| title = Forwards Response to Request for Addl Info Re Request for Exemption from Requirements of App R Subsection III.G.2.a for Electrical Raceways in Open Turbine Bldg.Rev 1 to PTN-FPER-97-013 Rept Encl | | title = Forwards Response to Request for Addl Info Re Request for Exemption from Requirements of App R Subsection III.G.2.a for Electrical Raceways in Open Turbine Bldg.Rev 1 to PTN-FPER-97-013 Rept Encl | ||
| author name = | | author name = Hovey R | ||
| author affiliation = FLORIDA POWER & LIGHT CO. | | author affiliation = FLORIDA POWER & LIGHT CO. | ||
| addressee name = | | addressee name = | ||
Line 19: | Line 19: | ||
=Text= | =Text= | ||
{{#Wiki_filter:CATEGORY 1~REGULAT(Y INFORMATION DISTRIBUTION SYSTEM (RIDS)ACCESSION NBR:9807080062 DOC.DATE: 98/07/02 NOTARIZED: | {{#Wiki_filter:CATEGORY 1 | ||
NO DOCKET SCIL:50-250 Turkey Point Plant, Unit 3, Florida Power and Light C 05000250 50-251 Turkey Point Plant, Unit 4, Florida Power and Light C 05000251 AUTH.NAME | ~ | ||
Florida Power&Light Co.5~ | REGULAT( Y INFORMATION DISTRIBUTION SYSTEM (RIDS) | ||
ACCESSION NBR:9807080062 DOC.DATE: 98/07/02 NOTARIZED: NO DOCKET SCIL:50-250 Turkey Point Plant, Unit 3, Florida Power and Light C 05000250 50-251 Turkey Point Plant, Unit 4, Florida Power and Light C 05000251 AUTH.NAME HOVEY,R.J. | |||
RECIP.NAME AUTHOR AFFILIATION Florida Power & Light Co. | |||
RECIPIENT AFFILIATION 5~ | |||
Records Management Branch (Document Control Desk) | |||
==SUBJECT:== | ==SUBJECT:== | ||
Forwards response to request for addi info re request for exemption from requirements of App R Subsection III.G.2.a for electrical raceways in open turbine bldg.Rev 1 to PTN-FPER-97-013 rept encl;DISTRIBUTION CODE: A006D COPIES RECEIVED: LTR i ENCL i SIZE:~TITLE: OR/Licensing Submittal: | Forwards response to request for addi info re request for exemption from requirements of App R Subsection III.G.2.a for electrical raceways in open turbine bldg.Rev 1 to PTN-FPER-97-013 rept encl; DISTRIBUTION CODE: A006D COPIES RECEIVED: LTR i ENCL i SIZE: | ||
Fire Protection | ~ | ||
-App R-GL-.88-12 NOTES: | TITLE: OR/Licensing Submittal: Fire Protection - App R - GL-.88-12 E NOTES: | ||
PLEASE HELP US TO REDUCE WASTE.TO HAVE YOUR NAME OR ORGANIZATION REMOVED FROM DISTRIBUTION LISTS | " RECIPIENT COPIES RECIPIENT COPIES 0 ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL PD2-3 LA 1 0 PD2-3 PD 1 1 JABBO K 1 1 INTERN : FILE CE 2 2 NRR/DSSA/SPLB 1 "1 | ||
~.f t | -ABSTRACT 1 1 OGC/HDS3 1 0 1 1 NRC PDR N | ||
,'rr L | t NOTE TO ALL "RIDS" RECIPIENTS: | ||
Document Control Desk Washington, D.C.20555 | PLEASE HELP US TO REDUCE WASTE. TO HAVE YOUR NAME OR ORGANIZATION REMOVED FROM DISTRIBUTION LISTS OR REDUCE THE-NUMBER OF COPIES RECEIVED-BY YOU OR YOUR ORGANIZATION, CONTACT-THE DOCUMENT CONTROL DESK (DCD), ON EXTENSION 415-2083 h | ||
TOTAL NUMBER OF COPIES REQUIRED: LTTR 10 ENCL 8 | |||
~ . | |||
f t | |||
JUL 02 1998 | |||
,' rr L L-98-153 10 CFR 550.12 10 CFR 550.48 10 CFR Part 50 Appendix R U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D. C. 20555 | |||
==Subject:== | ==Subject:== | ||
Turkey Point Units 3 and 4 Docket Nos.50-250 and 50-251 Response to Request for Additional Information on Request for Exemption-Fire Rating of Raceway Fire 1 By letter L-97-181, dated July 31, 1997, Florida Power&Light (FPL)submitted a request for exemption from the requirements of Appendix R subsection III.G.2.a for electrical raceways in the~ | Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 Response to Request for Additional Information on Request for Exemption - Fire Rating of Raceway Fire 1 | ||
FPL's response incorporates information requested by the NRC during the May 26, 1998 public meeting between NRC and FPL.Should there be any questions, please contact us.Very truly yours, R.J.Hovey Vice President Turkey Point Plant OIH Attachment Enclosures cc: L.A.Reyes, Regional Administrator, Region II, USNRC T.P.Johnson, Senior Resident Inspector, USNRC, Turkey Point 9807080062 9'80702 PDR ADQCK-05000250 | By letter L-97-181, dated July 31, 1997, Florida Power & Light (FPL) submitted a request for exemption from the requirements of Appendix R subsection III.G.2.a for electrical raceways in the | ||
NO DOCKET FACIL:50-250 Turkey Point Plant, Unit 3, Florida Power and Light C 05000250 50-251 Turkey Point Plant, Unit 4, Florida Power and Light C 05000251 AUTH.NAME | ~ | ||
Florida Power S Light Co.5~RECIP.NAME RECIPIENT AFFILIATION Records Management Branch (Document Control Desk) | open turbine building. By letter dated March 23, 1998, the Nuclear Regulatory Commission (NRC) | ||
~ | |||
requested additional information (RAI) in order to complete the review. In accordance with the NRC request, Attachment 1 provides the additional information requested. FPL's response incorporates information requested by the NRC during the May 26, 1998 public meeting between NRC and FPL. | |||
Should there be any questions, please contact us. | |||
Very truly yours, R. J. Hovey Vice President Turkey Point Plant OIH Attachment Enclosures cc: L. A. Reyes, Regional Administrator, Region II, USNRC T. P. Johnson, Senior Resident Inspector, USNRC, Turkey Point 9807080062 9'80702 PDR ADQCK- 05000250 | |||
~ | |||
. PDR a | |||
an FPL Group company | |||
I 0 | |||
0 I | |||
CATEGORY 1 REGULA'A RY INFORMATION DISTRIBUTION SYSTEM (RIDS) | |||
ACCESSION NBR:9807080062 DOC.DATE: 98/07/02 NOTARIZED: NO DOCKET FACIL:50-250 Turkey Point Plant, Unit 3, Florida Power and Light C 05000250 50-251 Turkey Point Plant, Unit 4, Florida Power and Light C 05000251 AUTHOR AFFILIATION AUTH. NAME HOVEY,R.J. Florida Power S Light Co. 5~ | |||
RECIP.NAME RECIPIENT AFFILIATION Records Management Branch (Document Control Desk) | |||
==SUBJECT:== | ==SUBJECT:== | ||
Forwards response to request for addi info re request for exemption from requirements of App R Subsection III.G.2.a for electrical raceways in open turbine bldg.Rev 1 to PTN-FPER-97-013 rept encl.DISTRIBUTION CODE: A006D COPIES RECEIVED: LTR 1 ENCL 1 SIZE: TITLE: OR/Licensing Submittal: | Forwards response to request for addi info re request for exemption from requirements of App R Subsection III.G.2.a for electrical raceways in open turbine bldg.Rev 1 to PTN-FPER-97-013 rept encl. | ||
Fire Protection | DISTRIBUTION CODE: A006D COPIES RECEIVED: LTR 1 ENCL 1 SIZE: | ||
-App R-GL-88-12 NOTES: | TITLE: OR/Licensing Submittal: Fire Protection - App R - GL-88-12 E NOTES: | ||
PLEASE HELP US TO REDUCE WASTE.TO HAVE YOUR NAME OR ORGANIZATION REMOVED FROM DISTRIBUTION LISTS OR REDUCE THE NUMBER OF COPIES RECEIVED BY YOU OR YOUR ORGANIZATION, CONTACT THE DOCUMENT CONTROL DESK (DCD)ON EXTENSION 415-2083 TOTAL NUMBER OF COPIES REQUIRED: LTTR 10 ENCL 8 r o r I 0 JUL 0 2 1998 L-98-153 10 CFR 550.12 10 CFR 550.48 10 CFR Part 50 Appendix R U.S.Nuclear Regulatory Commission Attention: | RECXPIENT COPIES " RECIPIENT COPIES | ||
Document Control Desk Washington, D.C.20555 | ~ | ||
ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL PD2-3 LA 1 0 PD2-3 PD 1 1 JABBOU 1 1 INTERNAL: 2 2 NRR/DSSA/SPLB 1 1 1 1 OGC/HDS3 1 0 EXTERNAL: NOAC 1 1 NRC PDR 1 1 D | |||
N NOTE TO ALL NRIDS" RECIPIENTS: | |||
PLEASE HELP US TO REDUCE WASTE. TO HAVE YOUR NAME OR ORGANIZATION REMOVED FROM DISTRIBUTION LISTS OR REDUCE THE NUMBER OF COPIES RECEIVED BY YOU OR YOUR ORGANIZATION, CONTACT THE DOCUMENT CONTROL DESK (DCD) ON EXTENSION 415-2083 TOTAL NUMBER OF COPIES REQUIRED: LTTR 10 ENCL 8 | |||
r o r I | |||
0 JUL 0 2 1998 L-98-153 10 CFR 550.12 10 CFR 550.48 10 CFR Part 50 Appendix R U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D. C. 20555 | |||
==Subject:== | ==Subject:== | ||
Turkey Point Units 3 and 4 Docket Nos.50-250 and 50-251 Response to Request for Additional Information on Request for Exemption-Fire Rating of Raceway Fire rrl i il in By letter L-97-181, dated July 31, 1997, Florida Power 8c Light (FPL)submitted a request for exemption from the requirements of Appendix R subsection III.G.2.a for electrical raceways in the open turbine building.By letter dated March 23, 1998, the Nuclear Regulatory Commission (NRC)requested additional information (RAI)in order to complete the review.In accordance with the NRC request, Attachment 1 provides the additional information requested. | Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 Response to Request for Additional Information on Request for Exemption - Fire Rating of Raceway Fire rrl i il in By letter L-97-181, dated July 31, 1997, Florida Power 8c Light (FPL) submitted a request for exemption from the requirements of Appendix R subsection III.G.2.a for electrical raceways in the open turbine building. By letter dated March 23, 1998, the Nuclear Regulatory Commission (NRC) requested additional information (RAI) in order to complete the review. In accordance with the NRC request, Attachment 1 provides the additional information requested. FPL's response incorporates information requested by the NRC during the May 26, 1998 public meeting between NRC and FPL. | ||
FPL's response incorporates information requested by the NRC during the May 26, 1998 public meeting between NRC and FPL.Should there be any questions, please contact us.Very truly yours, Nl, R.J.Hovey Vice President Turkey Point Plant OIH Attachment Enclosures cc: L.A.Reyes, Regional Administrator, Region II, USNRC T.P.Johnson, Senior Resident Inspector, USNRC, Turkey Point'rr807080062 | Should there be any questions, please contact us. | ||
'F80702 PDR ADOCK 05000250 F PDR an FPL Group company li Cf 4/fall' 2 4 d d | Very truly yours, Nl, R. J. Hovey Vice President Turkey Point Plant OIH Attachment Enclosures cc: L. A. Reyes, Regional Administrator, Region II, USNRC T. P. Johnson, Senior Resident Inspector, USNRC, Turkey Point | ||
'rr807080062 'F80702 PDR ADOCK 05000250 F PDR an FPL Group company | |||
li Cf 4 | |||
/fall' | |||
2 4 d d I | |||
I I | |||
I I | |||
I | Al I | ||
CPBO I I | |||
'""-"'FM C ll5l BOSTON-PROVIDENCE TURNPIKE, NORWOOD, MASS.FIRE TESTS OF AUTGMATIC SPRXIGKZR PROTECTION FOR OIL SPILL FIRES | I I | ||
The purpose of the tests vas to learn if automatic sprinklers vie.protect buf3cUngs, such as the Commission's gaseous diffusion plants, against fire'in lubricating oil accidentally spi33ed on the floor.Fire tests vere made involving oil, at elevated, temperatures, covering 2100 sq Xt of'1oor, also at elevated.temperatures, and.employing various methods of'gnition. | on I Aleo Avauab~s O'af6 I | ||
Xn a11 of the tests the f'loor fires were cLuickly controlled ancL minimized and the test building vas satlsfactor~ | p tnj efd f | ||
protected. | 'I I | ||
by sprinkler discharge. | 36 33 34 SS.I 33 sa 2S.I 26 I I | ||
at relatively lov pressure.In the fifth test an oil spray dis-charging from a nozzle above floor level provided an auxiliary fire against which the building vas protected. | I | ||
by lov discharge from the sprinklers. | = | ||
The spray fire vas'not extinguished in this case ancL a steel structural member ac/scent to it vas not protected. | I I | ||
against severe local exposure.It is.concludecL that the Atomic Energy Commission's gaseous cLfffusion plants can be satisfactorily protected. | ~~I | ||
by automatic sprinklers. | -jj dl I | ||
In the case of.floor spill'ires alone', protection would be complete against general and indiyicLual structural failure and against involvement of insulated. | I I | ||
metal deck roof'onstruction. | ass'.a. asaaa I | ||
In'he event of additional fire in oQ.spraying from.rupture'd. | : s. sas | ||
equipment,'eneral structural protection voulcL be maintained | 'ss I I | ||
Failure of incLLvidual structural members could.occur in this situation if such members were so located.as to be exposecL severe by the fire in the~oil spray..The principal obgectives of the test program were based.on fires in lubricating oil spilled.on a level concrete floor, with both oil and.Moor FOR BETTER PROTECTION OF INDUSTRY 0 0 | I I | ||
~2w at temperatures which vould be expected in a typical gaseous diffusion plant.1.To determine rate of flame spread.radially from a local ignition source vith no fire protection. | I I | ||
2 To determine the minimUm practical water discharge density from a sprinkler system required to control and.to extinguish an oil spill fire To obtain vith our test facQ.ities informstian vhich vould.lead.to a conclusion as to the effect of ceiling height araund, the order of 50 feet in bringing about any significant | ,I I I | ||
'delay in operation of autamatic sprinklers. | >L S5IK 1IdkIf I I | ||
To determine, vith snd.vithout sprinkler protection, the effect of an oil spill fire directly exposing structural steel in bringing about excessive stee3.temperatures.snd. | = c' | ||
in causing elevated.ceiling temperatures. | / I s./1 w/ I I | ||
L-5.To obtain from test results information vhich, combined.with previous test experience snd.)udgment~m1ght lead to an inte23.igent estimate of the number of sprin3Q.er heads which might operate due to an oil fire, so as to assist in the design of an effective automatic sprinkler system.6.Another obgective vhich vas developed during the test program vss to determine vhether a fire in hot lubricating oil discharged at a sub-stant1al rate.in the.form of an elevated.spray could be extinguished. | I | ||
or controlled, by.sprin3Q.ers vithin the range of ordinary discharge densities, and.'hqt the effect would.be af'Sire of'his type on ceiling and.exposed.steel | ~a I I | ||
'.'f I e | ~a ~~ | ||
steel frame construction, 12 in.brick va'.Lls, and a vermiculite plaster'n metal lathe ceiling suspended,-.,', from steel beams vhich also support a.poured.concrete roof.The locations and.sizes of doors, windows and, roof hatches are given in the sketch on page 2B~The sprinkler system employed, in the tests is a standard.arrangement of 2~standard.spray sprinkler heads (8 in.belov the ceiling)on 10 ft by 10 ft spacing.There are 4 heads on each of 6 branch 11nes sll supplied by a single | I I | ||
