Semantic search

Jump to navigation Jump to search
 Issue dateTitleTopic
ML20210H15923 July 1999Notice of Violation from Insp on 990308-10.Violation Noted: from Time of Receipt of Alarm Until Arrival at Three Different Vital Areas,Response Objective & Physical Security Plan Were Not Met
ML20236J6971 July 1998Notice of Violation from Insp on 980412-0530.Violation Noted:Several Conditions Adverse to Quality Associated W/Cr Ventilation Sys Were Not Promptly Corrected.Conditions Inappropriately Closed Out Before Adequate C/As CompletedSafe Shutdown
ML20217E59223 March 1998Notice of Violation from Insp on 980111-0212.Violation Noted:While Performing Maint on 1A Centrifugal Charging Pump,Maint Personnel Violated Requirements of FNP-0-M-001, Rev 13
ML20198N94829 December 1997Notice of Violation from Insp on 971019-1129.Violation Noted:As Early as June 1985,licensee Identified Degradation of Cork Seal Between Containment & Auxiliary Bldg Walls, Condition Adverse to QualityCondition Adverse to Quality
ML20199H12817 November 1997Notice of Violation from Insp on 970907-1018.Violations Noted:Battery Capacity After Svc Test Was Inadequate & Check Valve V003 & V002D F & H Were Not Flow Tested in Manner That Proves That Disk Travels to Seat on Cessation
ML20211Q9396 October 1997Notice of Violation from Insp on 970803-0906.Violation Noted:As of 970906 Licensee Installed One 1-inch Thick Wrap of Kaowool on Sides & Bottoms of Raceways BDE-9 & BDE-15, Carrying Train B Charging Pump Power Cable in Fire AreaFire Barrier
Exemption Request
Fire Protection Program
ML20211K81626 September 1997Notice of Violation from Insp on 970818-22.Violation Noted: Noted:Nrc Identified That Licensee Failed to Correctly Translate Applicable Design Specfication Input Requirements for Kaowool Electrical Raceway Fire Barrier Sys at PlantFire Barrier
Fire Protection Program
ML20217R20228 August 1997Notice of Violation from Insp on 970622-0802.Violation Noted:On 970616,most of M&TE Used Onsite Did Not Have Written & Approved Calibration Procedures
ML20148K6439 June 1997Notice of Violation from Insp on 970330-0510.Violation Noted:On 970321,facility Licensee Physician Determined That Licensed Operator Eyesight No Longer Met Min Stds Required by 10CFR55.33(a)(1) as Measured by Std of ANSI/ANS-3.4-1983
ML20196G4246 May 1997Notice of Violation from Insp Completed on 970314.Violation Noted:Prior to 970314,licensee Failed to Prescribe Documented Instructions or Procedures to Implement Listed Activities Affecting Quality of Operation of PRF Sys
ML20140B78517 March 1997Notice of Violation from Insp on 970105-0215.Violation Noted:Test Engineer Failed to Comply W/Procedural Requirements of FNP-1-STP-124.0 During Performance Testing of Plant Penetration Room Filtration Sys Train a
ML20133F68923 December 1996Notice of Violation from Insp on 961013-1123.Violation Noted:On 961010,security Guards Failed to Search Westinghouse Sludge Lance Trailer Prior to Allowing Trailer to Enter Plant Protected Area
ML20149M5774 December 1996Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $50,000.Noncompliance Noted:Licensee Failed to Assure Electrical Cables Associated W/Sys Necessary to Achieve & Maintain Hot SD Conditions Encl in Fire BarrierBoric Acid
Fire Barrier
Coatings
Exemption Request
Fire Protection Program
Fire Watch
ML20134J4208 November 1996Notice of Violation from Insp on 960901-1012.Violation noted:non-licensed Sys Operators in Two Separate Events Failed to Properly Implement Applicable Sys Operating Procedures
ML20128J95827 September 1996Notice of Violation from Insp on 960721-0831.Violation Noted:Unit 1 Nis IR Channel Compensating Voltage for NI-35 Was Adjusted by Plant Technicians,Being Below Scale & SR Counts Were Less than 100 Cps
