ML17151B068

From kanterella
Jump to navigation Jump to search
Fire Protection Evaluations for Unique or Unbounded Fire Barrier Configuration, M-663-00017A, Rev. W05, G2B1 to G2B79
ML17151B068
Person / Time
Site: Wolf Creek 
Issue date: 03/09/2017
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML17151A982 List: ... further results
References
WO 17-0045 M-663-00017A, Rev W05
Download: ML17151B068 (79)


Text

M-663-00017A, Revision W03 Page G281 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1101-1974 Building:

Auxiliary Fire Area:

==

Description:==

General Floor Area No.

Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-OS1311 N/A Member Type:

Beam N/A Member Size:

21 X 155 N/A Comments:

There are no columns in this room.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

02.1_ Temperature_NV.xls (Version 1805.1) 650 14.5 215 25 Vent Width (ft):

Vent Height (ft) :

Top of Vent from Floor (ft):

Vent

Description:

25 22.5 25 A-01 Barrier Type:

Concrete Largest of two large vents used (south corridor)

Barrier Thickness (in):

24 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 163.47 Room Sketch:

!)of-(E C:.T~£1. /.lOT SJN)Witl FOK GU9~1TY

M-663-00017A, Revision W03 Page G282 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1101-1974 Thermal Short #1 Sketch V/£W LODJ:J 6/Jt>~TJI Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2B3 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

1120-1974 Building:

General Floor Area No. 2 Thermal Short #1 (TS1) Data C-OS1231 Beam 24 X 76 Embedded beam. no evaluation required. Sketch & photo for reference only.

Auxiliary Fire Area:

Thermal Short #2 (TS2) Data C-OS1001 Column 14 X 342 NUREG-1805 FDT Input Data NUREG-1805 FDT:

02.1_Temperature_NV.xls (Version 1805.1)

Heat Release Rate (kW):

650 Vent Width (ft):

13 Compartment Width (ft):

24.5 Vent Height (ft):

22.5 Compartment Length (ft):

40 Top of Vent from Floor (ft):

13 Compartment Height (ft):

13 Vent

Description:

A-01 Barrier Type:

Concrete One of two vents used which are the same size Barrier Thickness (in):

24 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 246.20 Room Sketch :

I

"""+/-- _I Som '0 Tlifl.. /.JCI"

~"'

l=il ~ ~~1r

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1120-1974 Thermal Short #1 Sketch VI£ l....ooK/tJ(., liA57 Thermal Short #1 Photo 1 TS

~I Page G284 of G2B-79 Appendix G2B sc.c..rtotJ A-A Thermal Short #1 Photo 2 No photo required.

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data 1120-1974 Thermal Short #2 Sketch Thermal Short #2 Photo 1 I.,

I I

rs 2

/11342.

S~CIIOI\\l A*A Thermal Short #2 Photo 2 Page G285 of G2B-79 Appendix G2B

M-663-00017 A. Revision W03 Page G2B6 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

NUREG-1805 FDT:

1121-1968 Building:

Auxiliary Fire Area:

Access Pit Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data N/A Column 14 X 264 Reviewed beams as part of Room 1120. Center column reviewed as part of sump area. FP coating approx. 2.5" C-1S1001 NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1)

Heat Release Rate (kW):

650 Vent Width (ft):

13 Compartment Width (ft):

13.5 Vent Height (ft):

62 Compartment Length (ft):

40 Top of Vent from Floor (ft):

13 Compartment Height (ft):

19 Vent Description :

A-01 Barrier Type:

Concrete One vent, open on three sides (Width = linear length along perimeter of three sides)

Barrier Thickness (in):

24 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 218.80 Room Sketch:

E.Lev. IC)Co9' (NT~)

'B~."::f-\\<<1~ Fo~ T\\tiS

'il::OOrY\\ A~G 1::-d\\J\\C'I.;J.IriJ I~ ~COn-t!l l "Z.O~ 112l.

