ML20137P849

From kanterella
Jump to navigation Jump to search
Retran Computer Code Reactor Sys Transient Analysis Model Qualification
ML20137P849
Person / Time
Site: Calvert Cliffs  
Issue date: 01/31/1986
From: Cook T, Mirsky S, Wisniewski G
BALTIMORE GAS & ELECTRIC CO.
To:
Shared Package
ML20137P847 List:
References
REF-GTECI-A-49, REF-GTECI-RV, TASK-A-49, TASK-OR A-85-11, NUDOCS 8602050375
Download: ML20137P849 (155)


Text

{{#Wiki_filter:9" e TOPICAL REPORT A-85-11 R E-~ RA \\ Comou:er Coce Reac:or Sys:em ~~ransien~: Anaysis Voce Qua i ica: ion ERT CO BALTIMORE GAS AND ELECTRIC COMPANY NUCLEAR GENERATION ENGINEERING SECTION NUCLEAR LICENSING AND ANALYS15 UNIT D [;.p i \\^

A-35-I l TOPICAL REPORT RETRAN COMPUTER CODE REACTOR SYSTEM TRANSIENT ANALYSIS MODEL QUALIFICATION By T. L. Cook S. M. Mirsky G. R. Wisniewski BALTIMORE GAS AND ELECTRIC COMPANY NUCLEAR GENERATION ENGINEERING SECTION NUCLEAR LICENSING AND ANALYSIS UNIT January 31,1936

DISCLAIMER The information contained in this topical report was prepared for the specific requirements of the Baltimore Gas and Electric Company (BG&E) and its affiliated companies, and may contain materials subject to privately owned rights. The material therein is believed to be true and accurate to the best of our knowledge and information. Any use of all or any portion of the information, analyses, methodology or data contained in this topical report by third parties shall be undertaken at such party's sole risk. BG&E and its af filiated companics hereby disclaim any liability (including but not limited to tort, contract, statute, or course of dealing) or warranty (whether express or implied) for the accuracy, suitability for a particular purpose or merchantability of the information. Reviewed and Approved by ~ R. C. L. Olson c Principal Engineer Nuclear Licensing and Analysis Unit Reviewed and / Approved by / O R. F. Ash Supervising Engineer Nuclear Generation Engineering Section -ii-

ACKNOWLEDGEMENTS The authors would like to express their appreciation to Mr. B. S. Montgomery for his valuable editorial comments, and to Miss C. Sullins for her technical assistance. We also thank Miss V. Fields for her patient typing support, and a special thanks to Miss N. L. Bealmear and Mrs. D. P. Hoover for drawing the many figures and diagrams in this report. -111-

TABLE OF CONTENTS Page List of Tables vii List of Figures viii List of Acronyms xi

1.0 INTRODUCTION

1

2.0 DESCRIPTION

OF CALVERT CLIFFS NUCLEAR POWER PLANT 3 3.0 RETRAN CALVERT CLIFFS MODELS 10 3.1 Description of RETRAN 10 3.2 RETRAN One Loop Model of Calvert Cliffs 12 3.3 RETRAN Two Loop Model of Calvert Cliffs 16 3.4 RETRAN Four Loop Model of Calvert Cliffs 19 4.0 PLANT TRANSIENT COMPARISONS 21 4.1 RETRAN 02 Analysis of a Calvert Cliffs Multiple Secondary Side Malfunction Event 21 4.1.1 Description of Plant Event 21 4.1.2 Event Specific RETRAN Modeling Changes 23 4.1.3 Comparison of RETRAN Results to Plant Data 24 4.1.4 RETRAN Model Sensitivity Study 26 4.1.5 Summary of Results 29 4.2 Calvert Cliffs Unit i Startup Test - Four Pump Coastdown from 20% Power 41 4.2.1 Description of Plant Event 41 4.2.2 Event Specific RETRAN Modeling Changes 41 4.2.3 Comparison of RETRAN Results to Plant Data 41 4.2.4 Summary of Results 43 4.3 Calvert Cliffs Unit 1 Startup Test - Reactor Coolant Operation Pump Combination Flow Tests at Hot Zero Power 46 i 4.3.1 Description of Plant Event 46 l 4.3.2 Event Specific RETRAN Modeling Changes 46 l 4.3.3 Comparison of RETRAN Results to Plant Data 43 r, 4.3.4 RETRAN Sensitivity Study 50 i 4.3.5 Summary of Results 51 f i. . iv. I I i

Page 4.4 Calvert Cliffs Unit 1 Startup Test - One Pump Coastdown from 80% Power 53 4.4.1 Description of Plant Event 53 4.4.2 Event Specific RETRAN Modeling Changes 53 4.4.3 Comparison of RETRAN Re,ults to Plant Data 59 4.4.4 RETRAN Sensitivity Stud; 60 4.4.5 Summary of Results 61 4.5 Calvert Cliffs Unit 1 Startup Test - Total Loss of Flow / Natural Circulation Test from'40% Power 63 4.5.1 Description of Plant Event 63 4.5.2 Event Specific RETRAN Modeling Changes 69 4.5.3 Comparison of RETRAN Results to Plant Data 69 4.5.4 Summary of Results 70 5.0 TRAC ANALYSIS COMPARISON 77 5.1 Description of TRAC Calvert Cliffs Model 77 5.2 TRAC Analysis of Cooldown to RHR Entry Using ADVs and APS 34 5.2.1 Description of TRAC Transient 34 5.2.2 RETRAN Models for TRAC Comparison 35 3.2.3 Comparison of RETRAN Results and TRAC Results 35 5.2.4 Summary and Conclusion 36 5.3 RETRAN Comparison to TRAC Simulation of Runaway Main Feedwater to One Steam Generator 90 5.3.1 Description of TRAC Transient 90 5.3.2 RETRAN Model for TRAC Corr.parison 92 5.3.3 Comparison of RETRAN Results to TRAC 93 5.3.4 RETRAN Sensitivity Study 95 5.3.5 Summary of Results 96 6.0 LOFT TEST SIMULATION 103 6.1 Description of LOFT Facility and Tests 103 6.2 LOFT RETRAN Model 106 6.3 Test L6-1 Comparison !!O 6.3.1 LOFT Test L6-1 Transient Description 110 6.3.2 RETRAN Modeling for L6-1 Transient Simulation 110 6.3.3 Comparison of RETRAN Results to LOFT Test Data 111 6.3.4 RETRAN Sensitivity Study for LOFT Test L6-1 113 i 6.3.5 Summary of Results 114 v-I - - -.,,...,..,,, - -.,, -., - -, _ _ _ -, -.. ~, _ _., - -,.,., _.. ,y,.~.- ..., -. ~,,,,,,.,,,,.....,. _.. ~. _ _, _, _ _. _. - _ - _,., _ _,. -, _., _ _ _,

Page 6.4 LOFT Test L 6-3 Comparison 121 6.4.1 LOFT Test L6-3 Transient Description 121 6.4.2 RETRAN Modeling for L6-3 Transient Simulation 122 6.4.3 Comparison of RETRAN Results to LOFT Test Data 122 6.4.4 Sensitivity Study 124 6.4.5 Summary of Results 125 7.0

SUMMARY

AND CONCLUSIONS 133

3.0 REFERENCES

139 - vi - i

I LIST OF TABLES i TABLE TITLE Page 2-1 Calvert Cliffs Key Design Pa'rameters 7 4.1-1 October 11,1983 Calvert Cliffs 2 Event 31 Timing Comparison 4.1-2 Tolerance of Calvert Cliffs Plant Computer Data 32 4.1-3 Comparison of Key Event Parameters 32 4.2-1 Four Pump Coastdown from 20% Power Initial 44 Conditions 4.2-2 Comparison of RETRAN One Loop and Four Loop 45 Model Calculated Four Pump Coastdown Total RCS Flow with Plant Data 4 4.3-1 Reactor Coolant Pump Combination Flow Test Data 53 at Hot Standby 1 I 4.3-2 Comparison of Measured Plant Data with RETRAN 34 Calculated RCP Flow Split for RCP Operating ~ Combinations 4.3-3 Reduced Reactor Coolant Pump Operation Abnormal 55 Flow Paths J 4.4-1 Calvert Cliffs One RCP Trip at 80% Power 62 Sensitivity Study Results P [ 5.2-1 LOSP Cooldown Sequence of Events for TRAC and RETRAN 87 5.3-1 Runaway Main Feedwater to One Steam Generator Sequence of Events Comparison 97 6.3-1 Sequence of Events for Experiment L6-1 !!5 6.4-1 Sequence of Events for Experiment L6-3 127 i 7-1 RETRAN Analysis Matrix 135 ~ 7-2 .RETRAN Analysis Key Modeling Parameters 136 7-3 RETRAN Analysis Phenomenology 137 i 7-4 Calvert Cliffs RETRAN Model Improvements and i Lessons Learned 138 i - vil -

i 4 LIST OF FIGURES FIGURE TITLE Page 2-1 Calvert Cliffs Nuclear Steam Supply System Loop Arrangement 9 3.2-1 RETRAN One Loop Calvert Cliffs Model 15 3.3-1 RETRAN Two Loop Calvert Cliffs Model 18 3.4-1 RETRAN Four Loop Calvert Cliffs Model 20 t 4.1-1 October 11,1983 Event Core Thermal Power Response 33 4.1-2 October !!,1933 Event Main Feedwater Flow Response 34 i 4.1 -3 October 11,1983 Event Pressurizer Pressure Response 35 4.1-4 October 11,1983 Event Pressurizer Level Response 36 1 4.1-5 October 11,1983 Event Loop 21 Hot Leg Temperature

Response

37 4.1-6 October 11,1983 Event Loop 21 Cold Leg Temperature

Response

38 i 4.1-7 October 11,1983 Event Steam Generator 22 l 1 Secondary Side Pressure Response 39 4.1-8 October 11,1983 Event Steam Generator Lrrow Range Level Response 40 4 ^ 4.2-1 Four Pump Coastdown Total Reactor Coolant System Flow Response 45-A 4.3-1 Calvert Cliffs Primary Coolant System Flow Paths 56 4.4-1 One Pump Coastdown Total Reactor Coolant System Flow Response 63 4.4-2 One Pump Coastdown Hot and Cold Leg Temperature Response 64 4.4-3 One Pump Coastdown Pressurizer Pressure Response 65 4.4-4 One Pump Coastdown Pressurizer Level Response 66 i 4.4-5 One Pump Coastdown Steam Generator Secondary Side Pressure Response 67 4.5-1 Total Loss of Flow / Natural Circulation Test Total RCS Flow Response 72 - vili - 1

LIST OF FIGURES (Cont'd.) FIGURE ,T_ITLE Page 4.5-2 ' Total Loss of Flow / Natural Circulation Test Pressurizer Pressure Response 73 4.5-3 Total Loss of Flow / Natural Circulation Test Pressurizer Level Response 74 4.5-4 Total Loss of Flow / Natural Circulation Test Hot and Cold Leg Temperature Response 75 4.5-5 Total Loss of Flow / Natural Circulation Test Steam Generator Secondary Side Pressure Response 76 5.1-1 TRAC Noding of Calvert Cliffs Primary Side 30 3.1-2 TRAC Noding of Calvert Cliffs Main Feedwater Transient 32 5.1-3 TRAC Noding of Calvert Cliffs Main Steam Lines 33 5.2-1 Cooldown to RHR Entry - Primary and Secondary Pressure Response 38 5.2-2 Cooldown to RHR Entry - Hot Leg Temperature Response 39 5.3-1 Runaway Main Feedwater to One Steam Generator Pressurizer Pressure Response 93 5.3-2 Runaway Main Feedwater to One Steam Generator Pressurizer Level Response 99 5.3-3 Runaway Main Feedwater to One Steam Generator Downcomer Temperature Response 100 5.3-4 Runaway Main Feedwater to One Steam Generator Hot Leg Temperature Response 101 5.3-5 Runaway Main Feedwater to One Steam Generator Hot Leg Mass Flow Response 102 LOFT Facility Schematic 105 6.1-1 6.2-1 LOFT RETRAN Noding Diagram 103 6.3-1 LOFT Test L6-1 Pressure in Steam Generator Dome 116 6.3-2 LOFT Test L6-1 Liquid Levelin Steam Generator Secondary Side 117 6.3-3 LOFT Test L6-1 Pressure in Pressurizer 113 6.3-4 LOFT Test L6-1 Liquid Levelin Pressurizer 119 - Ix -

a LIST OF FIGURES (Cont'd.) FIGURE TITLE Page i 6.3-5 LOFT Test L6-1 Coolant Temperature in Intact Loop Steam Generator Primary Side Inlet Plenum 120 6.4-1 LOFT Test L6-3 Pressure in Steam Generator Dome 123 l 6.4-2 LOFT Test L6-3 Liquid Levelin Steam Generator Secondary Side 129 t 6.4-3 LOFT Test L6-3 Pressure in Pressurizer 130 6.4-4 LOFT Test L6-3 Liquid Levelin Pressurizer 131 6.4-5 LOFT Test L6-3 Coolant Temperature in Intact Loop Steam Generator Primary Side Inlet Plenum 132 I 4 -X- _ _ _,.., =_..., -.,.. _ -.

LIST OF ACRONYMS ADV Atmospheric Dump Valve AFAS Auxiliary Feedwater Automatic Signal AFW Auxiliary Feedwater APS Auxiliary Pressurizer Spray BG&E Baltimore Gas and Electric Company CCNPP Calvert Cliffs Nuclear Power Plant CE Combustion Engineering CEA Control Element Assembly CIS Containment Isolation Signal CRS Containment Radiation Signal CSAS Containment Spray Actuation Signal i CVCIS Charging and Volume Control Isolation Signal i DBA Design Basis Accident DNBR Departure from Nucleate Boiling Ratio ECCS Emergency Core Cooling System El Energy Incorporated EPRI Electric Power Research Institute ESFAS Engineered Safety Features Actuation System FRV Feedwater Regulating Valve GPM Gallons Per Minute HPI High Pressure Injection HPSI High Pressure Safety Injection IBM International Business Machines, Inc. IHTC Interface Heat Transfer Coefficient KW Kilowatt LANL Los Alamos National Laboratory LOCA Loss of Coolant Accident LOFT Loss of Fluid Test i LOSP Loss of Offsite Power LPSI Low Pressure Safety Injection MFRV Main Feedwater Regulating Valves MFW Main Feedwater MSFCV Main Steam Flow Control Valve MSIV Main Steam Isolation Valve - xi -

LIST OF ACRONYMS (Cont'd.) MW . Megawatt NRC Nuclear Regulatory Commission NSSS Nuclear Steam Supply System OL Operating License PCS Primary Coolant System PORY Power Operated Relief Valve PTS Pressurized Thermal Shock PWR Pressurized Water Reactor RAS Recirculation Actuation Signal RCP Reactor Coolant Pump RCS Reactor Coolant System RHR Residual Heat Removal RPS Reactor Protective System SER Safety Evaluation Report SG Steam Generator SGBS Steam Generator Blowdown System SGFP Steam Generator Feedwater Pump SGIS Steam Generator Isolation Signal SIAS Safety Injection Actuation Signal SRV Safety Relief Valve TBV Turbine Bypass Valve TBCS Turbine Bypass Control System TSV Turbine Stop Valve UGRA Utility Group for Regulatory Action VBUB Bubble Rise Velocity - xii -

l.0 INTRODUCTION During the past three years, The Baltimore Gas and Electric Company (BG&E) has been developing system transient thermal-hydraulic analysis capability for the Calvert Cliffs Nuclear Power Plant using the RETRAN computer code. The first application of this capability was to perform independent audit analyses of the TRAC Pressurized Thermal Shock (PTS) Project (Unresolved Safety Issue A-49) funded by the U. 5. Nuclear Regulatory Commission (NRC) (1, 2, 3). Since then, BG&E has performed other best estimate calculations with RETRAN (4). The purpose of this topical report is to document the BG&E best estimate RETRAN thermal-hydraulic analysis capability. The NRC has stated in Generic Letter No. 83-11 (3.' that: "NRC's experience with safety analyses using large, complex thermal-hydraulic computer codes such as RELAP and TRAC has shown that a large percentage of all errors or discrepancies discovered in safety analyses can be traced to the user rather than to the code itself. This realization has led NRR to place additional emphasis on assuring the capabilities of the code users as well as on the codes themselves... The information we look for includes comparisons performed by the user of the code results to experimental data, plant operational data, or other benchmarked analyses." This topical report was developed to demonstrate the capability of BG&E analysts to properly develop RETRAN models of Calvert Cliffs, perform calculations with these models to simulate realistic plant transient response and compare the results to measured plant data, another best

estimate computer code (TRAC) and experimental data (LOFT). Furthermore, model enhancement and appropriate sensitivity studies were performed to gain a greater insight and a better understanding of modeling Calvert Cliffs with RETRAN. In this manner, BG&E has established both the competence of our analysts to perform best estimate RETRAN calculations of Calvert Cliffs and completed an acceptable code verification in accordance with NRC Generic Letter No. 33-11. The basis for demonstrating BG&E RETRAN best estimate analysis capability is the comparison of five plant transients, two TRAC code analyses and two LOFT tests with BG&E 1 RETRAN calculations. a 4 4 f. .. -... -, -... ~ -.-.

