{{#Wiki_filter:M-663-00017A, Revision W03 Page G281 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:
1101-1974 Buildi ng: Auxi liary Fire Area:
== Description:==
General Floor Area No. Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-OS1311 N/A Member Type: Beam N/A Member Size: 2 1 X 155 N/A Comments:
There are no co l umns i n this room. NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartme nt Length (ft): Compartment Height (ft): 02.1_ Temperatu re_NV.xls (V ers i on 1805.1) 650 14.5 215 25 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent
== Description:==
25 22.5 25 A-01 Barrier Type: Concrete Largest of two large v ents u sed (south corridor)
Barrier Thickness (in): 24 Initial Room Temp. (F): 104 NUREG-1805 FDT Results Hot Gas Layer Temperature@
180 minutes (F): 163.47 Room Sketch: !)of-(E
/.lOT SJN)Witl FOK M-663-00017A , Revision W03 Page G282 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1101-1974 Thermal Short #1 Sketch V/£W LODJ:J Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.
M-663-00017A , Rev i sion W03 Page G2B3 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:
==
Description:==
Drawing: Member Type: Member Size: Comments:
1120-1974 Building: Ge nera l Floor Area No. 2 Thermal Short #1 (TS1) Data C-OS1231 Beam 24 X 76 Embedded beam. no evaluation requ i red. Sketch & photo for reference only. Auxi liary Fire Area: Thermal Short #2 (TS2) Data C-OS1001 Co l umn 14 X 342 NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.1_Temperature
_NV.x l s (Version 1805.1) Heat Release Rate (kW): 650 Vent Width (ft): 13 Compartment Width (ft): 24.5 Vent Height (ft): 22.5 Compartment Length (ft): 40 Top of Vent from Floor (ft): 13 Compartment Height (ft): 13 Vent
== Description:==
A-0 1 Barrier Type: Concrete One o f two v ents us ed wh i ch are the same s i ze Barrier Thickness (in): 24 Initial Room Temp. (F): 104 NUREG-1805 FDT Results Hot Gas Layer Temperature@
180 minutes (F): 246.20 Room Sketch: I """+/--_I Som* '0 Tli fl.. /.JCI" M-663-00017A , Rev i s i on W03 Structural Steel Fireproofing Data 1120-1974 Thermal Short #1 Sketch VI£ l....ooK/tJ(., liA57 T her m al S h ort #1 P h oto 1 -.. TS P age G284 of G2B-79 Appendix G2B sc.c..rtotJ A-A T h ermal S h ort #1 Pho to 2 No photo required.
M-663-00017 A , Rev i sion W03 Structural Steel Fireproofing Data 1120-1974 Thermal Short #2 Sketch Thermal Short #2 Photo 1 I ., I I rs 2 /113 4 2.
A*A Therma l Short #2 Photo 2 Page G285 of G2B-79 Appendix G2B M-663-00017 A. Rev i s i on W03 Page G2B6 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation
: Descr i ption: Drawing: Member Type: Member S i ze: Comments: NUREG-1805 FDT: 1121-1968 Build i ng: Auxiliary F i re Area: Access Pit Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data N/A Column 14 X 264 Rev i ewed beams as part of Room 1120. Cent e r column rev i ewed as part of sump area. FP coating approx. 2.5" C-1S1001 NUREG-1805 FDT Input Data 02.1_ Temperatu re_NV.xls (Vers i on 1805.1) Heat Release Rate (kW): 6 5 0 Vent W i dth (ft): 13 Compartment W i dth (ft): 13.5 Vent Height (ft): 62 Compartment Length (ft): 40 Top of Vent from F l oor (ft): 13 Compartment Heig h t (ft): 19 Ven t Desc ri pt i on: A-0 1 Barrier Type: Co ncrete One vent , o p en on three sides (Width = linear length along perimeter o f three sides) Ba r rier Thickness (i n): 24 Initial Room Temp. (F): 104 NUREG-1805 FDT Results Ho t Gas L aye r Tem pe r at ur e@ 1 80 m i nu tes (F): 2 1 8.80 Room Sketch: E.Lev. IC)Co9' T\tiS 'il::OOrY\ 1::-d\J\C'I.;J.IriJ l
112l.
M-663-00017A, Rev i sion W03 Page G2B7 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1121-1968 Thermal Short #1 Sketch V IE W Loo/<l tJfl Therma l Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017 A , Revis i on W03 Page G288 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:
1122-1974 Building:
A u x iliary Fire Area:
== Description:==
Ge n era l Floor Area No. 3 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-OS1341 Member Type: Beam Member Size: 36 X 260 Comments: NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Barrier Thickness (in): Initial Room Temp. (F): C-1 S100 1 Co lumn 14 X 342 Bui lding steel under N. hatch is protected by spr i nk l ers in lieu of fireproofing NUREG-1805 FDT Input Data 02.1_ Temperature
_NV.xls (V ersion 1805.1) 650 Vent Width (ft): 13 22.5 Vent Height (ft): 22.5 80.5 Top of Vent from Floor (ft): 13 13 Vent Description
: Conc rete L argest of two large vents used. 24 104 NUREG-1805 FDT Results Hot Gas Layer Temperature@
180 minutes (F): 220.98 Room Sketch: B.t:. 1 9 7'1' (illS) A-01 M-663-00017 A , Revision W03 Page G289 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1122-1974 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.
M-663-00017 A , Rev i s i on W03 Structural Steel Fireproofing Data 1122-1974 Thermal Short #2 Sketch '1/eliJ L!>Oji;IA/
A N61tTH Thermal Short #2 Photo 1 A l ' W i ll J }fZ Page G2810 of G28-79 Appendix G2B Sec.. TIOI.J A* A Thermal Short #2 Photo 2 M-663-00017A , Rev i s i on W03 Structural Steel Fireproofing Data Room-Elevation:
1130-1974 Building:
== Description:==
No rth C orrid o r Thermal Short #1 (TS1) Data Drawing: C-081321 Member Type: Beam Member Size: 16 X 36 Comments: Page G2811 of G2B-79 Appendix G2B A u xi liary F i re Area: A-01 Thermal Short #2 (TS2) Data N/A N/A No columns. NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Bar ri er Th i ckness (in): 02.1_ Temp e r a ture_N V.xls (Version 1805.1) 650 13.25 40 25 Concrete 24 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description
: 25 13.25 25 O n e of two ve nt s used of equal size. Max Temp. of 1 04 entered due all othe r open adjacent rooms , not in U S AR Table 3.11 Init i al Room Temp. (F): 104 NUREG-1805 FDT Results Hot Gas Lay e r Temperat u re@ 1 80 m i n u tes (F): 225.78 Room Sketch: a. cr. A I b [JTIQJ I> ... ' I p A . J:-::.aoo!
+-----4 1 Oil I v _,
M-663-00017A , Revis i on W03 Page G2812 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1130-1974 Thermal Short #1 Sketch s r.cno tJ A-A G t:: A!>T Thermal Short #1 Photo 1 Therma l S h ort #1 Pho to 2 M-663-00017A , Revision W03 Page G2813 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation
: 1202-1988 Building: Aux il i ary Fire Area: A-01
== Description:==
Access Area B & Ch il le r Surg e Tank Area Thermal Short #1 (TS1) Data Therma l Short #2 (TS2) Data Drawing: C-OS1331 C-OS1002 Member Type: B eam Column Member Size: 16 X 36 14 X 314 Comments: Add it io na l attachments i n close prox i mity. NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.1_Temp erature_NV
.x l s (V ersion 1805.1) Heat Release Rate (kW): 650 Vent Width (ft): Compartment Width (ft): Vent Height (ft): Compartment Length (ft): 14 37.5 Top of Vent from Floor (ft): Compartment Height (ft): 11 Vent
== Description:==
Barrier Type: Concrete Barrier Thickness (in): 24 Initial Room Temp. (F): 96 NUREG-1805 FDT Results Hot Gas Layer Temperature@
1 80 minutes (F): 303.33 Room Sketch: ..  "If lf I oPc"Jw,.,.
t I __ !  --------*1.------4 11 15.5 1 1 M-663-00017A , Rev i sion W03 Page G2814 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1202-1988 Thermal Short #1 Sketch VIe s e..c.I/61J le-A Thermal S h ort #1 Photo 1 Thermal Short #1 Pho to 2 M-663-00017 A , Rev i s i on W03 Page G2815 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1202-1988 Therma l Short #2 Sketch Thermal Short #2 Photo 1 Therma l Short #2 Photo 2 M-663-00017A , Rev i s i o n W03 Page G2816 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation
: 1117-1974 Build i ng: Auxi l iary F i re Area:
== Description:==
Boric Acid Tank R oom A Thermal Short #1 (TS1) Data Thermal Sho rt #2 (TS2) Data Drawing: Member Type: Member Size: C-OS1421 Beam 27 X 84 N/A N/A N/A Comments: Additiona l 4" W shape i n c l ose proxim i ty. There are no co lumn s in this room. NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment He i ght (ft): NUREG-1805 FDT Input Data 02.1_ Temperature_
N V.xls (Ver s ion 1805.1) 650 19.5 22 5 51 Vent Width (ft): Vent Height (ft): Top of Vent fr om F l oo r (ft): Vent Descr i pt i o n: 31 19.5 51 Barrier T ype: Concrete Natural air movemen t from transfer gr ill es Bar r ier T h i ckness (i n): 12 Initia l Room Temp. (F): 104 NUREG-1805 FDT Resu l ts Hot Gas La y er Te m peratu r e@ 1 80 mi nutes (F): 1 91.12 Room Sketch: P C r o eOCW'rl I A-03 M-663-00017A , Rev i s i on W03 Page G2817 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1117-1974 Thermal Short #1 Sketch II /liVJ Lto IA.I E 5f.C..TION A*A Thermal Short #1 Photo 1 Thermal Short #1 Pho to 2 M-663-00017A , Rev i s i on W03 Structural Steel Fireproofing Data Room-Elevation:
1301-2000 Building: Description
: Corridor No. 1 Thermal Short #1 (TS 1) Data Drawing: C-1 81411 Member Type: Beam Member Size: 21 X 62 Comments: Page G2B18 of G2B-79 Appendix G2B Auxi l iary Fire Area: A-08 Thermal Short #2 (TS2) Data N/A N/A N/A No columns. NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): 02.1_ Te mperature_NV.xls (Version 1805.1) 650 14.5 215 25 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Descrip tion: 25 14.5 25 Barrier Type: Concrete One of two large ven ts of equa l size used (North Corridor)
Barrier Thickness (in): 12 Initial Room Temp. (F): 104 NUREG-1805 FDT Results Hot Gas La ye r Tempera tu re@ 180 minutes (F): 17 2.58 Room Sketch: -P6DR 11D I 2. O""R I M-663-00017A , Revis i on W03 Structural Steel Fireproofing Data 1301-2000 Thermal Short #1 Sketch I . I>* *
* l.l fo 1* uo* * *
* 11 : () *
* t> *
* 4" C.Ro\S ( T'O) W ?..I X 1..2. (oTRA'f VIEW oOt..IJ./f..
NDRTH 3"x g** TU (; O::.fL [ 'f'.c'?) Page G2819 of G2B-79 Appendix G2B Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017A , Revision W03 Structural Steel Fireproofing Data Room-Elevation