ML20128H74327 September 1996Notice of Violation from Insp on 960812-16 & 26-30. Violations Noted:Properly Approved Configural Control Procedures & Drawings Not Followed in That as Built Sample Line Not Constructed IAW Production Change Notice
ML20058P7581 December 1993Notice of Violation from Insp on 930923-1025.Violation Noted:Planner for Work Package Did Not List Removal of A/C Panel as Required Per Step 7.5.1
ML20057E4871 October 1993Notice of Violation from Insp on 930816-0903.Violation Noted:As of 930903,measures Not Established Assuring That Cause of Conditions Adverse to Quality Determined & C/A Taken to Preclude Repetition of Listed Events
ML20057C30213 September 1993Notice of Violation from Insp on 930730-0830.Violation Noted:Plant Sys Operator & Licensed Shift Foreman Erroneously Isolated Component Cooling Water to Secondary HX Loads
ML20056E32212 August 1993Notice of Violation from Insp on 930712-16.Violation Noted: NRC Identified Multiple Examples of Containers of Radioactive Matl That Were Not Labeled as Required by Licensee Procedure
ML20056D21423 July 1993Notice of Violation from Insp on 930621-25.Violation Noted: Licensee Issued Liquid Waste Release Permit for Batch Release of Liquid Waste Monitor Tank Which Failed to Identify Particulate Nuclides
ML20128A68226 January 1993Notice of Violation from Insp on 921208-930108.Violation Noted:Lubricating Oil Was Not Properly Controlled in That Oil Other than That Specified in Applicable Equipment Lubrication & Vendor Manuals Used in Listed Equipment
ML20248C81127 July 1989Notice of Violation from Insp on 890424-27 & 0508-12. Violations Noted:Circuit Breakers Not Calibr for Several Yrs Due to Temporary Change Notice to Maint Procedure FNP-0-MP-28.116 Deleting Calibr Requirement for Dc Breakers
ML20247R52426 July 1989Notice of Violation from Insp on 890509-10.Violations Noted:On 890429,30 & 0501 Licensee Affixed Byproduct Matl to Us Currency to Identify Thief & on 890507 Plant Operator Observed Entering High Radiation Area W/O DosimeterHigh Radiation Area
ML20246B01216 June 1989Notice of Violation from Insp on 890411-0510.Violations Noted:Containment Integrity Breached During Replacement/ Placement of Fuel within Reactor Containment
ML20245H55619 April 1989Notice of Violation from Insp on 890311-0410.Violation Noted:Fire Protection Panel for Sys FSP-21-59 at 139 Ft Elevation of West Corridor Placed in Override Position on 890224 to Perform Cleaning & Calibr of Sys Smoke DetectorsHourly Fire Watch
ML20245D80626 September 1988Notice of Violation from Insp on 880811-0910.Violation Noted:Valve Left Open Following Addition of Resin to Cation Demineralizer During Mar-May 1988 Refueling Outage & Bearing Oil Cooler for Pump 2A Overheated
ML20151L57421 July 1988Notice of Violation from Insp on 880611-0710.Violation Noted:Deficient Procedural Implementation Re Storage of 18 Charcoal Filter Elements in Penetration Ventilation Equipment Room
ML20151D6407 July 1988Notice of Violation from Insp on 880511-0610.Violation Noted:Failure to Follow Procedures for Storage of Compressed Gas Cylinders & to Provide Adequate Operability Insps on Unit 1 post-accident Containment Ventilation Filter UnitEmergency Lighting
ML20150C12228 June 1988Notice of Violation from Insp on 880516-20 & 0606-10. Violation Noted:Procedure,Used to Perform RCS Water Inventory Balance,Was Not Capable of Performing That Required Surveillance Reliably
ML20154P59020 May 1988Notice of Violation from Insp on 880328-0401.Violation Noted:Licensee Failed to Make Attenuation Corrections for Calibr Detectors W/Solid Geometrics Which Resulted in Inaccurate Gamma Spectroscopy Measurements of Gaseous Matl