<<pro<<<<a known discharge pressure at the head, incU.cated in the sketch on 0 Cl Air temperatures 8 in.below the ceiling at.the.@locations shown in.the diagram'on Appendix Sheet 1 vere measured.by thermoiouples (20 gauge, chromel-alumel), The temperature of the concrete floor+was also measured by the same type of thermocouples imbedded 1 in.below its surface at locations shown on.Appendix Sheet 1.In order to evaluate the effect of fire.exposure stncL protection on exposed.steel structural members a steel test structure%ms erected in the building.Its construction and" location:are illustrate 1n the sketches on AppencLix Sheet 2 ancL page 20, The temperatures at 24 1@ations on this structure vere measured.during, the tests by 20 gauge CA.'@hermocouples imbedded l(10 in.deep in the steel.Msgrams on AppencUx Sheet,'5 show the locations of the thermocouples. | I I | ||
A means of'easuring rate of flame.spread.was.provdded by placing labeled firebricks standing on end.on the floor at 5 W:intervale. | I I | ||
racially from the 1gnition point in the point source ignition tests;The time at vhich the flame front reachecL these markers was recorded.by observers during the tests'ince the tests.vere to sinniLste normal temperature'conditions | I | ||
'at the gaseous-diffusion plants,.a means vas providecL to.heat;the..Moor, of'he test area to at least 1/0'efore each test and, to heat the.oil to at: least | ~ cl I | ||
aj I I I | |||
temperature and spiU.ed.on the floor of the test area through a distribution system consisting of"..'.'.:.-!"g..~",."-.a.Perforated. | 5 f4I I J I xh I IISCV SCIOCEQ 41r//r swlloaIIII I iNxxixa i Ts, I | ||
pipe (X-l/0 in.)located..along.,the east.and vest ends of'the floor and containing | I I | ||
>/16 in.diameter holes 1 ft on, centers.The oil was pumped.from the.heated..oil, storage tank to this piping. | I I | ||
~ | I Sl I | ||
I I | |||
the burning character-' | 0 0 0 J'c I | ||
istics of'he oi1 and the vtsib1e effect of sprixQ~r discharge vere recorda4,.by observers. | I loco EI I I | ||
The temperatures of'he floor, of the air at the ceiliug and:,, of the steel test structuxe vere recorded.by instruments. | QO GOSIOICf OSSTIS I | ||
5, SprizQQar discharge vas either automatic (natura1)or maxnm1 (by.'.opening a valve suppXyiug open heads)depeuiiug on the individua1 test xecLuirements. | I LEGEND CCCt:XII3 I I | ||
In a33.cases the discharge.pressure vas controllecL. | I CCCIXZD I rl I | ||
C..Test Conditions aucL Resu1ts (TabuXations. | I I | ||
of the test conditions encL.~.observations axe incZxldecL in the AppencUx of this reporh (Sheets 22 and.2g).'he foXXovtug descriptions incXude caQy'he essentia1 inf.'oxmatXon.):.: | I ga 'Ta sI I I | ||
Test 1.I | I aaaa aa aaa Il raLJ I | ||
open spriu3Qer heads vere u'sed | ~ fwf srsNQls sIssk ra | ||
: s. s I 1 cl I | |||
I I | |||
I I | |||
I I | |||
I I | |||
RFolCgee( Z -QI I I | |||
I I | |||
I I | |||
I I | |||
I TVRKEY PONT kICLEAR IIkTIS 3 Js d FLORIDA POWER 64 UGHT I | |||
I FIRE PROTECTION FIGURE I (L-98-TS3) | |||
;GROUND FLOOR PLAN "EL 18'-0 6( BELOW I I | |||
I 5 | |||
I 7 8 s~sa.- | |||
~sa. a | |||
II | |||
' 0 r | |||
ly 1 tp II II 4 I II I. | |||
~1 '4114 em ri II II IP4PC | |||
=- ill I | |||
II I-.--Adj | |||
$ 14 41 ~49 j)'t I il' I | |||
I, I'- | |||
2 3 ~ '4 c 9sc 35 34 3T.s 32 gsl I | |||
3D s | |||
28 27 20.1 26 ~ u.s Lt~AV@~I- Epos 25 I | |||
"8 P !!"24~ | |||
I | |||
~ I 0" | |||
I ii I si I ii ii I II i I ii I ii I I I | |||
I I | |||
I ii I I ii si I | |||
I I | |||
Lm Ci smaasZ I iI si I | |||
II I | |||
i I EZZZE a. EZZSVnENZ I | |||
ii Ii I I | |||
I I li I I | |||
II I ii I | |||
I I | |||
'l; ii I I li Is | |||
)I si I | |||
II I is si I I i I A I | |||
,I I | |||
QB 9 I | |||
l ljL c Is I I | |||
l,. -,( I Esl 3' | |||
c I i[, c I | |||
t Qn 3 I | |||
I QI I | |||
I I NIC>>>>>>>>>>>>>> el | |||
-~J'c C3 C3 C3 l | |||
LEGEND: | |||
<<>>>>>>>>>> MEES0LAC SONCNRT ! | |||
T~ | |||
I 2 | |||
I PLAN MEZZANINE LEVEL EL. 30'-0" | |||
'tVnae sec @z-oZ TURKEY IAONT NUCLEAR VNT$ 3 R 4 FLORIDA POWER dE UGHT FIRE PROTECTION FIGURE 2 (L-98-153) | |||
MEZZANINE LEVEL ELEVATION 30'-0 c4 4 l | |||
0> ((') Q h1 1 | |||
ll lf t | |||
il I | |||
E E | |||
'I | |||
5 D J'c I | |||
I I | |||
I I I @pamvt~K CMRATOR I | |||
I REHEAT MO51URE | |||
- + I SEPARATOR (ITP.) I TURBINE t SEse I | |||
! A~So Apggabt()) on goerture Card I 1 EXSTNO | |||
! !!F1 4IMH III I ARE !WE-IAO I I TEEOWATER HEATER (AP. VN 441411 j I:.I:-I;i':I:.II I)1I.-:NIXI.; | |||
I I I | |||
I wuv (OR& SHGOS) I HOUR 770 NORAOE BARR6! | |||
4IIII7 I ~ .~ . | |||
~ 11 ~ ~ ', 'I ~ | |||
41 40 SWITCHOEAR ROOM I | |||
OL SPEL ~ IWIP4 $ 4454 Q BERM I | |||
4 | |||
~ .. 4 | |||
~ 'A I 4'HK. BECK PIAlE EL | |||
~ | |||
2'-6'OTES: | |||
: l. I | |||
: 2. 25 ICNUIE | |||
~ | |||
HOUR RAlEO ARE COLWM RATEO BARR65 WIIH AUTOMABC SPRSXIEK BETWEEN A% BI TK PUMP PIT. | |||
!NE BARRKRS WllH AUIOMATC SPRNXLERS. I I BGWIEH COWMN EM I Oi. SPLL'- Oa. POOUNC | |||
: 5. 25 !CHUTE PATED ARE BARR65 BEIWEEH COWMN J-4'C I I | |||
='.."--'; | |||
~50M! i;."=-.", | |||
TURKEY POINT NUCLEAR UH!T 4 WWE OL INC PROKCTIW FIGURE 3 (L-98-153) | |||
@PL f | |||
.II | |||
I ,,)) Cu) r "l | |||
Il 1I | |||
't C | |||
I 3P6B 3P6C 3 6A 4160V SWITCHGEAR I | |||
I I | |||
CONDENSATE PUMPS I | |||
I P,p ~ye CSI 8 3K1966-4" 11'-3 I | |||
L.P. FEEDWATER HEATER 3E3A CV O | |||
PB 7340 I O I O O I I O O O L.P. FEEDWATER HEATER 3E3B W Y) 3A1397-1 1 2" | |||
3K 2020-4" 3K2021-4" 3K2022-4" 23 PB 34'-(P 3809 I I O | |||
cV O CD 15'-0" TURKEY POINT NUCLEAR UNIT 3 | |||
@PL FIRE ZONE 084, 088 8( 105 24 1 HR THERMO LAG UPGRADES PLAN I EL.18'-0" VARIOUS CONDUITS It'. PULL BOXES 8( EL.30' 0" DWG NO FIGURE 4 (L98 153) sHW 5 0 | |||
~(i 'I | |||
), E l | |||
a4'132. 32 DN TO EL 2'-8'0. 30 8-4A1 357 4A1372 APlEFITG CARE 4P6A 4A1369 4P6C P84874 18x32x44 4A1370 4A137'I 4160V SWITCHGEAR P84875 OONOENSATE PUL'PS 18x32x38 4JI 776 24x24x8 O'-'0'-4K1411 8-4K141 8-4A1357 B-4AI357 I | |||
CV 3K1724-3" I.LP.B.. )K1232 4K1232 4K1212 4K1212 | |||
'PF.W. | |||
E-1 HTR 4DA | |||
. 4'-0' 4K1421 4K1417 | |||
. 4K1421 4K1417 2'- | |||
5 I | |||
7'-9 zO 6'-0'ONDUITS V) BROW E!8f.18'-0'J1775-3'4 4A1 49 1 4 PB5491 PB4713 4J1838-1'A1417-1 4JI MB-I LPF.W. IITR 4E38 I 2 -4 4 -1.'I 4KI441-4 4K1441 4 TURKEY POINT NUCLEAR UNIT 4 FIRE ZONE 079 8( 105 1 HR THERMO LAG UPGRAOES V'IOUS CONDUITS 8c PULL BOXES EL.30' 0", 18' 0" 8c BELOW DWC NO FIGURE 5 (L98 153) REV IIEET 1 A 0 pbn004eh I A.DWG | |||
Py G Cu) . | |||
(~)- | |||
f V | |||
BL'TURY MUTUAL RHSEARL'H L'URPURATIUN '" " -"'FM C | |||
ll5l BOSTON-PROVIDENCE TURNPIKE, NORWOOD, MASS. | |||
September 9, 1957 FIRE TESTS OF AUTGMATIC SPRXIGKZR PROTECTION FOR OIL SPILL FIRES I XFKOEUCZIOH AHD ABSTRACT At the request of the United. States Atcmdc Energy Commission, the Factory Rxtual Research Corporation has concLucted, a series of'ire tests at their facilities at Norwood, Massachusetts. The purpose of the tests vas to learn if automatic sprinklers vie. protect buf3cUngs, such as the Commission's gaseous diffusion plants, against fire 'in lubricating oil accidentally spi33ed on the floor. | |||
Fire tests vere made involving oil, at elevated, temperatures, covering 2100 sq Xt of'1oor, also at elevated. temperatures, and. employing various methods of'gnition. | |||
Xn a11 of the tests the f'loor fires were cLuickly controlled ancL minimized and the test building vas satlsfactor~ protected. by sprinkler discharge. at relatively lov pressure. In the fifth test an oil spray dis-charging from a nozzle above floor level provided an auxiliary fire against which the building vas protected. by lov discharge from the sprinklers. The spray fire vas'not extinguished in this case ancL a steel structural member ac/scent to it vas not protected. against severe local exposure. | |||
It is.concludecL that the Atomic Energy Commission's gaseous cLfffusion plants can be satisfactorily protected. by automatic sprinklers. In the case of. floor spill'ires alone', protection would be complete against general and indiyicLual structural failure and against involvement of insulated. metal deck roof'onstruction. In'he event of additional fire in oQ. spraying from | |||
. rupture'd. equipment,'eneral structural protection voulcL be maintained of insulated metal deck roof construction vould. be prevented.; and.'nvolvement Failure of incLLvidual structural members could. occur in this situation if such members were so located. as to be exposecL severe by the fire in the ~ | |||
oil spray. | |||
.The principal obgectives of the test program were based. on fires in lubricating oil spilled. on a level concrete floor, with both oil and. Moor FOR BETTER PROTECTION OF INDUSTRY | |||
0 0 | |||
~ 2w at temperatures which vould be expected in a typical gaseous diffusion plant. | |||
: 1. To determine rate of flame spread. radially from a local ignition source vith no fire protection. | |||
2 To determine the minimUm practical water discharge density from a sprinkler system required to control and. to extinguish an oil spill fire To obtain vith our test facQ.ities informstian vhich vould. lead. to a conclusion as to the effect of ceiling height araund, the order of 50 feet in bringing about any significant 'delay in operation of autamatic sprinklers. | |||
To determine, vith snd. vithout sprinkler protection, the effect of an oil spill fire directly exposing structural steel in bringing about excessive stee3. temperatures.snd. in causing elevated. ceiling temperatures. | |||
L- | |||
: 5. To obtain from test results information vhich, combined. with previous test experience snd. )udgment~ m1ght lead to an inte23.igent estimate of the number of sprin3Q.er heads which might operate due to an oil fire, so as to assist in the design of an effective automatic sprinkler system. | |||
: 6. Another obgective vhich vas developed during the test program vss to determine vhether a fire in hot lubricating oil discharged at a sub-stant1al rate .in the. form of an elevated. spray could be extinguished. or controlled, by.sprin3Q.ers vithin the range of ordinary discharge densities, and. | |||
temperatu'res. | |||
'hqt the effect would. be af' Sire of'his type on ceiling and. exposed. steel | |||
'.'f I e | |||
'.5 III TESTS A. MethoA | |||
\ | |||
All of the tests very conducted in the high ceiling area of'he fire building illustrated by photograph'nd, sketches an. pages 2k~ 23 snd 'est 2C. This area measures 40 ft by 60 ft by $$ ft high and. Cs equipped with a smooth level- concrete floor. It hss protected. steel frame construction, 12 in. brick va'.Lls, and a vermiculite plaster'n metal lathe ceiling suspended, -., | |||
', from steel beams vhich also support a.poured. concrete roof. The locations and. | |||
sizes of doors, windows and, roof hatches are given in the sketch on page 2B ~ | |||
The sprinkler system employed, in the tests is a standard. arrangement of 2~ standard. spray sprinkler heads (8 in. belov the ceiling) on 10 ft by 10 ft spacing. There are 4 heads on each of 6 branch 11nes sll supplied by a single cross main. The cross main is fed. by a riser gust inside the vest vali of | |||
<<t the test area, vhich in turn is supplied,.by underground, piping from the pump In all of the tests the vater supply to the sprinklers was controlled. | |||
<< pro<<<< a known discharge pressure at the head, incU.cated in the sketch on | |||
0 Cl | |||
Air temperatures 8 in. below the ceiling at. the.@locations shown in | |||
.the diagram'on Appendix Sheet 1 vere measured. by thermoiouples (20 gauge, chromel-alumel), The temperature of the concrete floor+was also measured by the same type of thermocouples imbedded 1 in. below its surface at locations shown on. Appendix Sheet 1. | |||
In order to evaluate the effect of fire. exposure stncL protection on exposed. steel structural members a steel test structure%ms erected in the building. Its construction and" location:are illustrate 1n the sketches on AppencLix Sheet 2 ancL page 20, The temperatures at 24 1@ations on this structure vere measured. during, the tests by 20 gauge CA.'@hermocouples imbedded l(10 in. deep in the steel. Msgrams on AppencUx Sheet,'5 show the locations of the thermocouples. | |||
A means of'easuring rate of flame. spread .was.provdded by placing labeled firebricks standing on end. on the floor at 5 W :intervale. racially from the 1gnition point in the point source ignition tests; The time at vhich the flame front reachecL these markers was recorded. by observers during the tests'ince the tests. vere to sinniLste normal temperature'conditions 'at the gaseous -diffusion plants,.a means vas providecL to.heat;the..Moor, of'he test area to at least 1/0'efore each test and, to heat the.oil to at: least spiLLed on the floor; 165'hen | |||
: 3. Procedure The essential features of all fire tests vere. the" sama. They vere: | |||
: 1. The,. floor vss heated to a specified. temperature | |||
: 2. Dxbricating oil (see Appendix Sheet 0 for properties) vas heated, to a specified. temperature and spiU.ed. on the floor of the test area through a distribution system consisting of". . '. '. :.-!"g..~",." -. | |||
: a. Perforated. pipe (X-l/0 in.) located..along.,the east. and vest ends of'the floor and containing >/16 in. diameter holes 1 ft on, centers. The oil was pumped. from the. heated..oil, storage tank to this piping. | |||
~s 4 | |||
: b. 3rain connections (2 1n. pipe) carrying. oi3.'y gravity heacL C | |||
from the heatecL oil storage tank to two points on the floor at its south side approximately 15 ft from the east and. vest ends. | |||
Three hundred, and fifty gaLlons of oil vss spiX3.ed on the floor in each test except the last. This gave'a depth of 1/4 in. over the 2100 sq ft of level floor in the test area ("EK-Sect." frame area, 2400 sq ft, less wall thickness areas, drainage trench ares and. ramp areas equals 2100 sq ft). Tjrpical total t1me to spill $ 50 gallons of oil was 4-1/4 minutes. | |||
~ | |||
OB/ll/97 WED OB:38 FAX B17 551 9775 HEC STANDARD DIVISION Q 002 | |||
~ ~ | |||
$ Th oi1 wm ignited. (NethocL anC location for each test are describeC under "Tests". ) | |||