M-663-00017A, Revision W03 Page G2B7 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1121-1968 Thermal Short #1 Sketch V IEW Loo/<ltJfl ~OcAI Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017 A, Revision W03 Page G288 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1122-1974 Building:

Auxiliary Fire Area:

==

Description:==

General Floor Area No. 3 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-OS1341 Member Type:

Beam Member Size:

36 X 260 Comments:

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

C-1S1001 Column 14 X 342 Building steel under N. hatch is protected by sprinklers in lieu of fireproofing NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 Vent Width (ft):

13 22.5 Vent Height (ft):

22.5 80.5 Top of Vent from Floor (ft):

13 13 Vent

Description:

Concrete Largest of two large vents used.

24 104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 220.98 Room Sketch:

B.t:. 197'1' (illS )

A-01

M-663-00017 A, Revision W03 Page G289 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1122-1974 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data 1122-1974 Thermal Short #2 Sketch

'1/eliJ L!>Oji;IA/A N61tTH Thermal Short #2 Photo 1 A l '

W ill J }fZ Page G2810 of G28-79 Appendix G2B Sec.. TIOI.J A* A Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

1130-1974 Building:

==

Description:==

North Corridor Thermal Short #1 (TS1) Data Drawing:

C-081321 Member Type:

Beam Member Size:

16 X 36 Comments:

Page G2811 of G2B-79 Appendix G2B Auxiliary Fire Area:

A-01 Thermal Short #2 (TS2) Data N/A N/A No columns.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

02.1_ Temperature_NV.xls (Version 1805.1) 650 13.25 40 25 Concrete 24 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent Description :

25 13.25 25 One of two vents used of equal size. Max Temp.

of 1 04 entered due all other open adjacent rooms, not in USAR Table 3.11 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 225.78 Room Sketch:

a. cr.

N~

N ~

AI b

[JTIQJ I>

I p A

J:-::.aoo!+--- -

-41 Oil I

v

M-663-00017A, Revision W03 Page G2812 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1130-1974 Thermal Short #1 Sketch sr.cnotJ A-A l~

l G t:: A!>T Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G2813 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1202-1988 Building:

Auxiliary Fire Area:

A-01

==

Description:==

Access Area B & Chiller Surge Tank Area Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-OS1331 C-OS1002 Member Type:

Beam Column Member Size:

16 X 36 14 X 314 Comments:

Additional attachments in close proximity.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

02.1_Temperature_NV.xls (Version 1805.1)

Heat Release Rate (kW):

650 Vent Width (ft):

Compartment Width (ft):

Vent Height (ft) :

Compartment Length (ft):

14 37.5 Top of Vent from Floor (ft):

Compartment Height (ft):

11 Vent

Description:

Barrier Type:

Concrete Barrier Thickness (in):

24 Initial Room Temp. (F):

96 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 303.33 Room Sketch:

G./.6'111711~

1 1~&'

(~r<r)

~..

~----------~*.1 1 ~r**_J_~----~tln~--UI 1 ~~

~ ~

If lf I

-~;-,

oPc"Jw,.,.t I

~ - __ !

- --*1.------4 11 15.5 11

M-663-00017A, Revision W03 Page G2814 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1202-1988 Thermal Short #1 Sketch VIe se..c.I/61J le-A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017 A, Revision W03 Page G2815 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1202-1988 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G2816 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1117-1974 Building:

Auxiliary Fire Area:

==

Description:==

Boric Acid Tank Room A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

C-OS1421 Beam 27 X 84 N/A N/A N/A Comments:

Additional 4" W shape in close proximity.

There are no columns in this room.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft) :

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 19.5 22 5 51 Vent Width (ft) :

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

31 19.5 51 Barrier Type:

Concrete Natural air movement from transfer grilles Barrier Thickness (in):

12 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 191.12 Room Sketch:

P C ro eOCW'rl I

!Il L~

r---------~----------------~~ ~M A-03

M-663-00017A, Revision W03 Page G2817 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1117-1974 Thermal Short #1 Sketch II /liVJ Lto IA.I E P.~i 5f.C..TION A*A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

1301-2000 Building:

==

Description:==

Corridor No. 1 Thermal Short #1 (TS 1) Data Drawing:

C-1 81411 Member Type:

Beam Member Size:

21 X 62 Comments:

Page G2B18 of G2B-79 Appendix G2B Auxiliary Fire Area:

A-08 Thermal Short #2 (TS2) Data N/A N/A N/A No columns.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

02.1_ Temperature_NV.xls (Version 1805.1) 650 14.5 215 25 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

25 14.5 25 Barrier Type:

Concrete One of two large vents of equal size used (North Corridor)

Barrier Thickness (in):

12 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 172.58 Room Sketch:

P6DR 11DI 2.