2.0 DESCRIPTION

OF CALVERT CLIFFS NUCLEAR POWER PLANT The Calvert Cliffs Nuclear Power Plant consists of two units located in Lusby, Maryland on the Chesapeake Bay. Unit I began commercial operation in 1975 and Unit 2 in 1977. Each unit is currently licensed to operate at a core thermal power of 2700 Megawatts. Bechtel Power Corporation was the architect-engineer-constructor of the facility. Each Nuclear Steam Supply System (NSSS) is a Combustion Engineering (CE) design pressurized water reactor with a 2x4 loop arrangement: two hot legs and two U-tube steam generators with four cold legs and four reactor coolant pumps as illustrated in Figure 2-1. The core consists of 21714x14 CE fuel assemblies. The core is enclosed in a core shroud and core support barrel within the reactor vessel. The reactor vessel is typical of other CE plants except that it does not have a thermal shield. One hot leg of the primary coolant system is connected through a surge line to a cylindrical pressurizer. The pressurizer regulates primary coolant system pressure and provides overpressure protection. Pressure regulation is performed by the pressurizer heaters and spray to maintain saturated steam and water volumes at thermal equilibrium within the pressurizer. Two power-operated relief valves and two spring-loaded safety valves mounted on the top of the pressurizer can discharge steam to the quench tank for overpressure protection. A small continuous flow is maintained through the spray lines to keep the spray lines and surge line warm to minimize thermal shock during transients and to maintain the water chemistry in the pressurizer equivalent to that of the reactor coolant. Approximately 20% of the pressurizer heaters are continuously energized through proportional controllers to provide makeup for steady state heat losses. Auxiliary spray supplied by charging 't pumps provides an alternate means of depressurizing the primary coolant system. The two U-tube steam generators in each unit transfer heat generated in the reactor core via the primary coolant system to the secondary system. The steam generators are recirculating U-tube design. Each steam generator supplies saturated steam through flow-limiting orifices to the main steam line leading to the high pressure turbine. After passing through the high pressure and low pressure turbines, the steam is condensed in the main condensers. Two Atmospheric Dump Valves (ADVs) discharge steam from the main steam line directly to the atmosphere when condensers are not available and are also used in conjunction with the turbine bypass system to maintain a programmed average primary coolant temperature following turbine trip. Above 70% power, the ADVs are activated by a quick-open signal, while below 70% power they are opened by the control system. Sixteen spring-i loaded steam line Safety Relief Valves (SRV) provide steam line overpressure protection. Four Turbine Bypass Valves (TBV) are normally used to rapidly remove :.eactor coolant system stored energy and limit steam line pressure following a turbine-reactor trip by exhausting steam directly to the main condensers. Each of the two main steam lines is equipped with one Main l Steam Isolation Valve (MSIV) which closes in the event of an excessive steam demand event. 4 The main feedwater system for each unit consists of two turbine-driven main feedwater pumps, each of which could support 70% power operation. Auxiliary Feedwater (AFW) is supplied by up to three AFW pumps on each unit, drawing on water from the condensate storage tanks. Each unit has two turbine-driven and one motor-driven AFW pump. One safety grade and two non-safety grade condensate storage tanks are available as AFW sources for both units. _ t,.

l The Calvert Cliffs Reactor Protective System (RPS) functions to protect the core and reactor coolant system pressure boundary by tripping the reactor core. The parameters which initiate reactor trip are: l High Rate-of-Change of Power High Power Leve! l Low Reactor Coolant Flow Low Steam Generator Water Level Low Steam Generator Pressure High Pressurizer Pressure Thermal Margin / Low Pressure Loss of Load High Containment Pressure Axial Flux Offset High Differential Steam Generator Pressure The Engineered Safety Features Actuation System (ESFAS) initiates the start of equipment which protects the public and plant personnel by mitigating the effects of design basis accidents (DBAs). The ESFAS comprises the following functions: Safety Injection Actuation Signal (SIAS) Containment Spray Actuation Signal (CSAS) Containment Isolation Signal (CIS) Containment Radiation Signal (CRS) Recirculation Actuation Signal (RAS) Steam Generator Isolation Signal (SGIS) Auxiliary Feedwater Automatic Start (AFAS) Charging and Volume Control Isolation Signal (CVCIS) - 5,-

The Calvert Cliffs design includes a number of regulating systems which control key primary and secondary parameters to allow safe operation and ensure high plant availability. These regulating systems control: Control Element Assembly (CEA) position, boric acid concentration, reactor coolant pressure, pressurizer level, feedwater flow, primary coolant average temperature, main steam line pressure, steam generator level, and steam low to the main turbine generator. Important Calvert Cliffs design parameters are delineated in Table 2-i. ;

l l Table 2-1 Calvert Cliffs Key Design Parameters (each unit; except as noted) Current Licensed Core Power: 2700 MW Core: 217 CE 14x14 Fuel Assemblies Primary Coolant System: 4 cold legs, 2 hot legs, 2 reactor coolant pumps, 2 U-tube steam generators, reactor vessel, pressurizer Secondary System: 2 main steam lines, 2 main feedwater pumps, 3 auxiliary feedwater pumps (2 turbine-driven, I electric), I two-flow high pressure turbine, 3 two-flow low pressure turbines, one 3-shell condenser,2 MSIVs 3 Primary Coolant System Volume 9601 f t (Excluding Pressurizer) Normal Operating Pressure 2250 psia Normal Operating Cold Leg Temperature 543 F Normal Operating Hot Leg Temperature 599.4 F 6 Core Coolant Flow Rate 133.9 x 10 lb/hr Pressurizer: 1500 f t.3 volume (600-300 ft.3 water, 700-900 ft.3 steam) Proportional and Backup Electrical Heaters (1500 KW total) 2 2 PORVs (1.354 in flow area each) 2 2 SRVs (1.872 in flow area each) Normal Spray Maximum Flow - 375 GPM Auxiliary Spray Maximum Flow - 132 GPM _ _ - _

Steam Generator: Number per Unit - 2 Number of tubes per steam generator - 8519 Normal Operating Secondary Size Pressure - 850 psia 6 Steam flow per Steam Generator - 6 x 10 lb/hr Main Steam Line: 1 Atmospheric Dump Valve (ADV) per line Total 5% Full Power Steam Flow - for ' both lines 8 Safety Relief Valves (SRVs) per line Total 100% Full Power Steam Flow - for both lines ~ 4 Turbine Bypass Valves (TBVs) Total 40% Full Power Steam FLw Safety Injection System: 3 High Pressure Safety Injection (HPSI) pumps (Shutoff head of 1275 psia) 2 Low Pressure Safety Injection (LPSI) pumps (Shutoff head of 180 psia) 4 Safety Injection Tanks (operating pressure of 215 psia) 1 Refueling Water Tank (400,000 gallons) l FIGURE 2-1 l l CALVERT CLIFFS NUCLEAR STEAM SUPPLY SYSTEM LOOP ARRANGEMENT i I-4% s~ s l 4 l / I e l 'v* v' SURGE .~(/ 4, LINE 's /is l l STE AM GENERATOR r: 11(21),- g s f '*\\ 1 6.* ' ) RCPj ( y' Is _,N RCP I l 118 (218) 11A(21 A) %s ~ t PRESSURIZER / "~N / \\ REACTOR fl i VESSEL z4 / g gcp RCP 12 A (22 A) I I ( I 128(228) STEAM GENERATOR 's 12 (22) ,/ \\ i / >s 4 'b J,1 ( ') s t., _9_ l ~._

3.0 RETRAN CALVERT CLIFFS MODELS 3.1 Description of RETRAN RETRAN is a digital computer code designed to analyze nuclear power plant thermal-hydraulic transients. RETRAN 'vas developed from the RELAP series of codes and sponsored by EPRI since 1975. RETRAN simulates a nuclear power plant as a series of homogeneous volumes interconnected by flow path junctions. The conservation of mass, energy and momentum are maintained by RETRAN. Double-sided or adiabatic metal heat slabs and powered heat conductors (reactor core, passive pressurizer heaters) are explicitly modeled in RETRAN. A nonequilibrium thermal model and a bubble rise model are available for simulating the pressurizer, reactor vessel upper head and steam generator secondary side. Specific models for reactor coolant pumps, valves, control systems, reactor trips, critical (choked) flow, DNBR, transport delay, dynamic slip, steady state initialization, and reactor core neutronics are integral to RETRAN. RETRAN is described in greater detail in two EPRI reports (6,7). In October,1979 and October,1981, the Utility Group for Regulatory Action (UGRA) requested that the U.S. Nuclear Regulatory Commission (NRC) review two versions of the RETRAN code, RETRAN-Oi Mod 003 and RETRAN-02 Mod 002 (3, 9). A Safety Evaluation Report (SER) for these codes was issued in September, 1984 (10), in which the NRC approved of the RETRAN code for performing transiert thermal-hydraulics with certain restrictions. The Baltimore Gas and Electric Company uses RETRAN-02 Mod 003 to perform the analyses described in this document. The code modifications made to RETRAN-02 Mod 002 that resulted in RETRAN-02

Mod 003 are a direct result of the NRC and EPRI design review and user-found error correction. Modifications were performed in accordance with the E!/EPRI RETRAN project Quality Assurance Procedures which conforms with 10 CFR 50, Appendix B. The Calvert Cliffs RETRAN models and calculations discussed in the following sections were developed, documented and verified in accordance a with BG&E engineering calculation procedures. 1 - -..

3.2 RETRAN One Loop Model of Calvert Clifis The one loop RETRAN model of Calvert Cliffs was developed to analyze symmetrical transients (i.e., both steam generators, hot legs and all four cold legs /RCPs respond identically). This model, presented in Figure 3.2-1, consists of 32 volumes, 50 junctions and 41 heat slabs. Typical run times on the BG&E IBM 3081 mainframe computer for this model are equal to or faster than real(transient) time. The one loop model explicitly simulates the entire primary coolant system and that portion of the secondary system from the steam generator to the turbine intet. The reactor vessel comprises nine volumes which include a three-volume core, downcomer, lower plenum-head, bypass, upper plenum and upper head regions. A nonequilibrium volume is used for the reactor vessel - upper head. All heat conductors within the vessel are modeled as RETRAN heat slabs. The one loop model single hot leg, cold leg and reactor coolant pump (RCP) represent the combination of the two hot legs, four cold legs and four RCPs actually in the Calvert Cliffs design. While the hot leg is a single volume, the cold leg and RCP are represented as five RETRAN volumes. This detail allows for an accurate simulation of the loop seal elevation difference; charging, letdown and safety injection temporal effects; and proper pump performance characteristics. Detailed RCP performance curves are included in this model. The one loop model single U-tube steam generator (representing two steam generators) consists of eight nodes for the primary side and one node for the secondary. The U-tubes are modeled with six volumes and the inlet and outlet plenum as one each. This allows for sufficient detail to better predict degraded heat transfer if tube uncovery occurs. The single volume secondary side was found to produce acceptable results without the convergence problems and associated longer computer run times of a multi-noded recirculating steam generator secondary side RETRAN model. The pressurizer system is segmented into three volumes: one for the surge line, one for the spray line and one nonequilibrium volume for the pressurizer itself. All pressurizer pressure and level control systems are explicitly modeled. This includes normal and auxiliary sprays, power operated relief valves (PORVs), safety relief valves (SRVs) and pressurizer heaters. The secondary side flow path begins with a fill junction, boundary condition for the main and auxiliary feedwater flow into the steam generator shell. The steam generator's steam flows through a three volume steam line before entering either the turbine or condenser boundary conditions. The turbine boundary condition is a RETRAN negative fill junction which can be isolated by the turbine stop valve (TSV). The condenser boundary condition, a RETRAN time dependent volume, is normally isolated by a closed turbine bypass valve (TBV) which is actually representing four TBVs in the plant. One volume upstream of these two flow paths represents the steam header which would normally be connected to two main steam lines from their respective steam generators. This volume is isolable by closure of the main steam isolation valve (MSIV) modeled upstream in the RETRAN model. The next volume upstream of the MSIV is connected to four safety relief valve (SRV) flow boundary conditions. They simulate the sixteen SRVs at Calvert Cliffs. In actuality, there are eight SRVs on each main steam line with four different opening pressure setpoints for each pair of SRVs. Thus, each of the four SRVs in this RETRAN model accurately simulate the opening pressure setpoint and flow characteristics of four SRVs at the plant. The last main steam line = _ volume upstream of the SRV volume and downstream of the steam generator is used to provide the actual physical separation of the atmospheric dump valves ($DVs) from the SRVs as well as the flow restrictor at the steam outlet of the steam generator. The RETRAN model ADV flow boundary condition actually represents the two ADVs at Calvert Cliffs. The RETRAN secondary side model includes control systems for steam { generator level, TBV operation controlling pressure, ADV operation i controlling average primary coolant temperature and trips contro!!ing TSV, MSIV and SRV operation. Along with the aforementioned control systems and trips, other transient-specific trips have been incorporated into this model. 4 4 1 e J l 1 - 14 _

FIGURE 3.2-1 a RETRAN ONE LOOP CALVERT CLIFFS MODEL 591 592 To 594 590 593 TURBIN E ADV' ' SRV's 730 J k J LJ L J L J L 705 ysy 524 MSIV l 523 524 W 700 m m v, TSV 4 720 I STEAM 533 198 195 PORV l GENE RATOR AUX. SINK 5 PRAY 720 SRV 1 - 196 501 548 j g 7m MFW SPRAY SRV 2 - 197 l W UA U0 AFW ! II7, m>B j 113 j c^'""',""" l 57] i99 l119 Ill 193 h'9] [0] j 399 u RE ACTOR VESSEL i l 19I gi 3 gj I d-40 [ 125 109 193 l 45 101 ~~" 105 125 105 ) 101 75 27 27!. 127 193 25 23 29 C j u C C 137 C 139 135 13 2 135 137 y, 127 132 RCP l 19 l 129 1 15 15 14 0 142 14 4 146 II / CHARGING = 1 ti 13 i { HP51 i0 3 ,1i

I 3.3 RETRAN Two Loop Model of Calvert Cliffs The RETRAN two loop model of Calvert Cliffs was designed to analyze loop asymmetric transients (i.e., one steam generator and/or associated primary coolant piping responds differently than the other). The two loop model, depicted in Figure 3.3-1, used 71 volumes,111 junctions and 92 heat slabs, and runs slower than real (transient) time on the BG&E IBM 3031 mainframe computer. The two loop model explicitly models each steam generator, main steam line and hot leg at Calvert Cliffs. Two cold legs are modeled, one for each steam generator, each actually representing two cold legs and two RCPs. The number of volumes per hot leg, cold leg, main steam line, steam generator primary side and for the pressurizer are identical to that used in the one-loop model. Increased volume nodalization and detail was incorporated into the reactor vessel and steam generator secondary side for the two loop model. The reactor vessel, made up of 15 volumes, was segmented into a split downcomer, lower plenum, core, and bypass model. Each loop (i.e., hot and cold leg from a common steam generator) is connected to its own downcomer - lower plenum - core - upper plenum chain of volumes. All realistic cross flow and bypass flow paths are included between the two parallel sets of volumes. This split-core reactor vessel is especia!!y important in analyzing i asymmetric loop effects on reactor vessel thermal-hydraulic response. The steam generator secondary side is modeled as a four volume recirculating steam generator with a best estimate recirculation ratio. This model more accurately predicts steam generator performance, but requires considerably greater computer run time and modelling skills for a satisfactory -

i l l steady state and transient calculations. A!! other RETRAN model features (valves, control systems, trips, pump models, etc.) are identical to the one loop model described in Section 3.2. l I i s 1 8 l 1 i f