Fol3.owing fruition the rate of flame'spread~ the burning character-' | |||
istics of'he oi1 and the vtsib1e effect of sprixQ~r discharge vere recorda4, . | |||
by observers. The temperatures of'he floor, of the air at the ceiliug and:,, | |||
of the steel test structuxe vere recorded. by instruments. | |||
5, SprizQQar discharge vas either automatic (natura1) or maxnm1 (by.'. | |||
opening a valve suppXyiug open heads) depeuiiug on the individua1 test xecLuirements. In a33. cases the discharge.pressure vas controllecL. | |||
C.. Test Conditions aucL Resu1ts (TabuXations. of the test conditions encL .~. | |||
observations axe incZxldecL in the AppencUx of this reporh (Sheets 22 and. | |||
2g). 'he foXXovtug descriptions incXude caQy'he essentia1 inf.'oxmatXon.):.: | |||
Test 1. | |||
I The 'primary puxpose of the first test vas to determine the rate | |||
~ / | |||
I at | |||
.and. | |||
vhKch fire spreads ih the oQ., | |||
~ | |||
the vater supply vas vithhe1C fire spread: | |||
~Therefore~ open spriu3Qer heads vere u'sed them until ~F3, observation of become.'impossible so that aXI. possibXJe data .an'uninhibited,. | |||
spread''of fire'in the oil couXK be obtained,; | spread''of fire'in the oil couXK be obtained,; | ||
The temperature of the oil vhen spiXXe'd.on the f1oor vas 165 to I.70>I and.the temperature of the'loor vas 1?g vixen the oQ.vas'%gaited. | The temperature of the oil vhen spiXXe'd. on the f1oor vas 165 to I.70>I and. the temperature of the'loor vas 1?g vixen the oQ. vas '%gaited. | ||
at'ibont.16 min'and.conti at an acceXerating rate.This rate is.iXXustrated by the graph on Appe'.Sheet 5 vhich is a plot of the data.xecordeC by" four.observers. | I fix& vas started. in the oi1 at the-base of the stee1 sCxucturi's'." | ||
I'I Mhon the radius of the burxd~area had.increasek to 15 ft the air: temperature at the ceiling vas at 1200'nd.'increasing@ | ~ | ||
rapicQgr.Therefoxe~;., vater vas supplied to the spriu3Qers at 20.min~45 see (approx.5 min after'".'he start of fixe spzeacL)at a co'ntroIXed pressure of 5 psi at the heads | ~ | ||
Cl 5I J r | A central columnby four gas'oline-vet ceXXucotton ignitors+ 3.ocateL one at: | ||
structure. | each corner of'he column. Because these vere'3'.mr t'o start the oi1 b a handful of excelsior vas addeC at tvo of the coruers at 15-1/2 min after the original ignitors vere XfghtecL. | ||
This fire could.have been completely extinguished by continuecL sprinkler discharge.but in orcLer to prevent heat loss from the floor to..the sprinkler water, vhich voulcL delay preparation for the following test, the sprinkler vater supply was turnecL off and.the lingering fire extinguished by a 1-1/2 in.hose spray nozzle g-g/0 min after the start of sprinkler dischirjg. | ~ I in the oi1 vas established. at 'ibont. 16 min 'and. conti ZLame at an acceXerating spree!. | ||
+ | rate. This rate is.iXXustrated by the graph on Appe '. | ||
""used, in the first test.Standard,, upright, 212'eads were used.."..\\~ | Sheet 5 vhich is a plot of the data. xecordeC by" four. observers. | ||
onto the floox'as.170,,to | I ' | ||
of,a.cLuantity of commercial oQ.-absorbent | I Mhon the radius of the burxd~ area had. increasek to 15 ft the air: | ||
'".~edi-Dri.") | temperature at the ceiling vas at 1200'nd.'increasing@ rapicQgr. Therefoxe~;., | ||
at each'orner of the column;the saturated..oil-'absorbent.. | vater vas supplied to the spriu3Qers at 20. min~ 45 see (approx. 5 min after'".'he start of fixe spzeacL) at a co'ntroIXed pressure of 5 psi at the heads ft). | ||
being ignited by 1/4'size gasoline-vet cellucotton ignitors.;This also.resulted'in a slov start ancL fire vas not established. | gp /se These igtdtors consist of roXXs (2-$/4 in. ~quoter, 6 in. Xong). | ||
in the oil until about 18-1/0 minutes.However, the usual accelerating flame'spread rate folloved.'\The first automatic sprirQQer operated.17 sec after the,,burning area''"''acL grown to a racUus of 5 ft (19 min~57 sec after the'tart of;the test)'arid.several.additionaX heads.operated quickly thereafter'.-,.'(Spr'i'nkler. | of 20 ply cellucotton vatMing each veightug 2-1/0 ounces, dxy. '."As,,"; | ||
""-'ontxo3.pressure was 5'ps'."~,lg gpm/sq, ft cU.scharge densit'y.'.).;-, The maximum observed.fire spread.racUus was 6 ft at la'sec aftex the.first heacL opened but the fire vas knocked down and.reduced.;to a lingering flame at the base'of the steel structure one minute after the fix'st-head opened..Again, in.order to preserve floor temperature, the sprinkler water supply vas turned, off ancL the lingering flame extinguished by hose stream at 25 minutes. | .used. in these tests they contLLned 6-$ /0 ounces of gasoline each~ | ||
0 Ci 06/ll/97 WED 08:39 FAX 617 551 9775 HKC STANDARD DIVISION Ql 005 | in the roX1+ 'bsozbed | ||
operation of the'printed.ers. | |||
Test 3. | Cl 5I J | ||
5 upper iriadcnr units on the south.'and vest aces'f the<<EL~Sects vere opened before the test in excess'f'the tvO hit'ch opentngS used in Te'st 2.The teal.ventiLatkon area vas.16I.'Q r Xa@hUtion the ignition method.vas changed.in order to e1iminate the long delzLy in estabIishing burnizlg in the oi1 as exper1enced. | r prevented, a precise observation of the tMe when the fire was Smoke controlled but it was possibly as early as 1/2 min,after the'egging of sprinkler discharge ancL definitily by 1-g/4 minutes. At that time only lingering flame remained along the foot members of'he.stee3.. structure. This fire could. have been completely extinguished by continuecL sprinkler discharge | ||
in the first two te'sos..'.The'n'ev'mthod consisted''of poqring.one.piIIt of a 50-50,mix of gaso11ne-kerosene into thi oil.at epoch corner of the steel structure..E co1umn at'its: bssa.'his pruning f1uid vas ignited.~diately after | .but in orcLer to prevent heat loss from the floor to..the sprinkler water, vhich voulcL delay preparation for the following test, the sprinkler vater supply was turnecL off and. the lingering fire extinguished by a 1-1/2 in. | ||
of the ignition brea vas no greater than in the..'previous | hose spray nozzle g-g/0 min after the start of sprinkler dischirjg. | ||
~tests j,~~ | + | ||
at 5 psi':,Ip-joe/scL ft."': ': The:::teppiiature'.of the oiI when spend on the floor.vas.180 to 155~ | records on Appendix Sheets 6, 7, and. 8 illustrate the .'emperature intensity and. duration of fire exposure to the building and. stee3.'tructure during the'est. r" t Test 2. | ||
'the Moor vas 1~'hen.the o11 vas iga1ted..The.: cei1ing air'temperature was 95'. | The object of the second: test vas to detexmine the effectiveness of sprinklers as compared. to the delayed. manua1.control of'utomatic'opening | ||
~ | |||
Xt shouIC be borne in mind.that the photographs contend in this xeport indicate the conditions existing on1y at the very eaxIy staees of the fire.The very nature of.a lubricating OQ.fire procLuces erat;remedy Iarge votumes of heavy, dense, b1sch smoke{sce photograph on page 2L)prectud1ng the tcQsiag of.p1ctures, stiII, or motion, I~ | d | ||
0 Cl II Test 3-Before sprinkler discharge. | ""used, in the first test. Standard,, upright, 212'eads were used.. ".. | ||
Time-about 1 min., 15 sec.I I (3o6-3)fidius conds'ire- | \ \ ~ ~ w+ ~ ~ | ||
oil temperature | |||
'w 7 shortly after the initial spread, of fire..In fact, the smoke density became so great in from 2 to 5, min after the initial spreacL of fire that visual observation at Moor level was ususl3.y impossible. | ,The when discharged. onto the floox'as .170,,to the temperature of the floor itself vas 1?8't ignition. 'he air temp-175'nd, | ||
ELeven heads opened in this test in the pattern illustrated by the diagram on AppencUx Sheet 21.It is noteworthy that the time recLuired for sprizQQ.ers to operate after fire spread wss established, in the oil vas 2 min in this test compared.with 1-.g/4 min in Test 2.Temperature records on Appendix Sheets 12, 1$, and.14 again illustrate the quick, control of the f1re produced by automatic operation of the spriuklers. | . erature under the ceiling was 105'. Both roof'atches (total'56 sq ft) were opened: at'the time of ignition. | ||
""'est'4." | The ignition. source was located,.at the base of the steel'structure | ||
Under such condi-t1ons s f1ashoyer woulcL,be expected.and.a large area" of'11 would.be burning before heat could'r'esch the ceiling to actuate sprinklers. | ' as in Test 1. but consisted. of,a. cLuantity of commercial oQ.-absorbent t '".~edi-Dri.") at each'orner of the column; the saturated..oil-'absorbent.. | ||
This test also indicates'he effect of s delsyecL vater supply to the sprinklers. | being ignited by 1/4 'size gasoline-vet cellucotton ignitors.;This also . | ||
, Xn order, t*o';,simQate this situation the os.'spill was ignited in six locations.'ancL".avowed to..burn freely while withholding vater from open sprinklers uiiti2: s.,1'arge.'area of o11 vas burning.',Also to simu1ate added.ceiling'eight. | resulted'in a slov start ancL fire vas not established. in the oil until about 18-1/0 minutes. However, the usual accelerating flame'spread rate folloved. | ||
al1'.8 upper vindov units and.'the".Hi<<Sect."roof hatches.were | '\ | ||
the discharge pressure'ss again controlled at 5 psi~.i$gpm/scL..'W.;, At the time'CEe,,ilail was spilled.'on the Moor it vas at 184.The Moor.vss not'heatecL'since its temperature would.not affect the test and.at test time it vas.1094;"~-'pp-gy~'$'~:~pl | The first automatic sprirQQer operated. 17 sec after the,,burning area | ||
'a~<"~'htC". | ''"' 'acL grown to a racUus of 5 ft (19 min~ 57 sec after the'tart of;the test) | ||
'circular burning areas of.increasing diameter resulted.Typical diameter growth was-$ft at 55 sec;7 ft at 3.min, 15 sec;10 ft at 1 min, 55 seconds.Two f1res mergecL north and.south at, 1 min~40 sec and.two more at 1 min, 45 sec at which time the signal for supplying water to the sprinklers wss given.Water actually began dischargiag from the heads at 1 min,$0 seconds. | 'arid. several. additionaX heads. operated quickly thereafter'.-,.'(Spr'i'nkler. " "- | ||
0 0 06/11/97 WED 08:38 FAX 617 551 9775 H{RC STANDARD DIVISION gho04 | it a~'lj X~ | ||
but it vas betveen 2-1/>'nd.4'mtuntes. | I l | ||
During.the period befo exttuguishmcnt fumes'issued. | 'ontxo3. pressure was 5'ps'."~,lg gpm/sq, ft cU.scharge densit'y.'.).;-, | ||
5 to 10 ft out;from the upper s~tovs ancL from the" roof hatches to an udestimated..height. | The maximum observed. fire spread. racUus was 6 ft at la 'sec aftex the | ||
P AIL hesds in the sprinlQer iystem were open at the.cud.Of the'West.Xt vt11 be noted.in the'tImyerature records of this test on A~adix.'". | ~r | ||
Gheets,3,5, 16, and 17 that the:recovering:iaet~msnts" were'oM.fox a pcriocL'od ayyroxima~ | . first heacL opened but the fire vas knocked down and. reduced.;to a lingering flame at the base'of the steel structure one minute after the fix'st-head opened.. Again, in.order to preserve floor temperature, the sprinkler water supply vas turned, off ancL the lingering flame extinguished by hose stream at 25 minutes. | ||
3.monte.This vas eausecL by'the shorting of an actuatixqg circuit by racLiant:heat from the fire.On'the basis of other supporting observations it.is believed that the maximuIn'-temyeratureis vere recorded | A total of 17 heads opened. during the fire period. The pattern of As these openings is shovn on Appendix Sheet 21. | ||
'or automatic sprizQcLeirs to operate''".Reverseless,": | |||
the'.fire vas | 0 Ci | ||
06/ll/97 WED 08:39 FAX 617 551 9775 HKC STANDARD DIVISION Ql 005 | |||
Othei''conjKtioui-as regards.'the OQ.sZii11~'vere the'siiiie is'in Test 3 | \ | ||
sq&''of f1'o'or"area," at..the';east | T~~rature records on AppencLLx Sheets 9, 10, and 11, ccerp~d to | ||
'end of the test are'a,.vas ext:off.;from the'.spill. | ~ I those of'est 1. 111ustrate the rapicL contro1 of the fLre produced by the L automat1c {naturIQ.) operation of the'printed.ers. | ||
area'by" curb's".to.ccuiserve oil'upp', for the sprig Actua~290 ga3.of oil.vs.spiile4.,oa:a,1lt00 sq.ft Q.oor area.The..=temperature:of the OM vhen:spiXled,vas'-.X69'to.3.70 | Test 3. | ||
.'ntL'the floor vas 13.7'.=4 aC igrd,Cion.,..TM oil leehage fire was'shinQati4'.bj"jempihg,ci1'* | Since the cei1ing height in the test brea is Iess than in some areas of the gaseous diffusion p1snts, it vas'esixecL'to phmQate Me effect of bcmed. ceiling.h'eight by provtcLing acM1tioua1 upper ~aM3atiou in Test g.; | ||
a n'ozx1e (open',' | the purpose being to dotexmizN if bn bpp?eciab1c delay iIL oper!LtioIL of automatic sprintQsrs voalcL xesult. Therefoxe~ 5 upper iriadcnr units on the south.'and vest aces'f the <<EL~Sects vere opened before the test in excess | ||
d5ve1'ope.cl in the.usual.fashi.The racK4s'of the'burniug aiea'is 5'W at~3;min'35 sec.aud.it-did not | 'f'the tvO hit'ch opentngS used in Te'st 2. The teal. ventiLatkon area vas | ||
the~st of | .16I.'Q r l ~ Xa @hUtion the ignition method. vas changed. in order to e1iminate the long delzLy in estabIishing burnizlg in the oi1 as exper1enced. in the first two te'sos..'.The'n'ev'mthod consisted''of poqring. one.piIIt of a 50-50,mix of gaso11ne-kerosene into thi oil. at epoch corner of the steel structure. | ||
at I: min~39 sec,'ud" | .E co1umn at'its: bssa.'his pruning f1uid vas ignited. ~diately after so. the..'size. of the ignition brea vas no greater than in the..'previous I 'eering. | ||
Photo-.,:~ | ~ | ||
graphs on.psges 8L auk 83 shcnr the-..femY of the" oQ spray aud.the behavior.fire that deve1oped,.from it.'This fire cansetL aU.of the sprinkler heads to open (yrobabiz by 2-1/2 min)aud,~'althctugh the f1oor fire vas contro1IBC aud.the buQding itself protected'against the exposure from both fires by the 5 psi discharge, the stee3.structure continued. | I V ~ '4 ~ ~ tests j, ~ ~ | ||
to register temperature 0 ll 0 8A Test 5-.Shape of oil spray from.elevated nozzle.(Not burning) | 2.'hat's, | ||
:...:::,'::.':..-;=;--:-(iO7-5) | ~ | ||
N Test 5-Oi1 spray fire after sprinkler discharge began-.'-.. | . ~ | ||
