.Item 20The readout consists of four pressure indicators and position indication foreach of the valves. This provides the operator with clear concise information.Item 21The components are accessible for repair. Removal of one channel out ofservice will result in isolation of the associated shutdown line.Item 22The instrumentation and cables associated with the SDCS interlocks are notuniquely identified as such. The channels are identified to distinguish between redundant channels.7.6.2.2Safety Injection Tank Isolation Valve InterlocksThere are no specific NRC Regulatory Guides or General Design Criteria which apply to these interlocks.The requirements of IEEE Standard 279-1971 are written expressly for protection systems and, as such,they are not directly applicable to these interlocks. However, a discussion of the extent to which this IEEEstandard applies to these interlocks is provided below.The following discussion refers to the requirements set forth in the respective items of Section 4 of IEEEStandard 279-1971:IEEE Standard 279-1971 Section 4DiscussionItem 1The interlocks are designed to meet all requirements of Quality, Seismic andEnvironmental Class 1E electrical equipment described in Sections 3.10, and
3.11.Item 2No single failure of an interlock channel can prevent system operation when itis required.Item 3The sensors for these interlocks meet the same quality requirements that areimposed on protection system instrumentation.Item 4Type tests as described in Sections 3.10 and 3.11 are performed on theinstrumentation to ensure their operation during expected conditions of seismic activity.
WSES-FSAR-UNIT-3 7.6-8 Revision 305 (11/11)
Item 5 The interlocks are designed to main tain functional capability in the normal plant operating environment. They serve no protective function during abnormal or accident situations.
Item 6 The pressure transmitters are located on separate pressurizer nozzles, and separation is maintained between channels.
Item 7 The interlocks automatically open the valves when RCS pressure increases to 500 psig.
Item 8 Direct measurement of pressurizer pressure is used as the signal for these interlocks.
Item 9 The operational availability of the pressure sensing channels can be determined by comparing their outputs.
Item 10 Testing will be performed during norma l plant shutdown periods using standard test devices and approved procedures.
Item 11 Removal of one channel for test does not compromise system reliability.
Failure of the remaining channels during a test outage would not create an unacceptable situation, since administrative controls (key locks) effectively preclude inadvertent closing of the valves by the operator.
(EC-23616, R305)
Item 12 Bypass switches are installed for Safety Injection Tank Isolation Valves allowing the plant through 14 operator to override the SIAS and RCS pressu re interlock for closing of the valves during an Appendix R fire event. Adequate RCS pressu re is administratively verified prior to closing the valves. (EC-23616, R305)
Item 15 Multiple setpoints are not used.
Item 16 See item 7.
Item 17 A key-locked switch is provided to enable the operator to open the valves if required.
Item 18 Administrative controls are prov ided for access to setpoint adjustment and calibration controls.
Item 19 Correct functioning of the interlocks is indicated by the valve position indicators.
Item 20 The readout consists of pressure indicators and position indication for each of the valves. This provides the operator with clear concise information.
WSES-FSAR-UNIT-37.6-9Item 21The components are accessible for repair. Removal of one channel from servicewill leave two SI tanks' isolation valves in the open position.Item 22The instrumentation and cables associated with the SIT isolation valveinterlocks are not uniquely identified as such. The channels are identifiedto distinguish between redundant channels.7.6.2.3Refueling InterlocksRefueling interlocks analaysis is included in Section 9.1.
7.6.2.4Spent Fuel Pool Cooling and Cleanup SystemSpent fuel pool cooling and cleanup system analysis is included in Subsection 9.1.3.
7.6.2.5Containment Purge Isolation SignalThe requirements of IEEE Standard 279-1971 are written expressly for protection system. Containmentpurge isolation signal is not applicable to the requirements of IEEE Standard 279-1971. However, a discussion of Section 4 of IEEE Standard 279-1971 shall be applied.The following discussion refers to the requirements set forth in the respective items of Section 4 of IEEEStandard 279-1971:IEEE Standard 279-1971 Section 4DiscussionItem 1The permissive signals are designed to meet all the requirements of quality,seismic and environmental Class 1E electrical equipment described in Sections
3.10, and 3.11.Item 2No single failure of an CPIS can prevent system operation when it is required.
Item 3The sensors for these radiation monitors meet the same quality requirementsthat are imposed on protection system instrumentation.Item 4Type tests as described, in Sections 3.10 and 3.11 are performed on theinstrumentation to ensure their operation during expected conditions of seismic activity.Item 5The permissive signals are designed to maintain functional capability in thenormal plant operating and shutdown environment. CPIS protects against Fuel Handling accidents.Item 6The radiation sensors are located in separate areas and separation ismaintained between channels.Item 7The lack of permissive signal will automatically shut the valves.
WSES-FSAR-UNIT-37.6-10Revision 10 (10/99)Item 8Direct measurement of containment radiation is used to develop the logic forthe CPIS, along with two inputs from the plant stack vent.Item 9The operational availability of the radiation sensing detectors can bedetermined by comparing their outputs at the radiation monitors.Item 10Testing will be performed during normal plant shutdown periods using standardtest devices and approved procedures.Item 11Testing at one channel will not compromise system reliability. Failure ofthe remaining channel during a test would not create an unacceptable situation.Items 12There are no bypasses.through 14Item 15Each area and stack radiation monitor alarm/trip comes from the ODCM or somefactor above the normal (background) level of radiation the detector can sense accurately.Item 16Valves are automatically closed when containment radiation exceeds setpointsestablished by Technical Specifications.Item 17Control switches are provided in the control room to enable the operator to open thevalves if permissive conditions are met.Item 18Administrative controls are provided for setpoint adjustment and calibrationcontrols.Item 19Correct functioning of the permissive signal is indicated by the valve positionindicators.Item 20The readout consists of position indication for each of the valves. This provides the operatorwith clear concise information.Item 21The components are accessible for repair.Item 22The instrumentation and cables associated with the CPIS are not uniquely identifiedas such. The channels are identified to distinguish between redundant channels.7.6.2.6Reactor Coolant System Leak Detection System The RCS Leak Detection System and its instrumentation analysis is included in Subsection 5.2.5.
WSES-FSAR-UNIT-37.6-11Revision 10 (10/99)7.6.2.7Area and Process Radiation MonitoringArea radiation monitoring analysis is included in Section 12.3. Process radiation monitoring analysis isincluded in Section 11.5.7.6.2.8Containment Vacuum Relief SystemContainment Vacuum Relief System analysis is included in Subsection 6.5.3.7.6.2.9Low Temperature Overpressure ProtectionAnalysis for low temperature overpressure protection during heatup, cooldown and cold shutdown isaddressed in Appendix 5.2B.