: 1314-2000 Building:
== Description:==
Corridor No. 3 Thermal Short #1 (TS1) Data Drawing: C-1 S1411 Member Type: Beam Member Size: 27 X 84 Comments: Page G2820 of G28-79 Appendix G2B Aux il ia ry Fire Area: A-08 Therma l Short #2 (TS2) Data C-OS1002 Column 14 X 228 Large area caused by 2 ea. Tu be steel orientated across column. NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): 02.1_ Temperature_INV
.xls (Version 1805.1) 650 20 1 21 25 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description
: 25 33 25 Barrier Type: Concrete Largest opening v ent used of two large openings. Barrier Thickness (in): 12 Initial Room Temp. (F): 104 NUREG-1805 FDT Results H ot Gas Layer Temperature@
1 80 minutes (F): 164.57 Room Sketch: ., l l (O>{TA tiJ Me!: NT M-663-00017 A , Revision W03 Page G2821 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1314-2000 Thermal Short #1 Sketch SI!L.T 10.J A.-A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017A , Revision W03 Page G2822 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1314-2000 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 M-663-00017A, Revision W03 Page G2823 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:
1315-2000 Building:
Aux iliary Fire Area: A-08
== Description:==
Ctmt Spray Additive Tank Area Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-081421 Member Type: Beam Member S i ze: 24 X 84 Comments; NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Barrier Thickness (in): Initial Room Temp. (F): C-081002 Column 14 X 398 Additional at ta chments in close proximity. NUREG-1805 FDT Input Data 02.1_ Tempera tu r e_NV.xls (V ersion 1805.1) 650 13 21.5 25 Concrete 24 104 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent
== Description:==
NUREG-1805 FDT Results 7.5 3.5 7.5 Hot Gas Layer Tempe ratur e@ 180 minutes (F): 500.83 Room Sketch: I' I
M-663-00017 A , Rev i s i on W03 Structural Steel Fireproofing Data 1315-2000 T h ermal Short #1 Sketch Therma l Short #1 Photo 1 l'too t , ,..::.--1.4*
::.TI'NT
* Page G 2 8 2 4 of G2B-79 Appendix G2B Thermal Short #1 P h o to 2 No photo required.
M-663-00017A , Rev i s i on W03 Page G2B25 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1315-2000 Thermal Short #2 Sketch Thermal Short #2 Photo 1 T hermal Short #2 Photo 2 No photo required.
M-663-00017A , Revision W03 Page G2B26 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:
1318-2000 Building:
Auxi li a ry Fire Area: A-08
== Description:==
V a lv e Compartme nt Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0 8 1 421 Member Type: Beam Member Size: 33 X 11 8 Comments: N/A N/A N/A No co l u mn s. NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.1_ T emperatu r e_N V.x l s (Vers i on 1 805.1) Heat Release Rate (kW): 650 Vent Width (ft): Compartment Width (ft): 1 7 2 1.5 25 Vent Height (ft): Compartment Length (ft): Top of Vent from Floor (ft): Compartment Height (ft): Vent
== Description:==
Barrier Type: Conc r ete Barrier Thickness (in): 3 6 Initial Room Temp. (F): 1 04 NUREG-1805 FDT Results Hot Gas Layer Temperature@
180 minutes (F): 481.16 Room Sketch: A4) _ r ,.H _..,_
ef!t. AReA I Etev .-; T 313 t{)(XI ( ** !-r--r--------= 40 " (.vrs) * .l>
.. *' L "''x<! IHJI' \ ______ ,.!._ * . . ,'-------------Jet:. __ 1?. ...... 13/817 * ... 0 '*"' -/ * .0 ''f 7.5 3.5 7.5 M-663-00017A , Revision W03 Page G2B27 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1318-2000 Thermal Short #1 Sketch W33X liB y "' .. A-A r-r::\ -----'LI Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017A , Rev i sion W03 Page G2B28 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevat i on: 1320-2000 Building: Auxiliary F i re Area:
== Description:==
C o rrido r No. 4 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0 5 144 1 Member Type: B eam Member Size: 16 X 40 Comments: NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barr i er Type: Barr i er Thickness (in): Initial Room Temp. (F): C-151001 Col umn 14 X 264 B uilding steel under N. hatch i s protected by sprinklers in lieu o f fi r eproofing. NUREG-1805 FDT Input Data 02.1_ Temp e ra ture_NV.xls (Ver s i on 180 5.1) 650 Vent Width (ft): 25 36 Vent Height (ft): 14 53 Top of Vent from Floor {ft): 25 2 5 Vent
== Description:==
Concrete Largets o f two large open i ng used 24 104 NUREG-1805 FDT Results Hot Gas Layer Temperature
@ 1 80 m i nutes (F): 1 94.1 3 Room Sketch: A-08 M-663-0 0 017A , Revis i o n W03 Page G 2829 o f G2B-79 Structural Steel Fireproofing Data Append i x G2B 1 320-2000 Thermal Short #1 Sketch St::C.TlOIU A.-A-Thermal S h ort #1 Pho t o 1 Thermal S h ort #1 P h oto 2 No photo required.
M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1320-2000 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Page G2B30 of G2B-79 4.4 , A.IIIT sm .. JJ Thermal Short #2 Photo 2 Appendix G2B M-663-00017A , Rev i s i o n W03 Page G2B31 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:
1401-2026 Building: A uxiliary F i re Area: A-1 6
== Description:==
Component Coolin g P ump & Heat E xch Area B Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1 51 5 1 1 C-0 5 1002 Member Type: B eam Column Member Size: 24 X 76 14 X 158 Comments: Tube stee l i s or i enta t ed to cause 144 square Inches of unprotected steel. NUREG-1805 FDT: Heat Release Rate (kW): Compartme n t Width (ft): Compartment length (ft): Compartment He i g h t (ft): Barr i er Type: Ba r rier Thi ckness (i n): I nitial Room Temp. (F): NUREG-1805 FDT Input Data 02.1_ Tem p erat u re_NV.xl s (V e rsion 1805.1) 650 36.7 5 66 20 Conc r ete 1 2 104 Ve n t Width (ft): Vent He i ght (ft): Top of Vent from F l oor (ft): Vent Descr i pt ion: NUREG-1805 FDT Results H o t Gas layer Temperat u re@ 1 80 minutes (F): 176.12 Room Sketch: G.I.S A zou.1 (NT'O} N I I L_ __ 2 0 36.75 20 M-663-00017A, Revis i on W03 Page G2832 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1401-2026 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017A , Revision W03 Page G2B33 of G2B-79 Structural Steel Fireproofing Data Appendix G28 1401-2026 Thermal Short #2 Sketch Jf NO OY"' l S*o 1'-il-14tf SQ IN om*SScO'-)
Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 M-663-00017A , Revis i on W03 Page G2834 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:
1402-2026 Building:
A u x i l i ary F i re Area:
== Description:==
Cor r idor No. 1 Thermal Short #1 {TS1) Data Thermal Short #2 {TS2) Data Drawing: Member Type: Member Size: Comments: C-1 S15 11 Bea m 24 X 68 A d d i t ion al angle s t ee l within cl ose prox i m i ty. N/A N/A N/A No c ol umn in thi s roo m. NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Barrier Thickness (in): Initial Room Temp. (F): 0 2.1_ T emperatu r e_N V.xls (Vers i o n 1 8 05.1) 6 50 1 5 41 20 C o nc r ete 24 104 Vent W i dth (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description
: NUREG-1805 FDT Results Hot Gas Layer Temperature@
180 minutes (F): 238.98 Room Sketch: @---------------"' flf z.a u.: (..m.) ______________ Will .. )*-II l I I I! , 2 0 1 4.5 2 0 A-1 6 M-663-000 1 7 A , Rev i s i o n W03 Page G2835 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1402-2026 Thermal Short #1 Sketch 0 * <J --b I> -7 I APre*. Therma l Short #1 Photo 1 Thermal Short #1 P h o to 2 M-663-00017A , Revision W03 Page G2836 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation
: 1406-2026 Building: Auxil i ary F i re Area: A-16 Description
: Component Cooling Pump & Heat Exch Area A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1521 C-OS 1 002 Member Type: Beam Co l umn Member Size: 27 X 8 4 14 X 228 Comments: Add i t i o n a l i tems w i th i n close proxi m ity. NUREG-1805 FDT: Heat Release Rate (kW): Compartment W i dth (ft): Compartment Length (ft): Compartment He i ght (ft): NUREG-1805 FDT Input Data 0 2.1_ Temperature
_NV.x l s (Vers i on 1805.1) 650 26 61 20 Vent Width (ft): Vent Height (ft): Top of Vent from F l oor (ft): Vent
== Description:==
Barr i er Type: Conc r ete Room (vent) i s open on tw o sides Barr i er Thickness (i n): 1 2 Initial Room Temp. (F): 104 NUREG-1805 FDT Results Hot Gas Layer Temperature@
1 80 minutes (F): 170.15 Room Sketch: T 3 -EL*V. 20zb ... N >>TS * .... I> "' 20 76.5 20 M-663-00017A , Revision W03 Page G2837 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1406-2026 Thermal Short #1 Sketch Th ermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017 A , Rev i sion W03 Page G2838 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1406-2026 Therma l Short #2 Sketch 5eC.T IO N A*A Therma l Short #2 Pho to 1 Thermal Short #2 Photo 2 ;i !J*... . . . . .,_ . , ; .. n --
M-663-00017 A , Revision W03 Page G2839 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:
1408-2026 Building:
Auxiliary Fire Area:
== Description:==
Co rridor No. 2 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1541 Member Type: Beam Member Size: 21 X 55 Comments:
NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Barrier Thickness (in): Initial Room Temp. (F): C-1S1 001 Column 14 X 158 Building steel under N. hatch is protected by sprinklers in lieu of fireproofing per drawing. NUREG-1805 FDT Input Data 02.1_ Temperature
_NV.xls (Version 1805.1) 650 18 215 20 Concrete 12 104 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent
== Description:==
NUREG-1805 FDT Results 20 88.5 20 Hot Gas Layer Temperature@
180 minutes (F): 147.76 Room Sketch: A-16 M-663-00017A , Revision W03 Structural Steel Fireproofing Data 1408-2026 Thermal Short #1 Sketch