PACTORY MUTUAL RESEARCH CORPORATION Norwood, Mass. | '" Prike'chion'was'the same ar in Test 24. automatic, standard~ | ||
~I!4l (0 | ~ | ||
'uyr'Lght; 212, 'ijz~Qaz'.heads vith the cEscharge pres'sure contro11ed. at 5 psi ':,Ip- joe/scL ft." ': | |||
': The:::teppiiature'.of the oiI when spend on the floor.vas.180 to 155~ | |||
and"the tehipiratuxe'of 'the Moor vas 1~'hen.the o11 vas iga1ted.. The. | |||
: cei1ing air'temperature was | |||
~ ~ | |||
95'. | |||
"A ijgeaQig fire. in the oiI vas estab1ished vithout del'Iy and. the ~us | |||
~ ~ | |||
of. thi bu~g axea reached. 5 ft at I. min, 25 sec azLd 6 The.;i~it 'hixtomatic iyga)Qer operatecL at 2 min, 1;.Sec .at which tiIIL the fire ft I at min 45 seconds area racKus"jrobabg dilL:not exceed, 7 feet. ARLY.onaI heads. ojeratecL at 2'mi@'.7,,sec..'iicL the;.fire vas ahnost compZeteXg extinlpzishecL at 2 min, 20 sea at'ILich'Qm lingua@.'smaII fXames persisted cnQg at the north side | |||
'tre~Ore foCt members ~ of'steel | |||
\ | |||
~ | |||
""9hci.'sZiriihbn'ater was turnecL off and. a 1-I/2, in. hose spaz~ nozzIe uqecL to map-.~"at '> i'dn 55 sec in. Order to preserve. f1oor temperatuxe. | |||
~ ~ '. 7 | |||
'hotographs on" page 6L shciv the behavior of 'this fire before ancL gust I after the first sprinkLar discharge. Xt shouIC be borne in mind. that the photographs contend in this xeport indicate the conditions existing on1y at the very eaxIy staees of the fire. The very nature of .a lubricating OQ. | |||
fire procLuces erat;remedy Iarge votumes of heavy, dense, b1sch smoke {sce photograph on page 2L) prectud1ng the tcQsiag of. p1ctures, stiII, or motion, I | |||
~ | |||
0 Cl II | |||
Test 3 - Before sprinkler discharge. | |||
Time - about 1 min., 15 sec. | |||
I I (3o6-3) fidius conds'ire-Test 3 - Just after initisl sprinkler discharge . | |||
) sec', | |||
S le ust e | |||
Zy oil | |||
;on, (3O6%) | |||
"~TORY MJZUAL RESEARCH CORPORAT1ON Report No. | |||
Norwood, Mass. | |||
9, 1957 13434'eptember | |||
0 0 | |||
'w 7 | |||
shortly after the initial spread, of fire..In fact, the smoke density became so great in from 2 to 5, min after the initial spreacL of fire that visual observation at Moor level was ususl3.y impossible. | |||
ELeven heads opened in this test in the pattern illustrated by the diagram on AppencUx Sheet 21. It is noteworthy that the time recLuired for sprizQQ.ers to operate after fire spread wss established, in the oil vas 2 min in this test compared. with 1-. g/4 min in Test 2. | |||
Temperature records on Appendix Sheets 12, 1$ , and. 14 again illustrate the quick, control of the f1re produced by automatic operation of the spriuklers. | |||
""'est'4." | |||
The purpose,.ofthi.s test.vas,to determine the action of sprinklers against s.fire. that might occur in a large spill of'oil't or near its flash point or'with'simiLtaneous ignition in several. locat1ons. Under such condi-t1ons s f1ashoyer woulcL,be expected. and. a large area" of'11 would. be burning before heat could'r'esch the ceiling to actuate sprinklers. This test also indicates'he effect of s delsyecL vater supply to the sprinklers. | |||
, Xn order, t*o';,simQate this situation the os.'spill was ignited in six locations.'ancL".avowed to..burn freely while withholding vater from open sprinklers uiiti2: s.,1'arge.'area of o11 vas burning.',Also to simu1ate added. | |||
ceiling'eight. al1'.8 upper vindov units and.'the ".Hi<<Sect."roof hatches. were open. "Total;upperventilation area.vas 224 scL W. | |||
The.,sprhdQerheads vere, in effect,=-all open for this test. Actually the 11 he'ada'"open after Test g. vere open snd. the. remaining 1?j heacLs un-doubtedly fused before vater was supplied. to them. They were all 212', | |||
standard upright. heads,.and. the discharge pressure'ss again controlled at 5 psi ~ .i$ gpm/scL..'W.;, | |||
At the time'CEe,,ilail was spilled.'on the Moor it vas at 184 . The Moor.vss not'heatecL'since its temperature would. not affect the test and. at test time it vas. 1094; | |||
" ~ -'pp-gy~'$'~:~pl 'a~ <"~ 'htC". ", | |||
The,oil, vas ignited by tipping contaiiers of burning priming Muid into it 'aW 6.'Xocati'ons,'s1multsneous3y; There vss 1 pt of $ 0-$ 0 gasoline-kerosene mix.'n:.each., container ancL they vere located. in a symmetrical pattern 20 ft on'centers.'ix | |||
'circular burning areas of. increasing diameter resulted. Typical diameter growth was-$ ft at 55 sec; 7 ft at 3. min, 15 sec; 10 ft at 1 min, 55 seconds. Two f1res mergecL north and. south at, 1 min~ 40 sec and. two more at 1 min, 45 sec at which time the signal for supplying water to the sprinklers wss given. Water actually began dischargiag from the heads at 1 min, $ 0 seconds. | |||
0 0 | |||
06/11/97 WED 08:38 FAX 617 551 9775 H{RC STANDARD DIVISION gho04 At that time the total burning, area vas estimated to be 1lgp sq ft or | |||
. mately.2/3 of the .vhoIe Oil surface. Because observers vere for~d ~'o precise observation vas made'f the ext~piiehed. but it vas betveen 2-1/>'nd. 4'mtuntes. During.the period befo exttuguishmcnt fumes'issued. 5 to 10 ft out; from the upper s~tovs ancL from the" roof hatches to an udestimated..height. | |||
P AIL hesds in the sprinlQer iystem were open at the.cud. Of the'West. | |||
Xt vt11 be noted. in the'tImyerature records of this test on A~adix.'". | |||
Gheets,3,5, 16, and 17 that the:recovering:iaet~msnts" were 'oM. fox a pcriocL ' | |||
od ayyroxima~ 3. monte. This vas eausecL by'the shorting of an actuatixqg circuit by racLiant:heat from the fire. On'the basis of other supporting observations it. is believed that the maximuIn'-temyeratureis vere recorded the. pcwer faille. l | |||
'efOre I I | |||
;:Ruin water vas sugp1ied to the spriiQchpm.'.the cei1ing temperature' This 'shcnrs that vater,was withheld"beyoiad'the'time noxma11y'equirecL I | |||
'or 12tXl automatic sprizQcLeirs to operate''".Reverseless,": the'. fire vas | |||
[i .control qui~ vithcnrt.'si~Ig:effects'.t'o'".the'i1ildtug. ~ | |||
broulgt'-;>'under | |||
'.c' C I | |||
I E | |||
;,.The.'oligect of;~ test vas:4o":deCeimIiu'e the'effect of an addition.::.> | |||
fire'uch 'as might occ'ur in oil:s3jea;yea j"from'@upturn:ecgxipment. Othei' ' | |||
conjKtioui-as regards.'the OQ. sZii11 ~'vere the 'siiiie is 'in Test 3. | |||
sq &''of f1'o'or "area," at..the';east 'end of the test are'a,. ex'..'that:aZyrhximstelg.7pO. | |||
vas ext:off.; from the'.spill. area 'by" curb's".to.ccuiserve oil'upp', for the sprig Actua~ 290 ga3. of oil.vs. spiile4.,oa:a,1lt00 sq .ft Q.oor area. The..= | |||
temperature:of the OM vhen:spiXled,vas'-.X69'to.3.70 .'ntL'the floor vas 13.7 '.=4 I ~ | |||
aC igrd,Cion., | |||
~ t. | |||
~ | |||
c > | |||
.. TM oil leehage fire was'shinQati4'.bj"jempihg,ci1'* a n'ozx1e (open', | |||
' I' '"Autcmatic" ~6003~ SSU.head. vfth .316..tajjyxed'orifice) located 12 ft p | |||
~ | |||
above. the f1'oor axe'2 W sautheait"of.the atI6e1'. structure 2-column. Pumptug. | |||
to this. overhead, nozzle,:at.a rate"of XQ'"S ".gym~. vai begun 'at 3. min, 23 seo | |||
~ ~ | |||
l l'. | |||
,:aft;ei.the Moor fire vas started".'"" '+'"""" '-"''"" | |||
I! """-':A's far as the;f1oor'iria vas conc~4"iC. d5ve1'ope.cl in the .usual .fashi I'i | |||
.The racK4s'of the'burniug aiea'is 5'W at~3; min '35 sec. aud. it- did not | |||
& mcept lnenenta~.:Xt vas'.'cofrtrolZAd.by'the .sprinhXers> the ~st | |||
~4 of 6, | |||
it | |||
~ | |||
at I: min~ 39 sec,'ud" vas ndzdmised in less than p mizuxtes. 'ch,.operate8. | |||
The spray fixe, on the other hiud, cou1d;"uot be extinguished.. Photo-.,:~ | |||
graphs on.psges 8L auk 83 shcnr the-..femY of the" oQ spray aud. the behavior . | |||
fire that deve1oped,.from it. 'This fire cansetL aU. of the sprinkler heads to open (yrobabiz by 2-1/2 min) aud,~ 'althctugh the f1oor fire vas contro1IBC aud. the buQding itself protected'against the exposure from both fires by 0 the 5 psi discharge, the stee3. structure continued. to register temperature | |||
0 ll 0 | |||
8A Test 5 -.Shape of oil spray from | |||
.elevated nozzle. | |||
(Not burning) | |||
(3O7-a) | |||
<<ay Test 5 - Oil spray fire before hanoi sprinkler discharge. | |||
:ceed (Spattering in oil on f3aor is from unburned oil falling '; 'Y. | |||
from spray .fire .) | |||
;es .. | |||
\s (3O7-4) | |||
~ACZORY MUZUAL RESEARCH CORPORATION Report No. 13434 Norvood, Mass. September 9, 1957 | |||
0 | |||
:...:::, '::.':..-;=;--:-(iO7-5) | |||
N Test 5 - Oi1 spray fire after sprinkler discharge began-.'-.. | |||
PACTORY MUTUAL RESEARCH CORPORATION Report No. 13434 Norwood, Mass. September 9, 1957 | |||
~I! | |||
4l | |||
( | |||
0 | |||
C in the range from 1400'o 1800'. Therefore, the sprizQQ.er cLischarge pressure was increased. as follavs: | |||
At 3 min, 20 sec pressure to 10 psi = .19 gpm/scL ft density At 5 min, 0 sec pressure to 15 psi ~ .2?i gpm/sq ft density At 5 min, 30 sec pressure to 18 psi I .25 gpm/sq ft density At 6 min, 45 sec pressure to 28 psi -" .31 gpm/sq ft density | |||
'At 8 min, 0. sec pressure to 38 psi ~ .36 gpm/sq ft density This increased vater cLischarge prevented. further increase of. the 'steel structure temperature but it cU.d. not reduce the temperature. | |||
~ | 10 min the oil supply to the overhead. nozzle was shut aff'. Al3. temperatures Theref'ore, at (See Appendix..Sheets 18, 19, and. 20) decreased: quickly and. the sprin3Q.er vster vss shut:off at,l3-1/2 min vith the usual mop-up by hose sCream. | ||
XF COKCLUSIOHS'.. | |||
: l. Once ii .~erg ., | |||
~ | |||
a fire | |||
~ | |||
has been establishecL and begins to spread, beyond. the ignition source~ the rate of flsme spreacL is relatively, rapid, ancL increases as the f'ire progresses. It requires about 1-1/2 to 3.minutes (depencLing upon strength of'...ignition source) to spread. Co a radius between 4 and. 5 feet, about 1-1/2;minutes from 5 feet to 10 feet racUus, and. only about 30 seconds far 10 feet:;to.-15. feet.racUus. (gbservstions..beyoncL about 15 to 16 feet could naC;be made, in our tests on account of loss. of'isibility due to smoke.) | |||
: ~ <<'> I'>iV'V ~, | |||
Once an oil spill has been i'gnited and. sprescLing of'lame begun, the rapicL.grovth:of fire and volume of. smoke.produced. indoors is such that effective:manx'.fire.fightiag can only be done within a period of about 5 or possibly::.6!minutes::fram initiation af'preacL,- | |||
: 2. Autamatic spriaklers vill stop the spread. and. extinguish the fire in. an oQ. spiLl. on the floor at s cEscharge density of '0.13 gpm/st fC, - vith some margin: of".safety. | |||
'::,3.='.There vauld.be no serious delay in operation of automatic sprinlQers at an:elavatiaa;,of about 50 or 60 feet fram a floor spill fire in a. large ares. as.-camparecl"to results in the .test building-with a 33 f'oot ceiling height:.with'no upper ventilation. The delay in, operation vou1d. be about 15 seconds'.representing:an.increase in fire radius. of. from about 6 feet to 6-2/3 feet;-=-",: ~,.: | |||
With a floor spill fire around a building column but with autamatic sprinh1er:protection, the results incU.cate no temperatures which would. | |||
result in;failure of'tructural steel. However, serious cLKstortion and. actual column failure woulcL be expectecL within a periocL less than 10 minutes without automatic spx ia3d.ers in service. | |||
Where oil msy be cU.scharged. in the form of a spray at an elevation above floor level, vhether or not there is initially any substantial oil | |||
~ I | |||
~4 | |||
Cl 06/ll/97 WED 08:40 FAX 617 551 9775 HEC STANDARD DIVISION Coos | |||
-lO- | |||
~ | |||
f spill. on the floor, a fire under these conditions may bring about failure | |||
;l of exposs4 steM. in the ~diate vicizdty of the fire. The 4ischarge. fzam il automatic'zllQAikrs at any JZRchicaI density may not s&tinguish the Egc'ay There is no other econond.ca3~.X0Lacticable automatic means avaILlable vhich vtl1 extinguish such a spray fire at any one of 'a | |||
~ protection large nLuLLber of ~ssible locations;distributed. over: a, vids area, even it vere considere4 necessary to extinguish. | |||
if j t | |||
~ | |||
~ | |||
i Eovever, automatic sprin3QersI even at f?e~g.pressures as 1mr as ) | |||
5 psi.," vtll affor4.reliable fire cozztroI. by.:limiting dangerous.temrperatures | |||
~ ~ | |||
for 'both structmM steel an4 roof aeeas to a:location of reIativeIy saaQ3. | |||
radius laterally fraa the oil. @prajr.f$ re.. CcaisequentIy, for. as long as sprixQQer diochILrge can be maintainecL; serious damage ahau14 be vel3. | |||
localiea4. | |||
'I | |||
: 5. Our tests indicate that, <trLth an.oi3. spi13. fixe. on the floor and..a single small 'igzLition source not over'2:.to "g.ft, in iRiameter,.the zzumber sprtulzlers vhich might be.-.expeete4 to. Operate 'vhen sayplie4 at of.'automatic 5 psi pressure mnzl4 probably ncrt: cmcee4'5:heads.. Even uzLder scauavhat unfavorable conditions 'of tzLterference vith'SIzzizdrler distribution by piping or. BtrucQzriLL elements no mare than 20'heads voul4 be expeete4 to. cyen. | |||
Xf a Sire sholQ4 Start &ncl.spg8acL~M'81L oil. BQQ3: fire. izLVQlvi37g hLuuhe4'gallons of oil vfth'hai'.+alee".sipply to syefa1Qers 'shzLtoff,'. 'everal large numbers. Of heads .voul4 be expee4edhC'o-OIpen so.that the-vatex dis'charge.~ | |||
48nsity follcACEg delAQ&4 rcstorzztiozL'.:.of Water.Guppy+ Right bc.. reduced to '. | |||
a totally ineffective value. -..':~ .'Q. | |||
'll | |||
+. <',i~=;.~.,'.' | |||
" 'C ~ ~ | |||
~ ~, | |||
It is diffi.cult to esMmate..the zzauiber. of"sy~Qer be. aperate4 | |||
:h t ! '!C '-~i', | |||
in the event of a cou6~aus-veil distributed. | |||
I heads.vhich zmfght Sino oil spasm | |||
.of previous oxperienco is that gaia:idjjzt'.".'exjeet the znnaber of heads t'0 be oyens4'eventuzk1g veLM be 'in the40rCklr"of-'.frcmL 40.to .6Q heaCS: fox. an oQ. | |||
sjumgr arcnzn4 '10 gpaL,'. an4 for'arger .cIMIgney"-. 4ischarge. rat4Ls a; c'cexeipondi gxeater uLnnber of heads. Zf a. brest.diouk4 occur. releasing oil & a soli4: | |||
stream or vith pxe distribution an4"a. adiiemaua, of atomization, a smiller zzumber of heads might be apene4 even at Iarger.oi1 discharge rates. | |||
