ML17151B055

From kanterella
Jump to navigation Jump to search
Fire Protection Evaluations for Unique or Unbounded Fire Barrier Configuration, M-663-00017A, Rev. W05, G3D-27 to G4D-19
ML17151B055
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 03/09/2017
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML17151A982 List: ... further results
References
WO 17-0045 M-663-00017A, Rev W05
Download: ML17151B055 (74)


Text

M-663-00017A, Revision W03 Thermal Short #I Sketch Thml Short Thermal Short #I Photo 1 Page G3D-27 of G3D-50 Thermal Short #I Photo 2 Structural Steel Fireproofing Data Appendix 030 31 01-1 974 M-663-00017A, Revision W03 Page G3D-28 of G3D-50 Structural Steel Fireproofing Data Appendix G3D Room-Elevation:

Building:

Control Fire Area: C-05 I

Description:

Area Above Suspended Ceiling Thermal Short #I (TSI) Data I Drawing: I Member Type: Beam I Member Size: 27 X 94 Comments:

Additional 3" angle and 2-4 1 in close proximity.

Thermal Short #2 (TS2) Data NIA Column NIR Columns below drop ceiling are incased within CMU wall, and above drop ceiling there are no attachments.

NUREG-1805 FDT Input Data 02.2-Temperature-FV.xls (Version 1805.0) 02.3-temperature-~~~mvl .XIS (Version 1 W5.f ) Heat Release Rate (kW): Compartment Width (ft): Forced Ventilation Rate (cfm): Supply: 4925 Exht: 4350 Vent Descrlptbn:

Compartment Length (ft): Compartment Height (ft): Temp not in USAR Table 3.11, temp used is based on other similar rooms within the Control Building Initial Room Temp. (F): 90 Barrier Type: Concrete -- - Barrier Thickness (in): 24 I I; NUREG-1 805 FDT Results Time When Forced Ventilation Exceeds 200 F (min) I Compartment StaWng Temp, for Closed Room No Van 00.83 Hot Gas Layer Temperature

@ 180 minutes IF): . - Room Sketch: d Thermal Short #I Sketch Thermal Short #I Photo 1 M-663-00017A Revision W03 Page G3P29 of G3D-50 Structural Steel Fireproofing Data Appendix G~D ONAC-I984 Thermal Short #I Photo 2 M-663-000f 7A Revision W03 Page G3D-3Q of G3D-58 I Structural Steel Fireproofing Data Appendix 630 I Room-Elevation:

OSAC-1984 Bullding:

Control Fire Area: C-06 I

Description:

Area Above Suspended Ceiling Thermal Short #1 (TS1) Data 1 Drawing: I Member Type: Beam I Member Sire: Comments:

None. Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft]: Compartment Height (ft): Barrier Type: Thermal Short #2 (TS2) Data NIA Column NIR Columns below drop ceiling are incased within CMU wall, and above drop ceiling there are no attachments.

NUREG-4 805 FDT In~ut Data 02.2-TemperatureFV.xIs (Version 1805.0) M.3-~pemt~re~~:~revl .XIS {Version t8&.1) Forced Ventilation Rate (cfm): Supply: 3275 Exht: 2950 Vent

Description:

Temp not in USAR Table 3.1 1, temp used is based on other similar rooms within the Control Building.

lnltial Room Temp. (F): SO Barrier Thickness (in): 24 NUREG-I805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): I Q I Compartment Starting Temp. for Closed Room No Vent. FDT: 212.74 Hot Gas Layer Temperature

@ 180 minutes (F): bn.18' -- - -- - - Room Sketch:

Thermal Short #I Sketch 1 Themal Short #I Photo 1 M-683-00017A, Revision W03 Page 630-31 of G3D-50 Structural Steel Fireproofing Data Appendix G~D OSAC-I 984 Thermal Short #1 Photo 2 No photo required I M-663-0001

?A, Revision W03 Page G3D-32 of G3D-50 Structural Steel Fireproofing Data Appendix G~D Room-Elevation:

341 5-201 6 Building:

Control Fire Area: C-13

Description:

Access Ctrl& Elec Equip NC Units No. 1 Thermal Short #I US11 Data Thermal Short #2 (TS2) Data NIA NIA NIA No columns. Drawing: Member Type: Member Size: Comments:

Beam NUREG-1805 FDT lnsut Data 02.2-Temperature-FV.xls (Version 1805.0) 02.3-ternperatum-w-1wi.xls (Version 1805.1) I Heat Release Rate (kW): Compartment Width (ft): Forced Ventilation Rate (dm): Supply: 750 Exht: 750 Vent

Description:

Compartment Length (ft): Compartment Barrier Type: t5.25 Initial Room Temp. (F); 90 Block Barrier Thickness (in): 8 I Height (ft): NUREG-1 805 FPT Results I Time When Forced Ventilation Exceeds 200 F (min): 1 I Compaltmant Starting Temp. for Closed Room No Vent. FDT: 200 Hot Gas Layer Temperature

@ 180 minutes (F): M2iM Room Sketch:

M-663-00017A.

Revision W03 Page G3D-33 of G30-50 1 herrnal Short #I Sketch b. r -- * -' ) YDW~k?Uh~i SEffW A-A Thermal Short #l Photo 1 Structural Steel Fireproofing Data Appendix G~D 341 5-201 6 Thermal Short #I Photo 2 M-66340017A, Revision W03 Page G3D-34 of G3D-50 Structural Steel Fireproofing Data Appendix G~D Room-Elevatlon:

341 6-201 6 Building:

Control Fire Area: C-14 I

Description:

Drawing: Member Type: Member Size: I Comments:

Accsss Ctrl& Elec Equip AIC Units No. 2 Thermal Short #1 (TS1) Data Beam 24 X 68 Additional attachments In close proximity (J" x 114" angles). Thermal Short #2 (TS2) Data NIA NIA NIA No ccrlumns.

NUREG1805 FDT: Heat Release Rate (kW): Compartment Width (ft): I Compartment Length (R): NUREG-1805 FDT Input Data 02.2-Temperature-FV.xls (Version 1805.0) 02.3_t~prature_cc-~~ft.~l~ (Verslon 1805.1) Forced Ventilation Rate (cfrn): Supply: 750 Exht: 750 Vent

Description:

Compartment Height (ft): 15.25 Initial Room Temp. (F): W Barrier Type: Block Barrier Thickness (in): 8 NUREG-1 805 FDT Results Time When Forced Ventilatlan Exceeds 200 F (mtn): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 200 Hot Gas hyer Temperature

@ 180 minutes (F): 9393 Room Sketch:

Thermal Short #I Sketch wcw4d LA - 1 Thermal Short #I Photo 1 I Thermal Short #I Photo 2 MSH40017k.

Revision W3 Page G3D-35 of G30.50 Stt~ct~ral Steel Fireproofing Data Appendix G~D 341 6-201 6 M-66340017A, Revlslon W03 Page G3D-36 of G3D-50 Structural Steel Fireproofing Data Appendix G~D Room-Elevation:

3501 -2032 Building:

Control Fire Area: C-21 I

Description:

tower Cable Spreading Room Thermal Short #I (TSI) Data Drawing: Member Type: Member Size: Comments:

Beam Additional attachment in close proximity (6" X St1 6 1). Thermal Short #2 (TS2) Data COS3001 Column 14 X 342 NUREG-I 805 FDT lnaut Data NUREG-1 805 FDT: 02.2-Temperature-FV.xIs (Version 1805.0) 02.3_tempe~um-m-revl .XIS (Version 1805.1) Heat Release Rate (kW): Compartment Width (ft): Forced Ventilation Rate (cfm): Supply: 500 Exht: 500 Vent

Description:

Compartment Length (ft): Compartment Height {R): 14.75 lnltial Room Temp. (F): 104 Barrier Type: Concrete Barrier Thickness (in): 24 I I NUREG-I805 FDT Results I Time When Forced Ventilation Exceeds 200 F (min): 1 I Compartment Starting Temp. for Closed Room No Vent. FDT: 21 9.78 Hot Gas Layer Temperature

@ 180 minutes (F): 326.1 2 Room Sketch:

Thermal Short #I Sketch Thermal Short #I Photo 1 SELT~C~~\

A-A Thermal Short #I Photo 2 M-66300017A, Revision W03 Page G3D-37 of G3D-50 Structural Steel Fireproofing Data Appendix G~D 3501 -2032 Ma3-00017A, Revision W03 Page G3D-38 of G3D-50 Thermal Short #2 Sketch Thermal Short #2 Photo I -4 7' f- ly' Structural Steel Fireproofing Data Appendix G~D 3501 -2032 Thermal Short #2 Photo 2 M-663-00017A, Revision W03 Page G3P39 of G30-50 Thermal Short #2 (TS2) Data NIR Column NIR Unistrut only attached b co:umns. Structural Steel Fireproofing Data Appendix G~D Room-Elevation:

3801 -2073 Building:

Controt Flre Area: C-22

Description:

Upper Cabte Spreading Room Thermal Short #1 (TSI) Data' Drawing: C-1 S3811 Member Type: Beam Member Size: 33 X 1 18 Comments:

Orientation cause large area of unprotected steel. Columns only have Unistrut, acceptable.

