Fire Protection Evaluations for Unique or Unbounded Fire Barrier Configuration, M-663-00017A, Rev. W05-02
ML17151B058
Person / Time
Site: Wolf Creek 
Issue date: 03/09/2017
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML17151A982 List: ... further results
References
WO 17-0045
Download: ML17151B058 (4)


Text

Form APF-05-003-01, Rev. 2

~***,..

~**

ASSIGNED DISCIPLINE:

Mechanical None DESIGN DOCUMENT CHANGE NOTICE DOCUMENT NUMBER M-663-00017 A OTHER DDCN'S REQUIRED TO IMPLEMENT CHANGE:

None REASON FOR CHANGE:

2" pipe through penetration Pl35S0227 was removed by change package 013404.

DigsigOrg 4.5 0.5 PREPARED BY: ~~Jeff Suter 01125/2017 DATE:

Verifier Qualification will be to the same requirement as the parent document Jason Pankaskie VERIFIED BY:

DigsigApp 4.5 0.5 APPROVED BY:

DCRELEASE~ ~*

DESCRIPTiur'l VI' \\..ttA!~\\Jt-:

l/26/2017 DATE:

DATE:

Oli26i2017 Kay L Smith Released by Document Services.

Release Date:

2017.01.30 08:45:16 -06'00' Attachment B3 Page 6 of 8-Delete "(2 penetrants)" per attached markup.

INITIATING DOC.

TYPE: NIA NO. NIA DCP/CCP NO 013404 REV. 9 REV.

wos SEQ. NO.

02 PAGE l OF 4 RPE Certification For ASME Section III design specifications, refer to AP 05-004 for qualification requirements Appendix B3 Pages B3-29 and B3 Replace pages in entirety with attached markup. Changes are as follows:

PageB3-29 Items 3-Deleted {1)2"P Item 11-Changed gap between pen to: N/A Sketch-Revised to reflect single pipe penetrant Page B3-30 Side 1 Photo-New as built photo Side 2 PhotO-New as built photo

M-663-00017 A 3 Revision W01 Communicating Penetration Fire Areas Number Side 1 Side 2 P133S0799 A-25 A-1 P133S0810 A-25 A-1 P134S0860 A-24 A-1 P135S0227 A-15 A-33 (2 fl9A9!FaA!S)

P145S0952 A-23 A-15 P145S0954 A-23 A-15 P145W2468 A-23 T-2 P145W2469 A-23 T-2 P145W2470 A-23 T-2 P145W2471 A-23 T-2 Table Notes:

M-663-00017 A-WOS-02 Page 2 Typical Calculated 11:, Sealant Detail Service i, Condition Temp 1

Actual (oF)

I (Acc./Rej.)

RB-1 350 Ace 2 RB-5A 400 Ace 2 RB-1 400 Ace 2 FB-1 575 Ace 1 FB-1 575 Ace 1 & 2 FB-1 575 Ace 1 & 2 FB-1 600 Ace 1 & 2 FB-1 600 Ace 1 & 2 FB-1 600 Ace 1 & 2 FB-1 600 Ace 1 & 2 Page 6 of8 Comments/Disposition:

See 5.2 for temperature limitation acceptability. Insulation transitions through the seal protecting the Radflex from system temperatures

_(limitation of 206°F).

See 5.2 for temperature limitation acceptability.

See 5.2 for temperature limitation acceptability. Insulation transitions through the seal protecting the Radflex from system temperatures (limitation of 206°F).

See 5.2 for temperature limitation acceptability See 5.2 for temperature limitation acceptability Refer to Attachment 813 for as left configuration following field action necessary to address PIR 2005-2384.

See 5.2 for temperature limitation acceptability Refer to Attachment B 13 for as left configuration following field action necessary to address PIR 2005-2384.

See 5.2 for temperature limitation acceptability See 5.2 for temperature limitation acceptability See 5.2 for temperature limitation acceptability See 5.2 for temperature limitation acceptability

1.

Temperature limitations for this penetration seal applies only to the boot and silicone caulk adhesive.

Temperature limitations do not apply to the Ceramic Fiber sealant material.

2.

Sealant condition could not be confirmed due to boot installation preventing visual inspections.

Although, topside boots are not required for RB-1 detail, topside boots have been installed in many instances. FB-1 detail boot condition was acceptable with no evidence of degradation. In some cases topside seal configuration was also enclosed within insulation that prevent sealant inspection, but was accessible on the bottom side to allow visual evaluation of boot. In these cases the boot did not exhibit deqradation.

M-663-00017A M-663-00017 A-WOS-02 Page 3 Page 83-29 of 83-42 Penetration Seal Data Appendix: 83 Penetration #:

P13550227 Penetration Type:

FB-1 Fire Area (Side 1): A-15 Fire Area (Side 2): A-33 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1151

1. Barrier Thickness:

16"

10. Annular Gap (smallest):

1 3/4"

2. Opening Size:

10"0

11. Gap between pen:

N/A

3. Penetrants:

(1)1"P

12. Barrier Type:

A F

w

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej): N/A Prepared By:
8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Underside of slab has Q-Decking, effective barrier thickness is measured from corrugated valley.

Sketch:

M-663-00017 A Penetration Seal Data Photos:

P135S0227 Fire Area A-15 (Side 1)

Fire Area A-33 (Side 2)

M-663-00017 A-W05-02 Page4 Page 83-30 of 83-42 Appendix: 83 Fire Area A-15 (Side 1)

Fire Area A-33 (Side 2)