. Considering the constructionsind.'ocezpancy of these jdants;.it is expected that proper~ designed, autcinatic. sprinter protection voul4 C | |||
~ | |||
iO 0 | |||
0 | |||
be effective despite the opening of large numbers. of..heads> in view of the strong water supplies now being contemplated for the sprinklers. | |||
FACTORY MUTUAL RESEARCH CORPORATION Norman Jo Thompson~ | |||
Vice-President NJT:RJ-150 KPORT BY: g, J,: Thompson J'. B. Smith. | |||
E. V. Cousins PE E, Cotton TESTS BY: Test Station Staff ORIGINAL DATA! Notebook No,, 155 ATTACHED: Appendix, - 23. Sheets | |||
II 0 | |||
v Ap | |||
~ ~44 hVitP "~c.'~ "kR (3O7-lo) | |||
Viev of fire test building from southvest. | |||
(Photo taken during Test No. 5). | |||
FACTORY MUZUAL RESEARCH CORPORATION Report No. 13434 Norwood, Hass ~ September 9, 1957 | |||
0, D/A GRAM OF ZO''ag Q S7 AA?EAS AN'0 Du// O/NG O'O. /8 Vcrfioal Dimensions Are Clear Hori zontal Dimensions Are Frame Dimens/ons Sca/e E" = | |||
OPENINGS e /I/o. ZB 33'o'a sf Ele va ti on 40'tesf P'ump boiler | |||
/0'x /0'nsfrumrnf Door 8'm. | |||
A'm. Rm Roof Hatches-Possible Open Area -28 Sy. Ft; per Dn Worth Door e 60 s Pz Qz H | |||
("Lo-Section Low Ceil/nj /'I/gh Cei bn/J 7est Area Test Area | |||
') (" Hi - Section") | |||
Plan t/ii'ndows- Possible open Area West Upper INndows Zl Sq. Ff. per Unit 2 tlni fs Upper /ndows on Soufh Face (Ar'o Windows on Fastface) | |||
Same as Norfh Face Norlh Wesd Eleva(/on | |||
" Elevation h'i - S'ect " "fbi -Sect," | |||
FMPC Norwood, blass. Epd A'o. /Z4S4 9 ~ | |||
9 ~ | |||
57 | |||
li 4l | |||
Page No. ZC Sprinkler Heads Separation 8efween | |||
'Vli "and'Zo-Secf "Areas (Control Head) Curbed Dune'esfs. | |||
Plan View ."Hi-Sec&on- Bldg. Q3 | |||
&posed Slee/ | |||
Test Structure Prot'ected Steel Co/umn and 8eam A/of Loaded'. | |||
Drainage Trench Curbed Dunng 7esfs Section A-A FMRC EpE. A'o. 643'4 Norwood. Mass. 9.9 57 | |||
0 II 0 | |||
Appendix SQ& | |||
LOCA 7IONS AIIID /OZ'NTIIFIICA7 IOUS OF FLOOR ANO CE!L//NG 7HERMOCOLl/ LES | |||
/Z4-S4 st / | |||
StrNure~ | |||
eo zo ~<<so | |||
<(S F(oor Fs f" below 5vnace of Cuncrrfe Plan 'V'ewer Hugh Sect 8ldg. /B | |||
'Ceih'ng W Qn Qrs 8" be/ow Ce/ ling. | |||
/&era/ Locaflons | |||
>arne as F/oor F~ | |||
Oi4 ec. | |||
<<woo+,'ass. | |||
~O 0' | |||
Appena'i'x Shee j2 8 j2Z io 6Z XZk 8"1 2S Plan ai ZO R. Level | |||
/0 ro''I Nonh or Socnh Elevation 8 1 /84-2Z 8 I2Z 8 1'8A Plan aC box h /he ioH F Floor Leve/s All8"2 Grams > bofh /he /Ofy. g Floor levels are 5'long. | |||
7he Members Form/ng Phe 2O 6 Horizontal Level were cuP to mal'e a lO'x iO'guare. The Assem6ly was krmeciby Elec,Are 8'cldi'ng. | |||
'~ RC. | |||
ho<~~os, Mass. | |||
~O iO 0 | |||
Appena'iX She& Z lOCArlON OF 7ffERNOCODPL ES ON STEEL SrvuCru~Z rzwzw (AII pcened r'n S&el gio "oeep> | |||
F~ | |||
84( ) | |||
85 Ce) 90(f) 91(e) 87(c) 86(F) 7/(b) 89Ce) 72 &') | |||
Location oF | |||
+S 88&) on Upper Crossarm | |||
(~c I Ps =() 28'6(cO 6" 92 C 77(c) ~ | |||
78(a) 79(b) 80 (c') | |||
88(f) 99(c) 9S(e) 94 (F) 97(e) Sr(c) | |||
Location oF. | |||
ps Local/on oF 96&') on Lcrwer Crvssarrn 75 on H- Calurrin Ug (e) | |||
Lotion oF W Locw ion oF Fs on Crossarm on H" Column G.oss Sec&ton Cross Sec+ion x (a) | |||
(Sca/c -ls" S | |||
") | |||
x(b) | |||
~ X | |||
&2~/z"+ | |||
Oown (d) rior Ppf N<. rZOZ+ | |||
+cod @lass. 9-9-57 | |||
0 0 | |||
il | |||
Appendix 'Sheet 4 PROPERTIES OF LUBRICATING OIL | |||
'.C. | |||
USED'est O.C. | |||
No e of'i1 Used 7 oF'6 Viscosity oF 7'lash Fire 1, 2, and 3 Gulf'."Paragon 41" 5 ad.n>. 36 sec 59 sec 345 365 | |||
~ | |||
4 and 5>. 86$ Guif->>Par, 38"). | |||
34$ Gulf->>Par ~ 41>>) 3 min> 28 sec 48 sec 345 355 | |||
+Proportions are. hy,volume.. 'The origina1 intent.was to use Gulf "Paragon 41" throughout Gulf "Paragon 38>>. was used in the proportions shown due to an inadequate. supply of Gulf "Paragon 41" ~ | |||
pg tory | |||
'<<dp Mutual Research Massachusetts Corporation Report No 134,34 Sept. '9, 1957 | |||
~O II | |||
APPh=nCkX Sheek S 0 | |||
RATE OF'lAME SPREAD-.7 EST f Fovr Observer~ | |||
X QO 0 | |||
0 | |||
/6 /8 20 7am e a&er Ignthon AAnU~em'p~ | |||
No. /Z484. | |||
9-9-57 | |||
~li Il | |||
A'o. / | |||
ZOOO 0 0 7 ES7 V ~S Ie 0 0 Maxi'mum Cei'ling Temperature f4 a'60O 0 0 rs z8 | |||
/200 2K'P Fire RaCh'kiS rO'Si | |||
/7 ss T/ me f9 from Stark 2O | |||
. Zf Mlnu des 22 24. | |||
n | |||
0 II | |||
o Q 2000 TEST Na. 1 Max/ %0m H"Colvmn Temperatures | |||
-O fO 5'above | |||
/0-20 +Floor | |||
%8f | |||
/600 f200 800 KO above Floor F77 2i/g' Fire Radias ro.',fs'6 f7 f8 20 2f 22 Tx'me from S)ai-') Ak'nuPes | |||
0 4l | |||
TEST Na. i C 0 | |||
2000 ~i Max]'muon Crossarm Temperatures C | |||
L Vpper and Lower 1600 Lower Crossar m gg 97 | |||
/200 800 Upper~ | |||
Crossarm g 90 400 to's'- | |||
Fire Radius 0 | |||
0 a) Z 0 l6 17 1B >9 ZO 2Z 24 7i'me from Stark AA'nufes | |||
~Ci | |||
'0 0 | |||
200Q Maxi rn um H- Column Temperatures 0 -10 f600 tO'-2O'. | |||
~ f200 5'bove floor I ip 84 800 ZO'above floor g77 Fire R'adtus 5' 17 I9 20 2r 22 Time From Start M/'nuked | |||
0 0 | |||
TEST No .2 2000 Maximum Crossarm Temperatures 1600 Upper and Lower 4 | |||
. 1200 E | |||
800 Lower Crossarm Pg s8 Firq ~ | |||
5'pper Crossarm f91 RaChus Cs 6V-I | |||
/7 18 20 21 22 4) o tn 7ime From Start' Minutes | |||
'li 0 | |||
0 | |||
~ ~ | |||
TEST Mo.3 OOOO 0 0 | |||
'g l3 f6 Maximum Ceil)'ng Tern perature 0 0 ff f7 | |||
. t600 0 0 I5 18 4 | |||
l | |||
~ f200 | |||
} | |||
800 yC | |||
~ | |||
0",S%~ | |||
yO F/rq Pad)us gl 3 6. | |||
Time from Sf'arf AA'n ufes | |||
~ ~ | |||
0 0 | |||
TFST Mo.3 Z000 Maxi'mum 8-Column Temperatures 0 10 f600 /O'- eo' 1 | |||
~ 1200 +&jr o | |||
~r dP E | |||
~QJ r | |||
800 7-8l ~ | |||
5'ebov f0'boVe | |||
"."/oor floor Q 77 400 Fire 3 ', | |||
From Start Minutes 5'/me | |||
'0 4l | |||
Q TEST No 9 8000 Maxirnuin Crossarm 7ernperatures Upper and Loner 4. | |||
0 | |||
~ f200 800 | |||
~4 4+ | |||
'Sp Lower Crossarm | |||
~Upper Fire Crossarm Radivs @B7 gl 7/'me frotn SfaH Minutes | |||
0 0 | |||
0< | |||
< R | |||
<n TEST No.< | |||
2000 i~ | |||
Maximum Ceiling Temperafure L | |||
1600 Reco der 0 0 OF'1. $ 13 16 0 0 14 11 0 0 15 16 g f8 CD | |||
'b '0 CD Z 3 5 0 | |||
Vs W 7ime affer Start M]'nukes | |||
Cl ll | |||
Tzs7. No. 4 2000 kfANINUN 8" C0LvwY TENPEAATDREs 0 - 1'0 | |||
/600 20' 10 - | |||
l200 record'er 800 | |||
/0 Above Floor P'7 4O0 7/2'bove Floor 480 0 | |||
480 0 | |||
Time From Star t Minutes | |||
Cl 1' | |||
~ + ~ | |||
2000 Tzs7 bio.4 AAx!au~ CRossaR~ TE!rIPERAruREs | |||
/600 UPPER AN0 LovvER p+ /200 Rec rder 800 | |||
/ower~ | |||
Crossarm 498 ON''98 Up er 4oo Cr s sarm 85 Time From Start Minutes | |||
Tzsr No.5 0 0 2000 %/9 /6 Maximums Czu ms 7Ews zuAruuE. | |||
0 0 | |||
/4. /7 0 '80 | |||
/6oo /5 | |||
~l2QO L4 h h M CS 0'oo | |||
/0 /2 T/ me frorv Start QfnL/des | |||
0 0 | |||
0 | |||
2000 Gs7 A/o.5' 0 | |||
~4 4/AxlMUN IY- Cot, Uhlan'ENPEpAlvRE$ | |||
o'- /0'0 | |||
/600 - | |||
/7/Z Abc ve Floor ZO'/2 g 72 p l200 AbOv8 Floor g80 8oo Woo D /0 Time From Start Minutes | |||
II O'AXlklUbl CROSSARM TEMPERATURES: | |||
2000 UPPER ANo LowER | |||
/600 | |||
~ 'ower | |||
/ Vpper Crossarm 4.90 Cessarm | |||
...4'.97 p+/200 80O 4OO 0 /0 0 | |||
7 jme From Start - bfinuPes | |||
~O Ap endix Sheet 2f Hatch | |||
@ 1 0 0 | |||
Hatch e 2 0 0 0 T8s& Z Plan View - Hi -Sect."Showing Pattern ot" Sprinkler Heads Opened. (.6) 78SS 3 0 0 Hatch e P 0 0 Hatch 0 0 0 Z 0 KMNc 8'pd. Alo. gg34'. | |||
/Var uvood,bless: 9 ~ | |||
$7 | |||
i | |||
~ | |||
Appendix Sheet 22 TABULATXON OF 'gEST CONDZZXONS AND RESULTS Wind Ventilation Direction Degrees Wind Outside FLoor Oil rea Opened. at Area- Opened. at Prom Velocity Temp-Test No. Tem -'P Tem - P Ft Min-Sec S Ft Min-Sec North MPH oF 1/0 165-170 $2 0-00 ~ | |||
28- 10 to 15m 270 86 | |||
+H 10-00 +28 18-1/2 to 20m 2 170-175 164 0-00 56 0-00 -- No Observation-- | |||
1H 180-185. 164 0-00 161 0-00 -- No Observation , | |||
4 109 184 164 0-00 224 0-00 140 10-15 69 117 165-170 164 0-00 224 0-00 ~ | |||
180 10 60. | |||
Time Time to 5 ft Maximum 'I after Pire Pire (1), Six simultaneous fires. | |||
of'irst Radius Radius Observed. Start When 1st Radius FLgures ard typical fire | |||
'of'ne Fire Spread. of'pread A.S'. Operates Observed area. | |||
Test No. Min-Sec Min-Sec Ft Ft i (2) Maximum radius possible 16-00 2-45 15 for ind,ividual fire area | |||
'2 18-19 1-21 .6 6 before merging, with a+a-0-00 1-25 cent fire area. (Max. area 6 6 4(1) 0-00 10(2) involved, - 1400 sq ft) 0-55 5 0-00 1- 5 ~ | |||
5(5) , (>) Maximum persistent'ize is given. Occasional mo<< | |||
~ | |||
mentary outshoots not included.. | |||
Time 1st Time 1st SprinM.er Sprinkler'perates Discharge Operates Pressure Sprinkl.er'ischarge Number (1). Xnitial valu=s only. | |||
Min-Sec Min-Sec At of Sey text for in-From From 1st Sprinklers Density rinklers 'reases. | |||
Test No. I nition Pire S read, PSX GPM Ft ned. (2) Manual control. A13. | |||
24(') 24 heads open when 1 20-45. 4-45 5 0.1> | |||
.. 5--' water supplied to 2 19-57 x8 .0.1$ 17 them. | |||
2-03.. 2-'Ol 0.15 11 4 1-50 3.-50 5 24(2) ''.15 5 1- 9 1- 9 5(1) 0.1 (1) 24 FACTORY MPiUAL RE~~CH CORPORATION Report No. 1$ 4$ 4 Norwood, Mass. September 9, 1957 | |||
0 0 | |||
t ib | |||
Appendix Sheet 2y | |||
==SUMMARY== | ==SUMMARY== | ||
OF MAXIMUM TEMPERATURE DATA Avera es oz Maximum Recorded Tem eratures | OF MAXIMUM TEMPERATURE DATA Avera es oz Maximum Recorded Tem eratures F Ceiling Ceiling Steel Steel Steel Steel | ||
(2)Single average maximum ceiling.value'iven because this fire*~was from multiple rather than s1ngle point ignition.t FACTORY MUTUAL RESEARCH'CORPORATION | $ 2 ft Structur Structure ,Structure Structure Laterall Laterally H-Colum H-Column Lower from from 0'o 10'o Cross- ~ . | ||
~ | |||
Upper Cross-est Ignition Ignition 10'bove 20'bove arms ,arms 10'evel 0 ~ Point Point Floor - | |||
.Floor 20'evel 1/25 865 14qo 148o 16oo 10/5 | |||
$ 50 66o 505 .,550. | |||
275 580 505 4(1) ly75(2) 6oo 900 950 870 86o 6o5 1145 1>80 1510 1510 (1) Average maxima are probably above values'hown for Test No. | |||
because rapid temperature changes occurred. in less time than that required 'for one complete printing cycle of temperature recorders. | |||
(2) Single average maximum ceiling. value'iven because this fire * ~ | |||
was from multiple rather than s1ngle point ignition. | |||
t FACTORY MUTUAL RESEARCH 'CORPORATION Report No. 3.5434 Norwood., Mass. September 9, 1957 | |||
1 0 | |||
Cl 0}} |
Latest revision as of 21:12, 3 February 2020
ML17354B014 | |
Person / Time | |
---|---|
Site: | Turkey Point |
Issue date: | 07/02/1998 |
From: | Hovey R FLORIDA POWER & LIGHT CO. |
To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
Shared Package | |
ML17354B015 | List: |
References | |
GL-86-10, L-98-153, NUDOCS 9807080062 | |
Download: ML17354B014 (96) | |
Text
CATEGORY 1
~
REGULAT( Y INFORMATION DISTRIBUTION SYSTEM (RIDS)
ACCESSION NBR:9807080062 DOC.DATE: 98/07/02 NOTARIZED: NO DOCKET SCIL:50-250 Turkey Point Plant, Unit 3, Florida Power and Light C 05000250 50-251 Turkey Point Plant, Unit 4, Florida Power and Light C 05000251 AUTH.NAME HOVEY,R.J.
RECIP.NAME AUTHOR AFFILIATION Florida Power & Light Co.
RECIPIENT AFFILIATION 5~
Records Management Branch (Document Control Desk)
SUBJECT:
Forwards response to request for addi info re request for exemption from requirements of App R Subsection III.G.2.a for electrical raceways in open turbine bldg.Rev 1 to PTN-FPER-97-013 rept encl; DISTRIBUTION CODE: A006D COPIES RECEIVED: LTR i ENCL i SIZE:
~
TITLE: OR/Licensing Submittal: Fire Protection - App R - GL-.88-12 E NOTES:
" RECIPIENT COPIES RECIPIENT COPIES 0 ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL PD2-3 LA 1 0 PD2-3 PD 1 1 JABBO K 1 1 INTERN : FILE CE 2 2 NRR/DSSA/SPLB 1 "1
-ABSTRACT 1 1 OGC/HDS3 1 0 1 1 NRC PDR N
t NOTE TO ALL "RIDS" RECIPIENTS:
PLEASE HELP US TO REDUCE WASTE. TO HAVE YOUR NAME OR ORGANIZATION REMOVED FROM DISTRIBUTION LISTS OR REDUCE THE-NUMBER OF COPIES RECEIVED-BY YOU OR YOUR ORGANIZATION, CONTACT-THE DOCUMENT CONTROL DESK (DCD), ON EXTENSION 415-2083 h
TOTAL NUMBER OF COPIES REQUIRED: LTTR 10 ENCL 8
~ .
f t
JUL 02 1998
,' rr L L-98-153 10 CFR 550.12 10 CFR 550.48 10 CFR Part 50 Appendix R U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D. C. 20555
Subject:
Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 Response to Request for Additional Information on Request for Exemption - Fire Rating of Raceway Fire 1
By letter L-97-181, dated July 31, 1997, Florida Power & Light (FPL) submitted a request for exemption from the requirements of Appendix R subsection III.G.2.a for electrical raceways in the
~
open turbine building. By letter dated March 23, 1998, the Nuclear Regulatory Commission (NRC)
~
requested additional information (RAI) in order to complete the review. In accordance with the NRC request, Attachment 1 provides the additional information requested. FPL's response incorporates information requested by the NRC during the May 26, 1998 public meeting between NRC and FPL.
Should there be any questions, please contact us.
Very truly yours, R. J. Hovey Vice President Turkey Point Plant OIH Attachment Enclosures cc: L. A. Reyes, Regional Administrator, Region II, USNRC T. P. Johnson, Senior Resident Inspector, USNRC, Turkey Point 9807080062 9'80702 PDR ADQCK- 05000250
~
. PDR a
an FPL Group company
I 0
0 I
CATEGORY 1 REGULA'A RY INFORMATION DISTRIBUTION SYSTEM (RIDS)
ACCESSION NBR:9807080062 DOC.DATE: 98/07/02 NOTARIZED: NO DOCKET FACIL:50-250 Turkey Point Plant, Unit 3, Florida Power and Light C 05000250 50-251 Turkey Point Plant, Unit 4, Florida Power and Light C 05000251 AUTHOR AFFILIATION AUTH. NAME HOVEY,R.J. Florida Power S Light Co. 5~
RECIP.NAME RECIPIENT AFFILIATION Records Management Branch (Document Control Desk)
SUBJECT:
Forwards response to request for addi info re request for exemption from requirements of App R Subsection III.G.2.a for electrical raceways in open turbine bldg.Rev 1 to PTN-FPER-97-013 rept encl.
