Fire Protection Evaluations for Unique or Unbounded Fire Barrier Configuration, M-663-00017A, Rev. W05-01
ML17151B057
Person / Time
Site: Wolf Creek 
Issue date: 03/09/2017
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML17151A982 List: ... further results
References
WO 17-0045
Download: ML17151B057 (2)


Text

Form APF-05-003-01, Rev. 2 A

~*~

~

ASSIGNED DISCIPLINE:

Mechanical DESIGN DOCUMENT CHANGE NOTICE DOCUMENT NUMBER M-663-00017 A OTHER DOCUMENTS AFFECTED BY THIS CHANGE:

NONE OTHER DDCN'S REQUIRED TO IMPLEMENT CHANGE:

NONE REASON FOR CHANGE:

Incorporate changes per CCP 14714. Cable tray 115U5A94 now contains a PFSSD cable so clarification is needed since this cable tray is in the heat affected zone for some penetrations.

PREPARED BY:

DATE:

11/20/2014 Verifier Qualification will be to the same requirement as the parent document VERIFIED BY:

APPROVED BY:

DC RELEASE:

DESCRIPTION OF CHANGE:

02/07/2015 DATE:

DATE:

02/19/2015 Kay L Smith Released by Document Services.

Release Date:

2015.03.26 08:23:46 -05'00' On page B 13-66 ofB 13-88, make the following changes:

Fire Area (Side 1)

A-16 INITIATING DOC.

TYPE: N/A NO. N/A DCP/CCP NO 14714 REV. 0 REV.

W05 SEQ. NO.

01 PAGE I OF 2

~\\1111111111111//i//1(/t.

'!>.~,,~

.. I R

~1/ql.

  1. <1:1, P'-'". f::

if~

~~~'*********** 0_1.. ~

'Mv...-,ce.Nss:1jf***~ \\

~

~ ~.

~

~ :

g*s

~

i-11\\

) 6

'::'! 7l.

_.:P,:;,:::.

~ ~*

.*(t/i~

~ **.. /t;qNsf'-'3.* * * ~ of

~ ~**...... *~(:) ~

~'" 'IONAL 'C-'~,,#'

11111111111111111\\111\\\\\\

Digitally signed by Brian R Fox Date:

2015.02.20 08:21:36 -06'00' RPE Certification For ASME Section III design specifications, refer to AP 05-004 for qualification requirements I. 24" Cable Tray 5U5A94 is within Heat Affected Zone. Further review determined that this cable tray is PFSSD.

Document E-IF9910 provides the basis for acceptance.

Fire Area (Side 2)

A-5

1. 24" Cable Tray 5U5A94 is within Heat Affected Zone. Further review determined that this cable tray is PFSSD.

Document E-IF9910 provides the basis for acceptance.

Form APF-05-003-01, Rev. 0 i_

~---~?--~

~

ASSIGNED DISCIPLINE:

Mechanical DESIGN DOCUMENT CHANGE NOTICE DOCUMENT NUMBER M-663-00017A On page B 13-69 ofB 13-88, make the following changes:

Fire Area (Side 1)

A-16 INITIATING DOC.

TYPE: N/A NO. N/A DCP/CCP NO 14714 REV. 0 REV.

wos SEQ. NO.

01 PAGE 2 OF 2

1. 24" Cable Tray 5U5A94 is within Heat Affected Zone (1/2" clearance to pipe strut clamp). Further review determined that this cable tray is PFSSD. Document E-1F991 0 provides the basis for acceptance.

Fire Area (Side 2)

A-5

1. 24" Cable Tray 5U5A94 is within Heat Affected Zone (3-1/2"). Further review determined that this cable tray is PFSSD. Document E-1F9910 provides the basis for acceptance.