ML20154Q03118 May 1988Notice of Violation from Insp on 880222-26 & 0307-11. Violation Noted:Failure to Follow Procedures & Failure to Prevent Deficient Conditions from Reccurring in Cases Listed
ML20151N85919 April 1988Notice of Violation from Insp on 880321-24.Violation Noted: Cabinet Containing Safeguards Info Insecure & Unattended
ML20148E61918 March 1988Notice of Violation from Insp on 880229-0304.Violation Noted:Personnel Designated as Operations Shift Aide, Appointed by Interim Emergency Director,Did Not Receive Required Annual Retraining for Communications Personnel
ML20148F42710 March 1988Notice of Violation from Insp on 880104-06.Violation Noted:Radiological Exclusion Area Not Provided W/Locked Doors,But Was Provided W/Warning Signs & Flashing Red Light,Not Adequate to Prevent Unauthorized EntryHigh Radiation Area
ML20150B29825 February 1988Notice of Violation from Insp on 880112-0210.Violations Noted:Required Fire Watches Not Initiated & Fire Suppression Sys Inoperable for 14 HContinuous fire watch
Hourly Fire Watch
ML20150B58719 February 1988Notice of Violation from Insp on 871202-04.Violations Noted: Valve Testing Not Performed in Accordance W/Approved Test Procedure & Licensee Failed to Provide Instructions for Fill & Vent of Portion of RHR Train a Piping
ML20236X8284 December 1987Notice of Violation from Insp on 871102-06.Violation Noted: Emergency Diesel Generator Test Data Logs Not Completed as Specified in 850909 Operations Dept Memo
ML20236R83017 November 1987Notice of Violation from Insp on 871019-23.Violation Noted: Work Performed Inside Controlled Area W/O Wearing Protective Clothing Required by RWP 0-87-001A
ML20236M9983 November 1987Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $50,000.Noncompliance Noted:Inadequate Control & Installation of Purchased Equipment & Inadequate Corrective Actions & InspsUnanalyzed Condition
ML20236M80128 October 1987Notice of Violation from Insp on 870910-1009.Violation Noted:Continuous Fire Watch Assigned to Roof of Auxiliary Bldg to Monitor Open Flame Operations Associated W/Roofing Repairs Not Alert to DutiesContinuous fire watch
Fire Protection Program
Fire Watch
ML20235U9355 October 1987Notice of Violation from Insp on 870818-0910.Violation Noted:Normal Air Pressure Status Lights on Main Control Board in Control Room Not Illuminated When Sufficient Air Pressure in Air Receivers to Start Diesel Engines
ML20238A3791 September 1987Notice of Violation from Insp on 870710-0818.Violation Noted:Failure to Establish,Implement & Maintain Procedures, Per Tech Spec 6.8.1
ML20236J75630 July 1987Notice of Violation from Insp on 870611-0710.Violation noted:post-maintenance & Design Change Insp Program Not Adequate to Demonstrate That Sys & Components Installed,In That Fire Dampers on Trains a & B Electrically Inoperable
ML20235F4752 July 1987Notice of Violation from Insp on 870518-0612.Violations Noted:On 870508,RHR Pump Room Cooler Returned to Svc W/O Required Functional Acceptance Testing & Valve Lineup Performed & Failure to Establish Procedure for Testing
ML20215B3464 June 1987Notice of Violation from Insp on 870411-0518
ML20206C56027 March 1987Notice of Violation from Insp on 861211-870110.Violations Noted:Foreman & Group Supervisor Responsible for Activities of Work Re Maint Work Requests 141322,141323 & 141324 Failed to Control Quality of Work Performed
ML20205P74220 March 1987Notice of Violation from Insp on 870224-27Fire Protection Program
ML20205P07419 March 1987Notice of Violation from Insp on 870126-30
ML20207T57113 March 1987Notice of Violation from Insp on 870111-0210