Notice of Violation from Insp on 870611-0710.Violation noted:post-maintenance & Design Change Insp Program Not Adequate to Demonstrate That Sys & Components Installed,In That Fire Dampers on Trains a & B Electrically Inoperable
ML20236J756
Person / Time
Site: Farley  
Issue date: 07/30/1987
From: Verrelli D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20236J749 List:
References
50-348-87-14, 50-364-87-14, NUDOCS 8708060270
Download: ML20236J756 (2)


Text

-..-.

I ENCLOSURE 1 NOTICE OF VIOLATION Alabama Power Company Docket Nos. 50-348 and 50-364 Farlev 1 & 2 License Nos. NPF-2 and NPF-8 Ouring the Nuclear Regulatory Commission (NRC) inspection conducted on June 11

- July 10, 1987, a violation of NRC requirements was identified, The violation involved f ailure to perform adequate inspection and testing.

In accordance with the " General Statement of Policy and Procedure for NRC Enforcement Acticns," 10 CFR Part 2, Appendix C (19E6), the violation is cited-below:

10 CFR Part 50, Appendix 8, criterion X requires that a program for inspection of activities affecting quality shall be established and executed to verify conformance with the documented instructions, procedures, and drawings for accomplishing the activity.

10 CFR 50, Appendix S, crite-ion XI requires that a test program be established to assure that all testing required to demonstrate that system / components which have undergone modification will be corrpleted to assure satisfactory performances.

Test results shall be documented and evaluated to assure that test requirements have been satisf4ed.

Con t ra ry to tre accie, a ;ost maintenance anc esig charge inspetticr program was not adequate to demonstrate that systems and components hac been installed in accordance with instructions, procedures, and drawings in that the control room fire dampers on train " A" and trai n "B"

were found to be electr cally inoperable begirning :- February 13, 1931 t^

i June 1937.

Electrical links were found open in certain electrical junction boxes; two electrical jumpers were installed in one terminal box, and the electrical installation to the SRD's was int T:lete.

Tnis is a Severity tevel IV violatien (Supple:er: :).

Pursuant to the p-:vi:icns C 10 CFR 2.201, AlarsTa ;;4e-Cerpar.y is rereb_,

equired to submi t t: t-i s Of #i:e with'n 30 days c

e date f tne lettet transmitting this N:tice a citten state ent or epis at' -

-e:ly including 4-(for each violation): (1) 3c-i ssicn er denial cf t e."c'sticr, (2) the reas:-

f - the violation i# a:-itted, (3) the correct've < tere

'c" have teen take-e 8708060pg oh48 -

PDR AI 3 PDR G

i

.s Alabama Power Company 2

Docket Nos. 50-348 and 50-364

.Farlev 1.& 2 License Nos. NPF-2 and NPF-8 and the results achieved, (4) the corrective steps which will be taken to avoid further violations, and (5)-the date when full compliance will be achieved.

~

Where good cause is shown, consideration will be given to extending the response time..

FOR THE NUCLEAR REGULATORY COMMISSION

/r h

gwh.

)

>ILt

~ ~ ' ~

t s. David M. Verrelli, Chief Reactor Projects Branch 1 Divfsion of Reactor Projects i

Dated at Atlanta, Georgia This 30th day of July 1987 l