* A -* (i -. b , A -, a. . 0., . : t> Thermal Short #1 Photo 1 L> -' '-* -() . sc:c.no!J A* A Page G2840 of G28-7 9 Appendix G2B ] Thermal Short #1 Photo 2 M-663-00017A , Rev i s i on W03 Structural Steel Fireproofing Data 1408-2026 Thermal Short #2 Sketch Thermal Short #2 Photo 1 73 2 I Page G2841 of G2B-79 Appendix G2B A.-A Thermal Short #2 Photo 2 M-663-00017A , Rev i s i on W03 Page G2842 of G2B-79 Structural Steel Fireproofing Data Appendix G28 Room-Elevat i on: 1504-2047 Building: A ux i l i ary Fire Area: A-1 9 Description
: C t mt Purge E xhaust & Mech E qu ip Rm B Thermal Short #1 (TS1) Data Therma l Short #2 (TS2) Data Drawing: C-081631 C-0 8 1002 Membe r Type: Beam Co l um n Member Size: 24 X 68 14 X 184 Comments: Add i tional attach m ents i n close proxim i ty. Ad d i t io n a l at t ac h ments in close proxi m i t y (53" a n gle s uppo rt s). NUREG-1805 FDT: Heat Release Rate (kW): Compartment W i dth (ft): Compartment length (ft): Compart m ent Height (ft): Barrier Type: Barrier Th i ckness (i n): In i tial Room Temp. (F): NUREG-1805 FDT Input Data 02.1_ Tempera t u r e_NV.x l s (Ve r s i on 1 805.1) 650 39.75 89 25.25 Concre t e 12 104 Vent Width (ft): Vent He i ght (ft): Top of Vent from Floor (ft): Vent Descrip t io n: NUREG-1805 FDT Results Hot Gas l ayer T e m pe r at ur e@ 1 80 m i nu tes (F): 179.58 Roo m Sk e tc h: N
* EI.EV. "U-t7' 25.25 14 25.25 M-663-00017A , Revision W03 Page G2843 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1504-2047 Thermal Short #1 Sketch 6 * ' . 6 * . * *. 0 VIi Thermal Short #1 Photo 1 Therma l S h ort #1 P h oto 2 N o photo required.
M-663-000 1 7A , Revis i on W03 Page G2B44 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1504-2047 Thermal Short #2 Sketch S*C..TI6N A* A. Therma l Short #2 Photo 1 Thermal Short #2 Photo 2 N o photo required.
M-663-00017A , Rev i s i on W03 Page G2B45 of G2B-7 9 Structural Steel Fireproofing Data Appendix G2B Room-Elevation
: 1506-2047 Bu i lding: Au xiliary Fire Area: A-1 9
== Description:==
Ctmt Pu r ge S upply A i r Hand l i ng Un it A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Draw i ng: C-1 S 1641 C-1 51 001 Member Type: Beam Co lu m n Member Size: 24 X 76 14 X 3 7 0 Comments: Monora i l deter min ed to b e not w orse case , spacers and f ire proo fi ng insul a te a ttachme n t con f iguratio n. O r ien t at i on of tub e stee l c a us e s 5 6 p l us 16 squa r e i nches o f unpr ote cted surface. NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.1_ Tempe r a t ure_NV.x l s (V e r si on 1 805.1) Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Barr i er Thickness (in): Initia l Room Temp. (F): 650 48 94 25.25 Concrete 12 104 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description
: NUREG-1805 FDT Results Hot Gas L aye r Te m pe r a tur e@ 180 minutes (F): 175.17 Room Sketch: TW%1lt7C..
.1:! (1'5*1) t*N/ c tAQ ,lY 2 5.25 1 4 2 5.25 M-663-00017A, Revision W03 Page G2B46 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1506-2047 Therma l Short #1 Sketch WZ.-4 X7(.. Thermal Short #1 Photo 1 Therma l Short #1 Photo 2 N o photo required.
M-663-00017A , Rev i sion W03 Page G2847 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1506-2047 Thermal Short #2 Sketch Thermal Short #2 Pho t o 1 T hermal Sho rt #2 Photo 2 No photo required.
M-663-00017A, Revision W03 Page G2848 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation
: 1513-2047 Building: Auxiliary Fire Area:
== Description:==
Control Bldg V ent Supply A/C Unit Rm Thermal Short #1 (TS1) Data Thermal Short #2 (T S2) Data Drawing: C-081621 C-081002 Member Type: Beam Column Member Size: 24 X 76 14 X 184 Comments: Add i t i onal strut con n ect i on in close prox i m i t y. Add i t i ona l angle i n c l ose proxim i ty. NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.1_ Temperature
_NV.xls (Version 1805.1) Heat Release Rate (kW): 650 Vent Width (ft): Compartment Width (ft): 35 Vent Height (ft): Compartme_nt Length (ft): 15 25.25 Top of Vent from Floor (ft): Compartment Height (ft): Barrier Type: Barrier Thickness (in): Initial Room Temp. (F): Concrete 1 2 104 Vent Descr ip tio n: NUREG-1805 FDT Resu lt s Hot Gas Layer Temperature@
180 minutes (F): 222.58 Room Sketch:  ----,- I j /'\. I H
* v 'Ill -I ! 15*3] I , j) vJ2At 1t
* I_JI --I II W E1&#xa3;V. Zo41" j f I I /.JT) JiJ f-.....
- -OPe>l TO tVI 150(. ' I ... 25.25 15 25.25 A-19 M-663-00017 A , Revision W0 3 Page G2B49 of G28-7 9 Structural Steel Fireproofing Data Appendix G2B 1513-2047 T h erma l Short #1 Sketch S&#xa3;CTICI-J A-A Therma l Short #1 Photo 1 T herm al S h ort #1 P h oto 2 No photo required.
M-663-00017A , Revision W03 Page G2850 of G28-79 Structural Steel Fireproofing Data Appendix G28 1513-2047 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 M-663-00017A , Revision W03 Page G2B51 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:
1502-2047 Auxiliary Fire Area: A-20
== Description:==
Component Cooling Water Surge Tank Area B Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: Member Type: Member Size: C-081631 Beam 21 X 55 N/A N/A N/A Comments: Monora i l attachment , only 1 point is requ i red to be eva l uated. No columns. NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Barr i er Thickness (in): Initial Room Temp. (F): NUREG-1805 FDT Input Data 02.1_ Temperature
_NV.xls (Vers i on 1805.1) 650 39.75 16 25.25 Concrete 12 1 04 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description
: NUREG-1805 FDT Results Hot Gas Layer Temperature@
1 80 minutes (F): 219.21 Room Sketch: I &#xa3;t.eY 204-/ .Nrs 25.25 14 25.25 M-663-00017 A. Revision W03 Page G2852 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1502-2047 Thermal Short #1 Sketch . v I)
* w 2.11( 55 VJi.W LDol<tNI.
WrE ST Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.
M-663-00017A , Rev i s i on W03 Page G2B53 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:
1503-2047 Build i ng: A ux i li a ry Fire Area: A-20 Description
: Com po n e nt C oo li n g Wate r S urge T a nk A rea A Thermal Short #1 (TS1) Data Therma l Short #2 (TS2) Data Drawing: Member Type: Member S i ze: C-O S 1631 Beam 2 1 X 55 N/A N/A N/A Comments:
Mono r a i l attachme n t. on l y 1 po i nt i s requ i red to b e e va l uat ed. No co l umn s. NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment He i ght (ft): Barrier Type: Barrier Th i ckness (i n): I n i tial Room Temp. (F): NUREG-1805 FDT Input Data 02.1_T e mpe r ature_NV.x l s (Vers i on 18 0 5.1) 650 32 1 5 25.25 Con cr ete 12 1 04 Vent Width (ft): Vent Height (ft): Top of Vent from F l oor (ft): Vent Description
: NUREG-1805 FDT Results Ho t Gas L aye r Te m pera t u r e@ 1 80 m in u t es (F): 228.21 Roo m Ske t ch: N 25.25 1 4 25.25 M-663-00017A , Revision W03 Page G2854 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1503-2047 Thermal Short #1 Sketch A -A V/e.W LooKtiJCi Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.
M-663-00017A , Revision W03 Page G2855 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:
1505-2047 Building:
Auxiliary F i re Area: Description
: Corridor Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Draw i ng: C-OS1631 Member Type: Beam Member Size: 24 X 76 Comments: NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): N/A N/A N/A No exposed column. NUREG-1805 FDT Input Data 02.1_ Tempe ratu re_NV.xls (V e rsion 1805.1) 650 1 0 9 25.25 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Descript ion: 25.25 9 2 5.25 A-20 Ba r rier Type: Barrier Thickness (in): Concrete 12 One of two lar ge vent (equal in size) was used. Temp not in USAR Table 3.11 , used adjacent rooms Temp that are open to this room. Initial Room Temp. (F): 104 NUREG-1805 FDT Resu lt s Hot Gas Layer Temperature@
1 80 minutes (F): 3 1 7.54 Room Sketch: &#xa3;Lt l047 I NTS ** 0 , ... I -----. _.__ __ _
M-663-00017A , Revision W03 Structural Steel Fireproofing Data 1505-2047 Thermal Short #1 Sketch A Thermal Short #1 Photo 1 Page G2856 of G2B-79 Appendix G2B . '
* L' o ... . . --*_'Y**-t b
* STtJ;1. S c: c...l!o..J A *A Thermal Short #1 Photo 2 No photo required.
M-663-00017A , Rev i sion W03 Page G2B57 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation
: 1507-2047 Building:
A u xil i a ry F i re Ar e a: A-2 0 Descriptio n: Pe rsonnel Hatch Area Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Da t a Drawing: C-OS1631 C-1 S 1 001 Member Type: Beam C olumn Member Size: 24 X 75 14 X 158 Comments: Addit i ona l attachments in c l ose prox i m i ty. NUREG-1805 FDT Input Data NUREG-1805 FDT: 0 2.1_ Temperatu re_NV.x ls (Vers i on 18 0 5.1) Heat Release Rate (kW): 6 5 0 Vent W i dth (ft): Compartme n t Width (ft): Vent Height (ft): Compartment Length (ft): 32 33 Top of Ve n t from Floor (ft): Compartment He i ght (ft): Barr i er Type: Bar ri er T hickness (i n): Init i al Room Temp. (F): 25.2 5 Concrete 1 2 1 04 Vent Descr i pt ion: NUREG-1805 FDT Resu lt s Hot Gas Layer Te m perat ur e@ 1 80 m i n u tes (F): 223.79 Roo m Ske t c h: oPe:I<J -..;;-IS*i'---------------. !:LV. Zo47 I 25.25 9 25.25 M-663-00017 A , Revision W03 Page G2858 of G2B-79 Structural Steel Fireproofing Data Appendix G28 1507-2047 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.
M-663-00017A , Revis i on W03 Page G2859 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1507-2047 Thermal Short #2 Sketch St:CIION VIEW tiAST Therma l Sho rt #2 Photo 1 Thermal S h ort #2 P h oto 2 No photo required.
M-663-00017A , Revis i on W03 Page G2860 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:
1508-2047 Building: A u x i l i ary Fire Area:
== Description:==
Drawing: Ma i n S team Is o l a t i o n Valve R m No. 1 Thermal Short #1 (TS1) Data C-1 S 1 452 The r mal Short #2 (TS2) Data N/A Member Type: B e am Member Size: 30 X 99 Comments: NUREG-1 805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartme n t Height (ft): N/A N/A No column s. NUREG-1805 FDT Input Data 0 2.1_ T empera t ure_NV.x l s (V ersion 1 8 0 5.1) 650 Vent Width (ft): 22 35 48 Vent Height (ft): Top of Vent from Floor (ft): Vent Description