O""R I

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1301-2000 Thermal Short #1 Sketch I

I>*

  • ~

~

l.l fo 1

uo*

  • 11 : () *
  • t>

4" T~.tBt

~'il C.Ro\\S

('0~('11;\\

( T'O)

W ?..I X 1..2.

(oTRA'f ~PT VIEW oOt..IJ./f.. NDRTH 3"x g**

TU (; O::.fL

[ 'f'.c'?)

Page G2819 of G2B-79 Appendix G2B Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

1314-2000 Building:

==

Description:==

Corridor No. 3 Thermal Short #1 (TS1) Data Drawing:

C-1 S1411 Member Type:

Beam Member Size:

27 X 84 Comments:

Page G2820 of G28-79 Appendix G2B Auxiliary Fire Area:

A-08 Thermal Short #2 (TS2) Data C-OS1002 Column 14 X 228 Large area caused by 2 ea. Tube steel orientated across column.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

02.1_ Temperature_INV.xls (Version 1805.1) 650 20 121 25 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

25 33 25 Barrier Type:

Concrete Largest opening vent used of two large openings.

Barrier Thickness (in):

12 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F) : 164.57 Room Sketch:

l l (O>{TA tiJ Me!: NT

M-663-00017 A, Revision W03 Page G2821 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1314-2000 Thermal Short #1 Sketch

~

SI!L.T 10.J A. - A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G2822 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1314-2000 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G2823 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1315-2000 Building:

Auxiliary Fire Area:

A-08

==

Description:==

Ctmt Spray Additive Tank Area Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-081421 Member Type:

Beam Member Size:

24 X 84 Comments; NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

C-081002 Column 14 X 398 Additional attachments in close proximity.

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 13 21.5 25 Concrete 24 104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

NUREG-1805 FDT Results 7.5 3.5 7.5 Hot Gas Layer Temperature@ 180 minutes (F): 500.83 Room Sketch:

~

~.

J------------

1~

r~ ~

I' 1 31~.<> I

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data 1315-2000 Thermal Short #1 Sketch Thermal Short #1 Photo 1 l'too t

,..::.--1.4*

.TI'NT Page G2824 of G2B-79 Appendix G2B Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2B25 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1315-2000 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2B26 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1318-2000 Building:

Auxiliary Fire Area:

A-08

==

Description:==

Valve Compartment Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-08 1421 Member Type:

Beam Member Size:

33 X 118 Comments:

N/A N/A N/A No columns.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

02. 1_ Temperature_NV.xls (Version 1805.1)

Heat Release Rate (kW):

650 Vent Width (ft):

Compartment Width (ft):

17 21.5 25 Vent Height (ft):

Compartment Length (ft):

Top of Vent from Floor (ft):

Compartment Height (ft):

Vent

Description:

Barrier Type:

Concrete Barrier Thickness (in):

36 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 481.16 Room Sketch:

A4)

_ r

,.H _..,_

~ r-Lo~o ttt~il ef!t. AReA I ~

Etev T313

]~ ~

t {)(XI (

  • * !-r-

-r--

- ----=

40

(.vrs)