NUREG4 805 FDT Input Data NUREG-1 805 FDT: 02.2-Temperature-W.ds (Version 1805.0) 02.3-mperatum-0cOCrev1 .XIS (Versron 1805.1) Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 3450 Exht: 3020 Compartment Width (ft): 65.5 Vent

Description:

Compartment Length (ft): 99 Compartment Height (ft): 11.75 Initial Room Temp. (F): 104 Barrier Type: Concrete Barrier Thickness (in): 24 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 15 Compartment Starting Temp. for Ctosed Room No Vent. FDT: 200.00 Hot Gas Layer Temperature

@ 180 minutes (F): 96826 Room Sketch:

Structural Steel Fireproofing Data Appendix G~D Thermal Short #1 Sketch M-663-00017A, Revision W03 Page G3D4 of G3MO - -

WBB3-000 17A, Revision W03 Page G3Wf of G3D-50 (Structural Steel Fireproofing Data Appendix G~D I Room-Elevation:

61 04-2000 Building:

fuel Fire Area: F-02 I

Description:

Fuel Pool Cooling Heat Exch Room Thermal Short #d (TS1) Data Drawing: COS62 1 1 I Member Type: Beam 1 Member Size: 24 X 55 Comments:

Additional thermal shorts in close proximity.

MU REG-1 805 FDT: Heat Release Rate (kW): Compartment Wldth (PC): I Compartment Length (R): Thermal short #Z (TS2) Data NIA NIA NIA No columos. NUREG-1 805 FDT Input Data 02.2-Temperature-FV.xls (Version 1805.0) 02.3-temperat~re~cc~revl .xls (Version 1805.4) Forced Ventilation Rate (cfm): Supply: 1300 Exht: 1300 Vent

Description:

Open Grille Compartment Height (ft): 25 Initial Room Temp. (F): 122 Barrier Type: Concrete Barrier Thickness

{in): 12 I I NUREG-1805 FDT Results T1me When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 238.05 Hot Gas Layer Temperature

@ f80 minutes (F): 841 - - - Room Sketch:

M-663-00017A, Revision W03 Page G3D-42 of G3D-50 Thermal Short #I Sketch Thermal Short #1 Photo 1 Structural Steel Fireproofing Data Appendix G~D 61 04-2000 Thermal Short #I Photo 2 No photo required.

M-663-00017A, Revision W03 Page G30.43 of G3D-50 Structural Steel Fireproofing Data Appendix G~D I Room-Elevation:

Draw Ing : Building:

Fuel Fuel Pool Cwting Heat Exch Room Thermal Short #I (TS1) Data 1 Mernbw Type: Beam I Member Size: 24 X 55 Comments:

6 pipe. I NUREG-I805 FDT: Heat Release Rate &W): Compartment Width (ft): I Compartment Length (ft): Fire Area: Thermal Short #2 (TSZ) Data NIA NIA NIA N7o~~durnn,s, NUREG-1805 FDT Input Data W.2-Temperature-FV.xls (Version 1805.0) 02.3-tempwatu~e~c~~~Wl .xis (Vdn 1805.7 ) Forced Ventllation Rate (cfm): Supply: 1300 Exht: 1300 Vent

Description:

Open Grille Compartment Height (ft): 25 lnltlal Room Temp. (F): 122 Barrier Type: Concrete.

Bawier Thickness (in): 12 NUREG-1805 ED7 Results Time When Forced Ventllaflon Exceeds 200 F (rnin): 1 1 Compartment Startlng Temp. for Closed Room No Vent. FDT: 238.05 Hot Gas Layer Temperature

@ 180 minutes (F): 501 .&6 Room Sketch:

A-6634001 7A, Revision W03 Structural Steel Fireproofing Data Appendix G~D Thermal Short #I Sketch F 4 .1 5ELTtQN A-A Thermal Short #I Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G3D45 of G30-50 Structural Steel Fireproofing Data Appendix G~D Room-Elevation:

6202-2026 Building:

Fuel Fire Area: F-05 I

Description:

Electrical Equipment Room Drawing: I Member Size: Comments:

Thermal Short #1 (TS 1) Data Additional attachments in close proximity.

Thermal Short #2 (TS2) Data NIA NIA NIA No columns. NUREG-I 805 FDT In~ut Data 02.2-Temperature-FV.x$ (Version t 805.0) M.3-temperaturn-cc-mv9

.#Is (Version 1805.1 ) Heat Release Rate (kW): Compartment Width (ft): I Compartment Length (ft): Forced Ventilation Rate (cfm): Supply: 10800 Exht: 10800 Vent

Description:

Open Grille Compartment Height (ft): 20.5 Initial Room Temp. (F): 110 Barrier Type: Concrete Barrier Thickness (in): 12 NUREG-1 805 FDf Results Time When Forced Ventilation Exceeds 200 F (min): 'to Compartment Starling Temp. for Closed Room No Vent. FDT: 200.76 Hot Gas layer Temperature

@ 180 minutes (F): 53w.w Room Sketch:

Thermal Short #I Sketch a Thermal Short #I Photo 1 Thermal Short #1 Photo 2 M-663-00017A, Revision W03 Page G3D46 of G30-50 Structural Steel Fireproofing Data Appendix ~30 6202-2026 I No photo required.

M-663-00017A, Revision W03 Page G3D-47 of G3DSO I Structural Steel Fireproofing Data Appendix G~D I Room-Elevation:

I

Description:

Building:

Fuel Firm Area: Exhaust Filter Absorber Room A Thermal Short #I (TSI) Data ( Drawing: C1 S6411 I Member T*ei Beam I Member Sue: 16 X 36 I Comments:

NUREG-1805 FDT: Heat Release Rate (kW): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Thermal Short #2 (TSZ) Data - NIA NIA NIA No columns. NUREG-1 805 FDT lneut Data - 02.2-Temperature-N.xIs (Version 1805.0) 02.3-temperaturn-cc-rw1 .XIS (Version 1805.1) Forced Ventilation Rate (cfrn): Supply: 300 Exht: 300 Vent

Description:

Open Grilte lnitbl Room f emp. (F): Barrier Type: Concrete-, - - - Barrier Thtckness (in): 12 1 I NUREG-1805 FDT Results I Time When Forced Ventilation Exceeds 200 F (rnin): I Compartment Starting Temp. for Closed Room No Vent. FDT: 363.95 Hot Gas Layer Temperature

@ 180 minutes (F): ! --- - - - - - - - - --- . --.a- Room Sketch:

Page G3P48 of G3D-50 Structural Steel Fireproofing Data Appendlx G~D Thermal Short #I Sketch r3 Thermal Short #1 Photo 1 Thermal Shad #I Photo 2 M46340017A, Revision W03 Thermal Short #2 (TS2) Data N IA NIA NIA No columns. Structural Steel Fireproofing Data Appendix G3D Room-Elevation:

6303-2047 Bulding: Fuel Fire Area: F-07

Description:

Exhaust Filter Absorber Room B Thermal Short #I (TS1) Data Drawing: C1 S6411 Member Tm: Beam Member Size: 16 X 36 Comments:

NUREG-1805 FDT Input Data NUREG-1 805 FDT: 02 2-Temperature-FV.xls (Version 1805.0) 02.3-temperaturn-oc-mv1 .xis (Version 1805.1) Heat Release Rate (kW): 650 Forced Ventilation Rate (cfm): Supply: 300 Exht: 300 Compartment Width (Pt): 13.5 Vent

Description:

Open Grille Compartment Length (ft): 49.5 Comparhnent Height (ff): 16.5 Initial Room Temp. (F): 11 0 Barrier Type: Concrete Barrier Thickness (in): 12 NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 1 Compartment Starting Temp. for Closed Room No Vent. FDT: 363.95 Hot Gas Layer Temperature

@ 180 minutes (F): 32t -91 Room Sketch: I 1 gt&V t847' N5 WI(FX~ 1 M-663-00017A, Revision W03 Page G3D-50 of G3D50 Thermal Short #I Sketch Thermal Short #t Photo 1 Thermal Short #I Photo 2 Structural Steel Fireproofing Data Appendix G~D 6303-2047 No photo required.

Attachment G4 Fire Protection Evaluation For Structural Steel Fireproofing With Unprotected Thermal Shorts in Closed Rooms with a Credible Fire and No Ventilation or Forced Ventilation Page 1 Rev. No. W03 Prepared By Date 6120107 Reviewed By & Date 06120107 Table of Contents Revision Log .................................................................................................................................