FIGURE 3.3-1 RETRAN TWO LOOP CALVERT CLIFFS MODEL IUltlNE 730 SifAM GENEIATOR 590,i, 2, 3 I5V 690, i, 2, 3 SifAM GENE t Af08 ,,5Ivi ,5tYs [""""""""***""*"****"""**""*"j II' N' y i 54: III 533 594 94 03I MI F_Olv - lf s @] !'8 sin Gi@

i 5tvi.its 120 Dv iis i

l 5 72.i,7 i-": til i Iis CONIAINMENI 51N K g l l t il7 l h 999 TDV j 20 2i1 l zi n3 in ! Eir]

2n m

-ni 60i i 505 its i DEACIOR YE55tL -as5 :

54 5 *-+

! AulitlAlf III 11i ~ ~

  • ""*"""""""""""**""""*"*""""""*I Ili Ili AUlldAlf !

filDWAftt :

f E EDWAf fs "0

[ j 209 {it],, j i iOf l iti [ 24 40 T i T' 35 44 45 20, 425 225 - 7 25]'125 l j 525 109 193 iti : 1 ' o5 -- : 10 20 205 ao i Q] i 25 27 26 20: 205 loi 10 5 i

........................................=.....:

L-l C*- g it7 3, 227 s u iN 2, C 259C 237 ~~ 135 i37 235 r 22 @ 0 ] v-us ~ nr -"= le 23 ni - ns 232 in/ i, 2e 127 n2 i 2n ni E63 i 129 i40 ist,us,i46 i u a 242, 244,244 240 229 P 3 515 CA G/ j i5 se ~ j CHARGING / 515 m ur==N i i c gig m23 2 i 4 11 is is 12 m i 2 3 4 l I 1 Y i

.................................................'.....2

3.4 RETRAN Four Loop Model of Calvert Cliffs The RETRAN four loop model of Calvert Cliffs, depicted in Figure 3.4-1, explicitly simulates the two hot leg and four cold leg geometry of Calvert Cliffs. This model utilizes 81 volumes,123 junctions and 102 heat slabs, and as expected, is the slowest running model on the BG&E IBM 3081 mainframe computer. This model is only required when individual cold leg /RCP transients need to be analyzed. In some cases, simplification of this model may be warranted to reduce computer run times without 'affecting the accuracy of results. For example, the pump combination flow test simulation discussed in Section 4.3 of this report utilizes a steam generator secondary side energy removal boundary condition in lieu of the five steam generator volumes and three main steam line volumes per loop. All other features for the four loop model are identical to the two loop model described in Section 3.3.

  • o

=. = q i 5 =. R . to 4 o E. 3 i o N 1 o: ~ .~ 3: ~ n g ~ c. 4~ g n i,, : ~ ~ c. e 3 C'a C o a = a: g; 2 ~~ R =: 2 i e. l 3 a ~ ~ 3 i n C, c C. ~ ~- ~ ~

s. e,

.o g g g =. ~ g t 3 i .o ~., ~., r O 9%, q.

a

~

a..,_

~ g ~== -~ ._w o. ( g = ...................... g a o w o L' E g' 'E A .i.C g C* C 2C sC F ~ a[= ~ ~ g = ~ ~ = m g 1 a. J + w a +. z z o ~ o ~ 0 CI 4 ao m R ~ o. .J ~ a o z__ _o - z ~.+o-- .z. ,., -H. - ~ o. i sc _, = c-yw z. ~ A 3.c Mi e] i C C C i o w e = mo .,, = cc o a ."C ['- C .,C C ~ = a o c. 28

V

,T ma o a go =o=< l' ~ cc ,,o,, o o. u n g =-.,- e r-2.c z 2 t s .o ~ ~ z, w m o g ,.o ,~, .o w =. x .g -o- ~, = c w. g. i . =., o e o C C=C e ~ 3i =,..,.-i 0 =, i ~ i C z,. :. ~ _ : a g c c ._ c ~_ i,, . q o g

=

g,, ~ g [O . e. 1 e. WS g l m. c. o,, r A e =.

_

l I E. .W. o i.=* = o ."3..e.s m. a

i 4.0 PLANT TRANSIENT COMPARISONS 4.1 RETRAN 02 Analysis of a Calvert Cliffs Multiple Secondary Side Malfunction Event 4.1.1 Description of Plant Event On October 11,1933 at 11:36:46 (time T), Unit 2 Steam Generator Feedwater Pump (SGFP) No. 22 tripped on low oil pressure caused by a loose lubricating oil connection and oil leakage (11,12,13). The operators began reducing reactor power by inserting control rods and borating while simultaneously reducing turbine power by partially closing the turbine governor valves. These actions were intended to bring reactor power down to a level (70%) that could be supported by one main feedwater pump without tripping the reactor or exceeding technical specification limits. At T + 43 seconds, pressurizer pressure peaked at 2306 psia (159 MPa) due to a reactor power to steam flow mismatch caused by excessive throttling of the turbine governor valves. Subsequently, pressurizer level peaked at 254 inches (6.5 m) at T + 60 seconds. At T + 62 seconds, reactor trip occurred on low steam generator level (-50 inches /-l.3 m) resulting from the power to steam mismatch. At T + 66 seconds, SG 22 secondary pressure peaked at 1030 psia (71 MPa) because the reactor power exceeded steam flow due to the rapidly closing Turbine Stop Valve (TSV) and relatively slower opening TBVs and ADVs. The peak pressure was sufficient to lift some of the main steamline safety valves. Following reactor trip, No. 21 FRV failed to ramp down to its programmed 5% flow position and remained fully open instead. Also, No. 21 SGFP governor valve stuck on high speed stop causing maximum 21 SGFP flow. These feedwater malfunctions caused SG 21 level to reach its maximum measurable value at T + ISO seconds while SG 22 level reached its minimum measurable value at T + 90 seconds. The operators isolated 21 SGFP at T + 340 seconds. Upon reactor trip, the TSV rapidly closed, and the TBVs and ADVs opened. Although programmed to close at 870 psia (60 MPa), one of the TBVs failed to close at that pressure, remaining partially open until it was isolated by the operators at T + 300 seconds. This partially open TBV caused a continued cooldown and depressurization of the primary and secondary coolant systems. The operators later initiated Auxiliary Feedwater (AFW) to SG 22 and isolated AFW to SG 21 while using the Steam Generator Blowdown System (SGBS) to lower SG 21 level. During the transient, a minimum pressurizer pressure of 1659 psia (114.4 MPa) and level of 18.5 inches (0.5 m) were reached at T + 244 and T + 258 seconds, respectively. Primary coolant loop 21 cold leg temperature dropped to a minimum value of 509 F (538 K) at T + 233 seconds representing a 49 F (27 K) drop in 184 seconds. Safety injection Actuation Signal (SIAS) on 1725 psia (119 MPa) occurred at T + 175 seconds, but no High Pressure Safety Injection (HPSI) pump flow occurred because HPSI shutoff head is 1275 psia (88 MPa). After isolacing 21 SGFP and the stuck open TBV, the operators restored normal pressurizer pressure and level, primary coolant system temperatures, and steam generator levels. In summary, the October 11, 1983 event at Calvert Cliffs Unit 2 was initiated by the loss of one main feedwater pump which was later compounded by failures in the other feedwater pump. This condition caused the overfill of one steam generator and the underfill of the other steam generator following 1 a reactor trip on low steam generator level. This asymmetric cooldown-depressurization transient was further exacerbated by one turbine bypass valve failing to close. 4.1.2 Event Specific RETRAN Modeling Changes The BG&E RETRAN model of Calvert Cliffs used for this analysis is the two loop model depicted in Figure 3.3-1. Several model refinements were added for this analysis. A stack of three heat conductors were incorporated ,into the pressurizer to account for heat transfer between the vapor-liquid volumes and the metal walls which has been shown to be important (14,15). The spray line volume fluid was initialized at its actual measured temperature which is about 7 F (4 K) less than the cold leg temperature due to ambient heat losses from this relatively stagnant pipe (16). A realistic time delay of two minutes was added to the pressurizer heater model to account for the thermal time lag constant of these electrical heating elements (17). Other model changes were made to simulate plant initial conditions and the transient specific malfunctions and operator actions. RETRAN simulation of this event used measured main feedwater flow to each steam generator and core thermal power as temporal boundary conditions. The purpose of this analysis was to analyze the NSSS primary and secondary thermal-hydraulic response to these boundary conditions,along with other systems actuating (e.g., TBV, pressurizer spray, etc.). The core thermal power and main feedwater flow boundary conditions are presented in Figures 4.1-1 and 4.1-2. The TSV closing and TBV-ADV opening times were inferred from reactor trip time (plant data on reactor power and steam generator level). At steam pressures below 870 psia (60 MPa) and until T + 300 seconds, the TBV flow area was modeled as one half of the area of one TBV. As previously di'scussed, operators reduced reactor power and turbine power to match the 70% feedwater flow available and avoid a reactor trip. Based on measured l f plant data on the first stage turbine pressure reduction prior to trip and turbine manufacturer's performance data (IS), a reduction to 34% of full I power turbine steam flow was used in this analysis. Auxiliary feesfwater (AFW) simulation was accomplished by a!!owing AFW initiation on the low-low SG level of -170 inches (-4'.3 m), but only allowing AFW flow to SG 22. 4.1.3 Comparison of RETRAN Results to Plant Data A comparison of RETRAN results with measured plant data during the 360 second period after 22 SGFP trip for six key parameters is presented in Figures 4.1-3 to 4.1-3. RETRAN pressurizer pressure peaks at about the same time but to a somewhat higher value as shown in Figure 4.1-3. The subsequent drop in pressure due, at first, to reactor trip and later, to the open TBV compares well with the exception that RETRAN minimum pressure is again somewhat higher than the plant data. The pressurizer level comparison in Figure 4.103 shows RETRAN peaking at about the same time, but not as high as plant data. The drop in level compares well with RETRAN level higher than plant measured level. One would expect the overprediction in peak pressure to be accompanied by an underprediction in peak level. The Loop 21 hot and cold leg temperature comparisons in Figures 4.1-5 and 4.1-6 show excellent agreement Uurk i the first 160 seconds of the transient analysis. This agreemig suks tiates the selection of reduced turbine steam flow prior to reactor trip since the rise in these temperatures.

is due to this pre-trip power-steam flow mismatch. A good overall agreement exists after 160 seconds. Possibly higher run-out AFW pump flow rates and lower post-trip MFW temperatures could cause the more rapid cooldown af ter 160 seconds in plant data. The difference between RETRAN and plant data in this later period is the reason for RETRAN having higher minimum pressurizer pressure and level in Figures 4.1-3 and 4.1-4 which are due primarily to the lower temperature coolant density change. Figures 4.1-7 and 4.1-8 show comparisons of steam generator secondary side pressure and narrow range level. Steam generator pressure response was identical for both generators with the exception that their pressures differ by their initial values throughout the transient, thus only SG 22 is shown in Figure 4.1-7. RETRAN predicts a peak pressure very close to plant data both in magnitude and time with a good agreement in the post-trip depressurization phase of the transient. Differences in the comparison of SG pressure are attributed to the exact timing of TSV closing, TBV/ADV opening and the subsequent characteristics of the one TBV that failed to close at 370 psia (60 MPa). The plant data in Figure 4.1-7 indicates that the stuck-open TBV did not simply maintain a half open position until isolated by the operators at 300 seconds, but rather varied its position. Also, the RETRAN model does not account for miscellaneous steam loads (e.g., MFW pump and AFW pump turbine). This can account for 1% of full power steam flow or 10% of a single TBV's flow. The difference in SG pressure response accounts for differences in primary coolant system cooldown after 160 seconds. Figure 4.1-8 shows close agreement between RETRAN and plant data for SG narrow range level. RETRAN results indicate similar timing for SG 22 underfill and SG 21 overfill as well as showing the effect of later AFW to SG 22 and the subsequent rising level. 1 1 i

RETRAN calculated hot and cold leg temperatures for the two loops demonstrate the asymmetry of this cooldown transient. The two legs differ by 3 F (1.7 K) for the hot leg and 3 F (4.4 K) for the cold leg. Data for the other loop was not available from the plant computer for this event. I Table 4.1-1 shows a comparison of sequence of event timing between plant data and RETRAN. RETRAN calculated timing agrees closely with plant data. Table 4.1-2 compares key thermal-hydraulic parameters which also show good agreement between RETRAN and plant data. The comparisons in Table 4.1-2 should be evaluated in the context of the accuracy of measured plant data (19) presented in Table 4.1-3. RETRAN calculated values fall within the measured plant data tolerances for peak pressurizer pressure, steam generator pressure and loop 21 peak hot and cold leg A temperatures. Values are reasonably close for peak pressurizer level, minimum pressurizer pressure and minimum loop 21 cold leg temperature. The differences in minimum pressurizer level and minimum loop 21 hot leg temperature are significant. These parameters occur about 4-5 minutes into the transient and are a direct result of the stuck-open TBV-induced cooldown. As previously mentioned, the RETRAN simulation assumed this TBV at half its normally open area until isolation whereas a time varying flow area most probably existed. i 4.1.4 RETRAN Model Sensitivity Study A sensitivity study was performed with the RETRAN pressurizer model to evaluate the effects of model changes on calculated peak pressure and level during the insurge portion of the transient. The RETRAN pressurizer sensitivity study for this event evaluated the effects of the following ,.n .,,,.,-..--,m-,..--..,_n-.--._-nea, n-w --- - - -- ,n.


w-n,

---<--g - - ~ < - ~, n m --, - - - -,m., -a.,w-

features: spray junction model, rainout velocity, interface heat transfer coefficient, heat conductors, initial spray line temperature, and number of pressurizer volume nodes. Based on this sensitivity study, the following conclusions are made regarding RETRAN pressurizer modeling for rapid insurge transients (0.8 inches /sec or 2.0 cm/sec): 1. Spray junction model, rainout velocity, and presence or noding of heat conductors have no significant effect on peak pressurizer pressure ( l psi or.07 MPa) or level. 2. Best estimate initial spray line fluid temperature will slightly reduce (2 psi or.14 MPa) peak pressurizer pressure. 3. Two node pressurizer results in slightly higher peak pressure (3.4 psi or .23 MPa) and higher peak level (5.2 inche's or.13 m). 4. Large values of surge line loss factor significantly reduce peak pressure (28 psi or 1.90 MPa for a tenfold increase). 5. Large values of interface heat transfer coefficient (!HTC) (10,000 to 2 2 50,000 Btu /Hr-Ft -F or 56,780 to 283,900 W/M -K) significantly reduces peak pressure (26-56 psi or 1.8-3.8 MPa) and increases peak level. Such values of this parameter also reduce the time of peak pressure and level. The final RETRAN pressurizer model used for this analysis utilized best l i estimate initial spray line fluid temperature, " spray" junction option, a stack of three vertical heat conductors each segmented into 100 equal width nodes, single volume node, and an interface heat transfer coefficient of 32,400 2 2 Btu /Hr-Ft -F (183,967 W/M -K) based on recommendations for the TOPS code (20). This very large value of IHTC, although not realistic, accounts for steam condensation which is not adequately modeled in RETRAN. The greater condensation causes lower peak pressure, higher level and moves both. _ _

of these peaks back to an earlier time which more closely corresponds to plant measured data. Even with the high IHTC, RETRAN predicts about 72% of the pressurizer level swell from plant data. This points to the calculation of less steam condensation than actually occurred. Investigation of spray effectiveness with RETRAN involved a case in which the spray was deactivated. This resulted in a peak pressurizer pressure of 2411 psia (166.3 MPa) which was limited by PORY opening at 2400 psia (165.5 MPa). This spray effectiveness of 73 psia (5 MPa) in 33 seconds is within the range set by CE and confirmed during Calvert Cliffs startup tests (21). The actual spray flow rate is not tested but has been shown to be as much as twice the design flow in some CE plants. A RETRAN case with twice design rated spray flow resulted in a peak pressurizer of 2300 psia. Another RETRAN case was run in which the spray was set to open to its fully rated flow at 2300 psia (158.6 MPa) rather than its programmed flow characteristic of opening at this pressure, but not reaching fully rated flow until 2350 psia (162 MPa). This case resulted in a peak pressure of 2314 psia (159.6 MPa) and a peak level of 246.3 in. (6.3 m). The performance of spray valves is not tested to ensure the linear flow increase between 2300 psia (158.6 MPa) and 2350 psia (162 MPa) that is assumed in the RETRAN model. One process which may not be adequately simulated is the condensation of insurge induced superheated st,eam in the vapor space *onto the pressurizer metal walls. These wa!!s are modeled with RETRAN in fine heat conductor nodes ( .05 in. or.0014 m thick). The surface heat transfer coefficient is internally calculated by RETRAN using a range of available correlations. During the insurge, RETRAN selected the Collier correlation (22, 23) which 2 resulted in a heat transfer coefficient on the order of 300-400 Btu /Hr-Ft,p -