  • .l>

7-t'------------~

.. *' *~

L "x<! IHJI'

~~~0

~*

~

~

,,~--~-~--------

\\

  • ..,'-------------Jet:. __

1?.

...... 13/817

~.~ *

... 0 '* "'

/

  • .0

f 7.5 3.5 7.5

M-663-00017A, Revision W03 Page G2B27 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1318-2000 Thermal Short #1 Sketch W33X liB lof&-- 3o'~

3

  • ..,~ y

"'.. ~

~t.C.7 1o ~ A-A r-r::\\ -----

'LI Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G2B28 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1320-2000 Building:

Auxiliary Fire Area:

==

Description:==

Corridor No. 4 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-05 1441 Member Type:

Beam Member Size:

16 X 40 Comments:

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

C-151001 Column 14 X 264 Building steel under N. hatch is protected by sprinklers in lieu of fireproofing.

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 Vent Width (ft):

25 36 Vent Height (ft):

14 53 Top of Vent from Floor {ft):

25 25 Vent

Description:

Concrete Largets of two large opening used 24 104 NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 194.13 Room Sketch:

A-08

M-663-00017A, Revision W03 Page G2829 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1320-2000 Thermal Short #1 Sketch St::C.TlOIU A.-A-Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1320-2000 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Page G2B30 of G2B-79 w~ l 4.4

, ~ t..ob \\ A.IIIT sm.. JJ ~

b.A~ 'TY Thermal Short #2 Photo 2 Appendix G2B

M-663-00017A, Revision W03 Page G2B31 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1401-2026 Building:

Auxiliary Fire Area:

A-16

==

Description:==

Component Cooling Pump & Heat Exch Area B Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-1 51 511 C-05 1002 Member Type:

Beam Column Member Size:

24 X 76 14 X 158 Comments:

Tube steel is orientated to cause 144 square Inches of unprotected steel.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 36.75 66 20 Concrete 12 104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft) :

Vent

Description:

NUREG-1805 FDT Results Hot Gas layer Temperature @ 180 minutes (F): 176.12 Room Sketch :

G.I.SA 11~/>J zou. 1 (NT'O}

N I

I L_ __ ~._~~~--~~

20 36.75 20

M-663-00017A, Revision W03 Page G2832 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1401-2026 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G2B33 of G2B-79 Structural Steel Fireproofing Data Appendix G28 1401-2026 Thermal Short #2 Sketch Jf NO OY"' l S*o 1'-il-14tf SQ IN om*SScO'-)

Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G2834 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1402-2026 Building:

Auxiliary Fire Area:

==

Description:==

Corridor No. 1 Thermal Short #1 {TS1) Data Thermal Short #2 {TS2) Data Drawing:

Member Type:

Member Size:

Comments:

C-1 S1511 Beam 24 X 68 Additional angle steel within close proximity.

N/A N/A N/A No column in this room.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

02.1_ Temperature_NV.xls (Version 1805.1) 650 15 41 20 Concrete 24 104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F) : 238.98 Room Sketch:

~-=---~------ -----!--- ---

flf z.au.:

(..m.) ~

~.

~ L~

i l ______________ 1----4--~'

~ r 1

  • Will

~

~r.. ~ )*-

II l II I!

20 14.5 20 A-1 6

M-663-00017 A, Revision W03 Page G2835 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1402-2026 Thermal Short #1 Sketch 0

  • <J -

- b I>

7 I

APre*.

Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G2836 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1406-2026 Building:

Auxiliary Fire Area:

A-16

==

Description:==

Component Cooling Pump & Heat Exch Area A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-1S1521 C-OS1002 Member Type:

Beam Column Member Size:

27 X 84 14 X 228 Comments:

Additional items within close proximity.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 26 61 20 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

Barrier Type:

Concrete Room (vent) is open on two sides Barrier Thickness (in):

12 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 170.15 Room Sketch:

T 3 -

ELV. 20zb...

N

>>TS I>

20 76.5 20

M-663-00017A, Revision W03 Page G2837 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1406-2026 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017 A, Revision W03 Page G2838 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1406-2026 Thermal Short #2 Sketch 5eC.T IO N A*A Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

' -~-.

. ;i !J*...

