ML17151B053

From kanterella
Jump to navigation Jump to search
Fire Protection Evaluations for Unique or Unbounded Fire Barrier Configuration, M-663-00017A, Rev. W01, B1-99 to B2-40
ML17151B053
Person / Time
Site: Wolf Creek 
Issue date: 03/09/2017
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML17151A982 List: ... further results
References
WO 17-0045 M-663-00017A, Rev W05
Download: ML17151B053 (123)


Text

M-66340017A, Revision W01 Page B1-99 of BI-172 Penetration Seal Data

.I Appendix:

Bf I

I. Barrier Thickness:

12"

2. Opening Siw:

12-0 3, Penetrants:

11 WP

4. Sealant Type:

Foam

5. Damming Side1 :

114" recessed

6. Damming Side 2:

Flush

7. Damming Continuity (AcclRej):

Accept

8. Boot Condition (AcelRej):

NIA

9. Sealant Depth:

9-314" fire Area (Side 1): A-20 MOX Dwg: M-OXlQ4.6 Fire Area (Side 2): A 4

10. Annular Gap (smallest):

1-718"

11. Gap between pen:

NIA

12. Barrier Type:
13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregoad Prepared By:

Jeff Suter Reviewed By:

Walkdown Comments:

Barrier thickness based on drawing C-OC1531. Changed Detail from M-I to M-6A based on actual seal depth.

Sketch:

Penetration #:

P I 53W2550 Penetration Type:

M4A m

y 2065'- 0"

M-663-000 174 Revision WO 1 Page B1-100 of B1-172 (Side 2)

Flre Area A-5 (Side 2)

Penetration Seal Data Appendix:

BI Photos:

P153W2550 Fire Area A-20 (Side 1)

Fire Area A-5 I

Fire Area A-20 (Side 1)

M-663-00017A, Revision WOI Fire Area (Side I):

A-20 MQX Dwg: M-1 XI 948 Page B1-101: ofB1-172 Fire Area (Side 2): A-5

10. Annular Gap (smallest):

1-314"

11. Gap between pen:

MIA

12. Barrier Type:
13. Opening S l e d or Concrete:

Steel f 4. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff suter Reviewed By:

Penetration Seal Data Appendix:

BI Penetration #:

P I 53W2627 Penetration Type:

M6A LocElev.: 2069-2"

1. Barrier Thickness:

12"

2. Opening Size:

12"D

3. Penetrants:

(1)B.P A SealaniType:

Foam

5. Damming Side1 :

Flush

6. Damming Side 2:

Flush

7. Damming Continuity {AcclRej):

Accept

8. Boot Condition (AeclRej);

NIA

9. Sealant Depth:

10" Wal kdown Comments:

Barrier thickness based on drawing C-OC1531. Changed Detail from M-1 to M-6A based on actual seal depth.

There are restraint lugs installed on one side. Length of Lug can not be determined.

Sketch:

1 I

I.,

d I

M-663-000 17A, Revision W0 1 (Side 2)

Fire h a

A-20 (Side I)

Fire Area A-5 (Side 2)

Penetration Seal Data Appendix:

BI Photos:

P I 53W2627 Fire Area A-20 (Side 1 )

I Rre Area A-5 Page BI-102 ofS1-172 C

I

' 1

M-663-000 17A, Revision WO I Sketch:

Fire Area (Side I): C-l MOX Dwg: M-I X3901 Fire Area (Side 2): CC-1

10. Annular Gap (smailest):

1-1 14"

11. Gap between pen:

MA

12. Barrier Type:

A F

W

13. Opening Sleeved or Concrete:

Steel

$4. Pipe Insulated:

No Wayne Aregood Prepared By:

JefF Suter Reviewed By:

Penetration Seal Data Appendix:

BI Penetration #:

P311 W0846 Pe-ion Type:

IWA LoeJElev.; 1980'4 7 T. Barrier Thickness:

36"

2. Opening S i i :

10"D

3. Penetrants:

(116"P

4. Sealant Type:

Foam

5. Damming Side1 :

Flush

6. Damming Side 2:

25" recessed

7. Damming Continuity (AcclRej):

Accept

8. Boot Condition (AeclRej):

MA

9. Sealant Depth:

9" Wal kdown Comments:

Barrier thickness determined by Drawing C-I C3111. Changed Detail M-i to M-6A based on actual sealant: depth.

M-663-00017A, Revision WO1 Fire Area GI (Side I j Fire Area CGl (Side 2)

Page B1-104 of B1-172 Penetration Seal Data Appendk BI Photos:

P311 W0846 Fire Area C1

{Side 1)

Fire Area CG1 (Sie2)

I

M-663-00017A, Revision W01 Page B1-105 of B1-172 Penetration Seal Data Appendix: ~i Penetration #:

P321 SO083 Fire Area (Side 1): C-6 MQX Dwg: M-1 X324 1 Fire Area (Side 2): C-1 Penetration Type:

M-6A

1. Barrier Thickness:

8" 2 Opening Size:

12"D

10. Annular Gap (smallest):

9-1 R" 1 1. Gap between pen:

NfA

12. Barrier Type:
13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

Yes

3. Penetrants:
4. Sealant Type:

Foam

5. Damming Side1 :

Foam Flush wlslesve

6. Damming Side 2:

Prepared By:

7. Damming Continuity (AcdReJ): Unknown
8. Boot Condition (Ac-j):

Jeff h t e r Reviewed By:

9. Sealant Depth:

Walkdown Comments:

Slab thickness based on drawing C-I C32 11. Bottom side damming position and continuity can not be verified due to insulation. Insulation completely covers bottom side opening. However, lnspectbn report indicates 8 depth within barrier.

Sketch:

M-663-000 17A, Revision W01 (Side 2)

Fire Area GI (Side 2)

Fire Area G6 (Side 1)

Penetration Seal Data Appendix:

~9 Photos:

P321 SO083 Fire Area C6 (Side 1)

Fire Area. C-f I

M-663-000 17A, Revision W01 Page B1-107 ofB1-172 Fire Area (Side 1): C-6 MOX Dwg: M-1 X3211 Fire Area (Side 2): C-I

10. Annular Gap (smallest):

1-112" 1 1. Gap between pen; NIA

12. Barrier Type:
13. Opening Sleemd or Concrete:

steel I4 Pipe Insulated:

Yes Wayne Aregood Prepad By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix:

~. i Penetration #:

P321 SO084 Penetration Type; M-6A M l e v. : 1 984'-0"

1. Barrier Thickness:

8"

2. Opening Size:

12"D

3. Penetrants:

( W P

4. Seatant Type:

Foam 5, Damming Side1 :

Foam flush wlsleeve

6. Damming Side 2:

Unknown

7. Dammlng Continuity (AcclRej):

Unknown

8. Boot Condition (AcelRej):

WA

9. Sealant Depth:

1 Ow **

Walkdown Comments:

Slab thickness based on drawing C-1 C321 I.

Bottom side damming position and continuity can no! be verified due to insulation. Insulation completely covers bottom side apening.

Sketch:

M-663-00017A, Revision WO I r l.

Page B1-108 of El-172

+

Fire Area G 6 (Side 1)

Fire Area GI (Side 2)

Penetration Seal Data Appendix:

~4 Photos:

P321S0084 Fire Area G6 (Side 1) 1 I

Fire Area Gl

M-663-00017A, Revision WO 1 Sketch:

Fire Area (Side I): C-6 MOX DWQ: IW-1 X3211 Page Bl-I09 ofB1-172 Fire Area (Side 2): C-1 Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix:

BI Penetration #:

P32180097 Penetration Type:

h4-M IneElev.: 1984'-0" I. Barrier Thickness:

8"

10. Annular Gap (smallest):

112"

2. Opening Size:

'1 2"D 1 1. Gap between pen:

WA

3. Penetrants:

(1)6*P

12. 8arrier Type:
4. Sealant Type:

Foam

13. Opening Sleeved or Concrew.

Steel

5. Damming Side1 :

Foam flush wl top of support and S

'4 Pipe Insulated:

No

6. Damming Side 2:

Ftush wlQ-Deck Valley

7. Damming Continuity (AcclRej):

Accept

8. Boot Conditlon (AcdRej):

NIA

9. Sealant Depth:

13" Walkdown Comments:

Slab thickness based on drawing C-1 C3219. Changed Detail from M-1 ta M-6A based on actual foam depth.

M-663-00017A, Revision W0 1 (Side 2)

Fire Area C6 (Side 1)

Fire Area Gf (Side 2)

I Page 81-110 dB]-172 !

Penetration Seal Data Appendix:

BI Photos:

P321 SO097 Fire Area C-6 (Side 1)

C Fire Area G1

M-663-000 17A, Revision W0 1 Page B1-If 1 ofB1-172 Fire Area (Side I):

C-6 MOX Dwg: M-1 X321 f Fire Area (Side 2): C-t

10. Annular Gap (smallest):

714 1 I. Gap bdwoen pen:

MIA

12. Barrier Type:
13. Opening Sleeved or Concrete; Steel
44. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Sketch:

Penetration Seal Data Appendix:

BI Penetration #:

P321 SO1 10 Penetration Type:

M-6A LodEk~.: 1984-0"

1. Barrier Thickness:

8"

2. Opening Sire:

1 OUD

3. Penetrants:

(IWP

4. Sealant Type:

Foam

5. Damming Side1 :

Foam flush w/ top of sleeve

6. Damming Side 2:

Flush wlQ-Deck Valley

7. Damming Continuity (AcdRej):

Accept

8. Boot Condition { A d e j ) :

NIA

9. Sealant Depth:

I I" Wal kdown Comments:

Slab thickness based on drawing C-t C321t. Changed Detail from M-7 to M-6A due to seal depth (WSA)

M-663-00017A, Revision WO 1 Fire Area C-6 (Side 1)

(Side 2)

Fire Area GI (Side 2)

Page B1-112 ofB1-172 I

Penetration Seal Data Appendix; BI Photos:

P321 SO1 10 Fire Area C-6 (Side 1)

Fire Area GI

M-663-000 1 7A, Revision W0 1 Page B1-113 ofB1-172.

Fire Area (Side 4):

C-5 MOX Dwg: M-1 X3211 Fire Area (Side 2): G 1

t 0. Annular Gap (smallest):

1 "

11. Gap between pen:

NIA

12. Barrier Type:
13. Opening Sleeved or Concrete:

Stgel

14. Pipe Insulated:

No Wayne Aregood Prepad By:

Jeff Suter R e v i m By:

Penetration Seal Data Appendix:

BI Penetration #:

P321 SO1 15 Penetration Type:

M-6A IneJElev.: 1984'4"

1. Barrier Thickness:

8"

2. Opening Size:

1 OnD

3. Penetrants:

(I y'p

4. Sealant Type:

Foam

5. Damming Side*:

Foam Rush whop of sleeve

6. Damming Side 2:

2' recessed

7. Damming Continuity (AoelRej):

Accept

8. Boot Condition (AdRej):

NIA

9. Sealant Depth:

9" Walkdown Comments:

dab thickness based on drawing C-9 C32f 1. Changed Detail from M-1 to M-6A based on actual seaiant depth Sketch:

L I

I t :

M-663-000 17A, Revision W0 1 Page B1-114 ofB1-I72 (Side 2)

Penetration Seal Data Appendk

~1 Photos:

P321 SO1 15 Fire Area C-5 (Side 7)

Fire Area G7 I

I Fire-C5 (Side 1)

Fire Area El (Side 2)

M-663-000 17A, Revision WO 1 Fire Area (Side I ): C-1 0 M4X Dwg: M-1x3317 Fire Area (Side 2): C-6

10. Annular Gap (manest):

2" I 1. Gap between pen:

NIA

12. Barrier Type:

F W

13. Opening Sleeved or Concrete:

-1

$4. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix:

BI Penetration #:

P331 SO1 27 Penetration Type:

M4A LocRlev.: 2000'4" T. Barrier Thickness:

1 0"

2. Opening Si:

110

3. Penetrants:

Ll.WP

4. Sealant Type:

Foam

5. r)ammkg Sidel:

Foam Flush wltop of sleeve

6. Damming Side 2:

1' recessed

7. Damming Continuity (AcdRej]:

Acc~pl

8. Boot C o d i o n (AcdRej):

NIA

9. Sealant Depth:

12" Walkdown Comments:

Slab thickness determined by Drawing C-1 C32I I. Changed Detail from M-4 ta M-6A based on actual sealant depth.