2 (1703 to 2271 W/M -K). Steam condensation experimental data indicates 2 2 values of 700-2500 Btu /Hr-Ft -F (3975 to 14195 W/M -K) (24, 25,26). Saedi and Kim (14,15) have shown that heat conduction to the pressurizer walls substantially reduces pressure during insurge transient. Calculations of the possible condensation effect of the ambient heat loss and balancing continuous spray show that they would only account for less than 1% of the difference between RETRAN peak level and plant data. Finally, the presence and amount of non-condensible gases in the ' pressurizer vapor and liquid space were investigated. For oxygen scavenging. purposes, a concentration of 25-50 cc hydrogen per Kg of primary coolant water is maintained. This along with smaller quantities of other dissolved gases corresponds to less than 1% mass fraction in the vapor space (27). The effect of this concentration of non-condensible gases in the pressurizer vapor space has been shown to be insignificant by Leonard (28). 4.1.5 Summary of Results BG&E performed a RETRAN analysis of the asymmetric cooldown transient which occurred at Calvert Cliffs Unit 2 on October 11, 1983. Comparisons with measured plant data for pressurizer pressure and level, hot and cold leg temperature, and steam generator secondary side pressure and level all showed excellent agreement in both peak values and overall trends. The uncertainty in stue.k open TBV position affected the RETRAN simulation of the later phase of the cooldown. A sensitivity study was performed to evaluate RETRAN pressurizer models for rapid pressurizer insurge transients (0.8 inches /sec or 2.0 cm/sec). This study indicated that large interface heat transfer coefficients._ - _.-.

l i i 1 or large values of surge line loss factor significantly reduce the magnitude and time of peak pressurizer pressure and increase peak level. Spray junction model, rainout velocity, presence and noding of heat conductors, realistic initial spray line fluid temperature, and a two node model of the pressurizer had a small or insignificant effect on pressure and level for this type of transient. The RETRAN models for pressurizer spray heat transfer are a reasonable representation. The condensation heat transfer coefficients calculated by RETRAN for heat transfer from the vapor space to the walls appear to be low. The inability of RETRAN to model a steady state in which continuous spray flow and heater operation exist does not significantly affect its transient simulation capability. Results of the pressurizer spray sensitivity analysis in Section 6.0 indicate that actual plant spray flow at 2300 psia (153.6 MPa) is greater than that assumed in the RETRAN model. The actual plant continuous spray flow is seventeen times larger than the value reported in the FSAR (29). This larger initial spray valve open area would result in full spray flow delivery at a lower pressure than the programmed 2350 psia (162 MPa). It should be noted that there are no tests performed to confirm spray flow vs pressurizer pressure. This higher spray flow at 2300 psia (158.6 MPa) would reduce RETRAN calculated peak pressurizer pressure and increase peak Imet to more closely agree with plant data.

l Table 4.1-1 October 11,1983 Calvert Cliffs 2 Event Timing Comparison Time, seconds (normalized to 11:36:46) Event Plant Data RETRAN SGFP 22 Trip 0 0 Peak Pressurizer Pressure 48 53 Peak Pressurizer Level 60 66 Reactor Trip on Low SG Level 62 62 Peak Loop 21 T-Hot 64 64 Peak SG 22 Pressure 66 69 Peak Loop 21 T-Cold 70 70 SG 22 at Minimum Level 90 116 SIAS 175 191 SG 21 at Maximum Level 180 206 Minimum Pressurizer Pressure 244-256 261 Minimum Pressurizer Level 258 261 Open TBV isolated 300 310 SGFP 21 Isolated 340 340 Table 4.1-2 Tolerance of Calvert Cliffs Plant Computer Data Pressurizer Pressure 2 1 0% Pressurizer Level 1 5% 2 l Hot / Cold Leg i.5 F 2 Core Thermal Power 1 0% 3 Steam Generator Level 2 1 0% Steam Generator Pressure t.5% 2 Main Feedwater Flow 1 0% 2 Table 4.1-3 Comparison of Key Event Parameters Plant Data RETRAN Peak Pressurizer Pressure 2306 psia /159 MPa 2333 psia /161 MPa Peak Pressurizer Level 254 In./6.5 M 244.4 in./6.2 M Peak Loop 21 T-Hot 597.1 F/586.9 K 597.5 F/587.2 K Peak Loop 21 T-Cold 558.7 F/566.0 K 561 F/366.9 K l Peak SG 22 Pressure 1030 psla/71 MPa 1034 psia /71.3 MPa Minimum Pressure 1659 psia /Il4.4 MPa 1717 psla/Il8.4 MPa Minimum Level 18.5 in./0.47 M 61.2 in./1.55 M Minimum Loop 21 T-Hot 513.7 F/540.6 K 526.2 F/347.6 K Minimum Loop 21 T-Cold 509.5 F/538.6 K 513.6 F/540.6 K - _ _ _._

FIGURE 4.1-1 OCTOBER 11, 1983 EVENT CORE TilERMAL POWER RESPONSE 150 4 up W 100 O LLJ o e o-W LU u ~ O v 50 ID 0 4 0 0 10 0 200 300 360 TIME (SECONDS)

FIGURE 4.1-2 OCTOBER 11, 1983 EVENT MAIN FEEDWATER FLOW RESPONSE 758 6000 -\\. A ( l \\ -- SG 21 \\ i SG 22 J) \\ .N T 4000 - k, 505 e' \\. \\. x i M 1 C i o e

  • I E

3 SG 22 iSG 21 \\ w 2E 2000 - 253 \\. \\N. ~.-. I 0 0 0 100 200 300 360 TIME (SECONP3)

FIGURE 4.1-3 OCTOBER 11, 1983 EVENT PRESSUREZER PRESSURE RESPONSE 160 2300 - .e-T. ~ { RETRAN PLANT DATA <C \\ 150 m CL. - - = m= D g 140 g 2000 -\\ a. a-6 m a N_ \\ = \\ 130 m \\ G \\ m x N. N. N mn s ILu '\\. i N --.-. /. / '. p ' N-11 0 1600 0 100 200 300 360 1 1 TIME (SECONDS) l 1

FIGURE 4.1-4 OCTOBER 11, 1983 EVENT PRESSURIZER LEVEL RESPONSE 300 i i i i i i i i i 7 RETRAN P. PLANT DATA / 6 5 .j \\ =y 200 5 A 2' \\. m 3 1 4 = x \\ t 1 M m 3 i = Dm0 100 M w.N. 2 'N. 0 0 0 100 200 300 360 TIME (SECONDS) l

FIGURE 4.1-5 OCTOBER 11, 1983 EVENT LOOP 21 IIOT LEG TEMPERATURE RESPONSE 650 i RETRAN - - PLANT DATA 600 mm 600 589 = l O I- ^ e x i .mm O 5 O9 550 561 m 'N, N. N'x. ~~ l l o 533 l 0 100 200 300 360 l TIME (SECONDS)

FIGURE 4.1-6 OCTOBER 11, 1983 EVENT LOOP 21 COLD LEG TEMPERATURE RESPONSE 630 600 RETRAN PLANT DATA 600 C L o a h T 2 ~ 550 '\\ - 561 ' s m -\\ i mo o N a ~. N. N ' ' N ----. - - . 7 500 i 4 i 522 1 0 100 200 300 360 TIME (SECONDS)

FIGURE 4.1-7 OCTOBER 11, 1983 EVENT STEAM GENERATOR 22 SECONDARY SIDE PRESSURE RESPONSE 72 1050 + RETRAN 1000 PLANT DATA \\ / \\ s 950 / \\ \\ E ./ = 5 900 ./ 62 E =E m f

  1. N-N/

N. w g \\. i g 850 \\. i \\ - 800 N. N. i 750 52 0 100 200 300 360 TIME (SECONDS)

FIGURE 4.1-8 OCTOBER 11, 1983 EVENT STEAM GENERATOR NARROW RANGE LEVEL RESPONSE RETRAN -- PLANT DATA t 80 2 c -/ m I y 40 SG 21 SG 21 / s a i m ~ / e 0 / 0 m M -\\\\ ./ g -40 - %g -/ -1 E 7 o / m \\. -2 -80 SG 22\\. SG 22 r .\\. s x. ~>~ -2.92 0 10 0 200 300 360 TIME (SECONDS)

4.2 Calvert Cliffs Unit 1 Startup Test - Four Pump Coastdown From 20% Power .2.1 Description of Event 4 This startup test was used to obtain reactor coolant system (RCS) flow data during a four pump coastdown at 20% of full power (30). The transient was initiated using the trip pushbuttons on the reactor protective system panels. Measurements were made of the total RCS flow for the first 55 seconds after reactor trip. 1 4.2.2 Event Specific RETRAN Modeling Changes d Both the one loop and four loop RETRAN models described in Sections 4 3.2 and 3.4 were used to simulate this four pump coastdown transient. The RETRAN model was initialized at 20% of 2560 MWt and with key thermal-hydraulic parameters at the measured plant values delineated in Table 4.2-1. l These key parameters are: hot and cold leg temperature, pressurizer pressure and level, steam generator pressure and level. J 4.2.3 Comparison of RETRAN Results to Plant Data 1 Figure 4.2-1 presents a comparison of RETRAN calculated total RCS j flow with measured plant data. Both the one loop and four loop RETRAN model predicted flow coastdown closely following the measured plant data for 4 the first 55 seconds af ter RCP trip. RETRAN calculated flow was within about 3% of measured flow for the first 35 seconds of the transient. This I comparison is considered to be exce!!ent because the flow measurement i ..,. _,..., _.,,.. ~. _ _. _. - _ - _ _. _ _ _ _ _ _ _ _. _ - _ _ _ _ _. __ _,.__ __ _ ____._ _ _,__.,_ ~..,, m __ _ _ _ _. _ _. - -,..... _.,, -.

i I 1 accuracy is 2% and a time lag of up to 1.5 seconds is associated with this parameter. l Table 4.2-2 presents a comparison of RETRAN one loop model and four loop model with Calvert Cliffs measured total RCS flow for this transient. L Although both RETRAN models calculate a similar flow coastdown, the four loop model calculated flow is closer to measured flow. This closer agreement is attributed to the finer nodalization and more accurate representation of RCS flow paths, pressure loss and temporal effects inherent in the four loop model. This table also presents data from the CESEC Topical Report (31). j CESEC is the Combustion Engineering (CE) system transient thermal-hydraulir. code which CE uses for reload safety analysis licensing calculations and has been reviewed and approved by the USNRC. As part of the CESEC qualification, a comparison with measured four pump coastdown at hot zero power is presented in the CESEC topical report. The plant data and CESEC results are also presented in Table 4.2-2. The measured flow data is not identical to the Calvert Cliffs flow coastdown because it was taken from another CE plant which would be expected to have,somewhat different characteristics (i.e., impeller trim,.RCP motor performance, loop pressure drop, etc.) Also, this test was run at hot zero power which imp!!es a slightly lower RCS temperature and higher fluid density which affects the flow coastdown. However, the relevant conclusion from this CESEC-plant data comparison is that CESEC predicts flow to within the same 3% as RETRAN does for the Calvert Cliffs data. This substantiates the acceptability of the RETRAN calculation of four pump coastdown when compared to measured plant data. l

4.2.4 Summary of Results i i A calculation of four RCP coastdown was performed with the one loop and four loop RETRAN models. Both models predicted a flow coastdown similar to plant data, but the four loop model resulted in a closer comparison. Both models calculated four pump coastdowns within instrumentation uncertainty and other comparisons performed by the CE CESEC licensing computer code. i I { i r a e i f i i f i 1 , 4 ~,-- o---, a,- e-,me.--- --,--~.r--e ,-a, ,..--.-r-,,,,r--., ,....,-,,,..,n,-.r- ..-.wn m-,,y ,--,m--, -,r,--,y---,-w

r-Table 4.2-1 Four Pump Coastdown from 20% Power Initial Conditions Power 512 MWt (20% of 2560 MWt) Pressurizer Pressure 2242 psia Pressurizer Level 150 inches Hot Leg Temperature 544 F Cold Leg Temperature 534 F Steam Generator Pressure 855 psig Steam Generator Level 0 inch Narrow Range

2 Table 4.2-2 Comparison of RETRAN One Loop and Four Loop Model Calculated Four Pump Coastdown Total RCS Flow with Plant Data Fraction of Total RCS Flow RETRAN CESEC (Hot Zero Power) Time After Measured One Loop Four Loop Data CESEC RCP Trip (sec) Model Model 0 1.00 1.00 1.00 1.00 1.00 5 0.64 0.646 0.617 .65 .66 10 0.46 0.472 0.448 .50 .49 15 0.34 0.371 d.353 .39 .36 J 25 0.23 0.260 0.243 .28 .26 1 35 0.175 0.201 0.189 .21 .20 45 0.125 0.164 0.155 .16 .16 55 0.02 0.140 0.132 .13 .13 l l i il I l l L.