.. n --

M-663-00017 A, Revision W03 Page G2839 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1408-2026 Building:

Auxiliary Fire Area:

==

Description:==

Corridor No. 2 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-1S1541 Member Type:

Beam Member Size:

21 X 55 Comments:

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft) :

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

C-1S1 001 Column 14 X 158 Building steel under N. hatch is protected by sprinklers in lieu of fireproofing per drawing.

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 18 215 20 Concrete 12 104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

NUREG-1805 FDT Results 20 88.5 20 Hot Gas Layer Temperature@ 180 minutes (F): 147.76 Room Sketch:

A-16

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1408-2026 Thermal Short #1 Sketch A

- * (i

. b,

A -, a.

. 0.,.

t>

Thermal Short #1 Photo 1 L> -

().

sc:c.no!J A* A Page G2840 of G28-79 Appendix G2B

]

Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1408-2026 Thermal Short #2 Sketch Thermal Short #2 Photo 1 73 2

I Page G2841 of G2B-79 Appendix G2B S~c.no~ A.-A Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G2842 of G2B-79 Structural Steel Fireproofing Data Appendix G28 Room-Elevation:

1504-2047 Building:

Auxiliary Fire Area:

A-1 9

==

Description:==

Ctmt Purge Exhaust & Mech Equip Rm B Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-081631 C-08 1002 Member Type:

Beam Column Member Size:

24 X 68 14 X 184 Comments:

Additional attachments in close proximity.

Additional attachments in close proximity (53" angle supports).

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 39.75 89 25.25 Concrete 12 104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft) :

Vent

Description:

NUREG-1805 FDT Results Hot Gas l ayer Temperature @ 180 minutes (F): 179.58 Room Sketch:

N

  • EI.EV. "U-t7' 25.25 14 25.25

M-663-00017A, Revision W03 Page G2843 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1504-2047 Thermal Short #1 Sketch 6

. 6 *. * *.

0 VIi Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2B44 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1504-2047 Thermal Short #2 Sketch SC..TI6N A* A.

Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2B45 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1506-2047 Building:

Auxiliary Fire Area:

A-19

==

Description:==

Ctmt Purge Supply Air Handling Unit A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-1 S1641 C-151 001 Member Type:

Beam Column Member Size:

24 X 76 14 X 370 Comments:

Monorail determined to be not worse case, spacers and fire proofing insulate attachment configuration.

Orientation of tube steel causes 56 plus 16 square inches of unprotected surface.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

02.1_ Temperature_NV.xls (Version 1805.1)

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

650 48 94 25.25 Concrete 12 104 Vent Width (ft) :

Vent Height (ft):

Top of Vent from Floor (ft) :

Vent

Description:

NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 175.17 Room Sketch:

TW%1lt7C..

.1:! (1'5*1)

~....e: ~Tt£L t*N/

St~t~v.Jal t:~ ctAQ,lY 25.25 14 25.25

M-663-00017A, Revision W03 Page G2B46 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1506-2047 Thermal Short #1 Sketch WZ.-4 X7(..

Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2847 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1506-2047 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2848 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1513-2047 Building:

Auxiliary Fire Area:

==

Description:==

Control Bldg Vent Supply A/C Unit Rm Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-081621 C-081002 Member Type:

Beam Column Member Size:

24 X 76 14 X 184 Comments:

Additional strut connection in close proximity.

Additional angle in close proximity.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

02.1_ Temperature_NV.xls (Version 1805.1)

Heat Release Rate (kW):

650 Vent Width (ft):

Compartment Width (ft):

35 Vent Height (ft):

Compartme_nt Length (ft):

15 25.25 Top of Vent from Floor (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

Concrete 12 104 Vent

Description:

NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 222.58 Room Sketch:

~

I

~

1 j

/'\\.

-~ I H

  • 1 5"1~ 1 v ~

~ ~

'Ill I

! 15*3]

I j) vJ2At1t

  • I_JI

--I II W

E1£V. Zo41 " j f I

I

/.JT)

JiJ f-

- -----~ -

OPe>l TO tVI 150(.

I 25.25 15 25.25 A-19