Sketch:

M-663-00017A, Revision W01 (Side 2)

Fire Area GI0 (Side 1)

I I !

Page 51-116 afB1-172 :

Penetration Seal Data Appendk BI Photos:

P331 SO1 27 Fire Area 12-10 (Side 1)

Fire Area G6 Fire Area C6 (Side 2)

I b.

Page B1-117 ofB1-172 M463-000 17A, Revision W0 1 Penetration Seal Data Appendix; 81 Penetration #:

P331 SO1 36 Penetrafion Type:

M-6A LocJEtev.: 2000'-0" I. Barrier Thickness:

10"

2. Opening Sie:

12"D

3. Penetrants:

(1 )8"P

4. Sealant Type:

Foam

5. Damming Sidel:

Foam flush wltop of sleeve

6. Damming Side 2:
  • Unknown
7. Damming Continuity (AedUej): '

Unknown

8. Boot CodItion ( M e j ) :

MIA

9. Sealant Depth:

1 On Walkdown Comments:

Slab thickness determined by Drawing C-1 C3211.

  • Bottom side damming covered wlinsuIation and the area is behind the security barrier (not accessible). S~de photo can not be taken.

Fire Area (Side 1): C-1 0 MOX Dwg: MIX331 I Fire Area (Side 2): E 6

10. Annular Gap (smallest):

1-412"

11. Gap between pen:

MIA

12. Barrier Type:
13. Opening Sleeved or Concrete:
14. Pipe Insulated:

Yes WayneAregood Prepared By:

Jeff Suter Reviewed By:

Sketch:

M-663-00017A, Revision W01 Fire Area G1O (Side 1)

(Side 2)

Fire Area C6 (Side 2 )

Penetration Seal Data Appendix:

BI Photos:

P331 SO1 36 Fire Area G i O (Side 1) I Fire Area C 4

M-663-000 1 7 4 Revision W0 1 I

I

' i Page B1-119 of B1-172 ;

Fire Area (Side 1): C-I 0 MQX Dwg: M-f X3311 Fire Area (Side 2): C-B

10. Annular Gap (smallest):

1 "

11. Gap between pen:

NIA

12. Barrier Type:

W

13. Opening Sleeved or Concrete:

Steel Id Pipe Insulated:

Yes Prepared By:

Jeff Sutar Reviewed By:

Sketch; Penetration Seal Data Appendix:

BT Penetration #:

P331 SO1 37 Penetration Type:

M-6A LacElev.: 2000'-0" I.

Bamer Thickness:

1 On

2. Opening Size:

12'D

3. Penetrants:

{1)8"P

4. Sealant Type; Foam
5. Damming Sidef:

Foam flush w h p of sleeve

6. Damming Side 2:
  • Unknown
7. Damming Continuity (AcdRej):

Unknown

8. Boot Condition ( A m ) :

NIA

9. Sealant Depth:

iO" Walkdown Comments:

Slab thickness determined by Drawing C-I C3211. Bottom side damming covered wlinsulation and the area is behind the security barrier (not accessible). Side 2 photo can not be taken.

M-663-00017A, Revision W01 Page B1-120ofB1-172 Penetration Seal Data Appendix:

81 Photos:

P331 SO1 37 Fire.&ea GI0 (Sidel)

Fire Area C-6 Fire Area C6 (Side 2 )

M-663-00017A, Revision W01

' 1 I

Page B1-121 of B1-172:

Fire Area (Side 1): C-10 M 4 X bwg: M-1x3314 Fire Area (Side 2): C-6

10. Annular Gap (smallest):

1 "

11. Gap between pen:

NIA

12. Barrier Type:

W

13. Opening Sleeved or Concrete:

Garel

14. Pipe Insulated:

Yes Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix:

BI Penetration #:

P331S0138 Penetration Type:

M-6A Loc.Elev.: 2000'4"

1. Barrier Thickness:

-1 0" 2 Opening S i :

12"D

3. Penetrants:

11WP

4. Sealant Type:

Foam 5.DamrningSidel:

Foamflushwhopofsleeve

6. Damming Side 2:
  • Unknown
7. Damming Continuity ( M e j ) : ' Unknown
8. Boot Condition ( A d e j ) :

NIA

9. Sealant Depth:

lo*

Walkdown Comments:

Slab thickness determined by Drawing C-1C3211. Bottom side damming covered wlinsulation and the area Is behind the security barrier (not accessible).

Sketch:

M-663-00017A, Revision WO1 Penetration Seal Data Appendix; BI Photos:

P331 SO7 38 Fire Area G10 (Side I)

I Rre Area G6 Fire-C1Q (Side I)

Fire Area G6 (Side 2)

Page B1-122 of B1-172 (Side 2)

M-663-000 I7A, Revision W0 I i

Page B1-123 ofB1-172 I,

Sketch:

Fire Area {Side I):

C-10 M-OX Dwg: M-1 X331 I Fire Area (Sil2): C 6 f 0. Annular Gap (smallest):

3j4"

11. Gap between pen:

MIA f 2. Barrier Type:

W

13. Opening Sleeved or Concrete:

S W

14. Pipe Insulated:

Yes Wayne Aregod Prepared By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix:

81 Penetration #:

P331 SO1 39 Penetration Type:

M-@A LacJEtev.: 2O00'-OH I. Barrier Thickness:

1 OM 2 Opening Size:

12*D

3. Penetrants:

(1 )8"P

4. Sealant Type:

Foam

5. Damming Side1 :

Faam flush whop of sleeve

6. Damming Side 2:
  • Unknown
7. Damming Continuity (AeclRej):

Unknown

8. Bmt Condition {AeelRej):

MA

9. Sealant Depth:

10" Walkdown Comments:

Stab thickness deterrnhed by Drawing C1 C3211. '

Bottom side damming covered wlinsulation atid the area is behind the security barrier (not accessible).

I 3

M-663-00017A, Revision W0 1 Fire Area C10 (Side 1)

Fire Area CS (Side 2)

Penetration Seal Data Appendix:

BI Photos:

P331 SO1 39 Firft Area GI0 (Side 1)

L Fire Area E6 Page B1-124 of B1-172 9f!$

M-663-000 174 Revision WO 1 Page B1-125 of BI-172 Penetration Seal Data Appendix:

81 Penetration #:

P33180143 Fire Area (Side 2): C-6 Penetmtion Type:

M-6A

1. Barrier Thickness:

8"

2. Opening S i :

10nD

3. Penetrants:

(?)B"P 4 Sealant Type:

Foam

5. Damming Sidel:

Foam Flush wltop of sleeve

6. Damming Side 2:

Flush wlQ-Deck valley

7. Damming Continuity (AcelRej):

Accept

8. Boot Condition (AcclRej):

N A

9. Sealant Depth:

11

10. Annular Gap (smallest):

1-1 14" I I. Gap between pen:

NIA

12. Banfer Type:

W

13. Opening Sleeved or Concrete:

SWl

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Walkdawn Comments; Slabthickness determined by Drawing C-1C3211, Skeich:

M-663-00017A, Revision WQ1 (Side 2)

Fire Area GI0 (Side 1)

Page B1-126 ofB1-172 Penetration Seal Data Appendix:

BI Photos:

P331 SO1 43 Fire Area G I 0 (Side I}

l Fire Area C-6 C

Fire Area G 6 (Side 23

M-663-000 17A, Revision W01 Sketch:

Flre Area (Side 1): C-9 M4X Dwg: M-IX33i i 4

1

1.

Page B1-127 of B1-172 I

Fire Area (Side 2): C-5

10. Annular Gap (smallest):

1 "

I d. Gap between pen:

NIA

12. Barrier Type:

F W

13. Opening Sleeved or Concrete:

Steet

14. Pipe Insulated:

No Wayne Aregwd Prepared By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix:

BI Penetration #:

P331 SO200 Penetration Type; M-18 LaeAElev.: 2000'-0"

1. Barrier Thlc kness:

1 0" 2 Opening Size:

t OnD

3. Penetrants:

(1)FP

4. Sealant Type:

foam

5. Damming Sldel; Foam Flush w2lfop of support
6. Damming Side 2:

Outside opening

7. Damming Continuity (AcdRejh Accept
8. Boot Condition (AccRej):

WA

9. Sealant Depth:

15-112" Walkdown Comments; Slab thickness determined by Drawing C-1C3211. Changed Detail from M-l to M-18 based actual foam depth.

Fire Area C9 (Side 1)

(Side 2)

Fire Area G5 (Side 2)

Penetration Seal Data Appendix:

BI Photos:

P331 SO200 Fire Area C-9 (Side 1)

Fire Area C-5 Page B1-128 of B1-172 w

- 1

M-663-00017A, Revision W0 1

Sketch:

Fire Area (Side 1): C-I 0 MQXDwg: M-1x3903 1 34 I

Page Bf -129 of B1-172

' 1 dl Fire Area (Side 2): D-1

10. Annular Gap (smallest):

t -1 12" 1 1. Gap between pen:

NIA

12. Barrier Type:

A F

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Prepared By:

Jeff Suter R e v i m By:

Penetration Seal Data Appendix:

BI Penetration #:

P331 WO882 Penetmtion Type:

M-6A Loc.lEl~.: 201 3'-0" I. Barrier Thickness:

24"

2. Opening Sb:

12"D

3. Penetrants:

(w"P

4. Sealant Type:

Foam

5. Damming Side1 :

' Flush 6, Damming Side 2:

7" recessed

7. Damming Continuity ( A M e j ) :

Accept 8, Boot Condition (A~dRej):

NIA

9. Sealant Depth:

15" Walkdown Comments:

Covered by insulation, slight manipulation of insulation indicated flush damming. Changed Detail from M-I to M-6A based on actual sealant depth.

M-663-00017A, Revision W01 Page B1-130 ofB1-172' !

Penetration Seal Data Appendix:

B-I Photos:

P331 W0882 Fire Area GI0 (Side 1)

Fire Area Dl I

Firekea GI0 (Side 1)

(Side 2)

M-66340017A, Revision W01 Sketch:

Fire Area (Side I): C-10 M-OX D w ~ : M-1 X3903 Page B1-131 ofB1-172 :

Fire Area (Side 2): D-1

10. Annular Gap (smallest):

2" I I. Gap between pen:

NIA

12. Barrier Type:

A F

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepad By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix: BI Penetration #:

P331 W0883 Penetration Type:

M6A LocJEkv*: 20 1 3'-0"

1. Barrier Thickness:

24"

2. Opening Sie:

12"D

3. Penetrants:

(1)8"P

4. Sealant Type:

Foam

5. Damming Side1 :

Flush

6. Damming Side 2:

6" recessed

7. Damming Continuity (AcdRej):

Accept

8. Boot Condition (A-j):

NIA

9. Sealant Depth:

18" Walkdown Comments:

Covered by insulation, slight maniputation of insulation indicated flush damming. Changed Detail from M-i to M-6A based on actual sealant depth.