DISTRIBUTION CODE: A006D COPIES RECEIVED: LTR 1 ENCL 1 SIZE:
TITLE: OR/Licensing Submittal: Fire Protection - App R - GL-88-12 E NOTES:
RECXPIENT COPIES " RECIPIENT COPIES
~
ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL PD2-3 LA 1 0 PD2-3 PD 1 1 JABBOU 1 1 INTERNAL: 2 2 NRR/DSSA/SPLB 1 1 1 1 OGC/HDS3 1 0 EXTERNAL: NOAC 1 1 NRC PDR 1 1 D
N NOTE TO ALL NRIDS" RECIPIENTS:
PLEASE HELP US TO REDUCE WASTE. TO HAVE YOUR NAME OR ORGANIZATION REMOVED FROM DISTRIBUTION LISTS OR REDUCE THE NUMBER OF COPIES RECEIVED BY YOU OR YOUR ORGANIZATION, CONTACT THE DOCUMENT CONTROL DESK (DCD) ON EXTENSION 415-2083 TOTAL NUMBER OF COPIES REQUIRED: LTTR 10 ENCL 8
r o r I
0 JUL 0 2 1998 L-98-153 10 CFR 550.12 10 CFR 550.48 10 CFR Part 50 Appendix R U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D. C. 20555
Subject:
Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 Response to Request for Additional Information on Request for Exemption - Fire Rating of Raceway Fire rrl i il in By letter L-97-181, dated July 31, 1997, Florida Power 8c Light (FPL) submitted a request for exemption from the requirements of Appendix R subsection III.G.2.a for electrical raceways in the open turbine building. By letter dated March 23, 1998, the Nuclear Regulatory Commission (NRC) requested additional information (RAI) in order to complete the review. In accordance with the NRC request, Attachment 1 provides the additional information requested. FPL's response incorporates information requested by the NRC during the May 26, 1998 public meeting between NRC and FPL.
Should there be any questions, please contact us.
Very truly yours, Nl, R. J. Hovey Vice President Turkey Point Plant OIH Attachment Enclosures cc: L. A. Reyes, Regional Administrator, Region II, USNRC T. P. Johnson, Senior Resident Inspector, USNRC, Turkey Point
'rr807080062 'F80702 PDR ADOCK 05000250 F PDR an FPL Group company
li Cf 4
/fall'
2 4 d d I
I I
I I
Al I
CPBO I I
I I
on I Aleo Avauab~s O'af6 I
p tnj efd f
'I I
36 33 34 SS.I 33 sa 2S.I 26 I I
I
=
I I
~~I
-jj dl I
I I
ass'.a. asaaa I
- s. sas
'ss I I
I I
I I
,I I I
>L S5IK 1IdkIf I I
= c'
/ I s./1 w/ I I
I
~a I I
~a ~~
I I
I I
I I
I
~ cl I
aj I I I
5 f4I I J I xh I IISCV SCIOCEQ 41r//r swlloaIIII I iNxxixa i Ts, I
I I
I I
I Sl I
I I
0 0 0 J'c I
I loco EI I I
QO GOSIOICf OSSTIS I
I LEGEND CCCt:XII3 I I
I CCCIXZD I rl I
I I
I ga 'Ta sI I I
I aaaa aa aaa Il raLJ I
~ fwf srsNQls sIssk ra
- s. s I 1 cl I
I I
I I
I I
I I
RFolCgee( Z -QI I I
I I
I I
I I
I TVRKEY PONT kICLEAR IIkTIS 3 Js d FLORIDA POWER 64 UGHT I
I FIRE PROTECTION FIGURE I (L-98-TS3)
- GROUND FLOOR PLAN "EL 18'-0 6( BELOW I I
I 5
I 7 8 s~sa.-
~sa. a
II
' 0 r
ly 1 tp II II 4 I II I.
~1 '4114 em ri II II IP4PC
=- ill I
II I-.--Adj
$ 14 41 ~49 j)'t I il' I
I, I'-
2 3 ~ '4 c 9sc 35 34 3T.s 32 gsl I
3D s
28 27 20.1 26 ~ u.s Lt~AV@~I- Epos 25 I
"8 P !!"24~
I
~ I 0"
I ii I si I ii ii I II i I ii I ii I I I
I I
I ii I I ii si I
I I
Lm Ci smaasZ I iI si I
II I
i I EZZZE a. EZZSVnENZ I
ii Ii I I
I I li I I
II I ii I
I I
'l; ii I I li Is
)I si I
II I is si I I i I A I
,I I
QB 9 I
l ljL c Is I I
l,. -,( I Esl 3'
c I i[, c I
t Qn 3 I
I QI I
I I NIC>>>>>>>>>>>>>> el
-~J'c C3 C3 C3 l
LEGEND:
<<>>>>>>>>>> MEES0LAC SONCNRT !
T~
I 2
I PLAN MEZZANINE LEVEL EL. 30'-0"
'tVnae sec @z-oZ TURKEY IAONT NUCLEAR VNT$ 3 R 4 FLORIDA POWER dE UGHT FIRE PROTECTION FIGURE 2 (L-98-153)
MEZZANINE LEVEL ELEVATION 30'-0 c4 4 l
0> ((') Q h1 1
ll lf t
il I
E E
'I
5 D J'c I
I I
I I I @pamvt~K CMRATOR I
I REHEAT MO51URE
- + I SEPARATOR (ITP.) I TURBINE t SEse I
! A~So Apggabt()) on goerture Card I 1 EXSTNO
! !!F1 4IMH III I ARE !WE-IAO I I TEEOWATER HEATER (AP. VN 441411 j I:.I:-I;i':I:.II I)1I.-:NIXI.;
I I I
I wuv (OR& SHGOS) I HOUR 770 NORAOE BARR6!
4IIII7 I ~ .~ .
~ 11 ~ ~ ', 'I ~
41 40 SWITCHOEAR ROOM I
OL SPEL ~ IWIP4 $ 4454 Q BERM I
4
~ .. 4
~ 'A I 4'HK. BECK PIAlE EL
~
2'-6'OTES:
- l. I
- 2. 25 ICNUIE
~
HOUR RAlEO ARE COLWM RATEO BARR65 WIIH AUTOMABC SPRSXIEK BETWEEN A% BI TK PUMP PIT.
!NE BARRKRS WllH AUIOMATC SPRNXLERS. I I BGWIEH COWMN EM I Oi. SPLL'- Oa. POOUNC
- 5. 25 !CHUTE PATED ARE BARR65 BEIWEEH COWMN J-4'C I I
='.."--';
~50M! i;."=-.",
TURKEY POINT NUCLEAR UH!T 4 WWE OL INC PROKCTIW FIGURE 3 (L-98-153)
@PL f
.II
I ,,)) Cu) r "l
Il 1I
't C
I 3P6B 3P6C 3 6A 4160V SWITCHGEAR I
I I
CONDENSATE PUMPS I
I P,p ~ye CSI 8 3K1966-4" 11'-3 I
L.P. FEEDWATER HEATER 3E3A CV O
PB 7340 I O I O O I I O O O L.P. FEEDWATER HEATER 3E3B W Y) 3A1397-1 1 2"
3K 2020-4" 3K2021-4" 3K2022-4" 23 PB 34'-(P 3809 I I O
cV O CD 15'-0" TURKEY POINT NUCLEAR UNIT 3
@PL FIRE ZONE 084, 088 8( 105 24 1 HR THERMO LAG UPGRADES PLAN I EL.18'-0" VARIOUS CONDUITS It'. PULL BOXES 8( EL.30' 0" DWG NO FIGURE 4 (L98 153) sHW 5 0
~(i 'I
), E l
a4'132. 32 DN TO EL 2'-8'0. 30 8-4A1 357 4A1372 APlEFITG CARE 4P6A 4A1369 4P6C P84874 18x32x44 4A1370 4A137'I 4160V SWITCHGEAR P84875 OONOENSATE PUL'PS 18x32x38 4JI 776 24x24x8 O'-'0'-4K1411 8-4K141 8-4A1357 B-4AI357 I
CV 3K1724-3" I.LP.B.. )K1232 4K1232 4K1212 4K1212
'PF.W.
E-1 HTR 4DA
. 4'-0' 4K1421 4K1417
. 4K1421 4K1417 2'-
5 I
7'-9 zO 6'-0'ONDUITS V) BROW E!8f.18'-0'J1775-3'4 4A1 49 1 4 PB5491 PB4713 4J1838-1'A1417-1 4JI MB-I LPF.W. IITR 4E38 I 2 -4 4 -1.'I 4KI441-4 4K1441 4 TURKEY POINT NUCLEAR UNIT 4 FIRE ZONE 079 8( 105 1 HR THERMO LAG UPGRAOES V'IOUS CONDUITS 8c PULL BOXES EL.30' 0", 18' 0" 8c BELOW DWC NO FIGURE 5 (L98 153) REV IIEET 1 A 0 pbn004eh I A.DWG
Py G Cu) .
(~)-
f V
BL'TURY MUTUAL RHSEARL'H L'URPURATIUN '" " -"'FM C
ll5l BOSTON-PROVIDENCE TURNPIKE, NORWOOD, MASS.
September 9, 1957 FIRE TESTS OF AUTGMATIC SPRXIGKZR PROTECTION FOR OIL SPILL FIRES I XFKOEUCZIOH AHD ABSTRACT At the request of the United. States Atcmdc Energy Commission, the Factory Rxtual Research Corporation has concLucted, a series of'ire tests at their facilities at Norwood, Massachusetts. The purpose of the tests vas to learn if automatic sprinklers vie. protect buf3cUngs, such as the Commission's gaseous diffusion plants, against fire 'in lubricating oil accidentally spi33ed on the floor.
Fire tests vere made involving oil, at elevated, temperatures, covering 2100 sq Xt of'1oor, also at elevated. temperatures, and. employing various methods of'gnition.
Xn a11 of the tests the f'loor fires were cLuickly controlled ancL minimized and the test building vas satlsfactor~ protected. by sprinkler discharge. at relatively lov pressure. In the fifth test an oil spray dis-charging from a nozzle above floor level provided an auxiliary fire against which the building vas protected. by lov discharge from the sprinklers. The spray fire vas'not extinguished in this case ancL a steel structural member ac/scent to it vas not protected. against severe local exposure.
It is.concludecL that the Atomic Energy Commission's gaseous cLfffusion plants can be satisfactorily protected. by automatic sprinklers. In the case of. floor spill'ires alone', protection would be complete against general and indiyicLual structural failure and against involvement of insulated. metal deck roof'onstruction. In'he event of additional fire in oQ. spraying from
. rupture'd. equipment,'eneral structural protection voulcL be maintained of insulated metal deck roof construction vould. be prevented.; and.'nvolvement Failure of incLLvidual structural members could. occur in this situation if such members were so located. as to be exposecL severe by the fire in the ~
oil spray.
.The principal obgectives of the test program were based. on fires in lubricating oil spilled. on a level concrete floor, with both oil and. Moor FOR BETTER PROTECTION OF INDUSTRY
0 0
~ 2w at temperatures which vould be expected in a typical gaseous diffusion plant.
- 1. To determine rate of flame spread. radially from a local ignition source vith no fire protection.
2 To determine the minimUm practical water discharge density from a sprinkler system required to control and. to extinguish an oil spill fire To obtain vith our test facQ.ities informstian vhich vould. lead. to a conclusion as to the effect of ceiling height araund, the order of 50 feet in bringing about any significant 'delay in operation of autamatic sprinklers.
To determine, vith snd. vithout sprinkler protection, the effect of an oil spill fire directly exposing structural steel in bringing about excessive stee3. temperatures.snd. in causing elevated. ceiling temperatures.
L-
- 5. To obtain from test results information vhich, combined. with previous test experience snd. )udgment~ m1ght lead to an inte23.igent estimate of the number of sprin3Q.er heads which might operate due to an oil fire, so as to assist in the design of an effective automatic sprinkler system.
- 6. Another obgective vhich vas developed during the test program vss to determine vhether a fire in hot lubricating oil discharged at a sub-stant1al rate .in the. form of an elevated. spray could be extinguished. or controlled, by.sprin3Q.ers vithin the range of ordinary discharge densities, and.
temperatu'res.
'hqt the effect would. be af' Sire of'his type on ceiling and. exposed. steel
'.'f I e
'.5 III TESTS A. MethoA
\
All of the tests very conducted in the high ceiling area of'he fire building illustrated by photograph'nd, sketches an. pages 2k~ 23 snd 'est 2C. This area measures 40 ft by 60 ft by $$ ft high and. Cs equipped with a smooth level- concrete floor. It hss protected. steel frame construction, 12 in. brick va'.Lls, and a vermiculite plaster'n metal lathe ceiling suspended, -.,
', from steel beams vhich also support a.poured. concrete roof. The locations and.
sizes of doors, windows and, roof hatches are given in the sketch on page 2B ~
The sprinkler system employed, in the tests is a standard. arrangement of 2~ standard. spray sprinkler heads (8 in. belov the ceiling) on 10 ft by 10 ft spacing. There are 4 heads on each of 6 branch 11nes sll supplied by a single cross main. The cross main is fed. by a riser gust inside the vest vali of
<<t the test area, vhich in turn is supplied,.by underground, piping from the pump In all of the tests the vater supply to the sprinklers was controlled.
<< pro<<<< a known discharge pressure at the head, incU.cated in the sketch on
0 Cl
Air temperatures 8 in. below the ceiling at. the.@locations shown in
.the diagram'on Appendix Sheet 1 vere measured. by thermoiouples (20 gauge, chromel-alumel), The temperature of the concrete floor+was also measured by the same type of thermocouples imbedded 1 in. below its surface at locations shown on. Appendix Sheet 1.
In order to evaluate the effect of fire. exposure stncL protection on exposed. steel structural members a steel test structure%ms erected in the building. Its construction and" location:are illustrate 1n the sketches on AppencLix Sheet 2 ancL page 20, The temperatures at 24 1@ations on this structure vere measured. during, the tests by 20 gauge CA.'@hermocouples imbedded l(10 in. deep in the steel. Msgrams on AppencUx Sheet,'5 show the locations of the thermocouples.
A means of'easuring rate of flame. spread .was.provdded by placing labeled firebricks standing on end. on the floor at 5 W :intervale. racially from the 1gnition point in the point source ignition tests; The time at vhich the flame front reachecL these markers was recorded. by observers during the tests'ince the tests. vere to sinniLste normal temperature'conditions 'at the gaseous -diffusion plants,.a means vas providecL to.heat;the..Moor, of'he test area to at least 1/0'efore each test and, to heat the.oil to at: least spiLLed on the floor; 165'hen
- 3. Procedure The essential features of all fire tests vere. the" sama. They vere:
- 1. The,. floor vss heated to a specified. temperature
- 2. Dxbricating oil (see Appendix Sheet 0 for properties) vas heated, to a specified. temperature and spiU.ed. on the floor of the test area through a distribution system consisting of". . '. '. :.-!"g..~",." -.
- a. Perforated. pipe (X-l/0 in.) located..along.,the east. and vest ends of'the floor and containing >/16 in. diameter holes 1 ft on, centers. The oil was pumped. from the. heated..oil, storage tank to this piping.
~s 4
- b. 3rain connections (2 1n. pipe) carrying. oi3.'y gravity heacL C
from the heatecL oil storage tank to two points on the floor at its south side approximately 15 ft from the east and. vest ends.
Three hundred, and fifty gaLlons of oil vss spiX3.ed on the floor in each test except the last. This gave'a depth of 1/4 in. over the 2100 sq ft of level floor in the test area ("EK-Sect." frame area, 2400 sq ft, less wall thickness areas, drainage trench ares and. ramp areas equals 2100 sq ft). Tjrpical total t1me to spill $ 50 gallons of oil was 4-1/4 minutes.
~
OB/ll/97 WED OB:38 FAX B17 551 9775 HEC STANDARD DIVISION Q 002
~ ~
$ Th oi1 wm ignited. (NethocL anC location for each test are describeC under "Tests". )
Fol3.owing fruition the rate of flame'spread~ the burning character-'
istics of'he oi1 and the vtsib1e effect of sprixQ~r discharge vere recorda4, .
by observers. The temperatures of'he floor, of the air at the ceiliug and:,,
of the steel test structuxe vere recorded. by instruments.
5, SprizQQar discharge vas either automatic (natura1) or maxnm1 (by.'.
opening a valve suppXyiug open heads) depeuiiug on the individua1 test xecLuirements. In a33. cases the discharge.pressure vas controllecL.
C.. Test Conditions aucL Resu1ts (TabuXations. of the test conditions encL .~.
observations axe incZxldecL in the AppencUx of this reporh (Sheets 22 and.
2g). 'he foXXovtug descriptions incXude caQy'he essentia1 inf.'oxmatXon.):.:
Test 1.
I The 'primary puxpose of the first test vas to determine the rate
~ /
I at
.and.
vhKch fire spreads ih the oQ.,
~
the vater supply vas vithhe1C fire spread:
~Therefore~ open spriu3Qer heads vere u'sed them until ~F3, observation of become.'impossible so that aXI. possibXJe data .an'uninhibited,.
spreadof fire'in the oil couXK be obtained,;
The temperature of the oil vhen spiXXe'd. on the f1oor vas 165 to I.70>I and. the temperature of the'loor vas 1?g vixen the oQ. vas '%gaited.
I fix& vas started. in the oi1 at the-base of the stee1 sCxucturi's'."
~
~
A central columnby four gas'oline-vet ceXXucotton ignitors+ 3.ocateL one at:
each corner of'he column. Because these vere'3'.mr t'o start the oi1 b a handful of excelsior vas addeC at tvo of the coruers at 15-1/2 min after the original ignitors vere XfghtecL.