M-663-00017 A, Revision W03 Page G2B49 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1513-2047 Thermal Short #1 Sketch S£CTICI-J A-A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2850 of G28-79 Structural Steel Fireproofing Data Appendix G28 1513-2047 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G2B51 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1502-2047 Auxiliary Fire Area:

A-20

==

Description:==

Component Cooling Water Surge Tank Area B Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

C-081631 Beam 21 X 55 N/A N/A N/A Comments:

Monorail attachment, only 1 point is required to be evaluated.

No columns.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 39.75 16 25.25 Concrete 12 104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 219.21 Room Sketch:

~

I

£t.eY 204-/

.Nrs 25.25 14 25.25

M-663-00017 A. Revision W03 Page G2852 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1502-2047 Thermal Short #1 Sketch

. v I) w 2.11( 55 VJi.W LDol<tNI. WrEST Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2B53 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1503-2047 Building:

Auxiliary Fire Area:

A-20

==

Description:==

Component Cooling Water Surge Tank Area A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

C-OS1631 Beam 21 X 55 N/A N/A N/A Comments:

Monorail attachment. only 1 point is required to be evaluated.

No columns.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

NUREG-1805 FDT Input Data 02.1_Temperature_NV.xls (Version 1805.1) 650 32 15 25.25 Concrete 12 104 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent Description :

NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 228.21 Room Sketch :

N 25.25 14 25.25

M-663-00017A, Revision W03 Page G2854 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1503-2047 Thermal Short #1 Sketch ScCTtot.-:~ A -A V/e.W LooKtiJCi W~T Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2855 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1505-2047 Building:

Auxiliary Fire Area:

==

Description:==

Corridor Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-OS1631 Member Type:

Beam Member Size:

24 X 76 Comments:

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

N/A N/A N/A No exposed column.

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 10 9

25.25 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

25.25 9

25.25 A-20 Barrier Type:

Barrier Thickness (in):

Concrete 12 One of two large vent (equal in size) was used.

Temp not in USAR Table 3.11, used adjacent rooms Temp that are open to this room.

Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 317.54 Room Sketch:

£Lt l047 I NTS 0,

I ::P : t-_~------""'( :

~ - -

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1505-2047 Thermal Short #1 Sketch A

Thermal Short #1 Photo 1 Page G2856 of G2B-79 Appendix G2B

. ~

L' o

- ~ o~...

  • ' *~. -

-*_ 'Y **-

t b WZ4X7~

5xs"x~

~8£ STtJ;1.

S c:c...l! o..J A *A Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2B57 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1507-2047 Building:

Auxiliary Fire Area:

A-20

==

Description:==

Personnel Hatch Area Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-OS1631 C-1 S1001 Member Type:

Beam Column Member Size:

24 X 75 14 X 158 Comments:

Additional attachments in close proximity.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

02. 1_ Temperature_NV.xls (Version 1805.1)

Heat Release Rate (kW):

650 Vent Width (ft):

Compartment Width (ft):

Vent Height (ft):

Compartment Length (ft):

32 33 Top of Vent from Floor (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

Initial Room Temp. (F):

25.25 Concrete 12 104 Vent Description :

NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 223.79 Room Sketch:

~

oPe:I<J

-..;;- IS*i '--------- ------.

!:LV. Zo47 I

25.25 9

25.25

M-663-00017 A, Revision W03 Page G2858 of G2B-79 Structural Steel Fireproofing Data Appendix G28 1507-2047 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2859 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1507-2047 Thermal Short #2 Sketch St:CIION A*~

VIEW ~t:o.Jt, tiAST Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 No photo required.

M-663-00017A, Revision W03 Page G2860 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1508-2047 Building:

Auxiliary Fire Area:

==

Description:==

Drawing:

Main Steam Isolation Valve Rm No. 1 Thermal Short #1 (TS1) Data C-1 S1452 Thermal Short #2 (TS2) Data N/A Member Type :

Beam Member Size:

30 X 99 Comments:

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