M4634@017A, Revision W01 (Side 2)

Fire Area I31 (Side 2)

FireArea GI0 (Side 1)

Penetration Seal Data Appendix:

BI Photos:

P331 W0883 Fire-GI0 (Sidsl)

Fire Area O-I Page 81-132 ofB1-172

M-663-000 17A, Revision W0 1 I

Page B1-133 of B1-172 Fire Area ( S i l I): GI 0 M4X D w ~ :

M-1x3903 Fire Area (Side 2): 0-2

10. Annular Gap {smallest):

1 "

1 1. Gap between pen:

NIA

12. Barrier Type:

A F

W

13. Opening Sleeved or Concrete:

Sieel 14 Pipe Insulated:

No Wayne Aregoad Prepamd By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix:

BI Penetration #:

P331 W0890 Penetration Type:

M-6A tOc./Elev.:

2013'-0" I. Barrier Thickness:

24"

2. Opening S i :

12"D

3. Penetrants:

(1)8"P

4. Sealant Type:

Foam

5. Damming Side1 :

Flush

6. Damming Side 2:

10" recessed

7. Damming Continuity (AcclRej):

Accept

8. Boot Condttion (AcdRej):

NIA

9. Sealant Depth:

12" Walkdown Comments:

Changed Detail from M-l to M-6A based on actual sealant depth.

  • Damming flush under insulation.

Sketch:

M-663-000 17A, Revision WO I Penetration Seal Data Appendix:

BI Photos:

P331 W0890 Fire Area GI0 (Side 1)

Fire Area 0-2 Flre Area GI0 (Side 1)

(Side 2)

Fire Area 0-2 (Side 2)

M-663-000 17A, Revision W01 Fire Area (Side 1): C-6 M-OX Dwg: M-1 X3411 I

Page BI-135 of B1-172 FICItAma (Side 2): C-6

10. Annular Gap (smallest):

112"

11. Gap between pen:

NIA

12. Barrier Type:
13. Opening Sleeved or Concrete:

Steal

44. Pipe Insulated:

bb Wayne Aregood Prepad By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix:

BI Penetration #:

P341 SO272 Penetration Type:

M-6A M l e v. : 201 6'-0"

1. Barrier Thickness:

10"

2. Opening S i :

10"D

3. Penetrants:

(t p-P

4. Sealant Type:

Foam

5. Damming Side1 :

Foam flush wlslegve

6. Damming Side 2:

flush

7. Damming Continuity (AcdRej):

Accept

8. Boot Condition (AcclRej);

EUA

9. Sealant Depth:

13" Walkdown Comments:

Staimell Landing. Changed Data Base to reflect Nan-Appendix R (WSA). Could be bounded without darnrniw

~ 1 1 2 "

foam..

Sketch:

M-663-00017A, Revision W01 (Side 2)

Fire Area C6 (Side 1)

Penetration Seat Data Appendk BI Photos:

P341 SO272 Fire Area C 4 (Side I)

Fire Area G 6 Fire Area M

(Sie 2)

I Page B1-136 ofB1-172

M-663-00017A, Rafision WOl Page B1-137 of B1-172 Fire Area (Side 1): C-15 M-OX Dwg: M-1 X34t 1 Fire Area (Side 2): C-10

10. Annular Gap (smallest):

118" ta f 14" I f. Gap between pen; NIA

12. Barrier Type:

W

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregoad Prepared By:

Jeff Sutsr Reviewed By:

Penetration Sea[ Data Appendix:

BI Penetration #:

P341 SO288 Penetration Type:

M6A Loc.lEtev.: 20A6'-OH

3. Barrier Thickness:

10"

2. Opening Sue:

8"D

3. Penetrants:

jbS6"P

4. Sealant Type:

Foam

5. Damming Sidet:

Flush wlsleeve

6. Damming Side 2:

Flush wtsleeve 7, Damming Continuity (AcdRej):

Accept

8. Boot Condition (AcdRej):

NIA

9. Sealant Depth:

I Y Walkdawn Comments:

Changed Detail from M-1 to M-6A based on actual sealant depth.

Sketch:

M-663-00017A, Revision W01 Page B1-138 of B1-172 Penetration Sea1 Data Appndix:

BI Photos:

P341 SO288 Fire Area GI5 (Sie I)

Fire A m GI0

( S i 2)

Fire Area G15 (Side 4 )

Fire Area C10 (Side 2)

M-663-00017A, Revision W01 Sketch:

Fire Area (Side I):

C-16 MOX Dwg: M-1 XM11 Page B1-139 of B1-172 Fire Area (Side 2): C-9

10. Annular Gap (smallest):

314"

11. Gap between pen:

MA

12. Barrier Type:

W

13. Opening Sleeved or Concrete:

SIeel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendk BI Penetration #:

P341 SO306 Penetration Type:

M-6A LoeJElev.: 201 6'-0"

1. Barrier Thickness:

f O*

2 Opening S i :

F D

3. Penetrants:

(1)VP

4. Sealant Type:

Foam

5. Damming Side1 ;

Flush wlsleeve

6. Damming Side 2:

Flush wlsleeve

7. Damming Continuity (AcdRej):

Accept

8. Boot Condition ( M e j ) :

MA

9. Sealant Depth:

13" Walkdown Cornme*

Changed Detail from M-l to M-6A based on actual sealant depth.

M-663-00017A, Revision W01 (Side 2)

Penetration Seal Data Appendix: BI Photos:

P341 SO306 FireArea GI6 (Sidef)

Fire Area C-9.

Fire Area G16 (Side 1)

Fire Area G 9 (Side 2) u Page Bf -140 of B1-172

M-663-00017A, Revision W01 Fire Area (Side 1): C-16 MOX Dwg: M-1x3411 1

1 -,

Page Bl-141 ofB1-172 ;

Fire Area (Side 2): C-9

10. Annular Gap (smallest):

114"

11. Gap between pen:

NIA

12. Barrier Type:

W 13, Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Sketch:

Penetration Seal Data Appendix:

BI Penetration #:

P341 SO31 1 Penetraiion Type:

M-6A L o ~ v. : 2016'4" I. Barrier Thickness:

10"

2. Opening S i :

10nD

3. Penetrants:

(1)B"P

4. Seatant Type:

Foam

5. Damming Side1 :

Foam Flush wlsleeve

6. Damming Side 2:

Flush

7. Damming Continuity (AcclRej):

Accept

8. Boot Condition (AcclRej);

NIA

9. Sealant Depth; 13" Walkdown Comments:

Changed Detail from M-I to M-6A bawd on actual sealant depth.

M-663-00017A, Revision W01 (Side 2) fire Area G16 (Side 1)

Penetration Seal Data Appendix:

BI Photos:

P341 SO31 1 Fire Area E l 6 (Side 1)

Fire Area G9 n

Page B1-142 ofB1-172 Fire Area C-9 (Side 2)

M-663-00017A, Revision W0 1 Page B1-143 ofB1-172 Penetration Seal Data Appendix:

81 I

Penetration #:

P341 W0380 Penetration Type:

LocJElev.: 2028' Fire Area (Side I):

C-I 6 MOX Dwg: M-1X0342 Fire Area (Side 2): C-I 6

1. Barrier Thickness:

8" Nominal

2. Opening Size:

10"D

3. Penetrants:

( W P

4. Sealant Type:

Foam

5. Damming Side1 :

Flush wlsleevs

6. Damming Side 2:

Flush wlsleeve

7. Damming Continuity (AcdRej):

Accept

8. Boot Condition (AoelRej):

MIA

9. Sealant Depth:

6 3i4" Nominal

10. Annular Gap (smallest):

4" I I. Gap between pen:

NIA

12. Barrier Type:
13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

Mo Wayne Aregood Prepared By:

Jetf Suter Reviewed By:

Walkdown Comments:

Bounding not required, not Appendix R.

Sketch:

M-663-000 17A, Revision W0 1 FireArea GI6 (Sided)

I Page B1-144 of B1-172 Penetration Seal Data Appendix:

BI Photos:

P341 W0380 Fire Area C16 (Side 1)

Fire Area GI8 (Side 2)

Fire Area C-16 (Side 2)

M-663-000 I7A, Revision WO I Sketch:

Fire Ares (Side 1): G 2 1

M-OX D w ~ :

M-1x3511 Page B1-I45 of B1-172 Fire Area (Side 2): C-15

10. Annular Gap (smallest):

1 "

1 1. Gap between pen:

NIA

12. Barrier Type:
13. Opening Sleeved or Concrete:

S W

14. Pipe Insulated:

Ns Wayne Aregood Prepared By:

Jeff Suter Reviewed BY:

Penetration Seal Data Appendix:

BI Penetration #:

P35f SO339 Penetration Type:

M-6A LocEJw.: 2032'-0" I. Barrier Thickness:

8" 2 Opening Size:

qO*D

3. Penetrants:

(1P-P

4. Sealant Type:

Fuam

5. Damming Side?:

Foam flush wltop of support 6, Damming Side 2:

1" recessed

7. Damming Continuity (AcdRej):

Accept

8. BQ& Condition (AcdRej):

NIA

9. Sealant Depth:

11-114" Walkdown Comments:

Barrier thickness determined by Drawing GOC351 f. Changed Detail from M-1 to An-6A based on actual sealant depth.

M-663-000 17A, Revision W01 Page BI-146 of BI-172 Fire Area G21 (Side 1)

Penetration Seal Data Appendix:

BI Photos:

P351 SO339 Fire Area G21 (Side 1)

I,.L Fire Area GI5 (Side 2)

Fire Arm GI5 (Side 2)

M-663-00017A, Revision W01 Sketch:

Fire Area (Side 1): C-21 M-OX h g : WlX3511 Fire h a

(Side 2): C-15 Penetration Seal Data Appendix:

BI Penetration #:

P351 SO356 Penetration Type:

M-6A LodEkv.: 2032'-0"

1. Barrier Thickness:

8"

2. Opening Size:

10" D

3. Penetrants:

( 4 )6"P

4. Sealant Type:

Foam

5. Damming Sidel:

Foam 112" below top of sleeve

6. Damming Side 2:

Flush

7. Damming Continuity (AcelRej$

Accept

8. Boot Condition (AcdRej):

WA

9. Sealant Depth:

10-1/4A Wafkdown Comments:

Changd Detail from M-1 to MbA based on actual sealant depth. Barrier thickness determined by Drawing C-1C3511.

10. Annular Gap (smallest):

1 14" 1 1. Gap between pen:

NIA

12. Barrier Type:

4 3. Opening Slwved or Concrete:

14 Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

W Steel

M-663-000 17A, Revision W0 1 Penetration Seal Data Appendix:

BI Photos:

P351 SO356 Fire Area G21 (Side 1 )

Fire Area G15 (Side 2)

I Fire Area C-21 (Side 1)

Page BI-148 of 51-172 Fire Area GI 5 (Side 2) j I

M-663-000 17A, Revision W01 Fire Area (Side 4):

C-27 M4X DWQ: M-1x3611 Page B1-149 of BI-172 Fire Area (Side 2): C-21

10. Annular Gap (smallest):

2"

41. Gap between pen:

N IA t2. Barrier Type:

A F

W

13. Opening Sleeved or Concrete:

Steel t4. Pipe Insulated:

No Wayne Amgood Prepared By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix:

BI Penetration #:

P361 SO462 Penetration Type:

M-6A h.lElev.: 2047-6"

'I. Barrier Thickness:

8" 2 Opening Size:

1OD

3. Penetmnts:

(1)6"P

4. Sealant Type:

Foam

5. Damming Side1 :

Foam flush wltop of sleeve

6. Damming Side 2; Flush
7. Damming Continuity (AcclRej):

Accept

8. B d

Condifion (AeclRej);

NtA

9. Sealant Depth:

10-314" Walkdown Comments:

Slab thickness based on C-1 C361 I.