FIGURE 4.2-1 FOUR PUMP COASTDOWN TOTAL REACTOR COOLANT SYSTEM FLOW RESPONSE 100 PL ANT DATA RETRAN ONE ~ ~ ~ ~ LOOP MODEL 80 RETRAN FOUR LOOP MODEL 70 60 3: 50 l 0 d \\ \\ 40 \\\\ 30 .33...s .. N...s ...s. N. ~. ... D.::,' 20 ' D..t.:::. :.,,,,,_ C 10 0 O 10 20 30 40 50 TIME (Seconds) - 45A -

4.3 Calvert Cliffs Unit 1 Startup Test Reactor Coolant Pum p Operation Combination Flow Tests at Hot Zero Power 4.3.1 Description of Plant Event A series of fif teen Reactor Coolant System (RCS) flow tests were conducted to determine total and individual Reactor Coolant Pump (RCP) flow rates with all possible combinations of RCPs running (30). The tests were conducted with the reactor at hot standby (i.e., zero core power but RCS at 2250 psia and 532 F). The results of these tests were measured RCS flow at each of the four RCPs and total RCS flow. The fifteen RCS flow combination tests consisted of: one test with all four RCPs running, four tests with three different RCPs running, six tests with two different RCPs running (two of which were RCPs in the same loop; the remaining four being RCPs in opposite loops), and four tests with one RCP running. The measured plant data for each test, normalized to average RCP flow for four RCPs running, is presented in Table 4.3-1. 4.3.2 Event Specific RETRAN Modeling Changes The RETRAN four loop model described in Section 3.4 was used for this analysis. Since the tests were conducted at hot standby, the steam generator secondary side and associated steam line volumes and junctions were replaced by a non-conducting heat exchanger which removed the nominal 10 Mwt core power. This small, but non-zero power was required to allow the use of the existing four loop primary side model without further modifications and has no effect on the results of this analysis. ____

During early RETRAN calculations of pump flow combinations, analysis of RETRAN results showed a deficiency in accurately mode!!!ng the flow paths from operating RCPs through shut down RCP loops. With one or more RCPs shut down some flow from operating RCPs will short circuit the core. This bypass flows circumferentially around the downcomer and out the cold leg nozzle (s) in the reverse direction throuEh the shut down RCP(s) to the steam generator outlet plenum. The initial four loop RETRAN model was modified by adding a downcomer cross flow junction between the two identical downcomer volumes. Prior to this change, flow from one loop cold leg to the other loop cold let must first traverse the entire downcomer and then cross over to the other loop's lower plenum volume. The addition of this downcomer cross flow junction more accurately modelled the actual flow path available for reduced RCP operation configurations. Another important RETRAN modelling change was the input of an explicit locked rotor reverse flow pressure loss coefficient. The RCPs at Calvert Cliffs are equipped with an " anti-reverse" rotation device on the motor that prevents reverse rotation of the impeller af ter pump shut down. Thus, after coastdown, the rotor will remain stationery and not rotate in the reverse direction even under the force of coolant flowing backwards. Calvert Cliffs RCP-specific locked rotor reverse flow pressure loss coefficients were obtained from the NSSS vendor, Combustion Engineering (32). This locked rotor reverse flow coefficient is, as expected, much larger than the loss coefficient previously used by RETRAN which was based solely on normal flow friction losses. 4.3.3 Comparison of RETRAN Results to Plant Data RETRAN calculated results are compa' red to measured plant data for RCP operation combinations in Table 4.3-2. Five combinations of RCP operation are listed (4,3,2 same loop,2 opposite loop, and 1 RCP) along with their corresponding cases from Table 4.4-1. A mean flow and associated standard deviation (also in terms of percent difference) is listed for each RCP flow path. Along with each measured normalized flow, the RETRAN calculated flows for these cases are listed with their respective deviation from plant data. The standard deviation was calculated assuming a normal distribution of plant data. For a normal distribution, the mean value can be adjusted to encompass most of the data distribution by including one or more standard deviations as delineated below: Number of Standard Deviations Normal Distribution Data Inclusion +1 63 % 22 95.5% 23 99.7% The 3.2% standard deviation in RCP flow for four pumps running demonstrates the variation of individual pump flow characteristics and individual pipe loop hydraulic resistance. RETRAN pump and piping models are input with identical parameters for all four cold legs and thus show no flow asymmetry. The case with 3 RCPs running resulted in 130.4% of normal RCP flow in the operating RCP on the loop with one RCP shut down. The shut down RCP l l reverse flow is 36.9% of normal operating flow. The loop with two operating RCPs had 105.6% of normal flow in each cold leg. The three RETRAN cases, l (initial four loop model, downcomer crossflow junction added, and realistic l l operating RCP locked rotor reversed flow loss factor) are compared to the three RCP case plant data. The final RETRAN model (includes downcomer crossflow and realistic RCP reverse flow loss factor) predicts individual and total RCP flows within two standard deviations of measured plant flow. In a similar manner, two RCP and one RCP cases are presented and compared in Table 4.3-2. For almost all the RCP total flow comparisons, RETRAN calculated values are within two standard deviations of the measured plant data. The two exceptions are total RCS flow for two RCPs on in opposite loop and reverse flow for two RCPs on in the same loop. RETRAN predicted total RCS flow for two RCPs on in the same loops differs by 15.1% from mean measured plant data which has a 5.7% standard deviation. This RETRAN flow is within three standard deviations. This difference is not considered excessive in light of the relatively large standard deviation of measured data and the fact that only two cases were run for this data. In the comparison of total RCS flow for two RCPs running in opposite loops, plant measured data compilation showed only a 0.3% standard deviation whereas RETRAN calculated flow differs by 4.1%. Although, this number exceeds three standard deviations, its magnitude is well within the difference for other flow data point comparisons. Figure 4.3-1 illustrates the normal and abnormal primary coolant system flow paths for Calvert Cliffs. Three abnormal flow paths were evident from the RETRAN analyses of less than four RCP operating configurations. These abnormal flow paths are: 1. Crossflow between the two downcomer volumes which receive cold leg flow from separate loops. 2. Crossflow in the steam generator outlet plenum between the two RCP suction cold leg pipe lines. 3. Backflow through the RCP, steam generator tubes, and hot leg to the reactor vessel. Table 4.3-3 presents operating pump cases where these abnormal flow paths exist. Downcomer crossflow occurs for those pump combinations (one RCP on, two RCPs in the same loop on, or three RCPs on) where both loops do not have the same number of pumps operating thus creating a pressure differential between the two downcomer volumes. Reverse flow through cold legs, steam generator tubes and hot leg back to the reactor vessel occurs when neither pump on one loop is operating. This provides a second hydraulic loop for the operating pump (s). Steam generator outlet plenum crossflow exists when only one RCP in a loop is operating thus forcing reverse flow through that loop's other cold leg and back to the operating RCP's suction side. l 4.3.4 RETRAN Sensitivity Study The RETRAN sensitivity study performed for this analysis involved the variations of downcomer crossflow and RCP reverse flow loss coefficients as well as evaluating the importance of including downcomer crossflow and a realistic RCP reverse flow loss coefficient. As shown in Table 4.3-2, inclusion of a downcomer crossflow junction significantly affected the flow split and total flow for asymmetric RCP operating configurations (i.e., all cases but four RCP and two RCP in opposite 1 I > ,.m_.- _..,,,.. .__...._,.~--,_,,,c

,_.-._.__________..__.m m 1 loops). The downcomer crossflow junction generally increased back flow l through shut down RCPs and reduced total RCS tiow. It was also found that { 1 varying the downcomer flow loss coefficient over the range of.02 to 13.2 5 changed flows by less than 1%. This insensitivity to downcomer crossflow t j factor is due to the large flow area of this junction which resulted in low fluid velocities. 5 In Table 4.3-2, a realistic RCP reverse flow loss coefficient resulted in i i reduced reverse flow through stopped RCPs. Inclusion of this realistic higher loss coefficient dramatically reduced the difference between RETRAN j predicted back flow and plant data. The back flow difference dropped from: 19% to 1.9% for three RCPs on,32% to 15.5% for two RCPs on in the same i loop, 28.5% to 1.6% for two RCP on in opposite loops, and 39.6% to 3.2%/34.2% to 10.1% for one RCP on. The realistic RCP locked rotor reverse flow loss coefficient provided by CE was actually a range of values which varied by about 14% for RCPs. Using values at both ends of this range resulted in generally small (less chan 1%) changes in RCP flow. t l j 4.3.5 Summary of Results I A RETRAN simulation of combination of operating reactor coolant pumps (RCP) was performed to ccmpare to measured plant individual RCP flow and total reactor coolant system (RCS) flow. Tests with four, three, two same loop, two opposite loop, and one operating RCP were conducted at f Calvert Cliffs. The measured test individual RCP and total RCS flow data was used to calculate a mean and standard deviation for each flow path. A RETRAN four loop model of Calvert Cliffs was used to evaluate operating pump combination flow distribution. This model was modified by.

l adding a downcomer crossflow junction and accurate locked rotor reverse I i flow pressure loss coefficient which greatly improved RETRAN results as compared to plant data. RETRAN calculated flows were within two standard deviations (95.5% of data) of measured plant flows for 12 of the 14 flow paths r j in the four pump operation combinations. One of the remaining two flows differed by only 4.1%. The other flow that differed by more than two standard deviations was for a test in which only two data points were available with an inherent reduction in statistical significance. The absolute magnitude of the standard deviation for this particular flow was also much larger than for most of the other flow data. RETRAN predicted flow splits and total RCS flow was generally within about 4% of mean measured flow. Considering the fact that the standard deviation on individual RCP flow for the normal four pump configuration was 3.2%, this deviation is acceptable for reduced RCP operation conditions. Along with the aforementioned RETRAN model enhancement, this analysis provided insights into the three abnormal RCS flow paths which occur when one or more RCPs are shutdown. These flow paths are: downcomer crossflow, steam generator outlet plenum cross flow and complete reverse flow through an RCS loop..

-- - = l Table 4.3-1 Reactor Coolant Pump Combination Flow Test Data at Hot Standby + RCP Relative Flow Relative Total Case RCPs*** Running IIA !!B 12A 12B RCS Flow 't 1 1 II A, llB,12A,12B** .960 .987 1.030 1.022 1.000 j 2 11A,11B,12A 1.103 1.049 1.338 .376 0.756 3 3 IIA,llB,12B 1.019 1.041 .368 1.319 0.753 4 11A,12A,12B 1.278 .368 1.087 1.078 0.768 5 llB,12A,12B .363 1.282 1.087 1.070 0.769 6 11A,11B 1.060 1.090 .166 .151 0.459 7 12A,12B .151 .168 1.123 1.112 0.479 8 IIA,12A 1.320 .310 1.386 .324 0.518 9 IIA,12B 1.338 .312 .305 1.368 0.521 10 llB,12A .336 1.336 1.395 .330 0.516 11 11B,12B .327 1.323 .310 1.359 0.511 12 IIA 1.356 .275 .069 .067 0.236 13 IIB .292 1.359 .074 .057 0.234 14 12A .087 .099 1.427 .294 0.237 15 12B .087 .089 .276 1.392 0.235 RCS Temperature and pressure of 532 F and 2250 psia Flow is normalized to 25% of total flow for four RCPs running (Case 1)

      • RCPs ll A and llB are both on Loop 11 while RCPs 12A and 12B are both on Loop 12 -. __

O Table 4.3-2 Comparison of Measured Plant Data with RETRAN Calculated RCP Flow Split for RCP Operating Combinations

  • PLANT DATA RETRAN CALCULATED RESULTS Flow (% Difference from plant data)

Number of Cases From Downcomer Crossflow and RCPs Running Table 4.3-1 Mean Flow Standard Deviation Downcomer RCP Junction Reverse (% difference) Initial Model Crossflow Junction Flow Realistic Loss Factor 4 1 1.000 .032 (3.2) 1.000 1.000 1.000 3 2,3,4,5 1.304 .029 (2.2) 1.400 (7.4) 1.381 (5.9) 1.362 (4.4) .396 .005 (1.4) .439 (19) .466 (26.3) .362 (1.9) 1.056 .030 (2.8) 1.026 (2.8) 1.053 (0.3) 1.049 (0.7) Total RCS Flow .761 .008 (1.1) .753 (1.1) .756 (0.7) .775 (1.8) 2 6,7 (same 1.096 .028 (2.6) 1.048 (4.4) 1.095 (0.l) 1.090 (0.5) loop) .159 .009 (5.7) .108 (32) .173 (8.8) .135 (15.1) i Total RCS Flow .469 .014 (3.0) .470 (0.2) .461 (1.7) .477 (1.7) 2 8,9,10,11 1.353 .029 (2.1) 1.418 (4.8) 1.418 (4.8) 1.401 (3.5) (opposite loops) .319 .011 (3.4) .410 (28.5) .410 (28.5) .324 (1.6) Total RCS Flow .517 .004 (0.8) .504 (2.5) .504 (2.5) .538 (4.1) 1 12,13,14,15 1.384 .033 (2.4) 1.429 (3.3) 1.441 (4.1) 1.427 (3.1) .284 .010 (3.5) .396 (39.4) .371 (30.6) .293 (3.2) .079 .014 (17.7) .052 (34.2) .084 (6.3) .071 (10.l) Total RCS Flow .236 .001 (0.4) .234 (0.8) .225 (4.7) .248 (5.1)

  • Instrumentation Accuracy 12%

2

Table 4.3-3 Reduced Reactor Coolant Pump Operation Abnormal Flow Paths Number of Significant Outlet Plenum Operating Downcomer Crossflow Tube Side Reactor Crossflow (cold leg to Reverse Coolant Pumps Between Loops cold leg flow) Flow I YES YES YES 2 (same loop) YES NO YES 2 (opposite NO YES NO loop) i 3 YES YES NO 4 NO NO NO

Fig u r e 4. 3 - 1 CALV ERT CLIFFS PRIMARY COOLANT SYSTEM FLOW PATHS NORMAL FOUR RCP OPER ATION SG SG u HOT L EG y HOT LEG p p E UM TUBES TUBES h D 0 ON ON Y y g Q C SG 'V C R C V SG PLENUM O E O PLENUM ' RCP M M V' RC 'V E E ON R R ON I 4 4 1 3RCP O P E R ATION HOT LEG UPPER HOT LEG TUBES TUB ES h D D 0 0 o PLENUM O O PLENUM ON R R OFF l h k 2 RCPS ON S AME LOOP SG SG [ HOT L EG HOT L EG p TUBES TU B E S h O O G SG PLENUM O E O PLENUM 'V M M ' RC ' RCP E E ' V ON R R O FF ABNOR M AL FLOW PATH ~ ~

l Figure 4.3-1 ( Cont'd.) 2 RCPS ON OPPOSITE LOOP SG SG HOT LEG HOT LEG P ENUM TUBES TUBES h D D 0 0 OFF OFF A G S PLENUM O E O PLENUM RCP M M V' E E RCP - >V ON R R ON I 4 4 I IRCP SG SG u HOT LEG HOT LEG p ENUM TUBES TUBES n D D OFF ON RCP Y N O

V SG C

e C SG PLENUM PLENUM O E O RCP M M RCP E E R R opp OFF 4 4 I g lI ABNOR M AL FLOW PATH i l 4.4 Calvert Cliffs Unit 1 Startup Test - One Pump Coastdown From 80% Power 4.4.1 Description of Event i l The objective of this startup test was to measure the plant response to a partial loss of Reactor Coolant System (RCS) flow at 80% full power (30). This transient was initiated by securing 12A Reactor Coolant Pump (RCP) with the reactor operating at 80% of its full power which was 2560 Mwt for the original Operating License (OL). This test provided single RCP coastdown data and validated the low RCS flow trip from 80% power with one RCP secured. 4.4.2 Event Specific RETRAN Modeling Changes The Calvert Cliffs RETRAN model used for this analysis is the four loop model presented in Figure 3.4-1 and discussed in Section 3.4. The two loop model described in Sections 3.3 and 4.1.2 was expanded to a four loop model in which the two cold leg loops were converted into four individual cold legs and reactor coolant pumps. This model explicitly simulates the exact primary coolant system geometry which was required to analyze a single pump coastdown for the Calvert Cliffs design. Model enhancements (i.e., downcomer crossflow and realistic RCP reverse flow pressure loss coefficient) from Section 4.3 were also used. The other major event specific RETRAN model change for this analysis was to initialize the model at 80% of 2560 Mwt with all its associated thermal-hydraulic conditions. Along with core power, total RCS flow was adjusted to properly match the measured initial hot and cold leg temperatures. In addition pressurizer pressure and level and steam generator secondary side pressure were -

I 1 l changed to reflect initial conditions at this power level. Finally, the RCS level control system was adjusted to maintain initial level. 4.4.3 Comparison of RETRAN Results to Plant Data Figures 4.4-1 to 4.4-5 present a comparison of RETRAN calculated key thermal-hydraulic parameters with plant data. In Figure 4.4-1, RETRAN - calculated total RCS flow conservatively underpredicts plant data by 1% to 4% over the 60 second period. The difference is bounded by the flow instrumentation accuracy of,2% and time lag of up to 1.5 seconds. Another f flow comparison of interest for this transient is the time of reactor trip on low (95% of full) total RCS flow. RETRAN predicts this trip at 2.37 seconds af ter RCP trip which compares closely to the plant measured 2.2 seconds. Figure 4.4-2 presents a comparison of hot and cold leg temperatures between plant measurements and RETRAN calculated results. RETRAN results follow the same general trend as plant data and slightly overpredicts measured temperatures. This difference is due to the lower RCS flow coastdown and the unknown exact timing of Turbine Stop Valve (TSV) closure / Turbine Bypass Valve (TBV) opening following reactor trip. The small cold leg temperature rise reflects the temporary core power-steam flow mismatch that typically follows a reactor trip. Figures 4.4-3 and 4.4-4 compare measured pressurizer pressure and level with that calculated by RETRAN. These parameters slowly decrease in this transient in response to the primary coolant system cooldown. This same trend is calculated by RETRAN which predicts a slightly higher pressure and level with the higher RETRAN calculated loop temperatures. It should be noted that no information on the status or operation of the pressurizer pressure and level,