N/A N/A No columns.

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 Vent Width (ft) :

22 35 48 Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

32 35 48 Barrier Type:

Concrete Open to room below and at Missile Sheilds Barrier Thickness (in):

24 Initial Room Temp. (F) :

120 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 184.77 Room Sketch:

A-23

M-663-00017A, Revision W03 Page G2B61 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1508-2047 Thermal Short #1 Sketch

  • tJ liXI./fbfl/flt

o/'*11 fi"FPt:!Cf11J,; T/1 QtJ87.

~?.4~1Zc

,.,C..,.,

jroAI~

SH. T!o IJ A. -A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

No photo required.

M-663-00017A, Revision W03 Page G2862 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1509-2047 Building:

Auxiliary Fire Area:

==

Description:==

Main Steam Isolation Valve Rm No. 2 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-1S1452 Member Type:

Beam Member Size:

30 X 99 Comments:

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

N/A N/A N/A No columns.

NUREG-1805 FDT Input Data 02.1 _ Temperature_NV.xls (Version 1805.1) 650 22 35 48 Vent Width (ft):

Vent Height (ft) :

Top of Vent from Floor (ft) :

Vent

Description:

32 35 48 Barrier Type:

Concrete Open to room below and at Missile Sheilds Barrier Thickness (in):

24 Initial Room Temp. (F):

120 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 164.77 Room Sketch:

A-23

M-663-00017A, Revision W03 Page G2863 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1509-2047 Thermal Short #1 Sketch

. u

'Ny"" I

~I. - ti~FlfCTl II?

"Ttii<'.,...T:

~d:4 ~tZo St:LTlbN A-A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

No photo required.

M-663-00017A, Revision W03 Page G2B64 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1324-2000 Building:

Auxiliary Fire Area:

==

Description:==

Feedwater Pump Valve Compartment No. 1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

C-181352 Beam 14 X 34 N/A N/A N/A Comments:

Additional attachments in close proximity (3" x 1/4" angle).

No columns.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 10 10 12 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

3.5 3.5 10 Barrier Type:

Concrete Vent at ceiling to Room 1304 (3.5 X 3.5)

Barrier Thickness (in):

12 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 975.88 Room Sketch:

(o..JT.

c:.uv. woo, Nts A

13241

~-.1..-------,. v EL' z.ooo' A-29

M-663-00017 A, Revision W03 Page G2B65 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1324-2000 Thermal Short #1 Sketch SE '- TI6N Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G2866 of G28-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1330-2000 Building:

Auxiliary Fire Area:

A-30

==

Description:==

Feedwater Pump Valve Compartment No. 4 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

C-151352 Beam 8 X 17 N/A N/A N/A Comments:

Column encapsulated in concrete, no issues w/column.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 Vent Width (ft):

10 Vent Height (ft):

10 Top of Vent from Floor (ft):

12 Vent

Description:

3.5 3.5 10 Barrier Type:

Concrete Open at ceiling (3.5 X 3.5) Hatchway Barrier Thickness (in):

12 Initial Room Temp. (F):

104 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 975.88 Room Sketch:

Elf.V. l OOo '

}'Jr>

M-663-00017 A, Revision W03 Page G2B67 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1330-2000 Thermal Short #1 Sketch Loo 1N') No'!-rn Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type :

Member Size:

Comments:

1206-1989 Building:

Pipe Chase Thermal Short #1 (TS1) Data C-1 S1352 Beam 14 X 34 Additional attachments in close proximity.

Page G2868 of G2B-79 Appendix G2B Auxiliary Fire Area:

A-33 Thermal Short #2 (TS2) Data C-1 S 1001 Column 14 X 111 NUREG-1805 FDT Input Data NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

Barrier Type:

Barrier Thickness (in):

02.1_ Temperature_NV.xls (Version 1805.1) 650 23 38 10 Concrete 24 Vent Width (ft) :

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

10 12 10 Lragest of two large vent openings used. Not in USAR Table 3.11, used 1207 Temp because it is open to 1207 and directly adjacent.

Initial Room Temp. (F):

106 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 316.93 Room Sketch:

I

~I I

I I

I I

I EL£Y. I?B9' NTS

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1206-1989 Thermal Short #1 Sketch

.J*r..

Thermal Short #1 Photo 1

/...ca>J.;-.J'j ~nr' 4"Tlllk ITS\\