: 32 35 48 Barrier Type: Concrete Ope n to room be l ow an d at M i ss i l e S heil ds Barrier Thickness (i n): 2 4 Initial Room Temp. (F): 120 NUREG-1805 FDT Results Hot Gas La y er T empe r atu r e@ 180 mi n utes (F): 184.77 Room Sketch: A-2 3 M-66 3-00017A , Revisio n W03 Page G2B61 o f G2B-79 Structural Steel Fireproofing Data Appendix G2B 1508-2047 The rm al S h ort #1 Ske t ch
* tJ * . " liXI./fbfl/flt''
o/'*11 fi"FPt:!Cf11J,;
T/1 QtJ87.
,.,C..,.,
SH. T!o IJ A.-A T her m al S h o rt #1 Pho t o 1 Therm al S ho rt #1 P h o t o 2 No photo required.
No photo required.
M-663-00017A , Revis i o n W03 Page G2862 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation
: 1509-2047 Building:
Auxiliary Fire Area:
== Description:==
Main Stea m Is olation Valve Rm No. 2 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1452 Member Type: Bea m Member Size: 30 X 99 Com ments: NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): N/A N/A N/A No columns. NUREG-1805 FDT Input Data 02.1_ Temp erat ur e_NV.xls (Ver s i o n 1805.1) 650 22 35 48 Vent W i dth (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Descript ion: 32 35 48 Barrier Type: Concrete Open to room be l ow and at Missile Sheilds Barrier Thickness (in): 24 Initial Room Temp. (F): 120 NUREG-1805 FDT Results Hot Gas Layer Temperature@
1 80 minutes (F): 16 4.77 Room Ske tch: A-23 M-663-00017A , Rev i sion W03 Page G2863 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1509-2047 Therma l Short #1 Sketch .u 'Ny"" I -
II? "Ttii<'.,...T:
St:LTlbN A-A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 N o ph o to required.
No photo required.
M-663-00017A , Revision W03 Page G2B64 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:
1324-2000 Building:
Auxil i ary Fire Area: Description
: Feedwa te r Pump Valve Compartment No. 1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: Member Type: Member Size: C-181352 Beam 14 X 34 N/A N/A N/A Comments: Additional attachments i n close proximity (3" x 1/4" angle). No columns. NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): NUREG-1805 FDT Input Data 0 2.1_ Tempe r a t ure_NV.xls (Ve rsion 1805.1) 650 10 10 12 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description
: 3.5 3.5 1 0 Barrier Type: Conc rete Vent at ceiling to Room 1304 (3.5 X 3.5) Barrier Thickness (in): 12 Initial Room Temp. (F): 104 NUREG-1805 FDT Results Hot Gas Layer Temperature@
18 0 minutes (F): 975.88 Room Sketch: (o..JT. c:.uv. woo, Nts A 13241 v EL' z.ooo' A-29 M-663-00017 A , Rev i sion W03 Page G2B65 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1324-2000 Thermal Short #1 Sketch SE '-TI6N Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017A , Revision W03 Page G2866 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:
1330-2000 Build i ng: Auxi liary Fire Area: A-30
== Description:==
Feedwater P ump Valve Compartment No.4 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: Member Type: Member Size: C-1 51352 Bea m 8 X 1 7 N/A N/A N/A Comments:
Column encapsu la ted i n concret e , no i ssues w/column. NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): NUREG-1805 FDT Input Data 02.1_ Temperature
_NV.xls (V ersion 1 805.1) 650 Vent Width (ft): 10 Vent Height (ft): 10 Top of Vent from Floor (ft): 12 Vent
== Description:==
3.5 3.5 1 0 Barrier Type: Concrete O pen at ceil i ng (3.5 X 3.5) Hatc h way Barrier Thickness (in): 12 Initial Room Temp. (F): 104 NUREG-1805 FDT Results Hot Gas Layer Temperature@
180 minutes (F): 975.88 Room Sketch: Elf.V. l OOo ' }'Jr>
M-663-00017 A , Rev i s i on W03 Page G2B67 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1330-2000 Thermal Short #1 Sketch Loo 1N') No'!-rn Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017A , Revision W03 Structural Steel Fireproofing Data Room-Elevation:
==
Description:==
Drawing: Member Type: Member Size: Comments: 1206-1989 Building: P ipe Ch a se The r ma l Short #1 (TS1) Data C-1 S1352 B eam 14 X 34 Add i tional attachments in close proximity. Page G2868 of G2B-79 Appendix G2B A u x i l iary F i re Area: A-33 Thermal Short #2 (TS2) Da t a C-1 S 1001 C olumn 14 X 111 NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment W i dth (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Barrier Th i ckness (in): 02.1_ T e mperatu r e_NV.xls (Vers i on 1805.1) 650 23 38 10 Concrete 24 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Descriptio n: 10 12 10 Lrag est of two large vent openings used. No t in USA R Table 3.11 , us e d 1207 Temp because it is open to 1207 and dir e ctly adjacent.
Ini t ial Room Temp. (F): 106 NUREG-1805 FDT Results Hot Gas L a y er T e m pe ratur e@ 180 min utes (F): 3 1 6.93 Roo m Ske t c h: I I I I I I I EL&#xa3;Y.I?B9' NTS M-663-00017A , Revision W03 Structural Steel Fireproofing Data 1206-1989 Thermal Short #1 Sketch ;.J*r.. Thermal Short #1 Photo 1 /...ca>J.;-.J'j 4"Tlllk ITS\ SrL 0 Page G2869 of G28-79 Appendix G2B Therma l Short #1 Photo 2 M-663-00017A , Revision W03 Structural Steel Fireproofing Data 1206-1989 Thermal Short #2 Sketch Thermal Short #2 Photo 1 3--.... (lfO VA( 5u.Pr Page G2B70 of G2B-79 Appendix G2B St:C.TIO A*A Thermal Short #2 Photo 2 M-663-00017A , Revision W03 Page G2871 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevat i on: 1 207-1989 Bui l ding: A uxiliary F i re Area: Descr i ption: Pipe Chase Thermal Short #1 (TS1) Data Therma l Short #2 (TS2) Da t a Drawing: C-181352 C-1 8 1001 M e mber Type: B eam Column Member S i ze: 18 X 40 14 X 111 Comments:
Add iti ona l attachments in close prox imi ty. NUREG-1805 FDT: Heat Release Rate (k W): Compartment W i dth (ft): Compartment Length (ft): Co m pa rt ment He i g h t (ft): NUREG-1805 FDT Input Data 02.1_ Temperature
_NV.xls (V e r s i on 1 805.1) 650 23 38 10 Ven t Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Desc ri pt ion: 10 12 10 Barr i er Type: Concrete Lragest of two large vent open i ngs used. Ba r r i er Thickn e ss (i n): 2 4 I nit i al Room Temp. (F): 106 NUREG-1 805 FDT Resu l ts H o t Gas La ye r T em p eratu re@ 1 80 m inu tes (F): 316.93 Roo m S ke tc h: A-33 M-663-00017A , Revision W03 Page G2872 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1207-1989 Thermal Short #1 Sketch w-18J< 40
* Sf:t:: T tDII* A A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017A , Revision W03 Page G2B73 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1207-1989 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 M-663-00017A , Revision W03 Page G2B74 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation
: 3401-2016 Building:
Control Fire Area: C-35
== Description:==
Corridor No. 1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-083511 N/A Member Type: Beam N/A Member Size: 24 X 68 N/A Comments: No column s. NUREG-1805 FDT Input Data NU REG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height {ft): 02.1_ Temperature_NV
.xls (V ers i on 1805.1) 650 6 86.5 15.25 Vent W i dth (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description
: 15.25 11 15.25 Barrier Type: Block Temp. no t i n USAR Table 3.11 , used all adacent room temp of 90 Barrier Thickness (in): 8 Initial Room Temp. (F): 90 NUREG-1805 FDT Results Hot Gas Layer Temperature@
180 minutes (F): 276.82 Room Sketch:
M-663-00017A, Revision W03 Page G2875 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 3401-2016 Thermal Short #1 Sketch I
* tJ. . " . I . e..
* 0 . , . I 6.* ** rs St.:.t..f C N A*A Thermal Short #1 Photo 1 Therma l Short #1 Photo 2 M-663-00017A , Rev i sion W03 Structural Steel Fireproofing Data Room-Elevation:
==
Description:==
Drawing: Member Type: Member Size: Comments:
3406-2016 Building:
Corridor No. 2 Thermal Short #1 (TS1) Data C-083511 Beam 24 X 68 Additional Items i n close prox i m i ty. (6" l ong x 1/2" Plate). Page G2B76 of G2B-79 Appendix G2B Contro l Fire Area: C-35 Thermal Short #2 (TS2) Data C-083001 Column 14 X 426 Column embedded on both sides. ALBI is 2-1/2" thick minimum due to finish requ i rements. NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length {ft): Compartment Height (ft): 02.1_ Tempera ture_NV.xls (Version 1805.1) 650 11 20.75 15.25 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent
== Description:==
15.25 1 1 15.25 Barrier Type: Block Temp. not i n U8AR Tab l e 3.11 , used all adacent room temp o f 90 Barrier Thickness (in): 8 Initial Room Temp. (F): 90 NUREG-1805 FDT Results Hot Gas Layer Temperature@
180 minutes (F): 357.53 Room Sketch:
M-663-00017 A , Revision W03 Page G2877 of G28-79 Structural Steel Fireproofing Data Appendix G2B 3406-2016 Thermal Short #1 Sketch SE.c.TIO N A-fl.. Thermal Short #1 Photo 1 Therma l Short #1 Photo 2 M-663-00017A , Revision W03 Structural Steel Fireproofing Data Room-Elevation
: 3412-2016 Building:
== Description:==
Emergency Shower & Eyewas h Area Thermal Short #1 (TS 1) Data Drawing: C-OS3511 Member Type: Beam Member Size: 24 X 68 Comments: Page G2878 of G2B-79 Appendix G2B Control F i re Area: C-35 Thermal Short #2 (TS2) Data N/A N/A N/A No columns. NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): 02.1_ Temperature
_NV.xls (V ers ion 1805.1) 650 11 17 15.25 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description
: 15 25 11 15.25 Barrier Type: B l ock Temp. not in USAR Table 3.11 , used all adacent room temp of 90 Barrier Thickness (in): 8 Initial Room Temp. (F): 90 NUREG-1805 FDT Results Hot Gas Layer Temperature@
180 minutes (F): 373.15 Room Sketch: "'"'"} {Ni'S) '
M-663-00017A, Rev i sion W03 Structural Steel Fireproofing Data 3412-2016 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Page G2879 of G28-79 .ol w T'l sa '5TL A-A Therma l S h ort #1 Photo 2 Appendix G2B No photo required.}}