Changed Detail M-l to M-6A based on actual sealant depth.

Sketch:

M-663-000 17A, Revision W01 Fire Area C-27 (Side 1)

Penetration Seal Data Appendix:

BI Photos:

P361 SO462 Fire Area G27 (Side 1)

'I

'I Fire Area G21 b

C Fire Area C21 (Side 2)

Page BI-150 of B1-172

M-663-000 17A, Revision W0 1 Sketch:

Fire Area (Side I):

C-30 M-OX Dwg: M-1 X3611 Page BI-151 ofBI-172 Fire Area {Side 2): C-23 Wayne Aregood Prepared By:

Jeff Sufer Reviewed By:

Penetration Seal Data Appendix:

~1 Penetration #:

P36151052 Penetmtion Type:

E-2A LodElev.: 2047'-6"

f. Barrier Thickness:

8" f 0. Annular Gap (smallest):

NIA

2. Opening She:

8" X 2'-4" 1 1. Gap between pen:

NIA

3. Penetrants:

ET

12. Barrier Type:

A F

W

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Sickl:

1' recess area within tap side foam

14. Piw Insulated: No
6. Damming Side 2:

Flush

7. Damming Continuity (AcdRej):

Piccept 8, Boot Condition (AcctReJ):

NIA

9. Sealant Depth:

I Ow Walkdown Comments:

PMR 017% evaluates this seal as acceptable with only 8" of foam. PMR 01756 b no longer valid, 10" foam is installed.

M-663-000 17A, Revision WO 1 Page B1-152 of BI-172 Penetration Seal Data Appendix:

BI Photos:

P361 S1052 Fire Area C30 (Side I )

Fire Area G23 (Side 2)

Fire Area C30 (Side I )

Fire Area G23 (Side 2)

M-663-0001

?A, Revision W01 Penetration Seal Data Appendix:

BI Penetration #:

P361 S1055 Penetration Type:

E-2A L d l w. : 2047-6" I. Barrier Thickness:

8*

2. Opening Ske:

8" X 2'4"

3. Penetrants:

Er

4. Sealant Type:

Foam

5. Damming Sidrl:

Foam flush wltop of steeve

6. Damming Side 2:

Flush

7. Damming Continuity (AcclRen:

Accept

8. Boot Condition (AcdRej):

MA

9. Sealant Depth:

11" Walkdown Comments:

PMR 01756 evaluates this seal as acceptable with only 8" of foam. PMR 81 756 is no longer valid, 11" foam is installed.

Rre Area (Side I):

C-30 M-OX Dwg: M-1 X36i 1 Fire Area (Side 2): C-23

10. Annular Gap (smallest):

MIA I*.

Gap between pen:

MIA

$2. Barrier Type:

A F

W f 3. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregod Prepared By:

Jeff Suter Reviewed By:

Sketch:

M-663-00017A, Revision WO 1 fire Area C-30 (Side 1 )

Fire Area C23 (Side 2)

Page B1-154 of B1-172 Penetration Seal Data Appendix:

BI Photos:

P361 S1055 Fire Area C-30 (Side 1)

Fire Area G23 (Side 2)

M-663-00017A, Revision W0 1 Page B1-155 of B1-172 Sketch:

Fire Area (Side 1): G32 M-OX Dwg: M-1x3611 Fire Area (Side 2): C-26

10. Annular Gap (smallest):

MIA 1 1. Gap between pen:

NIA

12. Barrier Type:

A F

W

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix:

BI Penetration #:

P361 S1083 Penetration Type:

E -2A LodElev.: 2047'-V I. Barrier Thickness:

8"

2. Opening Size:

2'-4nX8"

3. Penetrants:

ET

4. Sealant Type:

Foam

5. Damming Sidel:

foam recessed 112" from top of sle

6. Damming Side 2:

Flush

7. Damming Continuity (AcclRej):

Acmpt

8. Boot Condition (AcclRej):

NiA

9. Sealant Depth:

1 0-1 12" Walkdown Comments:

PMR 01756 evaluates this seal as acceptable with only 8" of foam. PMR 01756 is no tonger valid,10-112" foam Is installed.

M-663-000 17A, Revision W01 Fire Area G32 (Side 1)

Fire Area G25 (Side 2)

Penetration Seal Data Appendix:

BI Photos:

P361 S1083 Fire Area G32 (Side I)

Fire Area G25 (Side 2 )

Page BI-156 ofB1-172 i

1

- 8

M-663-000 17A, Revision W0 1 Page B1-157 ofB1-172 Sketch:

Fire Area (Side 1): T-t2 M-OX Dwg: Max451 1 Fire Area (Side 2): T-8

10. Annular Gap (smallest):

N/A

11. Gap khveen pen:

NIA

12. Barrier Type:
13. Opening Sleeved or Concrete:

Steel I4 P i p lnsulat&

Yes Wayne Aregood Prepand By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix:

BI Penetration #:

P451 SO31 8 Penetration Type:

NM LocElev.: 2065'4"

1. Barrier Thickness:

6"

2. Opening Size:

8"D

3. Penetrants:

(1) 2'P, ( I ) 1"P N

4. Sealant Type:

None

5. Damming Side1 :

NIA

6. Damming Side 2:

NIA

7. Damming Continuity (AcclRej):

N A

8. Boot Condition (AcdRej):

NIA

9. Sealant Depth:

NIA Walkdown Comments:

This seal is Non-Appendix R located in the Turbine 9-314" North of column line T-8 and approximately 7 west of T-D.

There is no seal in this penetration. Changed Detail to "NU".

M-663-00017A, Revision WO1 Page B1-158 of B1-172 Sketch; Fire Area (Side I): T-12 M-OX Dwg: M4X45i i Fire Area (Side 2): T-8

10. Annular Gap (smallest):

NIA

11. Gap between pen:

NIA

12. Barrier Type:
13. Opening Sleeved or Concreie:

Steel

14. Pipe Insulated:

Yes Wayne Aregood Prepared By:

Jeff Suter Reviewed By; Penetration Seal Data Appendix:

BI Penetration #:

P451 SO321 Penetration Type:

NR W l e v. : 2065'-0"

1. Barrier Thickness:

6"

2. Opening Si:

16"D

3. Penetrants:

(2) 7" (1)3/4"P,

{I) 6 " ~

N

4. Sealant Type:

None

5. Damming Side1 :

NIA

6. Damming Side 2:

NIA

7. Damming Continuity (AcdRej):

NIA

8. Boot Condition (AcclRej):

NIA

9. Sealant Depth:

NIA Walkdown Comments:

This seal is Mon-Appendix R located in the Turbine 9'3" North of column line T-8 and approximately 6'4" west of T-F. There is no seal in this penetration. Changed Detail to "MR".

M-663-000 17A, Revision W0 1 Page B1-159 of B1-172 Fire Area (Side I): F-1 M4X Dwg: MIX6906 Fire Area (Side 2): F-3 f 0. Annular Gap (smatlest):

1'

11. Gap between pen:

NIA f 2. Barrier Type:

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

Alo Prepared By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix:

BI Penetration #:

P611 WOO71 Penetmtlon Type:

M-6A LoeJElev.: 2020'4"

1. Barrier Thickness:

12" 2 Opening Sixe:

72.0

3. Penetrants:

(1 WP

4. Sealant Type:

Foam

5. Damming Sikl:

Recessed f 12" I.DammingSide2:

Flush

7. Damming Continuity (AcclRej);

Accept

8. Boot Condidion (AcdRej):

WA

9. Sealant Depth:

9-312" Walkdown Comments:

Wall thickness determined by Drawing C-1 C6111. Changed Detail from M-I to M-6A based on actual sealant depth.

Sketch:

M-663-000 17A, Revision W01 Fire Area F-1 (Side 1)

(Side 2)

Fire Area F-3 (Side 2)

Penetration Seal Data Appendix:

81 Photos:

P611 WOO71 Fire Area F-1 (Side 1) -

= 1 Fire Area F-3 I

i

' I Page B1-I60 of B1-172 I

M-663-000 1 7A, Revision W0 1 Fire Area (Side 1): F-2 MOX Dwg: M-1x6906 Page 81-16] ofB1-172 Fire Area (Side 2): F-3

10. Annular Gap (smallest):

1-1 12"

11. Gap between pen:

NIA

12. Barrier Type:
13. Opening Slewed or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregmd Prepared By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix:

BI Penetration #:

P611 W0201 Penetration Type:

M-6A LocJElev.: 20 15'-3"

3. Barrier Thickness:

12"

2. Opening Sire:

12"D

3. Penetrants:

(1)8"P

4. Sealant Type:

Foam

5. Damming Side*:

Flush

6. Damming Side 2:

Flush

7. Damming Continuity ( W R e j ) :

Accept

8. Boot Condition ( A d e j ) :

WA

9. Sealant Depth:

10" Walkdown Comments:

Wall thickness determined by Drawing C-1 C6111. Changed Detail from M-1 to M-6A based no actual foam depth.

Sketch:

L Fire A m F-3 fire Area F-2 (Side 1)

(Side 2)

Fire Area F-3 (Side 2)

Penetration Seal Data

~ppendix: BI Photos:

P611 W0201 Fire Area F-2 (Slde 1) I.

t.

Sketch; Fire Area (Side 1 ):

F-5 M4X Dwg: M-OX621 I Page B1-163 ofB1-172 :i

' 4 a

1

.P Fire Area (Side 2): F-2
10. Annular Cap (smallest):

1-112" 1 I. Gap between pen:

NIA

12. Barrier Type:

F W

13. Opening Sleeved or Concrete; Steel
14. Pipe Insulated:

Nd Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix:

BI Penetration #:

P621 SO1 37 Penetration Type:

M A LocAEIev.: 2026'4"

1. Barrier Thickness:

10" Z Opening Sie:

I OUD

3. Penetrants:

(1 p P

4. Sealant Type:

Foam

5. Damming Side1 :

Foam 3" above Slab

6. Damming Side 2:

Recessed 2"

7. Damming Continuity (AcdRej):

Accept

8. Boot Condition (AcclRej):

MrA

9. Sealant Depth:

I Oh Walkdown Comments:

Slab thickness (12")

determined by C-1 C6211. Changed Detall from M-1 to M-SA based on actual ham thickness.