~ I in the oi1 vas established. at 'ibont. 16 min 'and. conti ZLame at an acceXerating spree!.
rate. This rate is.iXXustrated by the graph on Appe '.
Sheet 5 vhich is a plot of the data. xecordeC by" four. observers.
I '
I Mhon the radius of the burxd~ area had. increasek to 15 ft the air:
temperature at the ceiling vas at 1200'nd.'increasing@ rapicQgr. Therefoxe~;.,
vater vas supplied to the spriu3Qers at 20. min~ 45 see (approx. 5 min after'".'he start of fixe spzeacL) at a co'ntroIXed pressure of 5 psi at the heads ft).
gp /se These igtdtors consist of roXXs (2-$/4 in. ~quoter, 6 in. Xong).
of 20 ply cellucotton vatMing each veightug 2-1/0 ounces, dxy. '."As,,";
.used. in these tests they contLLned 6-$ /0 ounces of gasoline each~
in the roX1+ 'bsozbed
Cl 5I J
r prevented, a precise observation of the tMe when the fire was Smoke controlled but it was possibly as early as 1/2 min,after the'egging of sprinkler discharge ancL definitily by 1-g/4 minutes. At that time only lingering flame remained along the foot members of'he.stee3.. structure. This fire could. have been completely extinguished by continuecL sprinkler discharge
.but in orcLer to prevent heat loss from the floor to..the sprinkler water, vhich voulcL delay preparation for the following test, the sprinkler vater supply was turnecL off and. the lingering fire extinguished by a 1-1/2 in.
hose spray nozzle g-g/0 min after the start of sprinkler dischirjg.
+
records on Appendix Sheets 6, 7, and. 8 illustrate the .'emperature intensity and. duration of fire exposure to the building and. stee3.'tructure during the'est. r" t Test 2.
The object of the second: test vas to detexmine the effectiveness of sprinklers as compared. to the delayed. manua1.control of'utomatic'opening
~
d
""used, in the first test. Standard,, upright, 212'eads were used.. "..
\ \ ~ ~ w+ ~ ~
oil temperature
,The when discharged. onto the floox'as .170,,to the temperature of the floor itself vas 1?8't ignition. 'he air temp-175'nd,
. erature under the ceiling was 105'. Both roof'atches (total'56 sq ft) were opened: at'the time of ignition.
The ignition. source was located,.at the base of the steel'structure
' as in Test 1. but consisted. of,a. cLuantity of commercial oQ.-absorbent t '".~edi-Dri.") at each'orner of the column; the saturated..oil-'absorbent..
being ignited by 1/4 'size gasoline-vet cellucotton ignitors.;This also .
resulted'in a slov start ancL fire vas not established. in the oil until about 18-1/0 minutes. However, the usual accelerating flame'spread rate folloved.
'\
The first automatic sprirQQer operated. 17 sec after the,,burning area
"' 'acL grown to a racUus of 5 ft (19 min~ 57 sec after the'tart of;the test)
'arid. several. additionaX heads. operated quickly thereafter'.-,.'(Spr'i'nkler. " "-
it a~'lj X~
I l
'ontxo3. pressure was 5'ps'."~,lg gpm/sq, ft cU.scharge densit'y.'.).;-,
The maximum observed. fire spread. racUus was 6 ft at la 'sec aftex the
~r
. first heacL opened but the fire vas knocked down and. reduced.;to a lingering flame at the base'of the steel structure one minute after the fix'st-head opened.. Again, in.order to preserve floor temperature, the sprinkler water supply vas turned, off ancL the lingering flame extinguished by hose stream at 25 minutes.
A total of 17 heads opened. during the fire period. The pattern of As these openings is shovn on Appendix Sheet 21.
0 Ci
06/ll/97 WED 08:39 FAX 617 551 9775 HKC STANDARD DIVISION Ql 005
\
T~~rature records on AppencLLx Sheets 9, 10, and 11, ccerp~d to
~ I those of'est 1. 111ustrate the rapicL contro1 of the fLre produced by the L automat1c {naturIQ.) operation of the'printed.ers.
Test 3.
Since the cei1ing height in the test brea is Iess than in some areas of the gaseous diffusion p1snts, it vas'esixecL'to phmQate Me effect of bcmed. ceiling.h'eight by provtcLing acM1tioua1 upper ~aM3atiou in Test g.;
the purpose being to dotexmizN if bn bpp?eciab1c delay iIL oper!LtioIL of automatic sprintQsrs voalcL xesult. Therefoxe~ 5 upper iriadcnr units on the south.'and vest aces'f the <<EL~Sects vere opened before the test in excess
'f'the tvO hit'ch opentngS used in Te'st 2. The teal. ventiLatkon area vas
.16I.'Q r l ~ Xa @hUtion the ignition method. vas changed. in order to e1iminate the long delzLy in estabIishing burnizlg in the oi1 as exper1enced. in the first two te'sos..'.The'n'ev'mthod consistedof poqring. one.piIIt of a 50-50,mix of gaso11ne-kerosene into thi oil. at epoch corner of the steel structure.
.E co1umn at'its: bssa.'his pruning f1uid vas ignited. ~diately after so. the..'size. of the ignition brea vas no greater than in the..'previous I 'eering.
~
I V ~ '4 ~ ~ tests j, ~ ~
2.'hat's,
~
. ~
'" Prike'chion'was'the same ar in Test 24. automatic, standard~
~
'uyr'Lght; 212, 'ijz~Qaz'.heads vith the cEscharge pres'sure contro11ed. at 5 psi ':,Ip- joe/scL ft." ':
': The:::teppiiature'.of the oiI when spend on the floor.vas.180 to 155~
and"the tehipiratuxe'of 'the Moor vas 1~'hen.the o11 vas iga1ted.. The.
- cei1ing air'temperature was
~ ~
95'.
"A ijgeaQig fire. in the oiI vas estab1ished vithout del'Iy and. the ~us
~ ~
of. thi bu~g axea reached. 5 ft at I. min, 25 sec azLd 6 The.;i~it 'hixtomatic iyga)Qer operatecL at 2 min, 1;.Sec .at which tiIIL the fire ft I at min 45 seconds area racKus"jrobabg dilL:not exceed, 7 feet. ARLY.onaI heads. ojeratecL at 2'mi@'.7,,sec..'iicL the;.fire vas ahnost compZeteXg extinlpzishecL at 2 min, 20 sea at'ILich'Qm lingua@.'smaII fXames persisted cnQg at the north side
'tre~Ore foCt members ~ of'steel
\
~
""9hci.'sZiriihbn'ater was turnecL off and. a 1-I/2, in. hose spaz~ nozzIe uqecL to map-.~"at '> i'dn 55 sec in. Order to preserve. f1oor temperatuxe.
~ ~ '. 7
'hotographs on" page 6L shciv the behavior of 'this fire before ancL gust I after the first sprinkLar discharge. Xt shouIC be borne in mind. that the photographs contend in this xeport indicate the conditions existing on1y at the very eaxIy staees of the fire. The very nature of .a lubricating OQ.
fire procLuces erat;remedy Iarge votumes of heavy, dense, b1sch smoke {sce photograph on page 2L) prectud1ng the tcQsiag of. p1ctures, stiII, or motion, I
~
0 Cl II
Test 3 - Before sprinkler discharge.
Time - about 1 min., 15 sec.
I I (3o6-3) fidius conds'ire-Test 3 - Just after initisl sprinkler discharge .
) sec',
S le ust e
Zy oil
- on, (3O6%)
"~TORY MJZUAL RESEARCH CORPORAT1ON Report No.
Norwood, Mass.
9, 1957 13434'eptember
0 0
'w 7
shortly after the initial spread, of fire..In fact, the smoke density became so great in from 2 to 5, min after the initial spreacL of fire that visual observation at Moor level was ususl3.y impossible.
ELeven heads opened in this test in the pattern illustrated by the diagram on AppencUx Sheet 21. It is noteworthy that the time recLuired for sprizQQ.ers to operate after fire spread wss established, in the oil vas 2 min in this test compared. with 1-. g/4 min in Test 2.
Temperature records on Appendix Sheets 12, 1$ , and. 14 again illustrate the quick, control of the f1re produced by automatic operation of the spriuklers.
""'est'4."
The purpose,.ofthi.s test.vas,to determine the action of sprinklers against s.fire. that might occur in a large spill of'oil't or near its flash point or'with'simiLtaneous ignition in several. locat1ons. Under such condi-t1ons s f1ashoyer woulcL,be expected. and. a large area" of'11 would. be burning before heat could'r'esch the ceiling to actuate sprinklers. This test also indicates'he effect of s delsyecL vater supply to the sprinklers.
, Xn order, t*o';,simQate this situation the os.'spill was ignited in six locations.'ancL".avowed to..burn freely while withholding vater from open sprinklers uiiti2: s.,1'arge.'area of o11 vas burning.',Also to simu1ate added.
ceiling'eight. al1'.8 upper vindov units and.'the ".Hi<<Sect."roof hatches. were open. "Total;upperventilation area.vas 224 scL W.
The.,sprhdQerheads vere, in effect,=-all open for this test. Actually the 11 he'ada'"open after Test g. vere open snd. the. remaining 1?j heacLs un-doubtedly fused before vater was supplied. to them. They were all 212',
standard upright. heads,.and. the discharge pressure'ss again controlled at 5 psi ~ .i$ gpm/scL..'W.;,
At the time'CEe,,ilail was spilled.'on the Moor it vas at 184 . The Moor.vss not'heatecL'since its temperature would. not affect the test and. at test time it vas. 1094;
" ~ -'pp-gy~'$'~:~pl 'a~ <"~ 'htC". ",
The,oil, vas ignited by tipping contaiiers of burning priming Muid into it 'aW 6.'Xocati'ons,'s1multsneous3y; There vss 1 pt of $ 0-$ 0 gasoline-kerosene mix.'n:.each., container ancL they vere located. in a symmetrical pattern 20 ft on'centers.'ix
'circular burning areas of. increasing diameter resulted. Typical diameter growth was-$ ft at 55 sec; 7 ft at 3. min, 15 sec; 10 ft at 1 min, 55 seconds. Two f1res mergecL north and. south at, 1 min~ 40 sec and. two more at 1 min, 45 sec at which time the signal for supplying water to the sprinklers wss given. Water actually began dischargiag from the heads at 1 min, $ 0 seconds.
0 0
06/11/97 WED 08:38 FAX 617 551 9775 H{RC STANDARD DIVISION gho04 At that time the total burning, area vas estimated to be 1lgp sq ft or
. mately.2/3 of the .vhoIe Oil surface. Because observers vere for~d ~'o precise observation vas made'f the ext~piiehed. but it vas betveen 2-1/>'nd. 4'mtuntes. During.the period befo exttuguishmcnt fumes'issued. 5 to 10 ft out; from the upper s~tovs ancL from the" roof hatches to an udestimated..height.
P AIL hesds in the sprinlQer iystem were open at the.cud. Of the'West.
Xt vt11 be noted. in the'tImyerature records of this test on A~adix.'".
Gheets,3,5, 16, and 17 that the:recovering:iaet~msnts" were 'oM. fox a pcriocL '
od ayyroxima~ 3. monte. This vas eausecL by'the shorting of an actuatixqg circuit by racLiant:heat from the fire. On'the basis of other supporting observations it. is believed that the maximuIn'-temyeratureis vere recorded the. pcwer faille. l
'efOre I I
- Ruin water vas sugp1ied to the spriiQchpm.'.the cei1ing temperature' This 'shcnrs that vater,was withheld"beyoiad'the'time noxma11y'equirecL I
'or 12tXl automatic sprizQcLeirs to operate".Reverseless,": the'. fire vas
[i .control qui~ vithcnrt.'si~Ig:effects'.t'o'".the'i1ildtug. ~
broulgt'-;>'under
'.c' C I
I E
- ,.The.'oligect of;~ test vas
- 4o":deCeimIiu'e the'effect of an addition.::.>
fire'uch 'as might occ'ur in oil:s3jea;yea j"from'@upturn:ecgxipment. Othei' '
conjKtioui-as regards.'the OQ. sZii11 ~'vere the 'siiiie is 'in Test 3.
sq &of f1'o'or "area," at..the';east 'end of the test are'a,. ex'..'that:aZyrhximstelg.7pO.
vas ext:off.; from the'.spill. area 'by" curb's".to.ccuiserve oil'upp', for the sprig Actua~ 290 ga3. of oil.vs. spiile4.,oa:a,1lt00 sq .ft Q.oor area. The..=
temperature:of the OM vhen:spiXled,vas'-.X69'to.3.70 .'ntL'the floor vas 13.7 '.=4 I ~
aC igrd,Cion.,
~ t.
~
c >
.. TM oil leehage fire was'shinQati4'.bj"jempihg,ci1'* a n'ozx1e (open',
' I' '"Autcmatic" ~6003~ SSU.head. vfth .316..tajjyxed'orifice) located 12 ft p
~
above. the f1'oor axe'2 W sautheait"of.the atI6e1'. structure 2-column. Pumptug.
to this. overhead, nozzle,:at.a rate"of XQ'"S ".gym~. vai begun 'at 3. min, 23 seo
~ ~
l l'.
,:aft;ei.the Moor fire vas started".'"" '+'"""" '-"""
I! """-':A's far as the;f1oor'iria vas conc~4"iC. d5ve1'ope.cl in the .usual .fashi I'i
.The racK4s'of the'burniug aiea'is 5'W at~3; min '35 sec. aud. it- did not
& mcept lnenenta~.:Xt vas'.'cofrtrolZAd.by'the .sprinhXers> the ~st
~4 of 6,
it
~
at I: min~ 39 sec,'ud" vas ndzdmised in less than p mizuxtes. 'ch,.operate8.
The spray fixe, on the other hiud, cou1d;"uot be extinguished.. Photo-.,:~
graphs on.psges 8L auk 83 shcnr the-..femY of the" oQ spray aud. the behavior .
fire that deve1oped,.from it. 'This fire cansetL aU. of the sprinkler heads to open (yrobabiz by 2-1/2 min) aud,~ 'althctugh the f1oor fire vas contro1IBC aud. the buQding itself protected'against the exposure from both fires by 0 the 5 psi discharge, the stee3. structure continued. to register temperature
0 ll 0
8A Test 5 -.Shape of oil spray from
.elevated nozzle.
(Not burning)
(3O7-a)
<<ay Test 5 - Oil spray fire before hanoi sprinkler discharge.
- ceed (Spattering in oil on f3aor is from unburned oil falling '; 'Y.
from spray .fire .)
- es ..
\s (3O7-4)
~ACZORY MUZUAL RESEARCH CORPORATION Report No. 13434 Norvood, Mass. September 9, 1957
0
- ...:::, '::.':..-;=;--:-(iO7-5)
N Test 5 - Oi1 spray fire after sprinkler discharge began-.'-..
PACTORY MUTUAL RESEARCH CORPORATION Report No. 13434 Norwood, Mass. September 9, 1957
~I!
4l
(
0
C in the range from 1400'o 1800'. Therefore, the sprizQQ.er cLischarge pressure was increased. as follavs:
At 3 min, 20 sec pressure to 10 psi = .19 gpm/scL ft density At 5 min, 0 sec pressure to 15 psi ~ .2?i gpm/sq ft density At 5 min, 30 sec pressure to 18 psi I .25 gpm/sq ft density At 6 min, 45 sec pressure to 28 psi -" .31 gpm/sq ft density
'At 8 min, 0. sec pressure to 38 psi ~ .36 gpm/sq ft density This increased vater cLischarge prevented. further increase of. the 'steel structure temperature but it cU.d. not reduce the temperature.
10 min the oil supply to the overhead. nozzle was shut aff'. Al3. temperatures Theref'ore, at (See Appendix..Sheets 18, 19, and. 20) decreased: quickly and. the sprin3Q.er vster vss shut:off at,l3-1/2 min vith the usual mop-up by hose sCream.
XF COKCLUSIOHS'..
- l. Once ii .~erg .,
~
a fire
~
has been establishecL and begins to spread, beyond. the ignition source~ the rate of flsme spreacL is relatively, rapid, ancL increases as the f'ire progresses. It requires about 1-1/2 to 3.minutes (depencLing upon strength of'...ignition source) to spread. Co a radius between 4 and. 5 feet, about 1-1/2;minutes from 5 feet to 10 feet racUus, and. only about 30 seconds far 10 feet:;to.-15. feet.racUus. (gbservstions..beyoncL about 15 to 16 feet could naC;be made, in our tests on account of loss. of'isibility due to smoke.)
- ~ <<'> I'>iV'V ~,
Once an oil spill has been i'gnited and. sprescLing of'lame begun, the rapicL.grovth:of fire and volume of. smoke.produced. indoors is such that effective:manx'.fire.fightiag can only be done within a period of about 5 or possibly::.6!minutes::fram initiation af'preacL,-
- 2. Autamatic spriaklers vill stop the spread. and. extinguish the fire in. an oQ. spiLl. on the floor at s cEscharge density of '0.13 gpm/st fC, - vith some margin: of".safety.
'::,3.='.There vauld.be no serious delay in operation of automatic sprinlQers at an:elavatiaa;,of about 50 or 60 feet fram a floor spill fire in a. large ares. as.-camparecl"to results in the .test building-with a 33 f'oot ceiling height:.with'no upper ventilation. The delay in, operation vou1d. be about 15 seconds'.representing:an.increase in fire radius. of. from about 6 feet to 6-2/3 feet;-=-",: ~,.:
With a floor spill fire around a building column but with autamatic sprinh1er:protection, the results incU.cate no temperatures which would.
result in;failure of'tructural steel. However, serious cLKstortion and. actual column failure woulcL be expectecL within a periocL less than 10 minutes without automatic spx ia3d.ers in service.