3 1.0 Purpose

.............................................................................................................................

4 2.0 Scope ................................................................................................................................

4 3.0 References.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 4.0 Assumptions.. . . .... ... .... ... .. . . .... ... .... ... .... ... .... , . ... .... .. ... .... ... .... . . ... .. .... ... .... .... ... .... ... ... ...... .. ... 5 5.0 Assessment of Condition to Design Requirements

...........................................................

5 6.0 Methodology

.. .. .. ... .... ... .... .... ... ....... .... ... .... ..... .... .... . .... .... . .... ... .... ....

... .... ..... .... ... ... ..... ... .... .7 7.0 Evaluation

.........................................................................................................................

8 8.0 Conclusions

.....................................................................................................................

12 Appendix G4A, NUREG-1805 FDT Example - Closed Room No Ventilation

................................

.............................

(2 Total Pages)

Appendix G4B, NUREG-1 805 FDT Example - Closed Room Forced Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (4 Total, Pages) Appendix G4C, Thermal Short and Room Data Sheets Closed Room No Ventilation . . . . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . .. . .. . . . . .. . .. . . . . .

(1 3 Total Pages)

Appendix G4D, Thermal Short and Room Data Sheets Closed Room Forced Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (1 9 Total Pages) M-663-00017A Page 2 of 12 Attachment G4 Revision W03 Revision Log M-663-000 1 7A Page 3 of 12 Attachment G4 Revision W03 Revision W03 Reason for Revision Original Issue M-663-00017A Attachment G4 Revision W03 Page 4 of 12 1.0 Purpose 1.1 The purpose of this document is to evaluate the acceptability of protected structural steel with unprotected steel attachments (thermal shorts) that are welded to the building steel. This evaluation was conducted in accordance with the guidance of NRC Generic Letter 86-10 and Regulatory Guide 1.189.

2.0 Scope 2.1 This evaluation is applicable to the Rooms identified in Table II. 3.0 References 3.1 NRC Generic Letter 86-10, Implementation of Fire Protection Requirements, dated April 24, 1986 3.2 10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior To January 1, 1979 3.3 NRC lnspection Manual 0609, Appendix F, Fire Protection Significant Determination Process, dated 02/28/05.

3.4 NUREGICR-6850, Fire PRA Methodology for Nuclear Power Facilities, published 0912005 3.5 NUREG-1805, Fire Dynamics Tools (FDTs) Quantitative Fire Hazard Analysis Methods for the U.S. Nuclear Regulatory Commission Fire Protection lnspection Program, published 1212004 3.6 NUREG-1824, Verification and Validation of Selected Fire Models for Nuclear Power Plant Applications 3.7 Regulatory Guide 1.189, Fire Protection For Operating Nuclear Power Plants, April 2001 3.8 ASTM E-I 19, Standard Test Methods for Fire Tests of Building Construction and Materials 3.9 UL N-711, (A-126-OOOOI), Fire Test Report Of Loaded Restrained Beams Protected By Cementitious Mixture, Dated August 1 1, 1976 3.10 UL N-712, (A-126-00002), Fire Test Report Of Loaded Restrained Beams Protected By Cementitious Mixture, Dated May 13, 1977 3.1 1 A-126, Technical Specification For Cernentitious Fireproofing Of Structural Steel For The Standardized Nuclear Unit Power Plant Unit (SNUPPS) 3.12 PIR 2002-2287, Structural Steel Fireproofing With Unprotected Attachments 3.13 FP-M-012, Rev 0, Structural Steel Fireproofing Thermal Shorts and Omissions Evaluation M-663-00017A Page 5 of 12 Attachment G4 Revision W03 TABLE I ASTM E-119 Temperature Limitations for 3-Hour Fire Exposure -~ingle~oir wm Average ' 5.2 Assessment At Wolf Creek, fireproofing material is generally applied over exposed surfaces of structural members with the exwption of thermal shorts and intervening items. Underwriters Laboratories

{U L) has tested several different size members utilizing both Albi Duraspray and Monokote 2-146 coatings to 3-hour ASTM E- 119 fire exposures.

The testing for beams and columns, utilized W8 x 28 steel shapes incorporating two protection methods; contour and boxed. However, testing of both techniques did not incorporate thermal short attachments.

Therefore, the affect of heat flux into plant structural steel with unprotected 3.14 CNT-MC-600, Rev. 2, Fireproofing of Structural Steel 3.1 5 Drawing A-1 801, Rev. 10, Architectural Fire Delineation Floor Plan EL 1974-0" 3.16 Updated Safety Analysis Report (USAR) Section 9.5.1.2.2.3.c, Rev. 15 and Table 9.5A-1 Sheet 27, Rev. 4 3.1 7 AN-94-041, WCGS IPEEE Project IPEEE Fire Ignition Frequencies 4.0 Assumptions 4.1 It is assumed that fireproofing material used to protect building stee4 is applied to a thickness as required by CNT-MC-600.

This is an acceptable assumption based on a review of the Qualrty Control documentation maintained during initial fireproofing installation activities and subsequent inspections during ongoing plant repairs witnessed by Fire Protection personnel.

5.0 Assessment of Condition to Design Requirements 5.1 Requirements USAR Section 9.5.1.2.2.3.c , identifies that the notes wntained on Figure 9.5.1-2 [Drawing A-18011 define the structural steel fireproofing requirements.

The structural steel of all of the ceilings of the fire areas is fireproofed with 3-hour protection with the exception that no fireproofing is provided on the underside of the fuel building roof. USAR Table 9.5A-1 Sheet 27 (Rev. 41, that structural steel supporting the Control and Auxiliary Building roofs is protected with [3-hour] rated fireproofing.

Table I identifies the ASTM E-119 temperature limitations for structural steel protected with fireproofing.

A P a ge 6 of 12 Attachment G4 Revision W03 thermal shorts Is not directly bounded by fire testing. FP-M-0 12 revealed that unprotected thermal shorts, larger than Unistrut, contribute to single point temperatures that in so m e cas es exceed the ASTM E-119 accep ta nc e cri te ria, assuming a 3-h our fire exposure.

Typically, average temperatures sa t i s fied the ASTM E-119 acceptance Refer to Table II for the specific rooms that are addressed by this evaluation.

TABLE II T her mal Shorts in Closed Rooms with Credible F i re and No Ventilation or Forced Vent i lation Fire Room Building Elev. Description

Table Ill Table Ill I Area Group ASTM E-119 Rating A*3 1407 Auxiliary 2026-0 B or i c Acid Batching Tank 1 Beam: About 2-Hours Area See Note 3 A-29 1304 Auxiliary 2013-6 Aux Feedwater Pipe 1&4 Beam: 1.8 Hours, Attachment size is Chase smaller than analyzed , See Note 2 1327 Auxiliary 2000-0 Feedwater Pump Valve 1&4 Beam: 1.8 Hours, Attachment size is Compartment No. 2 smaller than analyzed, See Note 2 A-30 1305 Auxiliary 2013-6 Aux Feedwater Pipe 1 Beam: About 2-Hours Chase 3 Column: About 1-Hour , Attachment size is smaller than analyzed 1328 Auxiliary 200Q-0 Feedwater Pump Valve 1 Beam: About 2-Hours Compartment No. 3 A-33 1329 Auxiliary 20DO-O Vestibule 1 Beam: About 2-Hours C-15 3403 Control 2016-0 Non-Vital Swgr & Xfmr Rm 1 Beam: About 2-Hours No.1 See Note 3 Be1ow 3404 Control 2016-0 Switchboard Rm No. 4 1 Beam: About 2-Hours, See Note3 3405 Control 2016-0 Battery Rm No.4 1 Beam: About I See Note3 2 Column: Nearly 3-Hours, See Note 2 3410 Control 2016-0 Switchboard Rm No. 2 1 Beam: About 2-Hours SeeNote3 ! 3411 Control 2016-0 Battery Rm No.2 1 Beam: About 2-Hours C-16 3407 Control 2016-0 Battery Rm No. 1 1 Beam: About 2-Hours 3408 Control 2016-0 Switchboard Rm No. 1 1 Beam: About 2-Hours 2 Column: N early 3-Hours, See Note 2 3409 Control 2016-0 Non-Vital Swgr & Xfmr Rm 1&4 Beam: 1.8 Hours, Attachment size is No.2 smaller than an a lyzed, See Notes 2 & 3 3413 Control 2016-0 B attery Rm No. 3 1 Beam: About 2-Hours 3414 Control 2016-0 Switchboard Rm No. 3 1 Beam: About 2-Hours I Page 7 of 12 Table II Notes: M-663-000 1 7A Attachment G4 Revision W03 Category 1 (H member) as been conservatively assigned to this beam attachment configuration due to the lack of analysis of a W shape conf~uration welded to the boltom beam Range. It should be noted that W shapes thermally perform significantly better than H shapes due to the larger exposed area of the H shape. Hot spot farms in Web area around thermal short. Structural considerations could show this element perfohns its intended design function for threehours.