M-663#017A, Revision WO 1 Page B1-164 ofB1-172 (Side 1 )

Fire Area F-5 (Side I )

Penetration Seal Data Appendix:

BI Photos:

P621 SO1 37 RE Area F-5 Fire Area F-2 Fire Area F-2 (Side 2)

M-663-00017A, Revision WOI Sketch:

fire Area (Side I):

F-5 M-OX Dwg: M-OX6211 Fire Area (Side 2): F-2

10. Annular Gap (smallest):

114"

11. Gap between pen:

NIA 4 2. Barrier Type:

W

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepamd By:

Jeff Suter Reviewed By:

Penetration Seal Data Appendix:

BI Penetration #:

P621 SO1 58 Penetration Type:

M-6A LocEh.: 2026'-0"

1. Barrier Thickness:

10"

2. Opening Size:

94"D

3. Penetrants:

(1)lo"p

4. Sealant Type:

Foam

5. Damming Sidel:

3-314" above slab

6. Damming Side 2:

2" recessed wlQ-Deck Valley

7. Damming Contjnuity (AcclRej):

Accept

8. Bcd Condition (Acc/Rej):

NIA

9. Sealant Depth:

1044" Wal kdown Comments:

Slab thickness (12") determined by C-1 C6211. Changed Detail M-I to M-6A based on actual foam depth.

M-663-000 17A, Revision WO 1 Page B1-166 sfJ31-172 Penetration Seal Data Appendix:

81 Photos:

P621 SO1 58 Fire Area F-5 (Side 1) I Fire Area F-2 I

Fire Area F -5 (Side 1 )

(Side 2)

Fire Area F-2 (Side 2)

M-663-00017A, Revision W01 Sketch:

Fim Area (Side 1): F-4 M9X Dwg: M-OX6908 Page B1-167 of B1-172 Fire Area (Side 2): F-5

10. Annular Gap (smallest);

314"

11. Gap between pen:

NIA

12. Barrier Type:
13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated; Mo Wayne Aregood Prepared By:

Je# Suter Reviewed By:

Penetration Seal Data Appendix:

81 Penetratlon #:

P621 WOO1 1 Penstsation Type:

M-6A LoeJUev.: 2040'-111

1. Barrier Thickness:

12"

2. Opening S i :

10"D

3. Penetrants:

(1)6"P

4. Saalant Type:

Foam

5. Damming Side1 ;

Flush

6. Damming Side 2:

112" recessed

7. Damming Continuity ( M e j ) : Accept
8. Bmi Condition (AcdRej):

NIA

9. Sealant Depth:

9-1 12" Walkdown Comments:

Wall thickness (12") determined by C-1 C6211. Changed Detail from M-I to M-6A based on actual foam depth.

M-663-000 I7A, Revision W0 1 Fire Area F-5 (Side 2)

Fire Area f-5 (Side 2)

Page Bl-168 ofB1-172 Fire Area F 4 (Side 1)

Penetration Seal Data Appendix:

BI Photos:

P62l WOO1 1 Fire Area F-4 (Side 1)

M-663-00017A, Revision W0l Page B1-169 ofB1-172 Penetration Seal Data Appendix:

BI Penetration #:

P712S0013 Penetration Type:

RB-5A Fire Area (Side 1):

Fire Area (Side 2):

Loc.lElev.:

1986'-0" M-OX Dwg: M-OX7113

1. Barrier Thickness:
10. Annular Gap (smallest):
2. Opening Size:
11. Gap between pen:
3. Penetrants:
12. Barrier Type:

R

4. Sealant Type:
13. Opening Sleeved or Concrete:
5. Damming Side1 :
14. Pipe Insulated:

No

6. Damming Side 2:

Jeff Suter

7. Damming Continuity (AcclRej):

Prepared By:

8. Boot Condition (AcclRej):

Wayne Aregood

9. Sealant Depth:

Reviewed By:

Walkdown Comments:

This is not an Appendix R Barrier. The Penetration is located in the Radwaste Building.

Sketch:

M-663 -000 1 7A, Revision WO 1 Page Bl-170 ofB1-172 Penetration Seal Data Appendix:

BI Penetration #:

P712S0014 Penetration Type:

NIA Fire Area (Side 1):

Fire Area (Side 2):

Loc.lElev.: 1986'-0" M-OX Dwg: M-OX7113

1. Barrier Thickness:
10. Annular Gap (smallest):
2. Opening Size:
11. Gap between pen:
3. Penetrants:
12. Barrier Type:

R

4. Sealant Type:
13. Opening Sleeved or Concrete:
5. Damming Side1 :
14. Pipe Insulated:

No

6. Damming Side 2:

Jeff Suter

7. Damming Continuity (AccIRej):

Prepared By:

8. Boot Condition (AcclRej):

Wayne Aregood

9. Sealant Depth:

Reviewed By:

Walkdown Comments:

This is not an Appendix R Barrier. The Penetration is located in the Radwaste Building.

Sketch:

M-663-00017A, Revision W0 1 Page B1-171 ofB1-172 Penetration Seal Data Appendix:

BI Penetration #:

P712S0015 Penetration Type:

RB-1 Fire Area (Side 1):

Fire Area (Side 2):

Loc.lElev.:

1986'-0" M-OX Dwg: M-OX7113

1. Barrier Thickness:
10. Annular Gap (smallest):
2. Opening Size:
11. Gap between pen:
3. Penetrants:
12. Barrier Type:

R

4. Sealant Type:
13. Opening Sleeved or Concrete:
5. Damming Side1 :
14. Pipe Insulated:

No

6. Damming Side 2:

Jeff Suter

7. Damming Continuity (AcclRej):

Prepared By:

8. Boot Condition (AcclRej):

Wayne Aregood

9. Sealant Depth:

Reviewed By:

Walkdown Comments:

This is not an Appendix R Barrier. The Penetration is located in the Radwaste Building.

Sketch:

M-663-00017A, Revision WOl Page B1-172 ofB1-172 -

Penetration Seal Data Appendix:

BI Penetration #:

P712W1006 Penetration Type:

NIR Fire Area (Side 1):

Fire Area (Side 2):

Loc.lElev.:

1988'-4" M-OX Dwg: M-OX7907

1. Barrier Thickness:
10. Annular Gap (smallest):
2. Opening Size:
11. Gap between pen:
3. Penetrants:
12. Barrier Type:

N

4. Sealant Type:
13. Opening Sleeved or Concrete:
5. Damming Sidel:
14. Pipe Insulated:

No

6. Damming Side 2:

Jeff Suter

7. Damming Continuity (AcclRej):

Prepared By:

8. Boot Condition (AcclRej):

Wayne Aregood

9. Sealant Depth:

Reviewed By:

Walkdown Comments:

This penetration is not in an Appendix R Barrier. It is located in the wall between Radwaste and the Radwaste Tunnel.

Sketch:

Table of Contents M-663-000 17A Page 2 of 9 2 Revision W04 Revision Log................................................................................................................................. 3 1.0 Purpose............................................................................................................................. 4 2.0 Scope................................................................................................................................ 4 3.0 References 4

4.0 Evaluation......................................................................................................................... 5 5.0 Conclusions 9

Appendix B2, Penetration Seal Data....................................................... (95 Total Pages) I

Revision Log M-663-00017A Page 3 of 9 Attachment B2 Revision W04 I

Revision WO1 W 04 Reason for Revision Original Issue Included new penetration PI3580943 added by Change Package 012957.

M-663-000 1 7A Page 4 of 9 Attachment B2 Revision W04

/

1.0 Purpose 1.1 The purpose of this document is to evaluate existing penetration seals that are not directly bounded to the typical detail limitations established in M-663-00017.

This evaluation was conducted in effort to satisfy regulatory expectation regarding qualification and documentation of fire barrier penetration seals, as discussed in NRC lnformation Notice 88-04. This evaluation was conducted in accordance with the guidance of NRC Generic Letter 86-1 0.

2.0 Scope 2.1 The Table I penetrations in relation to the design requirements discussed in Section 5.1.

2.2 Refer to Section 7.0 of M-663-00017A for a cross-reference list of penetrations within Table I that are evaluated for additional seal parameters that do not satisfy the typical detail limitations of M-663-00017. In these instances, the potential cumulative affects of multiple unbounded attributes were considered for each penetration of concern.

3.0 References 3.1 NRC Generic Letter 86-10, Implementation of Fire Protection Requirements, dated April 24, 1986 3.2 NRC lnformation Notice 88-04, "Inadequate Qualification and Documentation of Fire Barrier Penetration Seals".

3.3 10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior To January 1, 1979 3.4 LER 87-10, Technical Specification Violations - Inoperable Fire Barriers Caused By Personnel Errors 3.5 M-663-00017, Penetration Seal Typical Details, Rev. W20 3.6 PIR 2005-2384, Penetrations Requiring Field Work 4.0 Assumptions 4.1 It is assumed that existing penetration seal materials have been installed as required by applicable typical design details and procedures.

This is an acceptable assumption based on a review of the Quality Control documentation maintained during initial penetration seal installation activities and the intrusive inspections conducted to address LER 87-10, regarding seal material depth.

M-663-00017A Page 5 of 9 Attachment B2 Revision W04 5.0 Evaluation 5.1 Assessment of Condition to Desian Requirements The Table I penetrations are large diameter openings containing a large pipe penetrant. Each Table I penetration opening exceeds the opening size limitation of the assigned typical detail from M-663-00017. The M-663-00017 typical detail opening size limitations are based on successful fire test configurations.

TABLE l Penetrations with Opening Sizes Exceeding Typical Detail Limitations Penetration Number P I 12W1378 P112W1380 P121S0264 P121S0271 P121S0277 P121S0278 P I 22S0362 P I 31 SO492 P I 32S0682 P I 32S0683 P 1 32S0684 Communicating Fire Side 1 A-I A-I A-I A-I A-I A-I A-I A-8 A-8 A-8 A-8 Typical Detail FB-1 FB-1 RB-1 FB-I RB-1 RB-1 RB-1 FB-1 FB-1 M-I M-I Areas Side 2 C-I C-I A-4 A-4 A-4 A-4 A-2 A-I A-I A-I A-I CommentslDisposition Acceptable annular gap. See Section 5.2 2 Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap See Section 5.2 1 Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap See Section 5.2.1.

Acceptable annular gap. See Section 5.2.1.

Acceptable annular gap. See Section 5.2.1.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap and free area. See Sect~on 5.2.1 and Note 1.

Pipe insulation abuts bottom side damming This configuration provides add~t~onal structural support for the damming and foam sealant durlng fire exposures.

Acceptable annular gap and free area. See Section 5.2 1 and Note 1.

Insulation completely covers the seal configuration, providing additional sh~elding from direct flame impingement, enhancing structural integrity of the enclosed seal configuration.

Detail Limit (in2) 113 113 154 113 154 1 54 154 11 3 113 648 648 Opening Size Actual Openin2 Size (in )

1385 2 385 201 201 707 380 201 707 707 707 707 Data Actual Seal Surface Area (in2) 679 679 151 88 553 226 173 254 254 254 254

M-663-000 1 7A Page 6 of 9 Attachment I32 Revision W04 Penetration Number P132S0693 P I 32S0739 P132W1844 P I 33S0799 P I 34S0860 P I 34W2053 PI3580232 PI3580233 PI3580943 P141S1014 P141W2486 P142S1083 P142S1086 P142W1933 P143W1488 P143W1489 P145S0943 PI4580944 CommentslDis n

Acceptable annular gap. See Section 5.2.1.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5 2.2.

Acceptable annular gap. See Section 5 2.1 Acceptable annular gap. See Section 5.2.1 Acceptable annular gap. See Section 5.2.1.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap and free area. See Sect~on 5.2.1 and Note 1.

Bottom side insulation completely covers the seal configuration provldlng add~t~onal shielding from direct flame ~mpingement, thus enhancing the overall configuration significantly.

Refer to Attachment B13 for as left configuration following field action necessary to address PIR 2005-2384.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2.1.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap See Section 5.2.2.

Acceptable annular gap. See Section 5.2.2.