Where oil msy be cU.scharged. in the form of a spray at an elevation above floor level, vhether or not there is initially any substantial oil
~ I
~4
Cl 06/ll/97 WED 08:40 FAX 617 551 9775 HEC STANDARD DIVISION Coos
-lO-
~
f spill. on the floor, a fire under these conditions may bring about failure
- l of exposs4 steM. in the ~diate vicizdty of the fire. The 4ischarge. fzam il automatic'zllQAikrs at any JZRchicaI density may not s&tinguish the Egc'ay There is no other econond.ca3~.X0Lacticable automatic means avaILlable vhich vtl1 extinguish such a spray fire at any one of 'a
~ protection large nLuLLber of ~ssible locations;distributed. over: a, vids area, even it vere considere4 necessary to extinguish.
if j t
~
~
i Eovever, automatic sprin3QersI even at f?e~g.pressures as 1mr as )
5 psi.," vtll affor4.reliable fire cozztroI. by.:limiting dangerous.temrperatures
~ ~
for 'both structmM steel an4 roof aeeas to a:location of reIativeIy saaQ3.
radius laterally fraa the oil. @prajr.f$ re.. CcaisequentIy, for. as long as sprixQQer diochILrge can be maintainecL; serious damage ahau14 be vel3.
localiea4.
'I
- 5. Our tests indicate that, <trLth an.oi3. spi13. fixe. on the floor and..a single small 'igzLition source not over'2:.to "g.ft, in iRiameter,.the zzumber sprtulzlers vhich might be.-.expeete4 to. Operate 'vhen sayplie4 at of.'automatic 5 psi pressure mnzl4 probably ncrt: cmcee4'5:heads.. Even uzLder scauavhat unfavorable conditions 'of tzLterference vith'SIzzizdrler distribution by piping or. BtrucQzriLL elements no mare than 20'heads voul4 be expeete4 to. cyen.
Xf a Sire sholQ4 Start &ncl.spg8acL~M'81L oil. BQQ3: fire. izLVQlvi37g hLuuhe4'gallons of oil vfth'hai'.+alee".sipply to syefa1Qers 'shzLtoff,'. 'everal large numbers. Of heads .voul4 be expee4edhC'o-OIpen so.that the-vatex dis'charge.~
48nsity follcACEg delAQ&4 rcstorzztiozL'.:.of Water.Guppy+ Right bc.. reduced to '.
a totally ineffective value. -..':~ .'Q.
'll
+. <',i~=;.~.,'.'
" 'C ~ ~
~ ~,
It is diffi.cult to esMmate..the zzauiber. of"sy~Qer be. aperate4
- h t ! '!C '-~i',
in the event of a cou6~aus-veil distributed.
I heads.vhich zmfght Sino oil spasm
.of previous oxperienco is that gaia:idjjzt'.".'exjeet the znnaber of heads t'0 be oyens4'eventuzk1g veLM be 'in the40rCklr"of-'.frcmL 40.to .6Q heaCS: fox. an oQ.
sjumgr arcnzn4 '10 gpaL,'. an4 for'arger .cIMIgney"-. 4ischarge. rat4Ls a; c'cexeipondi gxeater uLnnber of heads. Zf a. brest.diouk4 occur. releasing oil & a soli4:
stream or vith pxe distribution an4"a. adiiemaua, of atomization, a smiller zzumber of heads might be apene4 even at Iarger.oi1 discharge rates.
. Considering the constructionsind.'ocezpancy of these jdants;.it is expected that proper~ designed, autcinatic. sprinter protection voul4 C
~
iO 0
0
be effective despite the opening of large numbers. of..heads> in view of the strong water supplies now being contemplated for the sprinklers.
FACTORY MUTUAL RESEARCH CORPORATION Norman Jo Thompson~
Vice-President NJT:RJ-150 KPORT BY: g, J,: Thompson J'. B. Smith.
E. V. Cousins PE E, Cotton TESTS BY: Test Station Staff ORIGINAL DATA! Notebook No,, 155 ATTACHED: Appendix, - 23. Sheets
II 0
v Ap
~ ~44 hVitP "~c.'~ "kR (3O7-lo)
Viev of fire test building from southvest.
(Photo taken during Test No. 5).
FACTORY MUZUAL RESEARCH CORPORATION Report No. 13434 Norwood, Hass ~ September 9, 1957
0, D/A GRAM OF ZOag Q S7 AA?EAS AN'0 Du// O/NG O'O. /8 Vcrfioal Dimensions Are Clear Hori zontal Dimensions Are Frame Dimens/ons Sca/e E" =
OPENINGS e /I/o. ZB 33'o'a sf Ele va ti on 40'tesf P'ump boiler
/0'x /0'nsfrumrnf Door 8'm.
A'm. Rm Roof Hatches-Possible Open Area -28 Sy. Ft; per Dn Worth Door e 60 s Pz Qz H
("Lo-Section Low Ceil/nj /'I/gh Cei bn/J 7est Area Test Area
') (" Hi - Section")
Plan t/ii'ndows- Possible open Area West Upper INndows Zl Sq. Ff. per Unit 2 tlni fs Upper /ndows on Soufh Face (Ar'o Windows on Fastface)
Same as Norfh Face Norlh Wesd Eleva(/on
" Elevation h'i - S'ect " "fbi -Sect,"
FMPC Norwood, blass. Epd A'o. /Z4S4 9 ~
9 ~
57
li 4l
Page No. ZC Sprinkler Heads Separation 8efween
'Vli "and'Zo-Secf "Areas (Control Head) Curbed Dune'esfs.
Plan View ."Hi-Sec&on- Bldg. Q3
&posed Slee/
Test Structure Prot'ected Steel Co/umn and 8eam A/of Loaded'.
Drainage Trench Curbed Dunng 7esfs Section A-A FMRC EpE. A'o. 643'4 Norwood. Mass. 9.9 57
0 II 0
Appendix SQ&
LOCA 7IONS AIIID /OZ'NTIIFIICA7 IOUS OF FLOOR ANO CE!L//NG 7HERMOCOLl/ LES
/Z4-S4 st /
StrNure~
eo zo ~<<so
<(S F(oor Fs f" below 5vnace of Cuncrrfe Plan 'V'ewer Hugh Sect 8ldg. /B
'Ceih'ng W Qn Qrs 8" be/ow Ce/ ling.
/&era/ Locaflons
>arne as F/oor F~
Oi4 ec.
<<woo+,'ass.
~O 0'
Appena'i'x Shee j2 8 j2Z io 6Z XZk 8"1 2S Plan ai ZO R. Level
/0 roI Nonh or Socnh Elevation 8 1 /84-2Z 8 I2Z 8 1'8A Plan aC box h /he ioH F Floor Leve/s All8"2 Grams > bofh /he /Ofy. g Floor levels are 5'long.
7he Members Form/ng Phe 2O 6 Horizontal Level were cuP to mal'e a lO'x iO'guare. The Assem6ly was krmeciby Elec,Are 8'cldi'ng.
'~ RC.
ho<~~os, Mass.
~O iO 0
Appena'iX She& Z lOCArlON OF 7ffERNOCODPL ES ON STEEL SrvuCru~Z rzwzw (AII pcened r'n S&el gio "oeep>
F~
84( )
85 Ce) 90(f) 91(e) 87(c) 86(F) 7/(b) 89Ce) 72 &')
Location oF
+S 88&) on Upper Crossarm
(~c I Ps =() 28'6(cO 6" 92 C 77(c) ~
78(a) 79(b) 80 (c')
88(f) 99(c) 9S(e) 94 (F) 97(e) Sr(c)
Location oF.
ps Local/on oF 96&') on Lcrwer Crvssarrn 75 on H- Calurrin Ug (e)
Lotion oF W Locw ion oF Fs on Crossarm on H" Column G.oss Sec&ton Cross Sec+ion x (a)
(Sca/c -ls" S
")
x(b)
~ X
&2~/z"+
Oown (d) rior Ppf N<. rZOZ+
+cod @lass. 9-9-57
0 0
il
Appendix 'Sheet 4 PROPERTIES OF LUBRICATING OIL
'.C.
USED'est O.C.
No e of'i1 Used 7 oF'6 Viscosity oF 7'lash Fire 1, 2, and 3 Gulf'."Paragon 41" 5 ad.n>. 36 sec 59 sec 345 365
~
4 and 5>. 86$ Guif->>Par, 38").
34$ Gulf->>Par ~ 41>>) 3 min> 28 sec 48 sec 345 355
+Proportions are. hy,volume.. 'The origina1 intent.was to use Gulf "Paragon 41" throughout Gulf "Paragon 38>>. was used in the proportions shown due to an inadequate. supply of Gulf "Paragon 41" ~
pg tory
'<<dp Mutual Research Massachusetts Corporation Report No 134,34 Sept. '9, 1957
~O II
APPh=nCkX Sheek S 0
RATE OF'lAME SPREAD-.7 EST f Fovr Observer~
X QO 0
0
/6 /8 20 7am e a&er Ignthon AAnU~em'p~
No. /Z484.
9-9-57
~li Il
A'o. /
ZOOO 0 0 7 ES7 V ~S Ie 0 0 Maxi'mum Cei'ling Temperature f4 a'60O 0 0 rs z8
/200 2K'P Fire RaCh'kiS rO'Si
/7 ss T/ me f9 from Stark 2O
. Zf Mlnu des 22 24.
n
0 II
o Q 2000 TEST Na. 1 Max/ %0m H"Colvmn Temperatures
-O fO 5'above
/0-20 +Floor
%8f
/600 f200 800 KO above Floor F77 2i/g' Fire Radias ro.',fs'6 f7 f8 20 2f 22 Tx'me from S)ai-') Ak'nuPes
0 4l
TEST Na. i C 0
2000 ~i Max]'muon Crossarm Temperatures C
L Vpper and Lower 1600 Lower Crossar m gg 97
/200 800 Upper~
Crossarm g 90 400 to's'-
Fire Radius 0
0 a) Z 0 l6 17 1B >9 ZO 2Z 24 7i'me from Stark AA'nufes
~Ci
'0 0
200Q Maxi rn um H- Column Temperatures 0 -10 f600 tO'-2O'.
~ f200 5'bove floor I ip 84 800 ZO'above floor g77 Fire R'adtus 5' 17 I9 20 2r 22 Time From Start M/'nuked
0 0
TEST No .2 2000 Maximum Crossarm Temperatures 1600 Upper and Lower 4
. 1200 E
800 Lower Crossarm Pg s8 Firq ~
5'pper Crossarm f91 RaChus Cs 6V-I
/7 18 20 21 22 4) o tn 7ime From Start' Minutes
'li 0
0
~ ~
TEST Mo.3 OOOO 0 0
'g l3 f6 Maximum Ceil)'ng Tern perature 0 0 ff f7
. t600 0 0 I5 18 4
l
~ f200
}
800 yC
~
0",S%~
yO F/rq Pad)us gl 3 6.
Time from Sf'arf AA'n ufes
~ ~
0 0
TFST Mo.3 Z000 Maxi'mum 8-Column Temperatures 0 10 f600 /O'- eo' 1
~ 1200 +&jr o
~r dP E
~QJ r
800 7-8l ~
5'ebov f0'boVe
"."/oor floor Q 77 400 Fire 3 ',
From Start Minutes 5'/me
'0 4l
Q TEST No 9 8000 Maxirnuin Crossarm 7ernperatures Upper and Loner 4.
0
~ f200 800
~4 4+
'Sp Lower Crossarm
~Upper Fire Crossarm Radivs @B7 gl 7/'me frotn SfaH Minutes
0 0
0<
< R
<n TEST No.<
2000 i~
Maximum Ceiling Temperafure L
1600 Reco der 0 0 OF'1. $ 13 16 0 0 14 11 0 0 15 16 g f8 CD
'b '0 CD Z 3 5 0
Vs W 7ime affer Start M]'nukes
Cl ll
Tzs7. No. 4 2000 kfANINUN 8" C0LvwY TENPEAATDREs 0 - 1'0
/600 20' 10 -
l200 record'er 800
/0 Above Floor P'7 4O0 7/2'bove Floor 480 0
480 0
Time From Star t Minutes
Cl 1'
~ + ~
2000 Tzs7 bio.4 AAx!au~ CRossaR~ TE!rIPERAruREs
/600 UPPER AN0 LovvER p+ /200 Rec rder 800
/ower~
Crossarm 498 ON98 Up er 4oo Cr s sarm 85 Time From Start Minutes
Tzsr No.5 0 0 2000 %/9 /6 Maximums Czu ms 7Ews zuAruuE.
0 0
/4. /7 0 '80
/6oo /5
~l2QO L4 h h M CS 0'oo
/0 /2 T/ me frorv Start QfnL/des
0 0
0
2000 Gs7 A/o.5' 0
~4 4/AxlMUN IY- Cot, Uhlan'ENPEpAlvRE$
o'- /0'0
/600 -
/7/Z Abc ve Floor ZO'/2 g 72 p l200 AbOv8 Floor g80 8oo Woo D /0 Time From Start Minutes
II O'AXlklUbl CROSSARM TEMPERATURES:
2000 UPPER ANo LowER
/600
~ 'ower
/ Vpper Crossarm 4.90 Cessarm
...4'.97 p+/200 80O 4OO 0 /0 0
7 jme From Start - bfinuPes
~O Ap endix Sheet 2f Hatch
@ 1 0 0
Hatch e 2 0 0 0 T8s& Z Plan View - Hi -Sect."Showing Pattern ot" Sprinkler Heads Opened. (.6) 78SS 3 0 0 Hatch e P 0 0 Hatch 0 0 0 Z 0 KMNc 8'pd. Alo. gg34'.
/Var uvood,bless: 9 ~
$7
i
~
Appendix Sheet 22 TABULATXON OF 'gEST CONDZZXONS AND RESULTS Wind Ventilation Direction Degrees Wind Outside FLoor Oil rea Opened. at Area- Opened. at Prom Velocity Temp-Test No. Tem -'P Tem - P Ft Min-Sec S Ft Min-Sec North MPH oF 1/0 165-170 $2 0-00 ~
28- 10 to 15m 270 86
+H 10-00 +28 18-1/2 to 20m 2 170-175 164 0-00 56 0-00 -- No Observation--
1H 180-185. 164 0-00 161 0-00 -- No Observation ,
4 109 184 164 0-00 224 0-00 140 10-15 69 117 165-170 164 0-00 224 0-00 ~
180 10 60.
Time Time to 5 ft Maximum 'I after Pire Pire (1), Six simultaneous fires.
of'irst Radius Radius Observed. Start When 1st Radius FLgures ard typical fire
'of'ne Fire Spread. of'pread A.S'. Operates Observed area.
Test No. Min-Sec Min-Sec Ft Ft i (2) Maximum radius possible 16-00 2-45 15 for ind,ividual fire area
'2 18-19 1-21 .6 6 before merging, with a+a-0-00 1-25 cent fire area. (Max. area 6 6 4(1) 0-00 10(2) involved, - 1400 sq ft) 0-55 5 0-00 1- 5 ~
5(5) , (>) Maximum persistent'ize is given. Occasional mo<<
~
mentary outshoots not included..
Time 1st Time 1st SprinM.er Sprinkler'perates Discharge Operates Pressure Sprinkl.er'ischarge Number (1). Xnitial valu=s only.
Min-Sec Min-Sec At of Sey text for in-From From 1st Sprinklers Density rinklers 'reases.
Test No. I nition Pire S read, PSX GPM Ft ned. (2) Manual control. A13.
24(') 24 heads open when 1 20-45. 4-45 5 0.1>
.. 5--' water supplied to 2 19-57 x8 .0.1$ 17 them.
2-03.. 2-'Ol 0.15 11 4 1-50 3.-50 5 24(2) .15 5 1- 9 1- 9 5(1) 0.1 (1) 24 FACTORY MPiUAL RE~~CH CORPORATION Report No. 1$ 4$ 4 Norwood, Mass. September 9, 1957
0 0
t ib
Appendix Sheet 2y
SUMMARY
OF MAXIMUM TEMPERATURE DATA Avera es oz Maximum Recorded Tem eratures F Ceiling Ceiling Steel Steel Steel Steel
$ 2 ft Structur Structure ,Structure Structure Laterall Laterally H-Colum H-Column Lower from from 0'o 10'o Cross- ~ .
~
Upper Cross-est Ignition Ignition 10'bove 20'bove arms ,arms 10'evel 0 ~ Point Point Floor -
.Floor 20'evel 1/25 865 14qo 148o 16oo 10/5
$ 50 66o 505 .,550.
275 580 505 4(1) ly75(2) 6oo 900 950 870 86o 6o5 1145 1>80 1510 1510 (1) Average maxima are probably above values'hown for Test No.
because rapid temperature changes occurred. in less time than that required 'for one complete printing cycle of temperature recorders.
(2) Single average maximum ceiling. value'iven because this fire * ~
was from multiple rather than s1ngle point ignition.
t FACTORY MUTUAL RESEARCH 'CORPORATION Report No. 3.5434 Norwood., Mass. September 9, 1957
1 0
Cl 0