Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000293/LER-1980-094, Forwards LER 80-094/04T-0 + (ML19340F023)
- ML19340F024 + (ML19340F024)
- 05000259/LER-1980-091, Forwards LER 80-091/03L-0 + (ML19340F025)
- ML19340F026 + (ML19340F026)
- ML19340F027 + (ML19340F027)
- 05000259/LER-1980-091-03, /03L-0:on 801217,drywell Hydrogen Monitor, 1-H2M-76-39,would Not Calibr Properly to Calibr Gas Tech Spec.Caused by GE Model 47E226428G2 Sensor Failure.Alternate Sensor 1-H2E-76-39A Connected to Hydrogen Monitor + (ML19340F028)
- 05000324/LER-1980-109, Forwards LER 80-109/03L-0 + (ML19340F029)
- ML19340F030 + (ML19340F030)
- ML19340F031 + (ML19340F031)
- ML19340F032 + (ML19340F032)
- 05000245/LER-1980-018, Forwards LER 80-018/01X-1 + (ML19340F033)
- ML19340F035 + (ML19340F035)
- ML19340F036 + (ML19340F036)
- 05000336/LER-1980-041, Forwards LER 80-041/03L-0 + (ML19340F037)
- ML19340F038 + (ML19340F038)
- ML19340F039 + (ML19340F039)
- ML19340F040 + (ML19340F040)
- 05000302/LER-1980-056, Forwards LER 80-056/03L-0 + (ML19340F041)
- ML19340F042 + (ML19340F042)
- ML19340F044 + (ML19340F044)
- ML19340F045 + (ML19340F045)
- 05000293/LER-1980-094-04, /04T-0:on 801229,lab Rept Indicated Excessive Concentration of I-131 in Milk Sample Collected on 801120. Caused by Chinese Weapons Test.Consumption of Milk Poses No Threat to Health of Public + (ML19340F046)
- ML19340F047 + (ML19340F047)
- ML19340F049 + (ML19340F049)
- ML19340F050 + (ML19340F050)
- 05000324/LER-1980-109-03, /03L-0:on 801215,primary Containment Atmospheric Monitor 2-CAC-AT-1259 Tripped Due to Low Sample Flow.Caused by Moisture in Monitor Pressure Regulator & Photohelic Unit. Moisture Removed & Photohelic Unit Replaced + (ML19340F051)
- A01173, Responds to NRC Re Violations Noted in IE Insp Rept 50-213/80-15.Corrective Actions:Emergency Operating Procedures Review Being Accomplished by Scheduled self-study Technique & Requalification Program Revised + (ML19340F052)
- ML19340F053 + (ML19340F053)
- ML19340F054 + (ML19340F054)
- ML19340F056 + (ML19340F056)
- IR 05000213/1980015 + (ML19340F057)
- ML19340F058 + (ML19340F058)
- ML19340F061 + (ML19340F061)
- 05000245/LER-1980-018-01, /01X-1:on 801105,MSRH-32 & MSRH-28 Main Steam Line Support Members Found to Have Failed Welds Between Support Member & Support Structure.Caused by Lack of Penetration. Sys Scheduled for Reanalysis Per IE Bulletin 79-14 + (ML19340F062)
- ML19340F063 + (ML19340F063)
- ML19340F064 + (ML19340F064)
- 05000336/LER-1980-041-03, /03L-0:on 801210,HPSI Injection MOV 2-SI-616 Overtravelled 0.25 Inch.Cause Unknown.Valve Stroked Five Times & Traveled to Correct Position Each Time + (ML19340F066)
- ML19340F067 + (ML19340F067)
- ML19340F068 + (ML19340F068)
- 05000302/LER-1980-056-03, /03L-0:on 801219,atmospheric Radiation Monitor RM-A5 Found Inoperable,Rendering Control Complex Emergency Ventilation Sys Inoperable.Caused by Seized Sample Vacuum Pump Due to Normal Wear.Spare Pump Installed & Tested + (ML19340F069)
- ML19340F070 + (ML19340F070)
- ML19340F071 + (ML19340F071)
- ML19340F072 + (ML19340F072)
- IR 05000271/1980011 + (ML19340F073)
- ML19340F074 + (ML19340F074)
- ML19340F075 + (ML19340F075)
- ML19340F077 + (ML19340F077)
- ML19340F078 + (ML19340F078)
- ML19340F079 + (ML19340F079)
- IR 05000413/1980033 + (ML19340F080)
- ML19340F081 + (ML19340F081)