This Note is a direct excerpt fmm Calculation FP- M-042. Refer to Attachment G5 for the Heat Affected Zone (HAZ) review where steel is an integral element of the fire barrier assembly.

6.0 Methodology As discussed in Section 12.2.2 of M-663-00017A, Section 4.2.2 of Regulatory Guide 1 .I89 identifies that structural steel is not required to be protected to the fire resistance rating of the barrier [typically 3-hourq, provided analysis demonstrates that the steel temperature reached during fire exposure does not result in structural failure of the steel. Considering the results of FP-M-012, where an ASTM E-t 19 3-hour fire was modeled to assess thermal insult presented by unprotected attachments connected to protected steel, the Reg. Guide 1.189 approach allowance is utilized to address impact of unprotected thermal short attachments larger than Unistrut.

Walkdowns were conducted on a room-by-room basis utilizing structural steel drawings and a best effort visual inspection to determine the worse case thermal short configuration for columns, beams and where structural steel serves as an Appendix R fire boundary.

For the purpose of this evaluation, all unprotected thermal shorts greater than Unistrut were reviewed and considered relevant to determine worse case scenario.

FP-M-012 demonstrated that thermal short attachments equivalent to Unistrut did not present a thermal conductive path that would challenge structural steel integrity, assuming an ASTM E-119 fire exposure, See section 12.2.3 of M-663-00017A for furlher discussion regarding the overall fireproofing assessment methodology utilized in the identification process for selecting the worse case thermal short configuration.

Each worse case thermal short configuration was then compared to the configurations identified in Table Ill, from FP-M-Of 2, which were modeled assuming an ASTM E-119 3-hour fire exposure.

The fire resistance rating of the Table Ill configuration that provided the closest match to the worse case configuration was utilized to infer an approximate fire resistance rating, again assuming an ASTM E-119 3-hour fire exposure.

This comparison information is captured in Table 11. In all cases the structural steel for the rooms satisfied at least a I-hour rating, and in several cases nearly a 3-hour rating. Additionally.

many unprotected attachment members were smaller than that analyzed in FP-M-012, and therefore the beam or column being evaluated is expected to perfom better than that indicated.

In effort to assess structural steel performance considering representative plant configurations and hazards, the NUREG-1805 Fire Dynamics Tools (FDT) were utilized to determine the maximum hot gas layer temperature anticipated within the rooms considering simple fire heat release rates provided in Appendix F of NRC inspection Manual 0609. TABLE Ill Thermal Short Configurations Analyzed In FP-M412 1 Typical H-Shape thermal Abut two-hours Large segment of flange short on a moderate size exceeds peak temperature beam criterion.

2 Multiple W-Shape thermal Nearly three- Hot spot formation on the web. shorts on a large size hours Structural considerations could column show this element performs function for three-hours.

3 Large H Shape thermal short About ondour Large segment of entire ms- on a large size column section exceeds peak temperature criterion.

4 Typical W-Shape thermal 1 .Shours Hot spot bms in web area short on a moderate size around thermal short, Structural beam considerations could show this element performs function for three-hours.

5 Small thermal short Over threehours Provides indications of Unistrut (Unistrut) on a moderate impact on temperature field in size beam structural steel. These thermal shorts have little impact on primary structural element steel temperature.

6 Small thermal short Over three-hours Provides indications of Unistrut (Unistrut) on a moderate impact on temperature field in sine beam. Thermal structural steel. This is he Insulation on beam within most severe type of Unistrut the Unistrut is missing. thermal short. 7.0 Evaluation Each Room identified in Table II was reviewed and evaluated to determine if building structurat members with unprotected steel attachments larger than Unistrut would affect the steel integrity in the event of fire. It was determined by utilizing NUREG-1805 Fire Dynamics Tools that these rooms would not develop a hot gas layer that would influence the existing building steel, and existing building steel protection configurations are acceptable to maintain building integrity.

Each Table 11 room is either a dosed room with no ventilation or a closed room with forced ventilation.

A closed room with no ventilation is consistent with the application of NU REG-1805 FDT "02.3-temperature-~~~revl .XIS (Version 1805.1), as it addresses modeling closed compartments with natural ventilation associated only with compartment leakage. This is an acceptable approach, as rooms of concern will have limited natural ventilation leakage occurring predominantly around allowed door gaps. Therefore, this FDT was utilized to assess room hot gas layer temperature development M-663-00017A Page 9 of 12 Attachment G4 Revision W03 for closed rooms containing no ventilation.

An example of the FDT is provided in Appendix G4A. Where rooms were closed, with the exception of forced air ventilation openings, it was recognized that these rooms would effectively become a closed room once HVAC fire damper closure was achieved.

HVAC fire dampers are closed by one of the following means: Automatically close by the fire alarm system, following smoke detection activation, for dampers provided with an electto-thermal link (ETL). Closebythemeltingofafusiblelinkwithatemperatureratingof 165OF. Rooms with ETL controlled fire dampers were considered closed rooms with no forced ventilation, since room forced ventilation flow would be eliminated by fire alarm system activation, which would occur early in the fire development stage. Therefore, closed rmms with forced ventilation controlled by ETL fire dampers also utilize NUREG-1805 FDT '02.3-temperature_cc-rev1 .xis" (Version 1805.1 ). Where fusible link fire dampers provide rmm ventilation isolation, it was recognized that forced ventilation would continue for the room untit the compartment temperature reached the activation point of the fire damper fusible link.

Therefore, each of these rooms was first treated as compartment with forced ventilation until room hot gas layer temperature exceeded 200°F. NU REG-1 805 FDT '02.2-Temperature-W.xlsn (Version 1805.0), was utilized for this application.

An example of the FDT is provided in Appendix G4B. At the point that the hot gas layer temperature exceeded 200 OF, effectivety creating a closed room with no ventilation following fire damper closure, relevant data from the Closed Room - Forced Ventilation FDT was extracted and utilized as input within the previously discussed FDT, for a closed room with no forced ventilation.

When the duration for reaching 200°F was less than 1 minute, 200°F was utilized as the input temperature for the Closed Room - Forced Ventilation FDT. Data collection necessary for FDT input is provided in the individual room data sheets documented in Appendices G4C and G4D. Appendix G4C contains data for closed rooms with no ventilation, while G40 is for closed rooms with forced ventilation.

Input information necessary for each FDT utilized is as follows:

M-663-00017A Attachment G4 Revision W03 Page 10 of 12 Closed Room - No Ventilation NUREG -1 805 FDT "02.3~temperature~cc~rev1 .xlsn (Version 1805.1 ) Compartment width (ft) Compartment length (ft) Compartment height (ft) Barrier type (concrete or concrete block) Barrier thickness (in) Ambient air temperature (OF) Fire Heat Release Rate (kW) Time when Closed Room - Forced Ventilation FDT exceeds 200°F (min) Compartment starting temperature for Closed Room - No Ventilation FDT (OF) * *Data input from Closed Room - Forced Ventilation FDT Closed Room - Forced Ventilation NUREG-1 805 FDT "02.2-Temperature-FV.xlsn (Version 1805.0) Compartment width (ft) Compartment length (ft) Compartment height (ft) Barrier type (concrete or concrete block) Barrier thickness (in) Forced Ventilation Rate (cfm) Ambient air temperature (OF) Fire Heat Release Rate (kW) tnitially, a fire with a constant 650 kW heat release rate (HRR) was utilized for the Table I1 rooms. This HRR was chosen considering the guidance of Appendix F to NRC Inspection Manual 0609. Table IV, extracted from the Inspection Manual, reveals that a 650 kW HRR is based on a large electrical fire that reflects a high confidence limit (98'" percentile) fire severity.

This fire severity envelops large electrical fires, transient combustible fires, and 90% of very large fire sources. This HRR exceeds the credible fire severity for each room of concern. It was initially chosen in effort to eliminate the need for a detailed quantitative review of room contents.

When utilizing a 650 kW HRR for each of the Table II rooms, the gas layer modeled did develop temperatures that exceeded the Table I maximum average exposure temperatures limitations for beams andlor columns. To further evaluate and assess the Table II rooms, a room by room walk down along with a comparison to the IEEE ignition source frequency calculation AN-94-041 was conducted in effort to reasonably develop a credible scenario heat release rate, considering room combustible loading, equipment, and the associated fire hazard. NRC Inspection Manual 0609, Appendix F was utilized to aid in the process of mapping the general fire scenario characterization to a for each room evaluated.