Detail Limit (in2) 1 54 113 113 154 154 154 113 113 113 113 113 648 113 154 113 113 113 113 Typical Detail RB-1 FB-I FB-I RB-1 RB-I RB-8 FB-1 FB-1 FB-1 FB-I FB-1 M-I FB-1 RB-8 FB-I FB-I FB-1 FB-I Communicating Fire Side 1 A-10 A-8 A-8 A-25 A-24 A-8 A-15 A-15 A-15 A-16 A-16 A-16 A-16 A-16 A-5 A-5 A-23 A-23 Areas Side 2 A-I A-I A-3 A-I A-I A-24 A-33 A-33 A-33 A-8 A-26 A-8 A-8 A-10 F-4 F-4 A-29 A-29 Opening Size Actual Openin Size (in?

452 201 707 452 452 254 201 154 154 707 254 707 707 452 254 254 154 154 Data Actual Seal Surface Area (in2) 374 151 254 339 339 141 123 104 75 254 141 254 254 198 141 141 141 141

M-663-00017A Page 7 of 9 Attachment B2 Revision W04 CommentslDisposition Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2.2.

Refer to Attachment B13 for as left configuration following field actron necessary to address PIR 2005-2384.

Acceptable annular gap. See Section 5.2.2.

Refer to Attachment B13 for as left configuration following field action necessary to address PIR 2005-2384.

Acceptable annular gap. See Sectron 5.2.2.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2 2.

Acceptable annular gap. See Sectron 5.2.2.

Acceptable annular gap. See Section 5 2.2.

Acceptable annular gap. See Section 5 2.2.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2 2.

Acceptable annular gap. See Section 5 2.2 Acceptable annular gap. See Section 5.2.2.

Acceptable annular gap. See Section 5.2.2.

Penetration Number P145S0946 P145S0947 P145S0952 P145S0954 P I 45W2468 P145W2469 P145W2470 P145W2471 P152W2585 P311 W0839 P611W0197 P621S0153 P621S0156 P621 SO1 57 P621 SO1 62 P621W0009 P621 WOO17 P621W0221 P621 W0224 Communicating Fire Side 1 A-23 A-23 A-23 A-23 A-23 A-23 A-23 A-23 A-19 C-I F-2 F-5 F-4 F-4 F-4 F-4 F-5 A-5 A-5 Typical Detail FB-I FB-1 FB-1 FB-I FB-1 FB-I FB-1 FB-I FB-I FB-1 FB-1 FB-1 FB-1 FB-I FB-I FB-1 FB-I FB-1 FB-I Areas Side 2 A-30 A-30 A-15 A-15 T-2 T-2 T-2 T-2 A-22 CC-1 F-3 F-3 F-3 F-2 F-2 F-5 F-4 F-4 F-4 Data Actual Seal Surfac? Area (in )

141 141 141 141 141 141 141 141 75 31 1 88 75 88 88 88 88 88 141 141 Detail Limit (in2) 113 113 113 113 113 113 113 113 113 113 113 113 113 113 113 113 113 113 113 Opening Size Actual Openin Size (in?

154 154 154 1 54 154 154 1 54 154 154 101 8 20 1 154 201 201 201 20 1 201 254 254

M-663-00017A Page 8 of 9 Attachment B2 Revision W04 5.2 Evaluation of Condition 5.2.1 Silicone Foam (M-I) and Radflex (RB-1 and RB-8) Seals In most of the Table I cases, the annular gap between the opening sidewall and penetrant are relatively small in size, resulting in small free areas, and/or seal surface areas. When this is the case, the small free area (area of seal with no penetrants) minimizes the concern of structural failures during fire and hose stream exposures.

Structural failures during fire exposures is a concern primarily in Silicone Foam, Radflex, or Silicone Elastomer type seals with large free areas due to charring of the primary sealant. During the char process the primary sealant undergoes physical changes that tend to degrade structural integrity and the cohesion between the sealant, opening sidewall and penetrant.

However, due to smaller annular gaps and free areas, the smaller unsupported spans of primary sealant material resist the affects of sag and structural degradation. Industry testing has demonstrated that larger free areas have successfully sustained structural integrity during fire and hose stream exposure.

Therefore, if the annular gap or free area limitation is maintained, structurally the seal is unaffected regardless of opening size, due to the large pipe penetrant.

Based on this, it is reasonable to conclude that the penetration seal with opening sizes in excess of limitations and with annular gaps that are within limitations, will function and perform equal to tested configurations. In all cases, annular gaplfree area limitations of the assigned M-663-00017 typical detail are satisfied by the Table I penetrations sealed with Silicone Foam or Radflex. Therefore, the opening sizes for the M-I, RB-1 and RB-8 seals in Table I are acceptable, and will not present a negative affect regarding seal performance.

CommentslDi Penetration Number Notes: -

1 Additional justification for acceptability is provided in "CommentslDisposition" column. The comments addresses in-plant configurations that provide additional seal structural enhancement and shielding from direct flame impingement.

Communicating Fire Areas Typical Detail Side 1 Side 2 Opening Size Data Actual Seal Surface Area (i n2)

Detail Limit (in2)

Actual Openinp Size (in )

M-663-00017A Attachment B2 Revision W04 Page 9 of 9 5.2.2 Ceramic Fiber (FB-1) Seals Ceramic fiber materials are inert and not affected by char or sag caused by material characteristic changes during fire exposure. If the annular gap limitation is maintained, structurally the seal is unaffected regardless of opening size. Based on this, it is reasonable to conclude that the penetration seal with opening sizes in excess of limitations and with annular gaps that are within limitations, will function and perform equal to tested configurations. In all cases, annular gaplfree area limitations of M-663-00017 typical detail FB-1 are satisfied by the Table I penetrations sealed with ceramic fiber. Therefore, the opening sizes for the FB-1 seals in Table I are acceptable, and will not present a negative affect regarding seal performance.

5.3 Post Fire Safe Shutdown lm~act There is no impact to PFSSD systems or components as a result of this evaluation. The opening sizes presented by the Table I penetrations do not impact the penetration seal capability to provide fire boundary protection for a 3-hour duration.

6.0 Conclusions Based on the above discussions, it is reasonable to conclude that the Table I penetrations seal are acceptable and will perform their intended function regardless of opening size deviations.

The penetrations satisfy regulatory requirements and commitments, as well as WCNOC Fire Protection Program requirements.

-7Ty NUCLEAR OPERATING CORPORATION Attachment B2 Fire Protection Evaluation For Penetrations That Exceed Opening Size Limitation Page 1

M-663-00017A, Revision W04 Page B2-1 of B2-95 Penetration Seal Data Appendix; 82 Penetration #:

P I 12W1378 Penetration Type:

FBI LodElev.: 1979'-6" Fire Area (Side I): A-1 M-OX aWg: M-1x1902 Fire Area (Side 2): C-4

1. Barrier Thickness:

36"

2. Opening S i :

42"D

3. Penetmnts:

(1) 30"P

4. Sealant Type:

Ceramic Fiber

5. Damming Sidel:

Boot

6. Damming Side 2:

Boot

7. Damming Continuity (AcclRej);

NIA

8. Boot Condition (Mej):

Accept

9. Sealant Depth:

Assumed Per Detail

10. Annular Gap (smallest):

3" l I. Gap between pen:

NIA

12. Barrier Type:

A F

13. Opening Sleeved or Concrete:

Steel I4 Pips Insulated:

Yes Wayne Aregood Pmpawd By:

Jeff Suter Reviewed By:

Waikdown Comments:

Insulation abuts boot, does not transition through seal zone. Insulation removed, no longer insulated.

Sketch:

M-663-00017A, Revision W04 Page 82-2 of 82-95

, 1 Penetration Seal Data Appendix:

~2 Photos:

PllZW1378 Fire Area A-1 (Side I)

Fire Area A-l (Side I )

Fire Area GI (Side 2)

Fire Area C1 (Side 2)

M-663-00017A, Revision W04 Page B2-3 of 82-95 I Penetration Seal Data Appendk 82 Penetration #:

P? 12W1380 Penettation Type:

FB-1 Loc.lElev.: 1979'-6" Fire Area (Side I):

A-I MOX Dwg: WlX1902 Fire Area (Side 2): C-I

1. Barrier Thickness:

36" 2 Opening Si:

42"D

3. Penetmnts:

(1) 3 0 ~

4. Sealant Type:

Ceramic Fiber

5. Damming SihI:

Boot

6. Damming Side 2:

Boot

7. Damming Continuity (AcdRej):

MA

8. Boot Condition (AcdRej):

Accept

9. Sealant Depth:

Assumed Per Detail

10. Annular Gap (smallest):

3" I I. Gap between pen:

NIA

12. Barrier Type:

A F

13. Opening Sleeved or Concrete:

Steel 14 Pipe Insulated Yes Wayne Aregood Prepared By:

Jeff SSuter Reviewed By:

Walkdown Comments:

M-663-00017A, Revision W04 Page B2-4 of B2-95 1

Penetration Seal Data Appendbt:

62 Photos:

P I 12W1380 Fire Area A-l (Side 1)

Fire Area GI (Side 2)

Fire Area A-l (Side 1 )

Fire Area GI (Side 2)

I

i.

it' 2

C M-66340017A, Revision W04 Page 62-5 of B2-95 Penetration Seal Data Appendix: ~2 Penetration #:

PA21 SO264 Penetration Type:

R8-1 Fire Area (Slde 1): A-I MOX Dwg: M X t 2 1 1 I.

Barrier Thickness:

19"

2. Opening Sim:

1B" D

3. Penetrants:

(1) B9P

4. Sealant Type:

Radflex

5. Damming Sicfet:

Unknown

6. Damming Side 2:

Boot

7. Damming Continuity (AcclRej):

WA

8. Boot Condition ( A d e j ) :

Accept

9. Sealant Depth:

Assumed Per Detail Fire Area (Side 2): A 4

10. Annular Gap (smallest):

1"

11. Gap between pen:

NIA

12. Barrier Type:

F R

W

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

Yes Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Walkdown Comments:

Slab thickness determined by drawing C-OCl211 Sketch:

(Side 1)

Fire Area A-I (Slde 1)

(Side 2)

---r-'

- --Tq Fire Area A-4 (Side 2)

M-663-000 I 7A, Revision W04 Page 62-6 of B2-95 Penetration Seal Data Appendix:

~2 Photos:

P I 21 SO264 Fire Area A-1 I

Fire Area A 4 i

I i

'i A

I. Barrier Thickness:

22"

2. Opening Size:

16"D

3. Penetrants:

( 3 ) 12"P

4. Sealant Type:

Ceramic Fibar

5. Damming Side1 :

Boot

6. Damming Side 2:

Boot

7. Damming Continuity (AcdRej):

NIA

8. Boot Condition (AcdRej):

Acmpt

9. Sealant Depth:

Assumed Per Detail Fire Area (Side 1): A-I MOX Dwg: M-OX1211 Fire Area (Side 2): A-4

10. Annular Gap (smallest):

112"

11. Gap between pen:

MA

12. Barrier Type:

R W

13. Opening Sleeved or Concrete:

Steel

14. Pipe insulated:

No Wayne Aregood Prepared By:.

Jeff Suter Reviewed By:

Walkdown Comments:

Slab thickness determined from drawing C-OC1211.