Latest revision as of 18:12, 26 April 2019

Fire Protection Evaluations for Unique or Unbounded Fire Barrier Configuration, M-663-00017A, Rev. W05, G2B1 to G2B79
ML17151B068
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 03/09/2017
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML17151A982 List: ... further results
References
WO 17-0045 M-663-00017A, Rev W05
Download: ML17151B068 (79)


Text

M-663-00017A, Revision W03 Page G281 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1101-1974 Buildi ng: Auxi liary Fire Area:

Description:

General Floor Area No. Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-OS1311 N/A Member Type: Beam N/A Member Size: 2 1 X 155 N/A Comments:

There are no co l umns i n this room. NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartme nt Length (ft): Compartment Height (ft): 02.1_ Temperatu re_NV.xls (V ers i on 1805.1) 650 14.5 215 25 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent

Description:

25 22.5 25 A-01 Barrier Type: Concrete Largest of two large v ents u sed (south corridor)

Barrier Thickness (in): 24 Initial Room Temp. (F): 104 NUREG-1805 FDT Results Hot Gas Layer Temperature@

180 minutes (F): 163.47 Room Sketch: !)of-(E

/.lOT SJN)Witl FOK M-663-00017A , Revision W03 Page G282 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1101-1974 Thermal Short #1 Sketch V/£W LODJ:J Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A , Rev i sion W03 Page G2B3 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

==

Description:==

Drawing: Member Type: Member Size: Comments:

1120-1974 Building: Ge nera l Floor Area No. 2 Thermal Short #1 (TS1) Data C-OS1231 Beam 24 X 76 Embedded beam. no evaluation requ i red. Sketch & photo for reference only. Auxi liary Fire Area: Thermal Short #2 (TS2) Data C-OS1001 Co l umn 14 X 342 NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.1_Temperature

_NV.x l s (Version 1805.1) Heat Release Rate (kW): 650 Vent Width (ft): 13 Compartment Width (ft): 24.5 Vent Height (ft): 22.5 Compartment Length (ft): 40 Top of Vent from Floor (ft): 13 Compartment Height (ft): 13 Vent

Description:

A-0 1 Barrier Type: Concrete One o f two v ents us ed wh i ch are the same s i ze Barrier Thickness (in): 24 Initial Room Temp. (F): 104 NUREG-1805 FDT Results Hot Gas Layer Temperature@

180 minutes (F): 246.20 Room Sketch: I """+/--_I Som* '0 Tli fl.. /.JCI" M-663-00017A , Rev i s i on W03 Structural Steel Fireproofing Data 1120-1974 Thermal Short #1 Sketch VI£ l....ooK/tJ(., liA57 T her m al S h ort #1 P h oto 1 -.. TS P age G284 of G2B-79 Appendix G2B sc.c..rtotJ A-A T h ermal S h ort #1 Pho to 2 No photo required.

M-663-00017 A , Rev i sion W03 Structural Steel Fireproofing Data 1120-1974 Thermal Short #2 Sketch Thermal Short #2 Photo 1 I ., I I rs 2 /113 4 2.

A*A Therma l Short #2 Photo 2 Page G285 of G2B-79 Appendix G2B M-663-00017 A. Rev i s i on W03 Page G2B6 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation

Descr i ption: Drawing: Member Type: Member S i ze: Comments: NUREG-1805 FDT: 1121-1968 Build i ng: Auxiliary F i re Area: Access Pit Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data N/A Column 14 X 264 Rev i ewed beams as part of Room 1120. Cent e r column rev i ewed as part of sump area. FP coating approx. 2.5" C-1S1001 NUREG-1805 FDT Input Data 02.1_ Temperatu re_NV.xls (Vers i on 1805.1) Heat Release Rate (kW): 6 5 0 Vent W i dth (ft): 13 Compartment W i dth (ft): 13.5 Vent Height (ft): 62 Compartment Length (ft): 40 Top of Vent from F l oor (ft): 13 Compartment Heig h t (ft): 19 Ven t Desc ri pt i on: A-0 1 Barrier Type: Co ncrete One vent , o p en on three sides (Width = linear length along perimeter o f three sides) Ba r rier Thickness (i n): 24 Initial Room Temp. (F): 104 NUREG-1805 FDT Results Ho t Gas L aye r Tem pe r at ur e@ 1 80 m i nu tes (F): 2 1 8.80 Room Sketch: E.Lev. IC)Co9' T\tiS 'il::OOrY\ 1::-d\J\C'I.;J.IriJ l

112l.

M-663-00017A, Rev i sion W03 Page G2B7 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1121-1968 Thermal Short #1 Sketch V IE W Loo/<l tJfl Therma l Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017 A , Revis i on W03 Page G288 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1122-1974 Building:

A u x iliary Fire Area:

Description:

Ge n era l Floor Area No. 3 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-OS1341 Member Type: Beam Member Size: 36 X 260 Comments: NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Barrier Thickness (in): Initial Room Temp. (F): C-1 S100 1 Co lumn 14 X 342 Bui lding steel under N. hatch is protected by spr i nk l ers in lieu of fireproofing NUREG-1805 FDT Input Data 02.1_ Temperature

_NV.xls (V ersion 1805.1) 650 Vent Width (ft): 13 22.5 Vent Height (ft): 22.5 80.5 Top of Vent from Floor (ft): 13 13 Vent Description

Conc rete L argest of two large vents used. 24 104 NUREG-1805 FDT Results Hot Gas Layer Temperature@

180 minutes (F): 220.98 Room Sketch: B.t:. 1 9 7'1' (illS) A-01 M-663-00017 A , Revision W03 Page G289 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1122-1974 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017 A , Rev i s i on W03 Structural Steel Fireproofing Data 1122-1974 Thermal Short #2 Sketch '1/eliJ L!>Oji;IA/

A N61tTH Thermal Short #2 Photo 1 A l ' W i ll J }fZ Page G2810 of G28-79 Appendix G2B Sec.. TIOI.J A* A Thermal Short #2 Photo 2 M-663-00017A , Rev i s i on W03 Structural Steel Fireproofing Data Room-Elevation:

1130-1974 Building:

Description:

No rth C orrid o r Thermal Short #1 (TS1) Data Drawing: C-081321 Member Type: Beam Member Size: 16 X 36 Comments: Page G2811 of G2B-79 Appendix G2B A u xi liary F i re Area: A-01 Thermal Short #2 (TS2) Data N/A N/A No columns. NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Bar ri er Th i ckness (in): 02.1_ Temp e r a ture_N V.xls (Version 1805.1) 650 13.25 40 25 Concrete 24 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description

25 13.25 25 O n e of two ve nt s used of equal size. Max Temp. of 1 04 entered due all othe r open adjacent rooms , not in U S AR Table 3.11 Init i al Room Temp. (F): 104 NUREG-1805 FDT Results Hot Gas Lay e r Temperat u re@ 1 80 m i n u tes (F): 225.78 Room Sketch: a. cr. A I b [JTIQJ I> ... ' I p A . J:-::.aoo!

+-----4 1 Oil I v _,

M-663-00017A , Revis i on W03 Page G2812 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1130-1974 Thermal Short #1 Sketch s r.cno tJ A-A G t:: A!>T Thermal Short #1 Photo 1 Therma l S h ort #1 Pho to 2 M-663-00017A , Revision W03 Page G2813 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation

1202-1988 Building: Aux il i ary Fire Area: A-01

Description:

Access Area B & Ch il le r Surg e Tank Area Thermal Short #1 (TS1) Data Therma l Short #2 (TS2) Data Drawing: C-OS1331 C-OS1002 Member Type: B eam Column Member Size: 16 X 36 14 X 314 Comments: Add it io na l attachments i n close prox i mity. NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.1_Temp erature_NV

.x l s (V ersion 1805.1) Heat Release Rate (kW): 650 Vent Width (ft): Compartment Width (ft): Vent Height (ft): Compartment Length (ft): 14 37.5 Top of Vent from Floor (ft): Compartment Height (ft): 11 Vent

Description:

Barrier Type: Concrete Barrier Thickness (in): 24 Initial Room Temp. (F): 96 NUREG-1805 FDT Results Hot Gas Layer Temperature@

1 80 minutes (F): 303.33 Room Sketch: .. "If lf I oPc"Jw,.,.

t I __ ! --------*1.------4 11 15.5 1 1 M-663-00017A , Rev i sion W03 Page G2814 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1202-1988 Thermal Short #1 Sketch VIe s e..c.I/61J le-A Thermal S h ort #1 Photo 1 Thermal Short #1 Pho to 2 M-663-00017 A , Rev i s i on W03 Page G2815 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1202-1988 Therma l Short #2 Sketch Thermal Short #2 Photo 1 Therma l Short #2 Photo 2 M-663-00017A , Rev i s i o n W03 Page G2816 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation

1117-1974 Build i ng: Auxi l iary F i re Area:

Description:

Boric Acid Tank R oom A Thermal Short #1 (TS1) Data Thermal Sho rt #2 (TS2) Data Drawing: Member Type: Member Size: C-OS1421 Beam 27 X 84 N/A N/A N/A Comments: Additiona l 4" W shape i n c l ose proxim i ty. There are no co lumn s in this room. NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment He i ght (ft): NUREG-1805 FDT Input Data 02.1_ Temperature_

N V.xls (Ver s ion 1805.1) 650 19.5 22 5 51 Vent Width (ft): Vent Height (ft): Top of Vent fr om F l oo r (ft): Vent Descr i pt i o n: 31 19.5 51 Barrier T ype: Concrete Natural air movemen t from transfer gr ill es Bar r ier T h i ckness (i n): 12 Initia l Room Temp. (F): 104 NUREG-1805 FDT Resu l ts Hot Gas La y er Te m peratu r e@ 1 80 mi nutes (F): 1 91.12 Room Sketch: P C r o eOCW'rl I A-03 M-663-00017A , Rev i s i on W03 Page G2817 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1117-1974 Thermal Short #1 Sketch II /liVJ Lto IA.I E 5f.C..TION A*A Thermal Short #1 Photo 1 Thermal Short #1 Pho to 2 M-663-00017A , Rev i s i on W03 Structural Steel Fireproofing Data Room-Elevation:

1301-2000 Building: Description

Corridor No. 1 Thermal Short #1 (TS 1) Data Drawing: C-1 81411 Member Type: Beam Member Size: 21 X 62 Comments: Page G2B18 of G2B-79 Appendix G2B Auxi l iary Fire Area: A-08 Thermal Short #2 (TS2) Data N/A N/A N/A No columns. NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): 02.1_ Te mperature_NV.xls (Version 1805.1) 650 14.5 215 25 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Descrip tion: 25 14.5 25 Barrier Type: Concrete One of two large ven ts of equa l size used (North Corridor)

Barrier Thickness (in): 12 Initial Room Temp. (F): 104 NUREG-1805 FDT Results Hot Gas La ye r Tempera tu re@ 180 minutes (F): 17 2.58 Room Sketch: -P6DR 11D I 2. O""R I M-663-00017A , Revis i on W03 Structural Steel Fireproofing Data 1301-2000 Thermal Short #1 Sketch I . I>* *

  • l.l fo 1* uo* * *
  • 11 : () *
  • t> *
  • 4" C.Ro\S ( T'O) W ?..I X 1..2. (oTRA'f VIEW oOt..IJ./f..