Table IV was M-663-000 17 A Attachment G4 Revision W03 Page 11 of 12 used to bin predefined fire characteristics for each room considering AN-94-041 and walkdown data. Each room was binned to either a 200 kW or 70 kW HRR fire based on an assessment of room contents in relation to Table IV information. Specifically , a 200 kW fire envelops small electrica l, engine/heater , and transient combustible fires , while a 70 kW fire envelopes 90% of both engine/heater and transient combustible fires. The credible heat release rates determined for each r oom are i dent i fied in the Appendix G4C and G4D room data sheets. In all cases , specific room area input into the FDT using a credible HRR y i elded hot gas layer results at a 180-minute duration that were less than the ASTM E-119 average temperature limitat i ons identified in Table I. Refer , to the Appendix G4C and G4D room data sheets for specific results. During ASTM E-119 fi re testing , temperatures are reco r ded on the steel surface underneath the fireproofing protective coating in effort to assess fireproofing effectiveness when subjected to approximate 1925 o p fire exposure for a 3-hour duration. Considering that the FDT calculated room hot gas layer temperature was Jess than the Table I ASTM E-1 19 average temperatu r e limitations , it is reasonable to conclude that unprotected thermal short attachments will not present a thermal failure mode to the structural steel , since the 1 r oom will not attain temperatures during the postulated fire event that would challenge steel structural i ntegrity. TABL I E IV Generic Fire Bins 1 650kW 2 MW Table IV Note: Percentile F i re 1. Inf orma t ion ex tr acted from NRC I n spe c t i o n Ma nual 0609. A p pe n d i x F , Table 2.3.1.

  • i M-663-000 1 7A Attachment G4 Revision W03 Page 12 of 12 8.0 Post Fire Safe Shutdown Impact There is no impact to post-fire safe shutdown (PFSSD) capability, as the evaluation demonstrates that postulated fire event room temperate will not result in detrimental impact to structural steel integrity.

Refer to Attachment G5 for the Heat Affected Zone (HAZ) review where steel is an integral element of the fire barrier assembly.

9.0 Conclusions This evaluation demonstrates that unprotected thermal shorts, attached to structural steel within the Table II rooms, does not result in a detrimental impact to structural steel integrity. Utilization of NUREG-1805 FDTs revealed that hot gas layer temperatures for each of the Table II rooms did not exceed the ASTM E-119 maximum average exposure temperature for beam or column limitation in the associated room. Therefore, the protected structural steel configurations within these rooms are acceptable for the intended service, and will not degrade the affected fire barrier or structural integrity of the building steel, or affect redundant PFSSD capability.

Based on the above discussion, it is reasonable to conclude that the existing fireproofing on the structural steel with unprotected attachments will satisfy regulatory expectations and commitments as well as WCNOC Fire Protection Program requirements, to prevent building steel failure as a result of fire exposure.

  • *
  • M-663-00017A , Revision W03 _..._ __ ---, __ ..._..._.

CHAPTER 2. PREDICTING HOT GAS LAYER TEMPERATURE IN A ROOM FIRE WITH DOOR CLOSED Ca!e ....... ltWIIIII(..., c. .......

..,..,. .... --t ......... (Tal __ _......, .-., ,._ ... ___ ....... _ ....

..........1!11' 1 ,.. IM"' -$&1 Allool

  • L l* 1!.00 1! 00 15DC 12 oc !A n.oo V... A ___ ., .. _entiDIIIIG

__ , I w.=-*

Page G4A-1 of G4A*2 Appendix G4A

  • *
  • M-663-00017A , Revision W03 ..... MI.-. ............

-*-------, ....................

.... PNpnd by. ._! -----' Clleelied by; ._! -----' 111 Page G4A*2 of G4A-2 Appendbc G4A

  • *
  • M-663-00017 A. Revision W03 --------------.......................................

I CHAPTER 2. PREDICTING HOT GAS LAYER TEMPERATURE IN A ROOM FIRE WITH FORCED VENTILATION COMPARTMENT WITH THERMALLY THICK/TKIN BOUNDARlE Ver&TOn* 1105.0 .. Ou....,:--

.,.._"' ... _....,_. ** !*--1., ...,, .... o.pn<.#""'

"'"" tnp..li n. "P...,.,._ _...,..10"""""'

..,.,....,.

!).*' . ..,), e 00i1(11 rhe-inlw..-G

........ ,... ....... _._ .*. I. . ' Ei . . 12.001 T

,._ iT "T.

..............

nMIIIHMamllilnltll f ....... ....,....K Q*-... _ r-.af the ... (kWJ m * *+****4--*'lilll1 Row l'di lllgiMC) c. "specilc hell af .. lk.fta-K)

......... _._.(ltWIIrf-K A1

  • lilll8!

.. IDI .. biiid IUitllol Ull') Thennal Pa.--.on Thiilt Calculdon

,.. ""-" nr WI-. .. *lhenMI...-..on

.... lttc) f,. * . oontWuclllln

.... Clll*itl' It

.....

". inlefior 111tdi-(Ill) ZI1ZB.II MC Page G4B-1 ofG4B-4 Appendix G4B

  • *
  • M-663-00017 A , Revision W03 ..... __ _ Oloooloo .. _..,.. .........

---... -._ ... _,.._ .. or [Mil fal tnmdllr (kWin'i'-1()

11'1 ICif cansltiJC(OIIbeii:fill ir\tM1Ja W '-1( ._ (a tlwmal 11f01!MY ol tetpc>IWible fCf the ,.

t z vma .-igM!an (sec) S.lallle below,.,--

...... of COIIlplt'tn*11 Encto*IJ19 Swfac:e 8oundariH A 21* I WI :tfh. "

  • carnpiiMI*III-*"'*1J w* " CllllfiCMIItlll tqll tml h. * (m) area Cll*>l em' 301.16 111" Complftlnent Hot GIIS Layer Willi Fo,..,.d
r. 0.6 0/m( 1M rmc. a l:" *T .. l1mc Ah<r lgnol o Dn 1<1 "* \\f iT* !kWm "" 1 0 0 . . . 1 110 022 0.13 C2.24 2 120 0 1G 1 0.15 4 .85 l ... -.. 0 13 l" <0.11 5147 * . .. 0 11 *0.17 5C 21 -5 :100 0 10 <0.11 $143 l O ... I 0 07 0.20 6393 )5 ... I 0 06 11.22 &an 20 I 12Dtl 0.05 1 0.%3 7242 25 ' 1500 0 04 I 0.24 75.39 30 1100 0 04 I '0.25 71!10 35 *-0 04 I 0.20 80 0 .. 40 *-0 03 I 11.21 82 OS 45 I 2780 0 0) 0.27 83!0 so -0 O l 0.27 8541 55 lliO 0 03 0.28 86 89 60 -0 03 0.21 8&26 300 --T . 313.DO 355.24 3110.15 317.21 3811.43 371.13 311.77 315.42 311.31 3t0.10 313.10 315.05 311.10 391.41 319.n 401.21 l o T -r I -104.00 12.24 110.02 17.15 110.11 11.47 1 * .15 M.21 201.57 lUI 201.57 1IUI 211.07 ta77 227.71 112..42 ZIUI 111.11 ** 71 117 ** MUJ 121.1 0 l&t7 122.01 211.11 1U.IO .... 12U1 217.n 1-... 121.>> --

0 10 20 METHOD OF DEAL AND SEYLER tt.et T ........ Coefficient Cak:uhlllon ft.c 04 I) fort< Wh.,. h. ,_ Wnsfer cooniQenl (JAW!rrf K 30 Tlme(n*l)

'IC ,. 1t11et10r CQri!I1I'UCtJon lltetrMIIne<Ua tkWinf li.T ta lllwiMI PIOP"<<Y ol ,..,...,.

respoNible lor the rile

... lhldl.-oltnlallor lllling (Ill) 0.1111 kWim'-K ....,_ of Compemnent Enc l osi n g SUrface 8ouniWIH 21111

  • w ,l* 2
  • A,:: Jouc;m Q (IIIC, *1\.Ao) !50 110 Page G4B-2 of G4B-4 Appendix G4B .., ' ' 'l
  • *
  • M-663-00017A.

Revision W03 ................ ........ lllliiiJMI---

---r.. .........................

,..,.. .... r ...

0 t><o*i

  • a'& af 1M,..., !K"'l If!