I control systems (i.e., spray, heaters, charging, and letdown) was available for this event. The RETRAN model assumed normal operation of these systems normalized to the initial values of pressure and level. The comparison of Steam Generator #11 secondary side pressure with RETRAN in Figure 4.4-5 shows close agreement. Both show the initial post-trip characteristic core power-steam flow mismatch induced pressure rise. The subsequent pressure drop to about 375 psig reflects the Turbine Bypass Control System (TBCS) which maintains a pressure of 375 psig with the TBVs after a trip. RETRAN calculated peak pressure and later decrease compares well with measured plant data. 4.4.4 RETRAN Sensitivity Study A RETRAN sensitivity study was performed for this transient in which RCP moment of inertia and rated torque were varied to assess their effect on the RCS flow coastdown. Moment of inertia and torque were each varied by +10% in four separate runs. The RCS flow coastdown for each sensitivity case i as well as the base case and plant data is presented in Table 4.4-1. By either t increasing pump moment of inertia by 10% or decreasing pump torque by 10%, the temporal flow rate increased closer to measured plant data. Conversely, lower inertia or higher torque resulted in lower coastdown flow rctes, in addition, Table 4.4-1 presents coastdown flow data for the base case J modified by adding the downcomer cross flow path and RCP reverse flow loss factor discussed in Section 4.3. These model changes have no significant effect on flow coastdown until 13 seconds into the transient, after 13 seconds, the new model calculated RCS flow is 1% to 3% higher than the initial model. ] i

i i 4.4.5 Summary of Results A RETRAN four loop model of Calvert Cliffs was developed to simulate a single pump coastdown transient from 80% power which was conducted as part of the original startup tests. Several key thermal-hydraulic parameters were compared between RETRAN and measured plant data for sixty seconds following the RCP trip. A comparison of total RCS flow coastdown and time of low flow reactor trip showed excellent agreement. RETRAN underpredicted flow by less than 4% which is both conservative and within instrumentation measurement accuracy / time lag. A comparison of hot and cold leg temperatures, pressurizer pressure and level, and steam generator secondary side pressure all showed good agreement both in peak values (if any) and trends. Finally, ansitivity study on RCP inertia and torque indicated that these inputs can sigr.ificantly affect the flow coastdown. Larger values of inertia have the sa ne effect as smaller values of torque. Incorporating downcomer crossflo's and RCP reverse flow model enhancements developed from the analysis described in Section 4.3 had a small (3%) effect on the total RCS flow coastdown in the first sixty seconds. I 6 Table 4.4-1 Calvert Clifis One RCP Trip at 80% Power Sensitivity Study Results RETRAN Normalized Total Reactor Coolant System Flow Base Case with Downcomer Cross Floe Time af ter Trip Inertia Inertia Torque Torque and RCP Reverse Flow of RCP 12A Plant Data Base Case +10% -10% +10% -10% Loss Coefficient 4 seconds 0.925 0.914 0.923 0.905 0.906 0.923 0.913 6.5 seconds 0.900 0.867 0.867 0.858 0.859 0.877 0.865 8.5 seconds 0.875 0.843 0.851 0.835 0.836 0.851 0.842 10.5 seconds 0.850 0.826 0.833 0.817 0.818 0.834 0.825 12.5 seconds 0.825 0.810 0.817 0.802 0.803 0.818 0.812 i g 18 seconds 0.800 0.780 0.787 0.772 0.772 0.787 0.791 29 seconds 0.775 0.755 0.758 0.753 0.753 0.758 0.778 33-60 seconds 0.765 0.760 0.760 0.760 0.760 0.760 0.778 Time of low RCS flow trip (seconds) 2.2 2.37 2.59 2.17 2.18 2.61 2.37 } I i

FIGURE 4.4-1 ONE PUMP COASTDOWN TOTAL REACTOR COOLANT SYSTEM FLOW RESPONSE S PLANT DATA 1001. RETRAN \\ e N 75./. N. -- 5 m u = I I t i I e a e a g g 0 10 20 30 40 50 60 TIME (SECONDS)

0 6 %- ~ E S N O 0 P T .x h. 0 5 S O D D A E R H T L L A OO D E T C C R N U 2 T T T A 1 T N A R R & A A A T E L E 1 2 1 e P 1 1 1 P R N 4 M E ) T S D G 2E o oo N

4. D

\\ - L O C 4L ~ 0 x.% I O E 3 S EC R ( UD E GN I A M F T N% 0 T I N O I NW O 2 DTSA OC N. 0 P MU / P 1 E .,/f NO ^ 7~ ..0 5 5 5 5 5 5 0 8 7 6 5 4 3 3 5 5 5 5 5 5 5 ?- E< E, Eg A'

FIGURE 4.4-3 ONE PUMP COASTDOWN PRESSURIZER PRESSURE RESPONSE 2500 PLANT DATA 2400 RETRAN 5 2300 m .N. 2200 N.N.N 5 m 2100 oc ~~. A 2200 1900 0 10 20 30 40 50 60 TIME (SECON DS) i

FIGURE 4.4-4 ONE PUMP COASTDOWN PRESSURIZER LEVEL RESPONSE 300 PLANT DATA RETRAN 250 N g 200 ~. 150 .'~.N.'- E i d e 100 1 50 0 0 10 20 30 40 50 60 TIME (SECONDS) e

L _m. FIGURE 4.4-5 ONE PUMP COASTDOWN STEAM GENERATOR SECONDARY SIDE PRESSURE RESPONSE 950 PLANT DATA HMAN 925 - N. E / N 900 - / N- .-A ~ e m 875 = o 0 i 850 m I 825 800 0 10 20 30 40 50 60 TIME (SECONDS)

4.5 Calvert Cliffs Unit 1 Startup Test - Total Loss of Flow / Natural Circulation Test From 40% Power 4.5.1 Description of Plant Event This test was conducted to monitor plant response to a total loss of flow from 40% of full power and to determine the power-to-flow ratio during natural circulation (30). The test was conducted by tripping the breaker supplying power to all four reactor coolant pumps. Key plant parameters were recorded for the first sixty seconds of this transient. Natural circulation was verified at five minutes af ter the trip based on reactor coolant system hot and cold leg tersperature variations. The principal indication of natural circulation was the decreasing hot leg temperature at this time. ~ The power-to-flow ratio was obtained by two different methods. The first method involved securing feedwater to the steam generators and adjusting the turbine bypass valve controller to provide a constant cold leg temperature for one heur while steaming down the steam generators. This method was utilized from 70 to 130 minutes after RCP and reactor trip. The data indicated that 13.09 MWth decay heat (0.51% of rated power) was being removed with 9200 GPM of primary coolant flow (2.29% of full flow). This results in a power-to-flow ratio of 0.22. The second method, using the AT power readout, indicated a power-to-flow ratio of 0.207. These power-to-flow ratios (0.22 and 0.207) are well within the acceptance criterion of less than 1.0. 4.5.2 Event Specific RETRAN Modeling Changes in order to mcdel this total loss of flow / natural circulation test, the RETRAN two loop model was modified to initialize at the 40% power hot and cold leg temperatures, feedwater and main steam flow rates. Also, post-trip feedwater flow rate was adjusted to balance the temporal decay heat rate during the transient time period modeled by RETRAN. 4.5.3 Comparison of RETRAN Results to Plant Data Natural circulation was confirmed in the RETRAN analysis of this event at about four minutes into the transient by decreasing hot leg temperature. Another indication of the natural circulation in the RETRAN analysis was the primary coolant system loop flow rates. These flows drop rapidly until about 12 minutes into the transient after which the loop flows become relatively steady. From 12 minutes until the end of the RETRAN calculation at 37 minutes into the transient, the total loop natural circulation flow remained at about 2.7% of initial forced circulation flow. The RETRAN calculation was run out to 37 minutes. The key result of the Calvert Cliffs natural circulation test is the measured power-to-flow ratio during the period from 70 to 130 minutes after RCP and reactor trip. Using two different methods, plant data for this parameter was determined to be 0.220 and 0.207. The RETRAN calculated power-to-flow ratio at 75 minutes after RCP and reactor trip was 0.211. This closely agrees with plant data. Both the plant test natural circulation test power-to-flow data and similar RETRAN results were compared to other nuclear power plant data and theoretical calculations presented by Zvirin (33) -.

and were found to fall within the range of predicted performance for natural circulation. Figures 4.5-1, 4.5-2 and 4.5-3 compare measured plant data with RETRAN results for pressurizer pressure and level and total RCS flow for the first 60 seconds af ter reactor /RCP trip. RETRAN very closely follows plant data. Figures 4.5-4 and 4.5-5 compare RETRAN witn measured plant data for RCS loop hot-cold leg temperature and steam generator secondary side pressure, respectively, for the first 60 seconds. RETRAN calculated hot and cold leg temperatures follow the same trend as plant data during this time period. RETRAN overpredicts hot leg temperature and underpredicts cold leg temperature by one to five degrees fahrenheit during the sixty seconds. This

  • difference is attributed in TBV and ADV opening times and rates after reactor trip and does not affect the long-term onset of natural circulation.

The RETRAN underprediction of peak steam generator secondary pressure is due to the same difference in TBV and ADV performance. 4.5.4 Summary of Results The RETRAN Calvert Cliffs two loop model was used to simulate a total loss of flow / natural circulation test performance from 40% power at CCNPP Unit 1. For the first 60 seconds after reactor / turbine trip, RETRAN calculations were compared to measured plant data for pressurizer pressure and level, total RCS flow, hot and cold leg temperature and steam generator secondary side pressure. RETRAN closely matched measured RCS flow, pressurizer pressure and level. RETRAN results for hot and cold leg temperature and steam generator secondary side pressure differ slightly from - - -, - - - - - ~. +

plant data, but follow the important trends. The most important result of this test was the measured natural circulation flow to reactor thermal power ratio from 70 to 130 minutes after reactor / turbine trip. Using two different methods, plant data for this ratio was determined to be 0.220 and 0.207. The RETRAN calculated ratio at 75 minutes after reactor-turbine trip was 0.211, which closely agrees with plant data and theoretical predictions. 1 l,

FIGURE 4.5-1 TOTAL LOSS OF FLOW / NATURAL CIRCULATION TEST TOTAL RCS FLOW RESPONSE 125 PLANT DATA RETRAN 100 L. \\. 1 i. \\. \\\\ \\ 75 \\ \\ '\\ \\. ~ s 3 i O -\\ a i u. '\\ 50 \\, N '\\. N N 25 ' s, 's N ' ~. ~.,, ~ --. ~.. _,~ ~ ~.. 0 0 to 20 30 40 50 60 TIME (seconds) ' i

1 FfGURE 4.3-2 TOTAL LOSS OF FLOW / NATURAL CIRCULATION TEST PRESSURIZER PRESSURE RESPONSE t 2,350 i i i e i e i i PLANT DATA l RETRAN l 2300 2250 - ~.,,~.' ,o ~., il N. E 2200 n'- s.s 3 s-m s-m s.' ~ m oc .%.~._._,,,'~.' a. ~.'%, 2150 2100 2050 O 10 20 30 40 50 60 TIME (seconds).

FIGURE 4.5-3 i TOTAL LOSS OF FLOW / NATURAL CIRCULATION TEST PRESSURIZER LEVEL RESPONSE 225 i a i i i i i PLANT DATA RETRAN 200 j 175 1' c O -e.. ~~..,"*a==..%s u .5 ~ l 150 s. s. s s. u.s j N.N. w a '- --.~..,, j 1 125 1 1 100 1 .I s t e 75 0 10 20 30 40 50 60 TIME ( seconds).i ., ~......, . ~.... -., m. -. ~ - -.. ---r

FIGURE 4.5-4 TOTAL LOSS OF FLOW / NATURAL CIRCULATION TEST ' HOT AND COLD LEG TEMPERATURE RESPONSE I. 565 i PLANT DATA T Hot T Cold 560 RETRAN f -- g- - N. N. 555 N. \\ 'N, N N ~,,% 550 's. C N. s.s, N u. -s QC ? Sa5 "g ~.~.,_~ 4 .s N= u. >= 540 ,.-.~. y-.-./,. ~. 535

  • N N. %

530 525 O 10 20 30 40 50 60 TIME (seconds).

o FIGURE 4.5-5 TOTAL LOSS OF FLOW / NATURAL CIRCULATION TEST STEAM GENERATOR SECONDARY SIDE PRESSURE RESPONSE 950 i i e i e i e i PLANT DATA SG 11 SG 12 RETRAN 900 .l ' ~. .? ./ ' ~. '.. ' s. E / .f s s = / \\ D _I -s / s .s.,~' m ? .s.' ~. s,' .~.,,'s,'""*. 850 .I wfeI 800 O 10 20 30 40 50 60 TIME (seconds).

5.0 TRAC ANALYSIS COMPARISON 5.1 Description of the TRAC Calvert Cliffs Model TRAC-PF1 is an advanced best estimate finite-difference systems code capable of performing small, intermediate, and large-break loss of coolant accident (LOCA) analyses, and non-LOCA thermal-hydraulic transients in both one and three dimensions (31). TRAC solves the full set of field equations for mass, energy and momentum conservation for both steam and liquid. Figure 5.1-1 shows the TRAC noding diagram for the primary side of Calvert Cliffs (35). The reactor vessel of Calvert Cliffs - 1 is modeled three dimensionally with twelve axial levels, two radial rings - the inner ring represented the core region located within the core-support barrel, the outer ring represented the annular downcomer region, located between the vesal wall and the core support barrel and six symmetric azimuthal segments - one for each penetration (four cold legs and two hot legs). The vessel model totaled 144 calculational-mesh cells, and was divided into 12 axial levels, using the bottom of the vessel as a reference point. The top of the first level corresponded to the bottom of the core support barrel. The top of the second level corresponded to the bottom of the fuel column. The bottom end fitting of each fuel assembly was located in level 2. The active core height,11.4 ft. (3.5 m) was divided into five axial sections. The gas plenum of each fuel rod and the top end-fitting of each fuel assembly were located in level 8. The top of level 3 was at the same height as the bottom of the hot-leg penetrations and the top of level 9 corresponded to the top of the hot-leg penetrations. _

In the reactor vessel, a small portion of the total flow (1.9%) goes through the CEA shrouds located in the upper plenum into the upper-head region and is referred to as bypass flow. The flow recirculates back into the upper plenum through 19 small holes located in the CEA grid-support plate. Hot legs were modeled with an inner diameter of 48 in. (1.2 m) at the core barrel converging to 42 in. (1.0 m) outside the vessel. The surge line to the pressurizer was connected to the hot leg in Loop B. The pressurizer was represented by three TRAC components. The first, PIPE component 10, simulated the part of the pressurizer containing the proportional and backup heaters. TEE component 47 was the major part of the pressurizer with a connection to the power operated relief valves (PORVs) and the primary safety relief valves (SRVs). This component contained six cells, which were found to be adequate for modeling the liquid / steam interface. PRIZER component 9 fixed the pressure at 2250 psia (15.51 MPa) during a steady state calculation. There are two U-tube SGs with 3519 tubes, modeled in TRAC as a single flow path, with heat transfer area adjusted 10% to match stead state conditions supplied by BG&E. A typical study would use 20 primary cells, and 26 secondary ce!!s. The pump-suction end of the cold leg is a 6.5 ft. (2 m) U-shaped pipe leading to the RCPs. The rest of the piping is horizontal, with the HPI and charging flow injecting downstream of the RCPs. Each cold leg is modeled separately and represented the piping from the SG to the vessel. HPI was modeled as a mass flow vs. pressure boundary condition with the fluid at a temperature of 55 F (236 K). HPI is injected into all four cold legs based on delivery curves supplied by C-E. HPI lines inside (120 F (322 K)), and outside (85 F (302 K) of containment was also taken into account.._

Parts of the secondary system were included into the TRAC model of Calvert Cliffs. These parts included the steam lines up to the turbine-stop valves (TSVs) and turbine-bypass valves (TBVs) and about half of the feedwater train. Figure 5.1-2 shows the major components of the complete main feedwater train. The high-pressure heaters were modeled as one heater as were the low-pressure heaters. Some 3230 ft. (1000 m) of pipe length was modeled with 170 fluid cells. Main feedwater pumps were modeled separately allowing one to be run in manual and the other in automatic. Figure 5.1-3 shows the TRAC model noding diagram of the steam lines. The model did not include the steam lines that supply the MFW-and AFW-pump turbines. Furthermore, some liberty was taken with the arrangement of the line to the TBV. The line to the TBV is actually between the Loop-A main steam isolation valve (MSIV) and the lines to the high pressure (HP) turbines. l 0

FIGURE 5.1-1 TRAC NODING OF CALVERT CLIFFS PRIMARY SIDE. LEYEkJ @Luirig tiiiig@ %'- f.' / 17 10 x PORVs @ @ SRVs LFjLIJh4 k Stea m Steam 19 8 Line ll'> i rees. Lower Plenum Line at P Mixing Pipes di 114 62 62 Col Legs 1--7Crr i 5 .,/ 2 N y g g 2 Qtl 3,g g y .L.3epsI .12 (' --_2 g 3 6

  • - -- ---- --- r-.

12 --* I 4 - $1 / ess e \\_ l i 61 l 2 .2 Pr 3 6 Zl 13 f gg Cold legs SC : f Z h Z -1 Steam 2 16 SG Dowhcomer ,.f_ Steam AJ ) Generator _.J Downcorr{er Q F l l,-, 1 -Generator ,,R.'...'.. n..a'_ g i2 y.._m........ W R j I-l-I p Q u 10 177 f g to 3 3 j4rIT2T7TTTT121V 11 . IZEDli Pump (@) Hot Les \\ nym; d -m _ _-._/ Hot leg Pump g 2 2 76 teI51 131z 11124 1 1 11213141512 ' h h t I W

== 117 Loo -r +ff ,,,,,o,h@ 4 wy,3r I) cHe,roi 4 i ~~ 22 (5 hi. W 4WMXo : es,.,m, y,,9 34, m 131.- 3 4 ss, hh 3865 I c si9 net 6. HPI Fui i 3, om i HP, Flu a,,o g g y e e 1880 P.184'

FIGURE 5.1-1 (Cont'd.7 TRAC NODING OF CALVERT CLIFFS REACTOR VESSEL 12.540 's"4Y ^ 11.261 g_ h I 10.377 LEVEL 9 I'8"' I '8Y5'M 10 coto tecS 0.9 71-2 5 9 7 12 [ig 7 1 7.712-N 7 M 7; N' i "4 o 1l 2 O 5 I4 sis 4 _ ';Y/////// ~ / a a 3 i3. 339 5 / /,6pn y / / e o o 4l865 !//////- 3 4 \\ 3 3.170 d[8/ / 4 'r 2 so"eIErTE. 9 1 $3 e HW COLD LEX;S LEG 1.862 Lower Plenum Mixing Pipes 1 now BAME 1.880

  • 2.184

( ( N 5 R R 2 s- @t.'i @i!

  • E@t i 2@t

@il @il i e si @ sae e @i! E 3! 1 e C GE k g 5 g3 E 3 @![ I@l GI 18$ e @Ej 5 @ E"g n ,E n i e 2 8 5 E ' 3 3..... {=1.......gC @j' @sB- - 7 t : ~ I h. E " ~ m Q S sb 4 @h ! R 8 e 1 i re glg ! @d j! E II @I! IE @BR 11 El gg ~ 3 I---- > H [:_] E g -- j gg g O .I e 8 Eg - -J* c @ I I

5 e

@@sM @ls @l! 5 I 5i 8C- @,ba l a 2: s,-,-,-,....,- 3Y. 3 ,2 k 1 Eg E g @gg i l@li l g!s":3 G!! I 'k g g E z:bi 5 5= @. I @!! 8 ~ = r =e @E l Q , !@pi S j @i*a N.ri @ U" S@ i S - BI*l*iai */ai-i-13 FIGURE 5.1-3 TRAC NODING OF CALVERT CLIFFS MAIN STEAM LINES 2 64 e7 5 O fb ["O O s3 so nicn enessuns seg#1237o g a Tuas NE as 7ng SG 22 \\ f _;o72--: I h CONDENSER - Il 2 I 3 I 41'4 W@ 75% 2 taV 2 54 57 ADV SRV g,,,; I6" SG 12 MS!V HIGil PRESSURE \\ / TURBINE a i

5.2 TRAC Analysis of Cooldown to RHR Entry Using ADV and APS i 5.2.1 Description of TRAC Transient The Los Alamos National Laboratory (LANL) performed a TRAC-PFI analysis of the Baltimore Gas and Electric Company's Calvert Cliffs Nuclear Power Plant for a Loss of Off-Site Power (LOSP) natural circulation cooldown (36). A loss of off-site power causes the reactor and turbine to trip immediately. The turbine stop valves and turbine bypass valves shut to protect the turbine and condenser respectively. The main steam safety relief valves (SRVs) begin lifting at their set point of 935 psig. The plant diesel generators start up and. provide power to the vital busses, allowing the atmospheric dump valves to operate. The four reactor coolant pumps coast down and a natural circulation condition is established. Temperature is maintained by control of the atmospheric dump valves. Auxiliary feedw3te: is delivered by one steam driven and one electric driven Aux feed pump. Shutdown boron concentration is established and a 100 F per hour cooldown to RHR entry condition is begun. The LANL calculation commenced a cooldown immediately after reactor trip, not accounting for the delay necessary to ensure proper shutdown boron concentration. For consistency, this omission was duplicated in the RETRAN analysis. For the LOSP transient, LANL employed a fill boundary condition for the steam generator feedwater. ,3 4 -

5.2.2 RETRAN Models for TRAC Comparison j The RETRAN model used for this analysis was the simplified one loop primary coolant system and a non-recirculating steam generator described in Section 3.2. As a result, this model runs in real time on the BG&E IBM mainframe computer. 5.2.3 Comparison of RETRAN and TRAC Results Table 5.2-1 lists the sequence of events for the LOSP transient. No operator action is taken until 10 minutes have passed. At that time, auxiliary feedwater is delivered. One minute later the operators take control of the ADVs to begin the 100 F per hour cooldown. Af ter another minute, the operator realigns the charging pumps to provide auxiliary pressurizer spray (also disabling the makeup flow) and controls primary depressurization to maintain 30 F subcooling. As can be seen in Figure 5.2-1, primary pressure compares very well. Sensitivity analyses show that the rate of depressurization depends strongly i on APS flow rate and is unaffected by the interphase heat transfer coefficient. The sudden pressure drop predicted by RETRAN at 3200 seconds corresponds to an emptying of the pressurizer. This is consistent with a previous comparison to TRAC for an overcooling event (37) in which RETRAN predicted pressurizer emptying due to primary contraction and TRAC did not. Figure 5.2-2 shows the hot leg temperature response. Neither RETRAN nor TRAC predicted a cooldown to 300 F. RETRAN predicted a more limited cooldown due to a more restrictive ADV model which takes into account the geometry of all piping associated with the ADVs. The TRAC operator ADV -

control system oscillates to maintain the 100 F per hour cooldown average. The RETRAN control is much finer, producing no noticeable oscillations. Figure 5.2-1 shows the good agreement in calculated secondary pressure. RETRAN predicts slightly higher pressure than TRAC due to the ADV modeling. Again, the oscillating ADV control is noticeable in the TRAC results. Figure 3.2-2 once again demonstrates the importance of the ADV model to this calculation. The best estimate RETRAN model limits the steaming rate and slows the secondary liquid temperature cooldown relative to TRAC. l 5.2.4 Summary and Conclusion For a LOSP natural circulation cooldown at Calvert Cliffs, a simplified fast-running RETRAN model can duplicate the results of a sophisticated TRAC-PF1 model. In this case, the RETRAN model takes iull advantage of the symmetry of the event. The results are most sensitive to APS flowrate and ADV modeling. Although not investigated by sensitivity analyses, the primary system heat capacity and decay heat curves are also important in long term cooling transients.. -

Table 5.2-1 LOSP COOLDOWN SEQUENCE OF EVENTS FOR TRAC AND RETRA' 1 Time (s) Event 0.0 LOSP event 0.1 Reactor trip MFW trip

  • Turbine trip
  • Reactor coolant pumps trip
  • ADV trip signal but action delayed 14.5 s 0.52 TBV trip 14.73 ADVs quick-open after 14.5 s delay 600.9 AFW initiated 723.

APS on (cycling thereafter) 11500 END OF CALCULATION These events occurred at time zero in the RETRAN analysis. P 1 , f m-

FIGURE 5.2-1 COOLDOWN TO RHR ENTRY - PRIMARY AND SECONDARY PRESSURE RESPONSE 16 ......... RET R A N 210 0 p ~ 12 1400 O 0 o. 2 3 a PRIMARY 700 4 SECONDARY 0 O O 2000 4000 6000 8000 10000 12000 Time (s) . i

) i l l l_ FIGURE 5.2-2 COOLDOWN TO RHR ENTRY - HOT LEG TEMPERATURE RESPONSE I t I i l 4 600 600 RETRAN TRAC 550 520

  • K 500 44o

'F OO%S tegggggg gggS S.S.9 89 0 mm 450 360 W 200 t t t f f I f I f I I O 2000 4000 6000 8000 10000 12000 Time (s) 89 - i e ~ - - - - --,..--,----------.-n

I i l 5.3 RETRAN Comparison to TRAC Simulation of Runaway Feedwater to One Steam Generator i i 5.3.1 Description of TRAC Transient As part of the NRC sponsored pressurized thermal shock (PTS) project (1), the Los Alamos National Laboratory (LANL) was contracted to develop a detailed model of Calvert Cliffs Unit I and perform a set of PTS-limiting system transient analyses (35). These analyses were all performed as best estimate calculations without the imposition of the usual licensing analysis conservative assumptions. One of the categories of Calvert Cliffs PTS transient analyses analyzed by LANL was runaway feedwater. It was postulated that, following a reactor / turbine trip, the main feedwater regulating valves (MFRV) fail to close and MFW continues to be pumped into the steam generator. This injection of colder MFW with a reduced heat source on the primary side of the steam generator (i.e., core at decay heat) results in an overcooling PTS event. The specific TRAC runaway feedwater analysis chosen for this RETRAN comparison was the runaway main feedwater to one steam generator. This transient results in both an overcooling and asymmetric response of the primary cooling system. The key PTS parameters calculated by TRAC are downcomer temperature and primary system pressure since these are the thermal-hydraulic factors that influence high neutron fluence induced weld embrittlement to allow a preexisting weld crack to grow in PTS. TRAC calculated a minimum downcomer temperature of 424 F at 363 seconds. Primary system pressure initially drops due to the overcooling but at 1850 seconds rises and cycles around the PORV setpoint due to operator failure to shut off the charging pumps, i The TRAC analysis showed several interesting phenomena during this postulated transient. The transient response was div:ded into the following five phases: 1. Runaway main feedwater to one steam generator (0 to 363 seconds) 2. Reheat following termination of excess feedwater (363 to 3200 seconds) 3. Quasi-equilibrium (3200 to 4800 seconds) 4. Auxiliary feedwater to both steam generators (480d to 5800 seconds) 5. Extrapolation (3800 to 7000 seconds) During Phase 1, the steam generator receiving normal post-trip feedwater enters a reverse heat transfer mode in which it heats the primary coolant system. This phenomena is due to the overfed steam generator cooling down the primary coolant system below the normal post-trip saturation temperature being maintained by the other steam generator. This effect only lasts until the primary coolant temperature rises back above the steam generator saturation temperature after the runaway MFW is terminated by depletion of the condenser hotwell liquid inventory. SIAS and HPSI flow injection also occur during Phase I in which primary coolant pressure drops to 1000 psia. Phase 2 reflects the return to normal post-trip system thermal-hydraulic conditions af ter the runaway MFW train depleted condenser hotwell inventory. Phase 3 is the equilibrium state where normal decay heat removat via steam generator inventory steaming occurs. In Phase 4, low steam generator level initiates auxiliary feedwater which results in a slight cooldown as the colder AFW fluid enters the steam generator. Phase 5 is an extrapolation of TRAC results out to 7000 seconds for PTS purposes. -.

l The TRAC calculated sequence of events and plots of TRAC calculated system parameters are presented and compared to RETRAN results in Section 5.3.3. I 5.3.2 RETRAN Model for TRAC Comparison The two-loop model decribed in Section 3.3 was used to simulate the runaway feedwater transient. This model was modified in several areas to better simulate the transient sc-nario evaluated by TRAC. The Auxiliary Feedwater Control. System was isolated to prevent AFW injection in accordance with the TRAC simulation. In addition, the charging pump control system was modified to allow continuous operation af ter initiation even af ter pressurizer level returned to normal levels. This failure to isolate charging flow was also assumed in the TRAC calculation. A major modification of the tube volumes in the steam generator isolated from the runaway main feedwater was necessary for this RETRAN calculation. These modifications were: Consolidation of the four highest elevation steam generator tube volumes (nodes 111,113,115 and 117 in Figure 3.3-1) into a single volume (new node 111); inclusion of a bubble rise model for two phase thermodynamic conditions in the new consolidated volume (node 111); and elimination of the enthalpy transport model from the two junctions connected to this new consolidated volume (node 111). These changes were required because of the Phase I phenomena of steam generator reverse heat transfer discussed in Section 5.3.1. This reverse heat transfer causes void formation in the upper tube volumes. The two loop RETRAN model without the aforementioned modifications experienced large void formation in the relatively small upper tube volumes which causes RETRAN l to abort when calculating fluid properties. These modifications reduce the magnitude of void formation since the upper tube volume is four times larger. Also, by incl'uding the bubble rise model and deleting the enthalpy transport model, RETRAN can calculate fluid properties. The driving boundary condition for this transient is the temporal main feedwater flow rate and enthalpy to each steam generator. Since the RETRAN model does not include an explicit simulation of the feedwater train back to the condenser, the flow and enthalpy used in the TRAC analysis was used as a fill junction boundary condition in the RE'TRAN calculation. 5.3.3 Comparison of RETRAN Results to TRAC Key RETRAN calculated results for pressurizer pressure and level, downcomer temperature, hot leg temperature, and hot leg flow rate are compared to TRAC calculations in Figures 5.3-1, 5.3-2, 5.3-3, 5.3-4 and 5.3-5, respectively. The RETRAN calculation was terminated at 3600 seconds due to excessive computer run time, whereas TRAC results were presented out to 5800 seconds. All important trends and phenomena occur prior to 3600 seconds for this transient. In Figure 5.3-1, RETRAN pressurizer pressure drops to a minimum slightly lower than TRAC, but at the same time. RETRAN's pressure recovers and rises to the 2400 psia PORY setpoint slightly earlier than TRAC. The initial drop in pressure is due to the overcooling effect of runaway main feedwater. The subsequent pressure rise to 2400 psia reflects termination of main feedwater flow at 303 seconds and uninsolated continuous charging pump flow postulated as part of the basis for this PTS event. In the pressurizer level comparison in Figure 5.3-2, both RETRAN and,