NDRTH 3"x g** TU (; O::.fL [ 'f'.c'?) Page G2819 of G2B-79 Appendix G2B Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017A , Revision W03 Structural Steel Fireproofing Data Room-Elevation

1314-2000 Building:

Description:

Corridor No. 3 Thermal Short #1 (TS1) Data Drawing: C-1 S1411 Member Type: Beam Member Size: 27 X 84 Comments: Page G2820 of G28-79 Appendix G2B Aux il ia ry Fire Area: A-08 Therma l Short #2 (TS2) Data C-OS1002 Column 14 X 228 Large area caused by 2 ea. Tu be steel orientated across column. NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): 02.1_ Temperature_INV

.xls (Version 1805.1) 650 20 1 21 25 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description

25 33 25 Barrier Type: Concrete Largest opening v ent used of two large openings. Barrier Thickness (in): 12 Initial Room Temp. (F): 104 NUREG-1805 FDT Results H ot Gas Layer Temperature@

1 80 minutes (F): 164.57 Room Sketch: ., l l (O>{TA tiJ Me!: NT M-663-00017 A , Revision W03 Page G2821 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1314-2000 Thermal Short #1 Sketch SI!L.T 10.J A.-A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017A , Revision W03 Page G2822 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1314-2000 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 M-663-00017A, Revision W03 Page G2823 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1315-2000 Building:

Aux iliary Fire Area: A-08

Description:

Ctmt Spray Additive Tank Area Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-081421 Member Type: Beam Member S i ze: 24 X 84 Comments; NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Barrier Thickness (in): Initial Room Temp. (F): C-081002 Column 14 X 398 Additional at ta chments in close proximity. NUREG-1805 FDT Input Data 02.1_ Tempera tu r e_NV.xls (V ersion 1805.1) 650 13 21.5 25 Concrete 24 104 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent

Description:

NUREG-1805 FDT Results 7.5 3.5 7.5 Hot Gas Layer Tempe ratur e@ 180 minutes (F): 500.83 Room Sketch: I' I

M-663-00017 A , Rev i s i on W03 Structural Steel Fireproofing Data 1315-2000 T h ermal Short #1 Sketch Therma l Short #1 Photo 1 l'too t , ,..::.--1.4*

.TI'NT
  • Page G 2 8 2 4 of G2B-79 Appendix G2B Thermal Short #1 P h o to 2 No photo required.

M-663-00017A , Rev i s i on W03 Page G2B25 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1315-2000 Thermal Short #2 Sketch Thermal Short #2 Photo 1 T hermal Short #2 Photo 2 No photo required.

M-663-00017A , Revision W03 Page G2B26 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1318-2000 Building:

Auxi li a ry Fire Area: A-08

Description:

V a lv e Compartme nt Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0 8 1 421 Member Type: Beam Member Size: 33 X 11 8 Comments: N/A N/A N/A No co l u mn s. NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.1_ T emperatu r e_N V.x l s (Vers i on 1 805.1) Heat Release Rate (kW): 650 Vent Width (ft): Compartment Width (ft): 1 7 2 1.5 25 Vent Height (ft): Compartment Length (ft): Top of Vent from Floor (ft): Compartment Height (ft): Vent

Description:

Barrier Type: Conc r ete Barrier Thickness (in): 3 6 Initial Room Temp. (F): 1 04 NUREG-1805 FDT Results Hot Gas Layer Temperature@

180 minutes (F): 481.16 Room Sketch: A4) _ r ,.H _..,_

ef!t. AReA I Etev .-; T 313 t{)(XI ( ** !-r--r--------= 40 " (.vrs) * .l>

.. *' L "x<! IHJI' \ ______ ,.!._ * . . ,'-------------Jet:. __ 1?. ...... 13/817 * ... 0 '*"' -/ * .0 f 7.5 3.5 7.5 M-663-00017A , Revision W03 Page G2B27 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1318-2000 Thermal Short #1 Sketch W33X liB y "' .. A-A r-r::\ -----'LI Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017A , Rev i sion W03 Page G2B28 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevat i on: 1320-2000 Building: Auxiliary F i re Area:

Description:

C o rrido r No. 4 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-0 5 144 1 Member Type: B eam Member Size: 16 X 40 Comments: NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barr i er Type: Barr i er Thickness (in): Initial Room Temp. (F): C-151001 Col umn 14 X 264 B uilding steel under N. hatch i s protected by sprinklers in lieu o f fi r eproofing. NUREG-1805 FDT Input Data 02.1_ Temp e ra ture_NV.xls (Ver s i on 180 5.1) 650 Vent Width (ft): 25 36 Vent Height (ft): 14 53 Top of Vent from Floor {ft): 25 2 5 Vent

Description:

Concrete Largets o f two large open i ng used 24 104 NUREG-1805 FDT Results Hot Gas Layer Temperature

@ 1 80 m i nutes (F): 1 94.1 3 Room Sketch: A-08 M-663-0 0 017A , Revis i o n W03 Page G 2829 o f G2B-79 Structural Steel Fireproofing Data Append i x G2B 1 320-2000 Thermal Short #1 Sketch St::C.TlOIU A.-A-Thermal S h ort #1 Pho t o 1 Thermal S h ort #1 P h oto 2 No photo required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1320-2000 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Page G2B30 of G2B-79 4.4 , A.IIIT sm .. JJ Thermal Short #2 Photo 2 Appendix G2B M-663-00017A , Rev i s i o n W03 Page G2B31 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1401-2026 Building: A uxiliary F i re Area: A-1 6

Description:

Component Coolin g P ump & Heat E xch Area B Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1 51 5 1 1 C-0 5 1002 Member Type: B eam Column Member Size: 24 X 76 14 X 158 Comments: Tube stee l i s or i enta t ed to cause 144 square Inches of unprotected steel. NUREG-1805 FDT: Heat Release Rate (kW): Compartme n t Width (ft): Compartment length (ft): Compartment He i g h t (ft): Barr i er Type: Ba r rier Thi ckness (i n): I nitial Room Temp. (F): NUREG-1805 FDT Input Data 02.1_ Tem p erat u re_NV.xl s (V e rsion 1805.1) 650 36.7 5 66 20 Conc r ete 1 2 104 Ve n t Width (ft): Vent He i ght (ft): Top of Vent from F l oor (ft): Vent Descr i pt ion: NUREG-1805 FDT Results H o t Gas layer Temperat u re@ 1 80 minutes (F): 176.12 Room Sketch: G.I.S A zou.1 (NT'O} N I I L_ __ 2 0 36.75 20 M-663-00017A, Revis i on W03 Page G2832 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1401-2026 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017A , Revision W03 Page G2B33 of G2B-79 Structural Steel Fireproofing Data Appendix G28 1401-2026 Thermal Short #2 Sketch Jf NO OY"' l S*o 1'-il-14tf SQ IN om*SScO'-)

Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 M-663-00017A , Revis i on W03 Page G2834 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1402-2026 Building:

A u x i l i ary F i re Area:

Description:

Cor r idor No. 1 Thermal Short #1 {TS1) Data Thermal Short #2 {TS2) Data Drawing: Member Type: Member Size: Comments: C-1 S15 11 Bea m 24 X 68 A d d i t ion al angle s t ee l within cl ose prox i m i ty. N/A N/A N/A No c ol umn in thi s roo m. NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Barrier Thickness (in): Initial Room Temp. (F): 0 2.1_ T emperatu r e_N V.xls (Vers i o n 1 8 05.1) 6 50 1 5 41 20 C o nc r ete 24 104 Vent W i dth (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description

NUREG-1805 FDT Results Hot Gas Layer Temperature@

180 minutes (F): 238.98 Room Sketch: @---------------"' flf z.a u.: (..m.) ______________ Will .. )*-II l I I I! , 2 0 1 4.5 2 0 A-1 6 M-663-000 1 7 A , Rev i s i o n W03 Page G2835 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1402-2026 Thermal Short #1 Sketch 0 * <J --b I> -7 I APre*. Therma l Short #1 Photo 1 Thermal Short #1 P h o to 2 M-663-00017A , Revision W03 Page G2836 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation

1406-2026 Building: Auxil i ary F i re Area: A-16 Description
Component Cooling Pump & Heat Exch Area A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1521 C-OS 1 002 Member Type: Beam Co l umn Member Size: 27 X 8 4 14 X 228 Comments: Add i t i o n a l i tems w i th i n close proxi m ity. NUREG-1805 FDT: Heat Release Rate (kW): Compartment W i dth (ft): Compartment Length (ft): Compartment He i ght (ft): NUREG-1805 FDT Input Data 0 2.1_ Temperature

_NV.x l s (Vers i on 1805.1) 650 26 61 20 Vent Width (ft): Vent Height (ft): Top of Vent from F l oor (ft): Vent

Description:

Barr i er Type: Conc r ete Room (vent) i s open on tw o sides Barr i er Thickness (i n): 1 2 Initial Room Temp. (F): 104 NUREG-1805 FDT Results Hot Gas Layer Temperature@

1 80 minutes (F): 170.15 Room Sketch: T 3 -EL*V. 20zb ... N >>TS * .... I> "' 20 76.5 20 M-663-00017A , Revision W03 Page G2837 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1406-2026 Thermal Short #1 Sketch Th ermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017 A , Rev i sion W03 Page G2838 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1406-2026 Therma l Short #2 Sketch 5eC.T IO N A*A Therma l Short #2 Pho to 1 Thermal Short #2 Photo 2 ;i !J*... . . . . .,_ . , ; .. n --

M-663-00017 A , Revision W03 Page G2839 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1408-2026 Building:

Auxiliary Fire Area:

Description:

Co rridor No. 2 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1541 Member Type: Beam Member Size: 21 X 55 Comments:

NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Barrier Thickness (in): Initial Room Temp. (F): C-1S1 001 Column 14 X 158 Building steel under N. hatch is protected by sprinklers in lieu of fireproofing per drawing. NUREG-1805 FDT Input Data 02.1_ Temperature

_NV.xls (Version 1805.1) 650 18 215 20 Concrete 12 104 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent

Description:

NUREG-1805 FDT Results 20 88.5 20 Hot Gas Layer Temperature@

180 minutes (F): 147.76 Room Sketch: A-16 M-663-00017A , Revision W03 Structural Steel Fireproofing Data 1408-2026 Thermal Short #1 Sketch