'"""

  • l!'O I ,. &!!<<"' h .. <:fa.'< (kJIKQ Kl .>1Ml<:h*11 hut ikWii!"'-11 A -ltlw

"<Jril)Woou'"'on"'

1tJr T t int' AftC!r 1 h. } r., T T, **\910 -I . . " 0 0 . 31300 40..00 l 10 0.09 2.51 315 G.S7 2 120 0 06 3.63 316.53 a.a l 110 0.05 4.45 317 '5 4U5 4 240 oo* 5.13 311113 -.u 5 300 004 5.74 31117* &7-. 10 800 003 11.10 321 10 ....,. 15 toO 0.02 1.11 322.91 4U1 20 1200 002 11.43 32' 4l 25 1500 002 12.71 325 76 IIZ.ltl lO 1800 0 02 13.97 326.97 -lS 2100 001 15.07 328.07 11m .0 2400 001 11.10 329 10 .... '5 2700 0.01 17.01 33006 87AII so 3000 0 01 17.t7 33097 rsrm 55 3300 001 111.14 33114 .... liO 3800 0.01 11.11 332 6t .... Hot Ga Layw T.,.,.,. Rll"l*l Vtnlhlion

-01111 rod 8e)'ler u.thod 160 ------*---*-r f 104.00 101.63 110.54 112.01 113.2A 11US 111.A 121.13 12U7 tat7 121.14 1S1.1S 132.11 1$t.72 131.31 1S7.11 13UO ii:" 120 t-r:=-.... 40 20 0

0 10 20 300 30 Tma(rin) Hot 0.. Lapt T...,......

Forced Venlllalion 50 ----------------

60 Page G4B-3 of G4B-4 Append i x G4B ----__ DMI_Bejllr_

  • *
  • M-663-00017 A , Revis i on W03 -----_.c ___ _ ___ ... _____ _ l'fepaled by. L----' Date I,_ ___ _. Dale iL. ___ _, 4 Page G4B-4 of G4B-4 Append i x G4B
  • *
  • M-663-00017 A , Revision W03 Page G4C-1 ofG4C-13 . Structural Steel Fireproofing Data Appendix G4C Room-Elevation
3403-2016 Building: Control fire Area: C-15 Description
Non-Vital Swgr & Xfmr Rm No. 1 Thermal Short #1 (TS1) Data Thermal Short 1#2 (TS2) Data Drawing: C-OS3511 C-OS3001 Member Type: Beam Column Member Size: 14X30 14 X370 Comments: No thermal shorts, co l umn is bounded by test i ng. NUREG-1805 FDT Input Data NUREG-1805 FOT: 02.3_tempecature

_cc_rev1.xls (Version 1805.1) Credible Fire HRR (kW: Credible Fire Basis: SWGR: Moderate Fire MCC: Moderate Fife Cabinet: Small Fire Transformer 480V Moderate Fire Exposed cable: Minimal , Small Flre 200KW T r ansient Package: Majority o f BTU: Small Fire IPEEE I gnitio n Source Evaluat io n: 1.82E-03 Barrier Type: Barrier Thickness (In): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Initial Room Temp. (F): NUREG .. 1805 FDT Results Hot Gas Layer Temperature@

180 minutes (F): 534.27 Room Sketch: Block 8 12.5 30 15.25 90 M-663-00017 A , Revision W03 Page G4C-2 ofG4C-13

  • Structural Steel Fireproofing Data Appendix G4C 3403-2016 Thermal Short #1 Sketch I I I 1 I ' .., *. * . . . . 4 , . . . . .. f I * ( \
  • Thermal Short #1 Photo 1 Thermal Short #1 Photo 2
  • J *
  • *
  • M-663-00017 A. Revision W03 Page G4C-3 of G4C*13 Structural Steel Fireproofing Data Appendix G4C Room-Elevation:

3404-2016 Building:

Control Fire Area: C-15 Description

Switchboard Rm No. 4 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-053511 C-053001 Member Type: Beam Column Member Size: 24X 76 14 X 370 Comments: Column has no thermal shorts , considered bounded by testing. NUREG*1805 FDT ln,Put Data NUREG-1805 FDT: 02.3_temperature

_cc_rev1.xls (Version 18<15.1) Credible Fire HRR (kW: ' Credible Fire Basis: 200KW Barrier Type: SWGR: Moderate Fire MCC: Moderate Fire Cabinet: Small Fire Transformer 460V Moderate Fire Exposed cable: Minimum. Small Fire Transient Package: Majority of BTU: Small Fire IPEEE Ignition Source Evaluation

2.00E..03 Barrier Thickness (in): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Initial Room Temp. (F): NUREG-1805 FDT Results Hot Gas Layer Temperature@

180 minutes {F): 551.23 Room Sketch: Otl l I .: I I I _.... "I J , 7*t. ---, -..J l 3110"3 l o .. 51oi1 tiD<<' 'Hot l.. Block 8 22.5 17 15.25 90 A *

  • Structural Steel Fireproofing Data Appendix G4C 3404-2016 Thermal Short #1 Sketch b * * (f ,
  • p Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 * ' *
  • *
  • M-663-00017A, Revision W03 Page G4C-5 of G4G-13 Structural Stee l l Fireproofing Data Appendix G4C Room-Elevation:

3410-2016 Building:

Control Fire Area: C-15 Description

Switchboa rd Rm No. 2 Thermal Short #1 (TS1) Data C-OS3511 Thermal Short #2 (TS2) Data Drawing: Member Type: Member Size: Comments: Beam 24X 76 N/A N/A N/A No columns. NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.3_temperature

_cc_rev1.xls (Version 1805.1) Credible Fire HRR (kW: 200KW Barrier T ype: ' Credible Fire Basis: SWGR: Moderate Fire MCC: Moderate Fire Cabinet: Smau Fire Transformer 480V Moderate Fire Exposed cable: Minimum , Small Fire Transient Package: Majority of BTU: Small Fire IPEEE Ignition Source Evaluation

1 Barrier Thickness (In): Compartment W i dth (ft): Compartment Length (ft): Compartment Height (ft): Initial .Room Temp. (F): NUREG-1805 FDT Results Hot Gas Layer Temperature@

180 minutes *(F): 591.41 Room Sketch: --==----

Black 8 19 18 15.25 90 M-663-00017 A. Rev i sion W03 Page G4C-6 of G4C-13

  • Structural Steel Fireproofing Data Appendix G4C 3410-2016 Thermal Short #1 Sketch .. {tWO-Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 * *
  • *
  • M-663-00017A , Revision W03 Page G4C-7 of G4C-13 Structural Steel Fireproofing Data Appendix G4C Room-Elevation:

Building:

Control Fire Area: C-16 Description

Switchboard Rm No. 1 Thermal Short #1 (TS1) Data C-OS351 1 Thermal Short #2 (TS2) Data Drawing: C-OS300 1 Member Type: Beam Co lu mn Member Size: 24X68 14 X 398 Comments: NUREG-1805 F.DT Input Data 'NUREG-1805 FDT: 02.3_t empe ra ture_cc_revi

.XI (Version 18 0 5.1} Credible Fire HRR (kW: 200K W Barf'ier Type: Credible Fire Basis: SWGR: M oder a te Fire 1 MCC: Moderate Fire Cabinet: Smau Fire Transformer 480V M o derate Fire Exposed cable: Minimal. Sm a ll Fire Transient P ack age: M a jority of BTU: Small Fire IPEEE Ignition S ource Eva l uation* 2.00E-03 Barrier Thickness (in): Compartment Width (ft): Compartment

!Length (ft): Compartment Height (ft}: Initial Room Temp. (F): NUREG-1805 FOT Results Hot Gas Layer Temperature@

180 minutes (F): 541.47 Room Sketch: Block 8 22 18 1 5.25 90 ' 'I 1 i '

M-663-00017A , Revision W03 Page G4G-8 of G4C-13

  • Structural Steel Fireproofing Data Appendix G4C 3408-2016 Thermal Short #1 Sketch ..
  • Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 * *
  • M-663-00017A , Revis i on W03
  • Structural Steel Fireproofing Data Thermal Short #2 Sketch Thermal Short #2 Photo 1 *
  • Page G4C-9 of G4C-13 Appendix G4C Thermal Short #2 Photo 2 * , (
  • *
  • M-663-00017 A , Revision W03 Page G4C-10 of G4C-13 Structural Stee 1 1 Fireproofing Data Appendix G4C Room-Elevation:

3409-2016 Building: Control Fire Area: C-16 Description

Non-Vital Swgr & Xfmr Rm No. 2 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: 'Member Type: Member Size: Comments: C-0$3511 Beam 27 X 94 Additional Items In close proximity (4" l's and 21/2,. angles). N/A N/A N/A No columns. NUREG-1805 FOT Input Data NUREG-1805 FDT: 02.3_temperature

_cc_rev1.xls (Version 1805.1) Credible Fire HRR (kW: Credible Fire Basis: SWGR: Moderate F i re MCC: Moderate F.ir e Cabinet: Small Fire Transformer 480V Moderate Fire Exposed Cable: Minimal. Small Fire 200KW Transient Pacl<aga: Majority o f BTU: Small Fire I PEEE I gnition Source Evaluation

2.22E..03 Barrier Type: Barrier Thickness (in): Compartment Width (ft): Compartment Length (ft): Compartment Height (ft}: Initial Room Temp. (F): NUREG-1805 FDT Results Hot Gas Layer Temperature@

180 minutes (F): Room Sketch: A\.L COtO\l \T$ wAu, J\J!JIKPIT TO

.* HTU'It t.o"' 3olt01/ ND I"'Wl!!l 565.1 8 .. .... I@

Block 8 28 12.25 15.25 90 ... , J ' J M-663-00017A. Rev i sion W03 Page G4C*11 of G4C.13 Structural Steel Fireproofing Data

  • Appendix G4C 3409-2016 Thermal Short #1 Sketch t Thermal Short #1 Photo 1 T hermal Short #1 Photo 2 * *
  • *
  • M-663-00017A , Revision W03 Page G4C.12 of G4C.13 Structural Steel Fireproofing Data Appendix G4C Room-Elevation:

3414-2016 Building:

Control Fire Area: C-16 . Description

Switchboa rd Rm No. 3 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-053511 Member Type: Beam Member Size: 24X68 Comments: N/A N/A N/A No columns.