Sketch:

M-66340017A, Revision W04 Page B2-7 of B2-95 Penetration Seal Data Appendix:

~2 Penetration #:

P i 21 SO271 Penetration Type:

FBI L-.:

1988'4"

M-663-00017A, Revision W04 Page 82-8 of B2-95 1

Penetration Seal Data Appendix:

BZ I

Photos:

PI2150271 Fire Area A-l (Side 1)

Fin Area A 4 Fire Area A-1 (Slde 1)

(Side 2)

Fire Area A 4 (Side 2)

M-663-00017A, Revision W04 Page B2-9 of B2.

Penetration Seal Data Appendix:

~2 Penetration #:

PI21 SO277 Penetration Type:

RB-1 hJElev.: 1988'-0" I. Barrier Thickness:

19"

2. Opening S i :

30" D 3, Penetrants; 4 Sealant Type;

5. Damming Side1 :

Rad flex Boot

6. Damming Side 2:

Boot

7. Damming Continuity (AdRej):

NfA

8. Bwt CondMm ( A e e j ) :

Accept Fire Area (Side I): A-1 M-OX Dwg: M-OX1211 Fire Area (Side 2): A-4

10. Annular Gap (smallest):

6"

11. Gap between pen:

NIA

12. BanSer Type:

F R

W

13. Opening Sleeved or Concrete:

Stwl

14. Pipe Insulated:

Yes Wayne Aregood Prepared By:

Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness determined from drawing C-OC121 I.

Insulation appears to transition through seal area. Penetrant appears to be cbn&iniic3ll'ji mstW8d-ahB a'nnur'US is equal all the way around.

Sketch:

M-663-00017A, Revision W04 Page B2-1 0 of 82-95 I Penetration Seal Data Appendix:

B2 Photos:

P121S027:7 Fire Area A-1 (Side 1)

Fire Area A-l (Side 2)

Fire Area A-4 (Side 2)

Fire Area A-4 F--------

7

--- 4

M-663-00017A, Revision W04 Page B2-11 of B2-95

-4 Penetration Seal Data Appendix: ~2 Fire Area (Side I):

A-l M-OX Dwg; M-OX12f 1 Fire Area (Side 2): A 4 I. Barrier Thickness:

19" 2 Opening Size:

ZH D

3. Penetrants:

(1) 1PP

4. Sealant Type:

Radflex

5. Damming Sided:

Boot

6. Damming Side 2:

Boot

7. Damming Continuity (AdUej);

N A

8. Bmt Condition (AedRej):

Accept

9. Sealant Depth:

Assumed Per Detail

10. Annular Gap (smallest):

2"

11. Gap between pen:

NIA

12. Barrier Type:

R W

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Sutar Reviewed By:

Walkdown Comments:

Slab thickness determined from drawing C-OC7211.

M-663-00017A, Revision W04 Page B2-I2 of B2-95 I Penetration Seal Data Appendix:

B2 I

Pho&s; PI21 SO278 Fire Area A-1 (Side I)

Fire Area A-l (Side 2)

Fire Area A-4 (Side 2)

M-663-00017A, Revision W04 Page 82-1 3 of B2-95 Penetration Seal Data Appendix: ~2 Penetration #:

P12280362 Penetration Type:

RB-1 Fire Areatside 1): A-I M4X D w ~ :

M-OX1221 Fire Area (Side 2): A-2

1. Barrier T hickness:

f 9"

2. Opening Ske:

16"D

3. Penetrants:

(1 )6*P

4. Sealant Type:

Radfl ex

5. Damming Sidel:

Flush wlsleeve

6. Damming Side 2:

Boot

7. Damming Continuity (AcclRej):

MA

8. Boot Condition {AcdRej);
9. Sealant Depth:
    • 32" Accept
10. Annular Gap (smaltest):

3" f 1. Gap between pen:

NIA

12. Barrier Type:

R W

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Je# Suter Reviewed By:

Walkdown Comments:

Slab thickness determined from drawing C-OC121 I. " Rad Flex in bottom side boot is not included in seaiant depth.

Sketch:

M-663-00017A, Revision W04 Page B2-14 of B2-95 I Penetration Seal Data Appendix:

62 1

Photos:

P122S0362 Fire Area A-l (Side 1)

Fire Area A-1 (Side 1)

(Side 2)

Fire AM A-2 (Side 2)

M-663-00017A, Revision W04 Page 82-15 of B2-95 Penetration Seal Data Appendix:

EIZ Penetration #:

P I 31 SO492 Penetration Type:

FB-1 Fire Area (Side I): A-8 M-OX Dwg: M-1x1311 Fire Area (Side 2): A-l

1. Barrier Thickness:

10"

2. Opening Sbe:

30"D

3. Penetrants:

(1) 24"P

4. Sealant Type:

Ceramic Fiber

5. Damming Sidel:

Boot

6. Damming Side 2:

Boot

7. Damming Continuity (AeelRej):

NIA

8. B m t Condition (AcclRej):

Accept

9. Sealant Depth:

Assumed Per Detail

10. Annular Gap (smallest):

2" 1 1. Gap between pen:

NIA

12. Barrier Type:
13. Opening Sleeved or Concrete:

Steel

$4. Pipe Insulated:

Na Wayne Aregwd Prepamd By:

Jew Suter R z v i d By:

Walkdown Comments:

Slab thickness based on C-1 C1311.

Sketch:

M-663-000 1 7A, Revision W04 Page B2-1 6 of B2-95 Penetration Seal Data Appendix: 82 1

Photos:

P I 31 SO492 (Side 1)

Fire Area A-8 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-I (Side 2)

M-663-000 17A, Revision W04 Page B2-17 of 82-95 Penetration Seal Data Appendix:

~2 I

Penetration #:

P I 3280682 Penetration Type:

FB-I Fire Area {Side 1): A 4 MOXDwg: M-tXf321 Fire Area (Side 2): A-I

1. Barrier Thickness:

40" 2 Opening S i :

W D

3. Penetrants:
11) 24'P
4. Sealant Type:

Ceramic Fiber

5. Damming Sidel:

Boot

6. Damming Side 2:

Boot

7. Damming Continuity (AcelRej):

NIA

8. Bod Condition jAcc/Rej):

Accept

9. Sealant Depth:

Assumed Per Detail

10. Annular Gap (smallest]:

2' 1 t. Gap between pen:

NIA

12. Barrier Type:
13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Jeff Suter Prepared By:

Wayne Aregood Reviewed By:

Walkdown Comments:

Slab thickness determined by Drawing C-1 C1311 (wsa)

Sketch:

M-663-00017A, Revision W04 Page B2-18 of 82-95 Penetration Seal Data Appendix: w Photos:

P132S0682 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1 )

Fire Area A-1 (Side 2)

FiraArea A-I (Side2)

M-663-00017A, Revision W04 Page B2-19 of 82-95 Penetration Seal Data Appendix:

82 Penetration #:

PA 3280683 Penetration Type:

M-6A LocEIev.: 2000'-0" I. Barrier Thickness:

10" 2 Openbg Sue:

MUD

3. Penetrants:
4. Sealant Type:
5. Damming Sidel:
6. Damming Side 2:

Foam Assumed per detail Rre Area (Side 1): A-8 M-OX Dwg : M-1 XI 321 Fire Area (Side 2): A-l Recessed 4"

7. Darning Continuity ( A d e j ) :

Accept

8. B& Condition (AcclRej):
9. Sealant Depth:

il" NIA f 0. Annular Gap (smallest):

I "

t 1. Gap between pen:

M A

12. Barrier Type:

1 3. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

Yes Jeff Suter Prepared By:

Wayne Aregod Reviewed By:

Walkdown Comments:

Top side seal is enclosed within support insutation. Insulation abuts damming board on bottom side. Slab thickness determined by Drawing C-I C1311 (wsa). ' 11" foam depth baaed on installation QC documentation (WSA). (See Drawing M-13EF02; Essential Service Water Supply [EF] Line Number 076-HBE24", 95F Design Temp, 1-112" thick, Classification "AS" [Anti-Sweat] Fiberglass Type Insulation)

Sketch:

M-663-00017A, Revision W04 Page B2-20 of B2-95 i

Penetration Seal Data Appendht:

BZ Photos:

PI 32S0683 (Side 1)

Fire Area A-8 Fire Area A-1 Fire Area A-8 (Slde 7 )

(Side 2)

Ftre Area A-1 (Side 2 )

M-663-00017A, Revision W04 Page B2-21 of 82-95 Penetration Seal Data Appendix:

62 Penetration #:

PI 3280684 Penetration Type:

MI LocJElev,: 2000'-0" I. Barrier Thickness:

1 0"

2. Opening Size:

30"D

3. Penetrants:
4. Sealant Type:
5. Damming Side1 :

Assumed per detail Fire Area (Side l):

A-8 M-OX Dwg: M-1x1321 F i q Area (Side 2): A-I

6. Damming Side 2:

Assumed per detail

7. Damming Continuity (AcdRej):

WA

8. Boot Condition (Acckj):

MA

9. Sealant Depth:

Assumed per detail

10. Annular Gap (smallest):

Indeterminant

11. Gapbetweenpen:

NIA

12. Barrier Type:
13. Opening Sleeved or Concrete:

S W I4 Pipe Insulated:

Yes Jeff Suter Prepared By:

Wayne Aregood Reviewed By:

Walkdown Comments:

Insulation covers opening on both barrier sides. Slab thickness determined by Drawing C-1C13T1 (wsa) (See Drawing M-13EF03; Essential Service Water Return [EF] Line Number 080-HBC-24,l IOF Design Temp, 1-112" thick, Classification "AS" [Anti-Sweat] Fiberglass Type Insulation)

Sketch:

M-663-00017A, Revision W04 Page B2-22 of B2-95 Penetration Seal Data Appendix:

B2 Photos:

P132S0684 Fire Area A-8 (Side 1)

Fire h a

A-1 Fire Area A-8 (Side 1)

(Side 2)

Fire Area A-1 (Side 2 )

M-663-00017A, Revision W04 Page 82-23 of B2-95 Penetration Seal Data Appendix:

RZ Penetration #:

Pi 32S0693 Penetration Type:

RB-1 Fire Area (Side 1): A-1 0 M-OX Dwg: M-1x1321 Fire Area (Side 2): A-I I. Barrier Thickness:

20" 2 Opening Size:

24"D

3. Penetrants:

(1)tO"P

4. Sealant Type:

Radflex

5. Damming Side1 :

Radflex flush wltop of sleeve

6. Damming Side 2:

Boot

7. Damming Continuity (AcclRej):

NIA

8. Bmt Condition (AcdRej):

Accept

9. Sealant Depth:

27"

10. Annular Gap (smallest):

5*

11. Gap between pen:

NIA

12. Barrier Type:

R

13. Opening Sleeved or Concrete:

S t 4

14. Pipe Insulated:

Yes Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Walkdown Comments:

Slab thickness based on C-1C1311. Insulation appear to transition through the seal. FB-6 could not be confirmed.

Sketch:

M-663-00017A, Revision W04 Page B2-24 of B2-95 Penetration Seal Data Appendix:

82 I

Photos:

P I 32S0693 Fire Area A-1 0 (Side 1 )

Fire Area A-10 (Side 1)

Fire Area A-l (Side 2)

Fire A m A (Side 2)

M-663-00017A, Revision W04 Page B2-25 of B2-95 Penetration Seal Data Appendix: 82 Penetration #:

P I 3280739 Penetration Type:

FBI f. Barrier T hiekness:

12"

2. Opening Size:

16"D

3. Penetrants:

(1) 8"P

4. Sealant Type:

Ceremic Fiber

5. Damming Side1 :

Boot

6. Damming Side 2; Boot
7. Damming Continuity (AcclRej):

NIA

8. Boot Condition (AcdRej):

Accept

9. Sealant Depih:

Assumed Per Detail Fire Area (Side I):

A-8 M4X Dwg: M-f X I 321 Fire Area (Side 2): A-1 Wdkdown Comments:

Slab thickness based on C-1C1311.