  • A -* (i -. b , A -, a. . 0., . : t> Thermal Short #1 Photo 1 L> -' '-* -() . sc:c.no!J A* A Page G2840 of G28-7 9 Appendix G2B ] Thermal Short #1 Photo 2 M-663-00017A , Rev i s i on W03 Structural Steel Fireproofing Data 1408-2026 Thermal Short #2 Sketch Thermal Short #2 Photo 1 73 2 I Page G2841 of G2B-79 Appendix G2B A.-A Thermal Short #2 Photo 2 M-663-00017A , Rev i s i on W03 Page G2842 of G2B-79 Structural Steel Fireproofing Data Appendix G28 Room-Elevat i on: 1504-2047 Building: A ux i l i ary Fire Area: A-1 9 Description
C t mt Purge E xhaust & Mech E qu ip Rm B Thermal Short #1 (TS1) Data Therma l Short #2 (TS2) Data Drawing: C-081631 C-0 8 1002 Membe r Type: Beam Co l um n Member Size: 24 X 68 14 X 184 Comments: Add i tional attach m ents i n close proxim i ty. Ad d i t io n a l at t ac h ments in close proxi m i t y (53" a n gle s uppo rt s). NUREG-1805 FDT: Heat Release Rate (kW): Compartment W i dth (ft): Compartment length (ft): Compart m ent Height (ft): Barrier Type: Barrier Th i ckness (i n): In i tial Room Temp. (F): NUREG-1805 FDT Input Data 02.1_ Tempera t u r e_NV.x l s (Ve r s i on 1 805.1) 650 39.75 89 25.25 Concre t e 12 104 Vent Width (ft): Vent He i ght (ft): Top of Vent from Floor (ft): Vent Descrip t io n: NUREG-1805 FDT Results Hot Gas l ayer T e m pe r at ur e@ 1 80 m i nu tes (F): 179.58 Roo m Sk e tc h: N
  • EI.EV. "U-t7' 25.25 14 25.25 M-663-00017A , Revision W03 Page G2843 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1504-2047 Thermal Short #1 Sketch 6 * ' . 6 * . * *. 0 VIi Thermal Short #1 Photo 1 Therma l S h ort #1 P h oto 2 N o photo required.

M-663-000 1 7A , Revis i on W03 Page G2B44 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1504-2047 Thermal Short #2 Sketch S*C..TI6N A* A. Therma l Short #2 Photo 1 Thermal Short #2 Photo 2 N o photo required.

M-663-00017A , Rev i s i on W03 Page G2B45 of G2B-7 9 Structural Steel Fireproofing Data Appendix G2B Room-Elevation

1506-2047 Bu i lding: Au xiliary Fire Area: A-1 9

Description:

Ctmt Pu r ge S upply A i r Hand l i ng Un it A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Draw i ng: C-1 S 1641 C-1 51 001 Member Type: Beam Co lu m n Member Size: 24 X 76 14 X 3 7 0 Comments: Monora i l deter min ed to b e not w orse case , spacers and f ire proo fi ng insul a te a ttachme n t con f iguratio n. O r ien t at i on of tub e stee l c a us e s 5 6 p l us 16 squa r e i nches o f unpr ote cted surface. NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.1_ Tempe r a t ure_NV.x l s (V e r si on 1 805.1) Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Barr i er Thickness (in): Initia l Room Temp. (F): 650 48 94 25.25 Concrete 12 104 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description

NUREG-1805 FDT Results Hot Gas L aye r Te m pe r a tur e@ 180 minutes (F): 175.17 Room Sketch: TW%1lt7C..

.1:! (1'5*1) t*N/ c tAQ ,lY 2 5.25 1 4 2 5.25 M-663-00017A, Revision W03 Page G2B46 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1506-2047 Therma l Short #1 Sketch WZ.-4 X7(.. Thermal Short #1 Photo 1 Therma l Short #1 Photo 2 N o photo required.

M-663-00017A , Rev i sion W03 Page G2847 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1506-2047 Thermal Short #2 Sketch Thermal Short #2 Pho t o 1 T hermal Sho rt #2 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2848 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation

1513-2047 Building: Auxiliary Fire Area:

Description:

Control Bldg V ent Supply A/C Unit Rm Thermal Short #1 (TS1) Data Thermal Short #2 (T S2) Data Drawing: C-081621 C-081002 Member Type: Beam Column Member Size: 24 X 76 14 X 184 Comments: Add i t i onal strut con n ect i on in close prox i m i t y. Add i t i ona l angle i n c l ose proxim i ty. NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.1_ Temperature

_NV.xls (Version 1805.1) Heat Release Rate (kW): 650 Vent Width (ft): Compartment Width (ft): 35 Vent Height (ft): Compartme_nt Length (ft): 15 25.25 Top of Vent from Floor (ft): Compartment Height (ft): Barrier Type: Barrier Thickness (in): Initial Room Temp. (F): Concrete 1 2 104 Vent Descr ip tio n: NUREG-1805 FDT Resu lt s Hot Gas Layer Temperature@

180 minutes (F): 222.58 Room Sketch: ----,- I j /'\. I H

  • v 'Ill -I ! 15*3] I , j) vJ2At 1t
  • I_JI --I II W E1£V. Zo41" j f I I /.JT) JiJ f-.....

- -OPe>l TO tVI 150(. ' I ... 25.25 15 25.25 A-19 M-663-00017 A , Revision W0 3 Page G2B49 of G28-7 9 Structural Steel Fireproofing Data Appendix G2B 1513-2047 T h erma l Short #1 Sketch S£CTICI-J A-A Therma l Short #1 Photo 1 T herm al S h ort #1 P h oto 2 No photo required.

M-663-00017A , Revision W03 Page G2850 of G28-79 Structural Steel Fireproofing Data Appendix G28 1513-2047 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 M-663-00017A , Revision W03 Page G2B51 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1502-2047 Auxiliary Fire Area: A-20

Description:

Component Cooling Water Surge Tank Area B Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: Member Type: Member Size: C-081631 Beam 21 X 55 N/A N/A N/A Comments: Monora i l attachment , only 1 point is requ i red to be eva l uated. No columns. NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Barr i er Thickness (in): Initial Room Temp. (F): NUREG-1805 FDT Input Data 02.1_ Temperature

_NV.xls (Vers i on 1805.1) 650 39.75 16 25.25 Concrete 12 1 04 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description

NUREG-1805 FDT Results Hot Gas Layer Temperature@

1 80 minutes (F): 219.21 Room Sketch: I £t.eY 204-/ .Nrs 25.25 14 25.25 M-663-00017 A. Revision W03 Page G2852 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1502-2047 Thermal Short #1 Sketch . v I)

  • w 2.11( 55 VJi.W LDol<tNI.

WrE ST Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A , Rev i s i on W03 Page G2B53 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1503-2047 Build i ng: A ux i li a ry Fire Area: A-20 Description

Com po n e nt C oo li n g Wate r S urge T a nk A rea A Thermal Short #1 (TS1) Data Therma l Short #2 (TS2) Data Drawing: Member Type: Member S i ze: C-O S 1631 Beam 2 1 X 55 N/A N/A N/A Comments:

Mono r a i l attachme n t. on l y 1 po i nt i s requ i red to b e e va l uat ed. No co l umn s. NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment He i ght (ft): Barrier Type: Barrier Th i ckness (i n): I n i tial Room Temp. (F): NUREG-1805 FDT Input Data 02.1_T e mpe r ature_NV.x l s (Vers i on 18 0 5.1) 650 32 1 5 25.25 Con cr ete 12 1 04 Vent Width (ft): Vent Height (ft): Top of Vent from F l oor (ft): Vent Description

NUREG-1805 FDT Results Ho t Gas L aye r Te m pera t u r e@ 1 80 m in u t es (F): 228.21 Roo m Ske t ch: N 25.25 1 4 25.25 M-663-00017A , Revision W03 Page G2854 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1503-2047 Thermal Short #1 Sketch A -A V/e.W LooKtiJCi Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A , Revision W03 Page G2855 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1505-2047 Building:

Auxiliary F i re Area: Description

Corridor Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Draw i ng: C-OS1631 Member Type: Beam Member Size: 24 X 76 Comments: NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): N/A N/A N/A No exposed column. NUREG-1805 FDT Input Data 02.1_ Tempe ratu re_NV.xls (V e rsion 1805.1) 650 1 0 9 25.25 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Descript ion: 25.25 9 2 5.25 A-20 Ba r rier Type: Barrier Thickness (in): Concrete 12 One of two lar ge vent (equal in size) was used. Temp not in USAR Table 3.11 , used adjacent rooms Temp that are open to this room. Initial Room Temp. (F): 104 NUREG-1805 FDT Resu lt s Hot Gas Layer Temperature@

1 80 minutes (F): 3 1 7.54 Room Sketch: £Lt l047 I NTS ** 0 , ... I -----. _.__ __ _

M-663-00017A , Revision W03 Structural Steel Fireproofing Data 1505-2047 Thermal Short #1 Sketch A Thermal Short #1 Photo 1 Page G2856 of G2B-79 Appendix G2B . '

  • L' o ... . . --*_'Y**-t b
  • STtJ;1. S c: c...l!o..J A *A Thermal Short #1 Photo 2 No photo required.

M-663-00017A , Rev i sion W03 Page G2B57 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation

1507-2047 Building:

A u xil i a ry F i re Ar e a: A-2 0 Descriptio n: Pe rsonnel Hatch Area Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Da t a Drawing: C-OS1631 C-1 S 1 001 Member Type: Beam C olumn Member Size: 24 X 75 14 X 158 Comments: Addit i ona l attachments in c l ose prox i m i ty. NUREG-1805 FDT Input Data NUREG-1805 FDT: 0 2.1_ Temperatu re_NV.x ls (Vers i on 18 0 5.1) Heat Release Rate (kW): 6 5 0 Vent W i dth (ft): Compartme n t Width (ft): Vent Height (ft): Compartment Length (ft): 32 33 Top of Ve n t from Floor (ft): Compartment He i ght (ft): Barr i er Type: Bar ri er T hickness (i n): Init i al Room Temp. (F): 25.2 5 Concrete 1 2 1 04 Vent Descr i pt ion: NUREG-1805 FDT Resu lt s Hot Gas Layer Te m perat ur e@ 1 80 m i n u tes (F): 223.79 Roo m Ske t c h: oPe:I<J -..;;-IS*i'---------------. !:LV. Zo47 I 25.25 9 25.25 M-663-00017 A , Revision W03 Page G2858 of G2B-79 Structural Steel Fireproofing Data Appendix G28 1507-2047 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A , Revis i on W03 Page G2859 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1507-2047 Thermal Short #2 Sketch St:CIION VIEW tiAST Therma l Sho rt #2 Photo 1 Thermal S h ort #2 P h oto 2 No photo required.