FDT Input 1 Data NUREG-1805 FDT: 02.3_temperature

_ccJev1.xls (Version 1805.1) Credible Fire HRR (kW: Credible Fire Basis: SWGR: Moderate Fire MCC: Moderate Fire Cabinet: Small Fire Transformer 480V Moderate Fire Exposed cable: Minimal , Smau Fire 200KW Transient Package: Majority of B TU: Small Fire IPEEE Ignition Source Evaluation

1.93E-03 Barrier Type: Barrier Thickness (in): Compartment W i dth (ft): Compartment Length (ft): Compartment Height (ft): Initial Room Temp. (F): NUREG-1805 FDT Results Hot Gas Layer Temperature@

180 minutes (F): 591.4 1 Room Sketch: Block 8 19 18 15.25 90

  • 1 J I ..

M-663-00017 A , Revision W03 Page G4C-13 of G4C-13

  • Structural Steel Fireproofing Data Appendix G4C . 3414-2016 Thermal Short #1 Sketch ** *4 * . . . .. . ., . Thermal Short #1 Photo 1 Thermal Short #1 Photo 2
  • ph 0 * *
  • *
  • M-663-00017A , Revision W03 Page G4D-1 of G40-19 Structura: l Stee: l Fireproofing Data Appendix G4D Room-Elevation:

1407-2026 Buildin,g:

Auxi liary Fire Area: A-03

Description:

Drawing: Member Type: Member Size: Comments: Boric Acid Batching Tank Area Thermal Short #1 (TS1) Data C-1$1521 Beam 30 X 108 Only 1 of 4 points are required to be e valuat ed. Thermal Short .#2 (TS2) Data N/A Column N/R No thermal short attachments on column , bound ed by testing. NUREG-1805 FOT Input Data NUREG-1805 FDT: Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Credible Fire HRR {kW): Credible Fire Basis: Small Motors: Small Fire Small Pumps: SmaD Fire Cabinet Small Fire 02.2_ Temperature_FV

.xls (Vemon 1805.0) 02.3_temperature_cc_rev1.xls (Version 1805.1) 19 29.75 20 70KW Forced Ventilation Rate (cfm}: Supply: 300, Open Grille Vent Description

Exht: 300 No Attachments to columns. Open Grille Barrier Type: Block Barrier Thickness (in): 1 2 lnitial t Room Temp. (F): 104 ! Exposed cable: Minimum. Small Fire Transient Package: Majority of ' BTU: SmaQ Fire I IPEEE lgniUon Source Evaluation
1.69E-03 Room Sketch: NUREG-'1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): 15 Compartment Starting Temp. for Closed Room No Ve.nt FDT (Ft: 204.41 Hot Gas Layer Temperature@

180 minutes (F): 303.16

  • M-663-00017A.

Revision W03 Page G40-2 Structural Steel Fireproofing Data

  • Appendix G40 1407-2026 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo .2 * * *
  • *
  • M-663-00017A , Revision W03 Page G4[)..3 of G4D-19 Structural Steel Fireproofing Data Appendix G40 Room-Elevation:

1304-2013 Building:

Auxiliary Fire Area: A-29 Description

Aux Feedwater Pipe Chase Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-151352 C-151001 Member Type: Beam Column Member Size: 18X 50 14 X 111 Comments: Additional attachments In close proximity. Column In room only has Unistrut & JB's, column considered accep table based on calculation FP-M-012.

NUREG-1805 FDT: Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Credible Fire HRR (kW): Credible Fire Basis: I Exposed cable: Negli9 i ble Transient Package: Majority o f BTU: SmaU Fire IPEEE Ignition Source Evaluation

3.76E-04 Room Sketch: NUREG-1805 FDT Input Data 02.2_Temperature

_FV.xls (Version 1805.0) 02.3_temperature

_cc_rev1.xls (Version 1805.1) 22 10 Forced Ventilation Rate (cfm): Vent Description

Supply: 150 Exh t: 150 12 70KW Opening in floor where ladder is (3.5' X 3.5') Barrier Type: Barrier Thickness (In): Initial Room Temp. (F): NUREG..:1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): Concrete 12 104 2 Compartment Starting Temp. for , Closed Room No Vent FDT (F): 211.16 Hot Gas Layer Temperature

@ 180 minutes (F):

,., 0 ,, __ 1,-,.,T _.., 380.73 M-663-00017A , Rev i sion W03 Page G4D-4 of G40-19

  • Structural Steel fi , reproofing Data Appendix G4D 1304-2013 Thermal Short #1 Sketch p -:\1 ( .. :)""' 1) ** a-*,

/lt.*A Thermal Short #1 Photo 1 T hermal Short #1 Photo 2 * *

  • *
  • M-663-00017A , Revision W03 Structural Steel Fireproofing Data Appendix G40 Room-Elevation:

1327-2000 Building:

Auxiliary Fire Area: A-29 Description

Feedwater Pump Valve Compartme nt No. 2 Thermal Short 11 (TS1) Data Thermal Short #2 (TS2) Data Drawing: Member Type: Member Size: C-1S1352 Beam 14X34 N/A N/A NIA Comments: Ad ditional attachments in close proximity. No columns. NUREG-1805 FDT: Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Credible Fire HRR (kW): Credible Fire .Basis: Exposed cable: Negligible Transient Packag e: Ma j o rity of BTU: Small Fire IPEEE I gnition Source E va luation: 3.7 6E-04 Room Sketch: NUREG-1805 FDT Input Data 02.2_Temperaltl e_FV.xls (Ve rsio n 1805.0) 02.3_t emperaltlre

_cc_r ev1.xls (Version 1805.1} 10 10 12 70KW Forced Ventilation Rate (cfm): Vent Desc r;i ption: Barrier Type: Barr i er Thickness (In): Init ial Room Temp. (F): NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): Suppl y. 100 Exh t; 100 Concrete 24 104 1 Compartment Starting Temp. for Closed Room No Vent FDt (F): 200 Hot Gas Layer Temperature@

1 80 minutes (F): 502.33 (ON a. ---1 M-663-00017A.

Revision W03 Page G40-6 of G40-19

  • Structural Steel Fireproofing Data Appendix G4D 1327-2000 Thermal Short #1 Sketch . * ' .a . 0 * * *
  • SeCTI6 Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 * *
  • *
  • M-663-00017 A , Revision W03 Page G4D-7 of G4D-19 Structural Steel Fireproofing Data Appendix G4D Room-'Eievation:

1305-2013 Building:

Auxiliary Fire Area: A-30

Description:

Aux Feedwater Pipe Chase Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Da ta Drawing: C-1$1352 C-151001 1 Member Type: Beam Colum n Member Size: 18 X 50 14 X 1 11 Comments: Add i tional attachments i n close prox i mity orientation of 1 ea. 4" tube causes 40 sa IN. NUREG-1805 FDT: Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Credible Fire HRR (kW): Credible Fire Basis: Exposed cable: eg ll g lbl e Transient Package: M a jority of BTU: Sm a ll Fire IPEEE Ignition Source Evaluation

3.78E-04 Room Sketch: NUREG-1805 FDT Input Data 02.2_Te mperatur e_FV.xl s (Version 1805.0) 02.3_temperature

_cc_rev1.xls (Version 1805.1) 22 1 0 Forced Ventilation Rate (cfm): Vent Description

Su ppl y: 150 E.x:ht: 150 12 70KW Open i ng i n floor whe r e ladder is (3.5' X 3.5') Barrier Type: Barrier Thickness (In): Initial Room Temp. (F): NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): Concrete 12 1 04 2 Compartment Starting Temp. for Closed Room No Vent FDT (F): 211.1 6 Hot Gas Layer Temperature@