$0. Annular Gap (smallest):

3" f 1. Gap between pen:

NIA

12. Barrier Type:
13. Opening Sieeved or Concrete:

Steel

14. Pipe Insulated:

Yes Wayne Aregood Prepamd By:

Jeff Slrter Reviewed By:

Sketch:

M-663-00017A, Revision W04 Page B2-26 of B2-95 I

I Penetration Seal Data Appendix:

62 I

Photos:

PI3250739 (Side fire Area A-8 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017A, Revision W04 Page 82-27 of B2-95 Penetration Seal Data Appendix:

B2 Penetration #:

P132W1844 Penetration Type:

F B I LocElev.: 201 3'-V

1. Barrier Thickness:

12"

2. Opening Sie:

W D

3. Penetrants:

11.1 24°F'

4. Sealant Type:

Ceramic Fiber

5. Damming Sldel:

Boot

6. Damming Side 2:

Boot

7. Damming Continuity (AcelRej):

WA

8. Boot Condition (AeclRej):

Accept

9. Sealant Depth:

Assumed Per Detail Fire Area (Side I):

A-8 M-OX Dwg: M-1x1918 Fire Area {Side 2): A-3

10. Annular Gap {smallest):

3" 1 1. Gap between pen:

NIA

12. Barrier Type:
13. Opening Sleeved or Concrete:

Stwl

14. Pipe Insulated:

Yes Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Walkdown Comments:

Wall thickness determined by Drawing I

-C01321, Insulation encapsulated, assumed OK.

Sketch:

FA:

I I - ' " - '

I r

I 1

+

1 M-663-000 I 7A, Revision W04 Page B2-28 of 82-95 4

1 I

I 4

Penetration Seal Data Appendii:

~2 1

Photos:

PI 32W1844 Fire Area A-8 (Side 1) I i

i i

t I

1 Fire Area A3 I

I I

i 1

1:

I I

1 1

I I

I

'&-I. I L

L (Side 2)

Fire Area A-8 (Side 1)

M-663-00017A, Revision W04 Page 82-29 of B2-95 I

Penetration Seal Data Appendix:

~2 I

Penetration #:

P I 33S0799 Penetration Type:

RB-1 Fire Area (Side 1): A-25 M-OX Dwg: M-OXi331 Fin Ama (Side 2): A-l

1. Barrier Thickness:

12" 2 Opening Size:

24"D

3. Penetrants:
4. Sealant Type:
5. Damming Side1 :

Unknown

6. Damming Side 2:

Boot

7. Damming Continuity (AcclRej):

MA

8. Boot Condition (Acaej):

Accept '

9. Sealant Depth:

Assumed Per Detail

10. Annular Gap (smallest):

4'

11. Gap between pen:

NIA

12. Barrier Type:

F R

13. Opening Sleeved or Concrek:

Steel

14. Pipe Insulated:

Yes Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Walkdown Comments:

+ Boot for boitom side only, top side enclosed. Insulation appears to transition through the seatant zone. (WSA)

(See Drawing M-13EJ02; Residual Heat Removal Train B [EJ] Line Number 009-ECB-IT, 350F Design Temp, 2" thick. Classification "X" Calcium Silicate Type Insulation)

Sketch:

M-663-00017A, Revision W04 Page 82-30 of 82-95 Penetration Seal Data Appendix:

~2 Photos:

P I 3380799 Fire Area A-25 (Side 1) 1 I

I I-.

Fire Area A-25

{Side 1)

Fire Area A-I (Side 2)

Fire Area A-l (Side 2)

M-663-00017A, Revision W04 Page W-31 of B2-95 I

Penetration Seal Data Appendix:

BZ I

Penetration #:

P13450860 Penetration Type:

RB-1 I. Barrier Thickness:

12"

2. Opening Size:

2Y 0

3. Penetrants:
4. Sealant Type:

5, Damming Sick1 :

6. Damming Side 2:

Radflex

  • Unknown Boot
7. Damming Continuity (AcclRej):

NIA

8. Boot Condition (AdReJ):

Accept Fire Area (Side I):

A-24 M-OX Dwg: M-1x1341 Fire Area (Side 2):

A-I

9. Sealant Depth:

Assumed Per Detail

10. Annular Gap (smallest):

4"

11. Gap between pm:

NIA

12. Barrier Type:

R

13. Opening ~teevdor conmete:

Stml

14. Pipe Insulated:

Yes Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Walkdown Comments:

S1& thickness based on drawing C-f C1311. '

Top side seal is covered with support insulation and shielding, obscuring inspection attributes. Insulation appears to transition thrwgh the sealant via bottom side examination.

Sketch:

A d

, +

I I

1

M-663-000 1 7A, Revision W04 Page B2-32 of B2-95

( Penetration seal Data Appendix:

B2 Photos:

P134S0860 Fire Area A-24 (Side 1)

Fire Area A-24 (Side 1)

I Fire Area A-1 (Side 2)

Fire Area A-?

(Side 2)

M-663-00017A, Revision W04 Page B2-33 of B2-95 Penetration Seal Data Appendix:

~2 I Penetration #:

P I 34W2053 I

Penetration Type:

RB-8 2012'-3" 4, Barrier Thickness:

38"

2. Opening S i :

1 %"D

3. Penelranis:
4. Sealant Type:
5. Damming Side1 :

(1 ) f T P R a d e h a m NIA

6. Damming Side 2:

MIA

7. Damming Continuity (AcdRej):

N A

8. Boot Condition (AccRej):

Accept

9. S.a,?!!#&p?h:

34" *'

Fife Area (Side I):

A-8 MOX Dwg: M-1x1921 Fire Area (Side 2): A-24

10. Annular Gap (smallest):

2"

11. Gap b e h e n pen:

NIA

12. Barrier Type:

F w

13. Opening Sleeved or Concrete:

Steel

34. Pipe Insulated:

No Prepared By:

Wayne Aregood Reviewed By:

Walkdown Commenk Barrier thickness determined by Drawing C-OC1341 (wsa). "Sealant depth determined by inspection report.

Sketch:

M-663-00017A, Revision W04 Page 82-34 of B2-95 Penetration Seal Data Appendlx:

B2 1 Photos:

P I 34W2053 Fire Area A-8 (Side 1)

Fire Area A-24 (Side 2)

Fire Area A-8 (Side 1)

Fire Area A24 (Side 2)

M-663-00017A, Revision W04 Page B2-35 of B2-95 Penetration Seal Data

~ p ~ d i i :

B2 Penetration #:

P13580232 Penetration Type:

F B I LodElev.: 2000'-0" Fire Area (Side 1): A-I 5 MOX Dwg: M-1x1 t 51 Fire (Side 2): A-33

1. Barrier Thickness:

16'

2. Opening Size:

16"D

3. Penetrants:

(1 ) 10-P

4. Sealant Type:

Ceramic Fiber

5. Damming Sidel:

Boat

6. Damming Side 2:

Boot

7. Damming Continuity (AcclRej):

NIA

8. Bmt Condition (AcdRej):

Accept

9. Sealant Depth:

Assumed Per Detail

10. Annular Gap (smallest):

1 112"

11. Gap between pen:

NIA

12. Barrier Type:

A F

W

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne A r e g d Prepared By:

Jeff Suter Reviewed By:

Walkdown Comments:

Underside of slab has Q-Decking, effective barrier thickness is measured from corrugated valley.

Sketch:

Fire Area A-I5 (Slde 1)

M-663-00017A, Revision W04 Paae B2-36 of B2-95 Penetration Seal Data Appendix:

~2 Photos:

P I 35S0232 F i r e h A-15 (8de 1)

Fire Area A-33 (Side 2)

Fire Area A-33 (Side 2 )

M-663-00017A, Revision W04 I

Page B2-37 of 82-95 Penetration Seal Data Appendix:

BZ 1 I Penetration #:

P13580233 Penetration Type:

FB-I LoeAElev.: 2000'-On

1. Barrier Thickness:

18"

2. Opening S i :

fdnD

3. Penetrants:

(t) 8 " ~

4. Sealant Type:

Ceramic Fiber 5, Damming Side1 :

Boot

6. Damming Side 2:

Boot

7. Damming Continuity (AcdRej):

FUA

8. Boot Conditian {Amej):

Accept

9. Sealant Depth:

Asummed Per Detail Fire Area (Slde 1); A-15 MOX Dwg: M-1x1159 Fire Area (Side 2): A43

10. Annular Gap {smallest):

1"

11. Gap between pen:

NIA

12. Barrier Type:

A F

13. Opening sleeved or Ebncrete:

Steel

14. Pipe Insulated No Wayne Aregood Prepad By:

Jeff Suter Reviewed By:

Walkdown Comments; Underside of slab has Q-Decking, effective barrier thickness Is rneasurad from corrugated valley.

Sketch:

M-663-000 1 7A, Revision W04 Page B2-38 of 82-95 I Penetration seal Data Appendix:

B2 Photos:

P135SO233 Fire Area A-1 5 (Side 1 )

Fire Area A-33 (Si

2)

Fire Area A-1 5 (Side 1 )

Fire Area A-33

[Side 2)

M-663-00017A, Revision W04 Page 82-39 of B2-95 Penetration Seal Data Appendix:

BZ Penetration #:

P13580943 Penetration Type:

FB-f

1. Barrier Thickness:

12"

2. Opening Size:

14"D

3. Penetrants:

(I) 10" P

4. Sealant Type:

Ceramic Fiber

5. Damming Sided:

NI A

6. Damming Side 2:

NIA

3. Damming Continuity (AcdRej): NIA
8. Boot Condition (AcIRej):

Not Reviewed

9. Sealant Depth:

Not Reviewed Fire Area (Side 1): A-1 5 M-DX Dwg:

M-1x1352 Fire Area (Side 2): A-33 f 0. Annular Gap (smallet):

Not Reviewed

11. Gap between pen:

Not Revimd

12. Barrier Type:

A F

P W

13. Opening Sleeved or Concrete; Steel
14. Pipe Insulated:

No Jeff Suter Prepared By:

Don Garbe Reviewed By:

Walkdown Comments:

The walkdown review was based on design Imtion of the penetration, as identified on Sketch:

FA; A - 1 s

=F 4

M-663-00017A, Revision W04 Page 82-40 of 82-95 i

1 Penetration Seal Data Appendix:

82 1

Penetration #:

P I 41 S i 01 4 Penetmtion Type:

F B I LocJElev.: 2026'4"

9. Barrier f hickness:

20"

2. Opening Sie:
3. Penetrants:
4. Sealant Type:
5. Damming Sidel:

30"D (1 ) 24"P Ceramic Fiber Boot

6. Damming Side 2:

Boot

7. Damming Continuity (AcdRej):

MIA

8. Boot Condition (A-ej):

fire Area (Side I):

A4 6 M-OX Dwg: M-1X1411

9. Sealant Depth:

Assumed per detail Walkdown Comments:

Slab thickness based on GOC1411.

t 0. Annular Gap (smallest):

2-114"

11. Gap beiween pen:

NIA

12. Barrier Type:
13. Opening Sleeved or Concrefe:

Steel

14. Pipe Insulated:

No Jeff Suter Prepared By:

Wayne Aregood Reviewed By: