Form APF-05-003-01, Rev. 2 A
~*~
~
ASSIGNED DISCIPLINE:
Mechanical DESIGN DOCUMENT CHANGE NOTICE DOCUMENT NUMBER M-663-00017 A OTHER DOCUMENTS AFFECTED BY THIS CHANGE:
NONE OTHER DDCN'S REQUIRED TO IMPLEMENT CHANGE:
NONE REASON FOR CHANGE:
Incorporate changes per CCP 14714. Cable tray 115U5A94 now contains a PFSSD cable so clarification is needed since this cable tray is in the heat affected zone for some penetrations.
PREPARED BY:
DATE:
11/20/2014 Verifier Qualification will be to the same requirement as the parent document VERIFIED BY:
APPROVED BY:
DC RELEASE:
DESCRIPTION OF CHANGE:
02/07/2015 DATE:
DATE:
02/19/2015 Kay L Smith Released by Document Services.
Release Date:
2015.03.26 08:23:46 -05'00' On page B 13-66 ofB 13-88, make the following changes:
Fire Area (Side 1)
A-16 INITIATING DOC.
TYPE: N/A NO. N/A DCP/CCP NO 14714 REV. 0 REV.
W05 SEQ. NO.
01 PAGE I OF 2
~\\1111111111111//i//1(/t.
'!>.~,,~
.. I R
~1/ql.
- <1:1, P'-'". f::
if~
~~~'*********** 0_1.. ~
'Mv...-,ce.Nss:1jf***~ \\
~
~ ~.
~
~ :
g*s
~
i-11\\
) 6
'::'! 7l.
_.:P,:;,:::.
~ ~*
.*(t/i~
~ **.. /t;qNsf'-'3.* * * ~ of
~ ~**...... *~(:) ~
~'" 'IONAL 'C-'~,,#'
11111111111111111\\111\\\\\\
Digitally signed by Brian R Fox Date:
2015.02.20 08:21:36 -06'00' RPE Certification For ASME Section III design specifications, refer to AP 05-004 for qualification requirements I. 24" Cable Tray 5U5A94 is within Heat Affected Zone. Further review determined that this cable tray is PFSSD.
Document E-IF9910 provides the basis for acceptance.
Fire Area (Side 2)
A-5
- 1. 24" Cable Tray 5U5A94 is within Heat Affected Zone. Further review determined that this cable tray is PFSSD.
Document E-IF9910 provides the basis for acceptance.
Form APF-05-003-01, Rev. 0 i_
~---~?--~
~
ASSIGNED DISCIPLINE:
Mechanical DESIGN DOCUMENT CHANGE NOTICE DOCUMENT NUMBER M-663-00017A On page B 13-69 ofB 13-88, make the following changes:
Fire Area (Side 1)
A-16 INITIATING DOC.
TYPE: N/A NO. N/A DCP/CCP NO 14714 REV. 0 REV.
wos SEQ. NO.
01 PAGE 2 OF 2
- 1. 24" Cable Tray 5U5A94 is within Heat Affected Zone (1/2" clearance to pipe strut clamp). Further review determined that this cable tray is PFSSD. Document E-1F991 0 provides the basis for acceptance.
Fire Area (Side 2)
A-5
- 1. 24" Cable Tray 5U5A94 is within Heat Affected Zone (3-1/2"). Further review determined that this cable tray is PFSSD. Document E-1F9910 provides the basis for acceptance.