180 minutes (F): 380.73 M-663-o0017A , Revision W03 Page G4D-8 of G4D-19

  • Structural Steel Fireproofing Data Appendix G4D 1305-2013 Thermal Short .#1 Sketch .. -.

t/11 ** *I"-. * *** . g..ca ...... .,.i: Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 *

  • Structural Steel Fireproofing Data Appendix G4D 1305-2013 Thermal Short #2 Sketch .. ' 1 .. Thermal Short #2 Photo 1 Thermal Short '#2 Photo 2 * *
  • *
  • M-663-00017A , Revision W03 Page G4D-1 0 of G4D-19 Structural Steel Fireproofing Data Appendix G4D Room-Elevation:

1328-2000 Building: Auxiliary Fire Area: A-30

Description:

Feedwater Pump Valve Compartment No. 3 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data I N/A Drawing: C-181352 Member Type: Beam Member Size: 14 X 34 Comments: NUREG-1805 FDT: Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Credible Fire HRR (kW): Credible Fire Basis: Exp06ed cable: Negligible Transient Package: Majority o f BTU: SmaH F i re IPEEE Ignition Sou r ce Eva l uati on: 3. 76E-04 Room Sketch: N/A N/A Column encapsulated in concrete , columAs considered bou nded by testing. NUREG-1805 FOT Input Data 02.2_Temperature_FV

.Jds (Ve rsion 1805.0) 02.3_temperature

_cc_rev1.xls (Version 1805.1) 10 10 12 70KW Forced Ventilation Rate (cfm): Vent

Description:

Barrier Type: Barrier lihi ckness (in): Initial Room Temp. (F): NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): Sup ply: 1 00 Exh *1 00 Concrete 24 104 1 Compartment Starting Temp. for Closed Room No Vent FDT (F): 200 Hot Gas Layer Temperature@

180 minutes (F): I [!ill] ,.., c ,..., , I I I I L--* J , I I I I "' I I /\. B U t 'v 502.33 M-663-00017 A , Revision W03 PageG40-11 ofG4D-19

  • Structural Steel Fireproofing Data Appendix G4D 1328-2000 Thermal Short #1 Sketch I>
  • I \ .. .. * '.6 I>'*
  • q -. Thermal Short #1 Photo 1 Thermal Short #1 , Photo 2 * *
  • *
  • M-663-00017A, Revision W03 Structural Steel Fireproofing Data Appendix G4D Room-Elevation
1329-2000 Building:

Auxiliary Fire Area: A-33

Description:

Vestibule Thermal Short #1 (TS1) Data Thennal Short #2 (TS2) Data Drawing: Member Type: Member Size: C-181352 Beam 10 X 21 N/A N/A N/A Comments: Only 1 of 6 points are required to be evaluated. Column encapsulated in concrete , columns considered bounded by testing. NUREG-1805 FDT: Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Credible Fire HRR {kW): Credible Fire Basis: Exposed cable: Negligible Transient Package: Majority o f BTU: Small Fire IPEEE Ignition Source Eva l uation: 3.76E-04 Room Sketch: A* t1Z91 v NUREG-1805 FDT Input Data 02.2_ Temperature

_FV.xls (Version 1805.0) 02.3_lemperature

_cc_rev1.xls (Version 1805.1) Forced Ventilation Rate (cfm): Vent Description

Supply: 100 Exh t: 100 7 27.75 12 70KW Vent at floor (Hatchway to 1207 , 3.5' X 3.5'). Temp not in USAR Table 3.11 , used room 1207 below Barrier Type: Barrier Thickness (in); Initial Room Temp. (F): NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): Concrete 12 106 1 Compartment Starting Temp. for Closed Room No Vent FDT (F): 200 Hot Gas Layer Temperature@

180 minutes (F): 368.12 M-663-00017A , Revis i on W03 Page G40-13 of G40-19

  • Structural Steel Fireproofing Data Appendix G4D 1329-2000 Thermal Short #1 Sketch w 10 X. 2.1 1 ..

AA Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 * *

  • *
  • M-663..00017A , Revision W03 Page G4D-14 of G4D-19 Structural Steel Fireproofing Data Appendix G4D Room-Elevation
3405-2016 Building: Control fire Area: C-15

Description:

Battery Rm No. 4 Thermal Short #1 (TS1} Data Thermal Short #2 (TS2} Data Drawing: C-OS3511 Member Type: Beam Member Size: 24X76 Comments: NUREG-1805

FDT
i Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Credible Fire HRR (kW): Credible Fire Basis: Batte rie s I PEEE I gnitio n Sou rce E v a lua t i on: 7.7 6 E-04 Room Sketch: C-OS3001 Column 14 X426 Column embedded on both sides. ALBI Is 2-1/2" thick minim u m due to finish requ i rements. NUREG-1805 FDT Input Data 0 2.2_ Tempe ra ture_F V .xis (Version 1805.0) 02.3_t empe r at u re_cc_rev1.)[1s (Vel$ion 1805.1) 20.5 12 1 5.25 200KW Forced Ventilation Rate (cfm): Vent Description
Barrier Type: Barrier Thickness (in): Initial Room Temp. (F): NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): Supp ly: 300 Exh t 3 90 Block 8 90 Compartment Starting Temp. for Closed Room No Vent I FDT (F): 2(i)0 Hot Gas Layer Temperature@

180 minutes (F): 812.83 1 3'1 11 I ... 0.0 MR .... I I t J*o*l fJ 464 I W t<f.t.f<<.J. I- -[S4tc, i .,. V' -1N&*U76. ...... I @ [Effi I I I l J .. , *

  • 1 M-663-00017A, Revision W03 Page G4D-15 of G4D*19
  • Structural S , teel Fireproofing Data Appendix G4D Thermal Short 11 Sketch Is * . ' I*' . ,., ,. ; . .. b ,
  • 0
  • Q .. *' .. 1 0 l-f s.ecT 1o w A* A. Thermal Short 11 Photo 1 Thermal Short 11 Photo 2 * *
  • *
  • M-663-00017A, Revision W03 Page G4D-16 ofG4D-19 Structural Steel Fireproofing Data Appendix G4D Room-Elevation:

3407-2016 Building:

Description

Battery Rm No. 1 Thermal Short #1 {TS1) Data Drawing: C-OS3511 Member Type: Beam Member Size: 24 X 68 Comments: Add i tiona l items in close prox i mity. Control Fire Area: C-16 Thermai_Short #2 (TS2) Data N/A N/A N/A No columns. NUREG-1805 FDT Input Data NUREG-1805 FDT: 02.2_ Temperature

_FV.xls (Version 1805.0) 02.3_temperature

_cc_rev1.xls (Version 1805.1) Compartment Width (ft): Compartment Length (ft): Compartment Height (ft): Credible Fire HRR (kW): Credible Fire Basis: Batteries IPEEE Ignition Source Evaluation

7.76E-04 Room Sketch: 12 20.5 15.25 200KW Forced Ventilation Rate (cfm): Vent Description
Barrier Type: Barrier Thickness (in): Initia l Room Temp. (F): NUREG-1805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): Supply: 300 Exht:390 Block 8 90 1 Compartment Starting Temp. for Closed Room No Vent FDT (F): 200 Hot Gas Layer Temperature

@ 180 minutes (F): 812.83 I {

M-663-00017A , Revision W03 Pa,ge G4D-17 of G4D-19 Structural Steel Fireproofing Data

  • Appendix 'G4D 3407-2016 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short#1 Photo 2 * * *
  • *
  • M-663-QOO 17 A , Revision W03 Page G4D-18 of G4D-19 Structural Stee1 Fireproofing Data Appendix G4D Room-Elevation:

3413-2016 Building: Control Fire Area: G-16

Description:

Battery Rm No. 3 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing: C-OS351 1 Member Type: Beam Member Size: 24X68 Comments: NUREG-1805 FDT: Compartment Width (ft): Compartment 1 Length (ft): Compartment Height (ft): Credible Fire HRR (kW): Credible Fire Basis: Batteries IPEEE Ignition Source Evaluation

7. 76E-o4 Room Sketch: N/A N/A N/A No columns. NUREG-1805 FDT Input Data 02.2_ Temperature_FV .xis (Version 1805.0) 02.3_temperature_cc_rev1

.xls (Version 1805.1) 21 12 15.25 200KW Forced Ventilation Rate (cfm): Vent Description

Barrier Type: Barrier Thickness (in): Initial Room Temp. (F): NUREG-1'805 FDT Results Time When Forced Ventilation Exceeds 200 F (min): Supply: 200 Exht: 340 Block 8 90 1 Compartment Starting Temp. for Closed Room No Vent FDT (F): 200 Hot Gas Layer Temperature@

180 minutes (F): 801.75 ------J M*663-00017A , Revis i on W03 Page G40*19 ofG4D-19

  • Structural Steel Fireproofing Data Appendix G40 Thermal Short #1 Sketch 1 f Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 * *