M-663-00017A , Revis i on W03 Page G2860 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1508-2047 Building: A u x i l i ary Fire Area:

Description:

Drawing: Ma i n S team Is o l a t i o n Valve R m No. 1 Thermal Short #1 (TS1) Data C-1 S 1 452 The r mal Short #2 (TS2) Data N/A Member Type: B e am Member Size: 30 X 99 Comments: NUREG-1 805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartme n t Height (ft): N/A N/A No column s. NUREG-1805 FDT Input Data 0 2.1_ T empera t ure_NV.x l s (V ersion 1 8 0 5.1) 650 Vent Width (ft): 22 35 48 Vent Height (ft): Top of Vent from Floor (ft): Vent Description

32 35 48 Barrier Type: Concrete Ope n to room be l ow an d at M i ss i l e S heil ds Barrier Thickness (i n): 2 4 Initial Room Temp. (F): 120 NUREG-1805 FDT Results Hot Gas La y er T empe r atu r e@ 180 mi n utes (F): 184.77 Room Sketch: A-2 3 M-66 3-00017A , Revisio n W03 Page G2B61 o f G2B-79 Structural Steel Fireproofing Data Appendix G2B 1508-2047 The rm al S h ort #1 Ske t ch
  • tJ * . " liXI./fbfl/flt

o/'*11 fi"FPt:!Cf11J,;

T/1 QtJ87.

,.,C..,.,

SH. T!o IJ A.-A T her m al S h o rt #1 Pho t o 1 Therm al S ho rt #1 P h o t o 2 No photo required.

No photo required.

M-663-00017A , Revis i o n W03 Page G2862 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation

1509-2047 Building:

Auxiliary Fire Area:

Description:

Main Stea m Is olation Valve Rm No. 2 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-1S1452 Member Type: Bea m Member Size: 30 X 99 Com ments: NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): N/A N/A N/A No columns. NUREG-1805 FDT Input Data 02.1_ Temp erat ur e_NV.xls (Ver s i o n 1805.1) 650 22 35 48 Vent W i dth (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Descript ion: 32 35 48 Barrier Type: Concrete Open to room be l ow and at Missile Sheilds Barrier Thickness (in): 24 Initial Room Temp. (F): 120 NUREG-1805 FDT Results Hot Gas Layer Temperature@

1 80 minutes (F): 16 4.77 Room Ske tch: A-23 M-663-00017A , Rev i sion W03 Page G2863 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1509-2047 Therma l Short #1 Sketch .u 'Ny"" I -

II? "Ttii<'.,...T:

St:LTlbN A-A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 N o ph o to required.

No photo required.

M-663-00017A , Revision W03 Page G2B64 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1324-2000 Building:

Auxil i ary Fire Area: Description

Feedwa te r Pump Valve Compartment No. 1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: Member Type: Member Size: C-181352 Beam 14 X 34 N/A N/A N/A Comments: Additional attachments i n close proximity (3" x 1/4" angle). No columns. NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): NUREG-1805 FDT Input Data 0 2.1_ Tempe r a t ure_NV.xls (Ve rsion 1805.1) 650 10 10 12 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description
3.5 3.5 1 0 Barrier Type: Conc rete Vent at ceiling to Room 1304 (3.5 X 3.5) Barrier Thickness (in): 12 Initial Room Temp. (F): 104 NUREG-1805 FDT Results Hot Gas Layer Temperature@

18 0 minutes (F): 975.88 Room Sketch: (o..JT. c:.uv. woo, Nts A 13241 v EL' z.ooo' A-29 M-663-00017 A , Rev i sion W03 Page G2B65 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1324-2000 Thermal Short #1 Sketch SE '-TI6N Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017A , Revision W03 Page G2866 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1330-2000 Build i ng: Auxi liary Fire Area: A-30

Description:

Feedwater P ump Valve Compartment No.4 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: Member Type: Member Size: C-1 51352 Bea m 8 X 1 7 N/A N/A N/A Comments:

Column encapsu la ted i n concret e , no i ssues w/column. NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): NUREG-1805 FDT Input Data 02.1_ Temperature

_NV.xls (V ersion 1 805.1) 650 Vent Width (ft): 10 Vent Height (ft): 10 Top of Vent from Floor (ft): 12 Vent

Description:

3.5 3.5 1 0 Barrier Type: Concrete O pen at ceil i ng (3.5 X 3.5) Hatc h way Barrier Thickness (in): 12 Initial Room Temp. (F): 104 NUREG-1805 FDT Results Hot Gas Layer Temperature@

180 minutes (F): 975.88 Room Sketch: Elf.V. l OOo ' }'Jr>

M-663-00017 A , Rev i s i on W03 Page G2B67 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1330-2000 Thermal Short #1 Sketch Loo 1N') No'!-rn Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017A , Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing: Member Type: Member Size: Comments: 1206-1989 Building: P ipe Ch a se The r ma l Short #1 (TS1) Data C-1 S1352 B eam 14 X 34 Add i tional attachments in close proximity. Page G2868 of G2B-79 Appendix G2B A u x i l iary F i re Area: A-33 Thermal Short #2 (TS2) Da t a C-1 S 1001 C olumn 14 X 111 NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment W i dth (ft): Compartment Length (ft): Compartment Height (ft): Barrier Type: Barrier Th i ckness (in): 02.1_ T e mperatu r e_NV.xls (Vers i on 1805.1) 650 23 38 10 Concrete 24 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Descriptio n: 10 12 10 Lrag est of two large vent openings used. No t in USA R Table 3.11 , us e d 1207 Temp because it is open to 1207 and dir e ctly adjacent.

Ini t ial Room Temp. (F): 106 NUREG-1805 FDT Results Hot Gas L a y er T e m pe ratur e@ 180 min utes (F): 3 1 6.93 Roo m Ske t c h: I I I I I I I EL£Y.I?B9' NTS M-663-00017A , Revision W03 Structural Steel Fireproofing Data 1206-1989 Thermal Short #1 Sketch ;.J*r.. Thermal Short #1 Photo 1 /...ca>J.;-.J'j 4"Tlllk ITS\ SrL 0 Page G2869 of G28-79 Appendix G2B Therma l Short #1 Photo 2 M-663-00017A , Revision W03 Structural Steel Fireproofing Data 1206-1989 Thermal Short #2 Sketch Thermal Short #2 Photo 1 3--.... (lfO VA( 5u.Pr Page G2B70 of G2B-79 Appendix G2B St:C.TIO A*A Thermal Short #2 Photo 2 M-663-00017A , Revision W03 Page G2871 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevat i on: 1 207-1989 Bui l ding: A uxiliary F i re Area: Descr i ption: Pipe Chase Thermal Short #1 (TS1) Data Therma l Short #2 (TS2) Da t a Drawing: C-181352 C-1 8 1001 M e mber Type: B eam Column Member S i ze: 18 X 40 14 X 111 Comments:

Add iti ona l attachments in close prox imi ty. NUREG-1805 FDT: Heat Release Rate (k W): Compartment W i dth (ft): Compartment Length (ft): Co m pa rt ment He i g h t (ft): NUREG-1805 FDT Input Data 02.1_ Temperature

_NV.xls (V e r s i on 1 805.1) 650 23 38 10 Ven t Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Desc ri pt ion: 10 12 10 Barr i er Type: Concrete Lragest of two large vent open i ngs used. Ba r r i er Thickn e ss (i n): 2 4 I nit i al Room Temp. (F): 106 NUREG-1 805 FDT Resu l ts H o t Gas La ye r T em p eratu re@ 1 80 m inu tes (F): 316.93 Roo m S ke tc h: A-33 M-663-00017A , Revision W03 Page G2872 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1207-1989 Thermal Short #1 Sketch w-18J< 40

  • Sf:t:: T tDII* A A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 M-663-00017A , Revision W03 Page G2B73 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1207-1989 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 M-663-00017A , Revision W03 Page G2B74 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation
3401-2016 Building:

Control Fire Area: C-35

Description:

Corridor No. 1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-083511 N/A Member Type: Beam N/A Member Size: 24 X 68 N/A Comments: No column s. NUREG-1805 FDT Input Data NU REG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height {ft): 02.1_ Temperature_NV

.xls (V ers i on 1805.1) 650 6 86.5 15.25 Vent W i dth (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description

15.25 11 15.25 Barrier Type: Block Temp. no t i n USAR Table 3.11 , used all adacent room temp of 90 Barrier Thickness (in): 8 Initial Room Temp. (F): 90 NUREG-1805 FDT Results Hot Gas Layer Temperature@

180 minutes (F): 276.82 Room Sketch:

M-663-00017A, Revision W03 Page G2875 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 3401-2016 Thermal Short #1 Sketch I

  • tJ. . " . I . e..
  • 0 . , . I 6.* ** rs St.:.t..f C N A*A Thermal Short #1 Photo 1 Therma l Short #1 Photo 2 M-663-00017A , Rev i sion W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing: Member Type: Member Size: Comments:

3406-2016 Building:

Corridor No. 2 Thermal Short #1 (TS1) Data C-083511 Beam 24 X 68 Additional Items i n close prox i m i ty. (6" l ong x 1/2" Plate). Page G2B76 of G2B-79 Appendix G2B Contro l Fire Area: C-35 Thermal Short #2 (TS2) Data C-083001 Column 14 X 426 Column embedded on both sides. ALBI is 2-1/2" thick minimum due to finish requ i rements. NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length {ft): Compartment Height (ft): 02.1_ Tempera ture_NV.xls (Version 1805.1) 650 11 20.75 15.25 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent

Description:

15.25 1 1 15.25 Barrier Type: Block Temp. not i n U8AR Tab l e 3.11 , used all adacent room temp o f 90 Barrier Thickness (in): 8 Initial Room Temp. (F): 90 NUREG-1805 FDT Results Hot Gas Layer Temperature@

180 minutes (F): 357.53 Room Sketch:

M-663-00017 A , Revision W03 Page G2877 of G28-79 Structural Steel Fireproofing Data Appendix G2B 3406-2016 Thermal Short #1 Sketch SE.c.TIO N A-fl.. Thermal Short #1 Photo 1 Therma l Short #1 Photo 2 M-663-00017A , Revision W03 Structural Steel Fireproofing Data Room-Elevation

3412-2016 Building:

Description:

Emergency Shower & Eyewas h Area Thermal Short #1 (TS 1) Data Drawing: C-OS3511 Member Type: Beam Member Size: 24 X 68 Comments: Page G2878 of G2B-79 Appendix G2B Control F i re Area: C-35 Thermal Short #2 (TS2) Data N/A N/A N/A No columns. NUREG-1805 FDT Input Data NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): 02.1_ Temperature

_NV.xls (V ers ion 1805.1) 650 11 17 15.25 Vent Width (ft): Vent Height (ft): Top of Vent from Floor (ft): Vent Description

15 25 11 15.25 Barrier Type: B l ock Temp. not in USAR Table 3.11 , used all adacent room temp of 90 Barrier Thickness (in): 8 Initial Room Temp. (F): 90 NUREG-1805 FDT Results Hot Gas Layer Temperature@

180 minutes (F): 373.15 Room Sketch: "'"'"} {Ni'S) '

M-663-00017A, Rev i sion W03 Structural Steel Fireproofing Data 3412-2016 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Page G2879 of G28-79 .ol w T'l sa '5TL A-A Therma l S h ort #1 Photo 2 Appendix G2B No photo required.