SrL 0 Page G2869 of G28-79 Appendix G2B Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 1206-1989 Thermal Short #2 Sketch Thermal Short #2 Photo 1 3--.... ~~

(lfO VA( 5u.Pr Page G2B70 of G2B-79 Appendix G2B St:C.TIO A*A Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G2871 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

1207-1989 Building:

Auxiliary Fire Area :

==

Description:==

Pipe Chase Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-181352 C-1 8 1001 Member Type:

Beam Column Member Size:

18 X 40 14 X 111 Comments:

Additional attachments in close proximity.

NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

NUREG-1805 FDT Input Data 02.1_ Temperature_NV.xls (Version 1805.1) 650 23 38 10 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft) :

Vent

Description:

10 12 10 Barrier Type:

Concrete Lragest of two large vent openings used.

Barrier Thickness (in):

24 Initial Room Temp. (F):

106 NUREG-1805 FDT Results Hot Gas Layer Temperature @ 180 minutes (F): 316.93 Room Sketch:

A-33

M-663-00017A, Revision W03 Page G2872 of G28-79 Structural Steel Fireproofing Data Appendix G2B 1207-1989 Thermal Short #1 Sketch w-18J< 40

  • Sf:t:: T tDII
  • A A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Page G2B73 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 1207-1989 Thermal Short #2 Sketch Thermal Short #2 Photo 1 Thermal Short #2 Photo 2

M-663-00017A, Revision W03 Page G2B74 of G2B-79 Structural Steel Fireproofing Data Appendix G2B Room-Elevation:

3401-2016 Building:

Control Fire Area:

C-35

==

Description:==

Corridor No. 1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-083511 N/A Member Type:

Beam N/A Member Size:

24 X 68 N/A Comments:

No columns.

NUREG-1805 FDT Input Data NU REG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height {ft):

02.1_ Temperature_NV.xls (Version 1805.1) 650 6

86.5 15.25 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent Description :

15.25 11 15.25 Barrier Type:

Block Temp. not in USAR Table 3.11, used all adacent room temp of 90 Barrier Thickness (in):

8 Initial Room Temp. (F):

90 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 276.82 Room Sketch:

M-663-00017A, Revision W03 Page G2875 of G2B-79 Structural Steel Fireproofing Data Appendix G2B 3401-2016 Thermal Short #1 Sketch I

tJ.

. ". I

, ~. e..

0

.,. I

6. *

~ **

rs St.:.t..f CN A*A Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

3406-2016 Building:

Corridor No. 2 Thermal Short #1 (TS1) Data C-083511 Beam 24 X 68 Additional Items in close proximity. (6" long x 1/2" Plate).

Page G2B76 of G2B-79 Appendix G2B Control Fire Area:

C-35 Thermal Short #2 (TS2) Data C-083001 Column 14 X 426 Column embedded on both sides. ALBI is 2-1 /2" thick minimum due to finish requirements.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length {ft):

Compartment Height (ft):

02.1_ Temperature_NV.xls (Version 1805.1) 650 11 20.75 15.25 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

15.25 11 15.25 Barrier Type:

Block Temp. not in U8AR Table 3.11, used all adacent room temp of 90 Barrier Thickness (in):

8 Initial Room Temp. (F):

90 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 357.53 Room Sketch:

M-663-00017 A, Revision W03 Page G2877 of G28-79 Structural Steel Fireproofing Data Appendix G2B 3406-2016 Thermal Short #1 Sketch SE.c.TIO N A-fl..

Thermal Short #1 Photo 1 Thermal Short #1 Photo 2

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

3412-2016 Building:

==

Description:==

Emergency Shower & Eyewash Area Thermal Short #1 (TS 1) Data Drawing:

C-OS3511 Member Type:

Beam Member Size:

24 X 68 Comments:

Page G2878 of G2B-79 Appendix G2B Control Fire Area:

C-35 Thermal Short #2 (TS2) Data N/A N/A N/A No columns.

NUREG-1805 FDT Input Data NUREG-1805 FDT:

Heat Release Rate (kW):

Compartment Width (ft):

Compartment Length (ft):

Compartment Height (ft):

02.1_ Temperature_NV.xls (Version 1805.1) 650 11 17 15.25 Vent Width (ft):

Vent Height (ft):

Top of Vent from Floor (ft):

Vent

Description:

15 25 11 15.25 Barrier Type:

Block Temp. not in USAR Table 3.11, used all adacent room temp of 90 Barrier Thickness (in):

8 Initial Room Temp. (F):

90 NUREG-1805 FDT Results Hot Gas Layer Temperature@ 180 minutes (F): 373.15 Room Sketch:

"'"'"}

E~"Ylot~ *

{Ni'S)

M-663-00017A, Revision W03 Structural Steel Fireproofing Data 3412-2016 Thermal Short #1 Sketch Thermal Short #1 Photo 1 Page G2879 of G28-79

.ol w A ~ T'l sa '5TL

~~CII tH.J A-A Thermal Short #1 Photo 2 Appendix G2B No photo required.