TRAC predict a rapid drop in level to an empty pressurizer by about 200 seconds. This level drop corresponds to the pressurizer pressure drop caused i by the runaway MFW. Both codes calculate level recovery af ter cessation of MFW flow although RETRAN shows a more rapid level rise to the top of the pressurizer (30 foot level). The level rise is due to the termination of the runaway MFW overcooling source which is later exacerbated by the runaway charging pump flow. Figures 5.3-3 and 5.3-4, RETRAN calculated downcomer and hot leg temperatures follow the same trends as TRAC results. In both figures, RETRAN predicts a lower minimum temperature occurring at the same time and the same trend of increasing temperature throughout the balance of the event. The lower RETR AN temperatures can be attributed to the finer nodalization in TRAC. TRAC utilizes six circumferential cells (nodes) and nine axial levels for' a total of 34 nodes to represent the downcomer as compared to RETRAN's two node downcomer. The. greater number of nodes and concomitant crossflow paths in the TRAC model allows greate mixing of the colder fluid from the overfed steam generator with the warmer fluid from j the unaffected steam generator. Figure 5.3-5 presents the hot leg flow rates for both loops as calculated 3 by TRAC and RETRAN. The loop A flow drops to about 750 lbm/sec whereas the loop B flow drops close to zero and subsequently recovers to match the i loop A flow at about 3600 seconds. The higher loop A flow in the early phase (500 to 3000 seconds) of this transient was driven by the higher natural 4 circulation induced by the runaway feedwater to steam generator A and resulting larger temperature drop across this steam generator. After MFW isolation at 303 seconds and the gradual establishment of thermal equilibrium between the two loops, the natural circulation flow becomes loop-94 r i i

symmetrical. RETRAN calculated flow rates for each loop closely follow TRAC results including the large difference between loops until about 3000 seconds when both loop flows converge. This loop hot leg convergence is i predicted by both RETRAN and TRAC. Table 5.3-1 presents a comparison of key sequence of events for this transient as calculated by both TRAC and RETRAN. RETRAN predicts almost identical timing for initiation of steam generator B reverse heat transfer, SIAS, and minimum average downcomer temperature. The event initiation and cessation of main feedwater flow times are dictated by the transient specific assumptions. i 5.3.4 RETRAN Sensitivity Study Due to the long computer run times associated with this analysis, a limited sensitivity study was performed for the RETRAN simulation of this transient. The nonequilibrium pressurizer model interface heat transfer c.oefficient (IHTC) was varied from the base case value of 32,400 2 2 BTU /HR-FT -F down to 1000 and 10 BTU /HR-FT -F. The base case value of IHTC was substantiated in Section 4.1, which evaluated a rising pressure transient. Since the runaway main feedwater event is a decreasing pressure event, these two additional calculations with lower IHTCs were performed to evaluate the effect on subsequent pressure response. Both cases of lower IHTC resulted in no significant effect on pressurizer pressure or level response for this transient. ;

I 5.3.5 Summary of Results 4 Using a modified version of the CCNPP two loop model described in Section 3.3, RETRAN calculations of a postulated runaway main feedwater to I one steam generator event were performed. This scenario had also been analyzed with the TRAC PF1 computer code as part of the PTS project. RETRAN results followed the same trends and timing for key thermal-hydraulic parameters such as pressurizer pressure and level, downcomer and hot leg temperature and hot leg flow rates. RETRAN slightly underpredicted i ) the minimum pressure and temperatures. Important asymmetric phenomena including different loop natural circulation flow rates and steam generator B reverse heat transfer were predicted by RETRAN in agreement with TRAC. Also, capability for analyzing steam generator tube voiding and pressurizer level from empty to water solid with RETRAN was demonstrated. 1 i J f I. 1 l }

i Table 5.3-1 RUNAWAY MAIN FEEDWATER TO ONE STEAM GENERATOR SEQUENCE OF EVENTS COMPARISON TIME (SECONDS) EVENT TRAC RETRAN O O Reactor / Turbine Trip - MFRV to Stuam Generator A failed to open - ADVs and TBVs open on " quick-open" logic 102 106 Steam Generator B enters into reverse heat transfer mode 123 122 Safety Injection Activation Signal (SIAS) on RCS pressure of 1740 psia j 153 152 Reactor Coolant Pumps tripped off by operator 30 l seconds after SIAS 303 303 Main Feedwater pumps trip off due to loss of liquid inventory in condenser /hotwells 363 368 Minimum average downcomer temperature reached. _.

FIGURE 5.3-1 RUNAWAY MAIN FEEDWATER TO ONE STEAM GENERATOR PRESSURIZER PRESSURE RESPONSE 18 i i 2450 ~~ 16 l l 2100 14 - l l l I 12, l 1750 I o to 4 a.

E l

l 1400 .o E ~ 5 .I e E 8 J h a E l ,I 1050 2 l I !

l 6

\\.l 700 4 TRAC 350 RETRAN 2 - 0 O O 1000 2000 3000 4000 5000 6000 7000 8000 Time (s).

FIGURE 3.3-2 RUNAWAY MAIN FEEDWATER TO ONE STEAM GENERATOR PRESSURIZER LEVEL RESPONSE 10 i i i i i i i e i i i 7._..__._. 30 i .i I 8 - j 1 25 I i i i j 20 6 I i j -3 1 i 15 I e l 3 s .I g o l ~ 3 i y i 10 l 2 7 f I i 5 i i i !lO 0 0 TRAC RETRAN -2 O 1000 2000 3000 4000 5000 6000 Time (s).

FIGURE 5.3-3 RUNAWAY MAIN FEEDWATER TO ONE STEAM GENERATOR DOWNCOMER TEMPERATURE RESPONSE 590 i i e i i a i 600 l l 560 .p 500 530 3 ,/ / / / \\ .l 500 \\ t ' 400 C. ) x l,i 470 ~ ~ s ij s o F e 5 p 440 y a a 300 e 1 '5 '5 h 410 380 200 350 TRAC 320 RETRAN goo 290 O 1000 2000 3000 4000 5000 6000 7000 8000 Time (s) 100 -

f. l FIGURE 5.3-4 RUNAWAY MAIN FEEDWATER TO ONE STEAM GENERATOR HOT LEG TEMPERATURE RESPONSE 580 580 570 560 560 540 / \\ 550 d ./ 2 / 320 E l e e \\ / 2 2 5<0 e .;\\ e a ./ E i .i. i ./.[. 500 I, 3 3 530 i l / / 480 520 / \\ i, ./ L / 460 510 - i(! {,l TRAC 500 ~ ,,'/ RETRAN 490 O 1000 2000 3000 4000 5000 6000 Time (s) - 101 -

FIGURE 5.3-5 RUNAWAY MAIN FEEDWATER TO ONE STEAM GENERATOR HOT LEG MASS FLOW RESPONSE ~ 1000 i i i i i i i TRAC RETRAN 2000 900 I I I -{ 1750 800 t e 0 e 700 -l l 1500 i I 600 e i I. 1250 8 E. LOOP A e. 3 500 ) O g o E e 8 1000 C o y I 400 750 s. e. 300 -j ,rril,. - Y i ( / f;ist / e I l / ./ - 500 8 e e 200 -l l ,/ e l / I l l l I i l - 250 e l l / 100 l / LOOP 8 Y!/ i e i i e i t 0 0 1000 2000 3000 4000 5000 6000 7000 8000 Time (s) - 102 - -c- -r-

6.0 LOFT TEST SIMULATION 6.1 Description of LOFT Facility and Tests The LOFT (Loss of Fluid Test) facility was used in a series of experiments administered by the Department of Energy to provide data required to evaluate the adequacy and improve the analytical methods currently used to predict the loss of coolant accident (LOCA) response and anticipated transients caused by abnormal operation of pressurized water - reactors (38,39). A schematic of LOFT is presented in Figure 6.1-1. The primary objective of this facility was to test the performance of the engineered safety features with particular emphasis on emergency core cooling system and the quantitative margins of safety inherent in the performance of the engineered safety features. Another objective was to identify and investigate an unexpected event in the response of the plant or the engineered safety features and develop analytic techniques to adequately describe such behavior. A third objective was to evaluate and develop methods to prepare, operate and recover systems and plant for and from reactor accident conditions. The last objective was to identify and investigate methods by which reactor safety can be enhanced, with emphasis on the interaction of the operator with the plant. LOFT is a 50 MW thermal scale model which closely models a 3000 MW thermal PWR, major emphasis being on the reactor system, primary coolant system, blowdown system, blowdown suppression system, ernergency core cooling system, and secondary cooling system. The major series of experiments included nonnuclear mini-blowdown experiments, nuclear small-break experiments, nonnuclear large-break 1 - 103 -

experiments, nuclear intermediate-break experiments, and finally anticipated transients and transients with multiple failures experiments. LOFT tests L6-1 and L6-3 were analyzed with RETRAN with results being discussed in Sections 6.3 and 6.4. The L6-1 and L6-3 tests are from the Anticipated Transient Experiment Series L6 (40). The objectives of these experiments were to: 1) evaluate the automatic recovery methods in bringing the plant to a hot-standby condition; to 2) provide data to evaluate computer code capabilities to predict secondary system initiated events; for L6-1 to 3) investigate plan response to a transient in which the heat removal capabilities to the secondary system are significantly reduced, and for L6-3 to 4) investigate plant response to a transient in which the heat removal capability of the secondary system is significantly increased. - 104 -

o 0 ,n, e s , v) 0 3 ,a l 2 a( 10 , v n ,s e# r k o o pt r a B ml u u l tn N Pmta n is nm io e e sl e C ( imr s e un e s g r so r s I e ai pe g N{ T t pea pv A g x u emt n s S M in) 1 l p E 2 e% s l e( e 1 C o la v . S k [f" d 6 lcv Y u ET O t r RI oe UL mt t aa ar l GI I C teeu nm Sei FA '.,"e, y } ol gs F t T l tn I, ^ tcs a e F tnm I. e as ~ O e L e c ee imr Rv u n i so la. r n e ait pea t O"

  • vQ.-

tnm emt nm x s e t im,. .~ la n o n e r so e gpeat ai e e tmr s W s u n pemts r so 3 1 e i at Cpea y 'm t .i' .*.Y x Pemts r p o o lo a er e 1 l t t lee .,^ tnm-a n c n e a Se I k"

  • e mr t

G e n e (. i so un r 3 e ai t Cpee x Pemis 'e V tr russe r r P g.

  • i i

6.2 LOFT RETRAN Model The BG&E RETRAN model of the LOFT facility was based 'on a RETRAN-01 deck used by Energy Incorporated (EI) to simulate the L6-5 test l (39). The El deck was revised to execute under the RETRAN-02 Mod 3 code l version and was then modified to simulate the L6-1 and L6-3 tests. A noding l diagram is presented in Figure 6.2-1. Both the unbroken and broken coolant loops are modeled. Since neither the L6-1 nor the L6-3 tests involved a pipe break, the broken loop was modated simply by using two 1-volume piping stubs connected to the unbroken loop by small circulation lines. In contrast, multiple volumes were used to model the unbroken hot and cold legs. The hot leg is modeled using four volumes. There is one volume for the hot leg nozzle, two volumes for the 14 inch piping, and one volume for the 16 inch piping. The primary side of the steam generator is modeled using four volumes. One volume is used for the steam generator inlet plenum. There are two volumes representing the steam generator tubes and one volume for the steam generator outlet plenum. The cold leg is modeled using nine volumes. There are three volumes leading to the reactor coolant pump inlet and individual volumes for each pump and its outlet. Two further volumes combine the pump outlets and connect to the reactor vessel. The reactor vessel model includes a 5 volume core, volumes for the upper and lower plena, and a 2 volume downcomer. The pressurizer vessel is modeled using one volume and the non-equilibrium option. Pressurizer spray is provided by a one volume connection to the cold leg. There is a one volume surge line which connects to the 14 inch piping in the hot leg. The steam generator secondary is modeled to recirculate and uses four volumes. The - 106 -

feedwater piping has one volume and is connected to a fill junction. The steam line is modeled as with the Main Stnm Flow Control Valve (MSFCV) in between two volumes. Steam is exhausted ic a time dependent volume acting as the air cooled condenser. There are a total of 42 volumes and 50 junctions in the system. There are 28 heat slabs used to simulate the metal mass of the system' and 3 non-conducting heat exchangers used to simulate the pressurizer heaters. Control systems and trips are provided to simulate the Reactor Protective System logic, the pressurizer pressure control logic, the steam generator pressure control logic, and the ECCS actuation logic. Special controls are provided for each transient to simulate its particular initiator. l l - 107 -

FIGURE 6.2-1 LOFT RETRAN NODING DIAGRAM A Q Q MAIN STEAM CONTROL VALVE AIR COOLED { CONDENSE R { a . _L ri 0.7 1r STEAM @ GENERATOR O O - F EEDWATE R e CONTROL VALVE AA ioo u 'L/ N .y .i /'O g g [ 22 PRE 55URIZER 40 set i, / ..l.. -e f-/-- + @+ e vl s2+e+" 2-+ 24 '_d 3. 35 34 REACTOR i VESSEL as so ss l 44 4. 23 e @-- 4_@ u=-h- @ ' m. B a n 6 _ a -.-@. 20 - 108 -

FIGURE 6.2-1 ( Con?, ' d ) LOFT RETRAN NODING DIAGRAM O @ ~ '- L @O a 6s g L P 64dk 'I 63;L 0 628 61 k g L 2_ g <r - 109 -

6.3 LOFT Test L6-1 Comparison 6.3.1 LOFT Test L6-1 Transient Description Experiment L6-1 was a loss of steam load anticipated transient and was performed on October 8, 1980 (40). The experiment was initiated from a power level of 36.9 MW by closing the Main Steam Flow Control Valve. (MSFCV) at its maximum rate, resulting in reduced steam flow and degraded l l heat transfer between the primary 'and secondary. The primary pressure increased until 9.1 seconds when pressurizer spray was initiated resulting in a small and short-lived pressure decrease. The primary pressure began to increase again, causing the reactor to scram at 21.8 seconds. The MSFCV then began to open to reduce secondary side pressure. As primary pressure followed the decreasing core power, spray was terminated at 30.4 seconds and the pressurizer backup heaters were activated at 32.5 seconds. The MSFCV i opened and closed automatically at 91.2 seconds and 104.4 seconds, and was manually opened and closed at 312.6 seconds and 339 seconds to regulate secondary pressure. The pressurizer backup heaters were shut off at 415.4 seconds. The experiment was terminated at 700 seconds (40). 6.3.2 RETRAN Modeling for L6-1 Transient Simulation The model described in Section 6.2 was used to analyze LOFT Test L6-1 without modifications. - 110 - v 7--eer .-~+-e ..e- -rr--,ee-'- 1 ---r- <+r- -~-

6.3.3 Comparison of RETRAN Results to LOFT Test Data The response of the LOFT fac'ility to the L6-1 test initiator is described in detail in Reference 40. Data from that document have been plotted with our RETRAN results and are presented here as Figures 6.3-1 through 6.3-5. Only the first 200 seconds of the transient were simulated. Beyond 200 seconds, the plant was in a recovery mode which was dominated by the operators. All important thermal-hydraulic phenomena occurred during the first 200 seconds. The RETRAN and test recorded event sequences have been tabulated 2..d are presented as Table 6.3-1. There is generally very good agreement in both the sequence and timing of events. RETRAN predicts an earlier reactor trip, causing some RETRAN events to occur earlier than the corresponding L6-1 e' ents. More detail on the significance of the event sequence is given in v the discussions of the Figures. Figure 6.3-1 shows the pressure response in the steam generator dome. The RETRAN predicted pressure compares well with measured data. The RETRAN peak pressure is somewhat lower because less energy is deposited in the secondary due to the early scram. The second pressure peak is lower for the same reason. RETRAN did not predict the reopening of the MSFCV at 91.2 seconds because not enough energy had been transferred to the secondary side to cause the pressure to exceed the reopening setpoint. It appears from the slowly rising pressure that, further out in time, RETRAN will calculate a reopening of the MSFCV and exhibit the second dip and climb in steam dome pressure. Figure 6.3-2 shows the steam generator level response (the LOFT wide range indication was used). The RETRAN predicted level response falls - 111 -

somewhere between that of the LOFT wide range (shown) and narrow range (not shown) measurements. While RETRAN does predict the trend and magnitude of the falling level fairly well, whenever the MSFCV is closed, RETRAN does a poor job. This is an artifact of the secondary model. The level is calculated as an equivalent liquid level summing volumes 61 (the steam dome) and 75 (the dow'ncomer). Af ter the MSFCV closes, the pressure builds up in the steam line (volume 64) and a reverse flow is calculated from the steam line to the steam dome. This results in a surge in the equivalent liquid level. As the pressure equilibrates, the level returns to normal. Thus, during the secondary transients caused by the cycling of the MSFCV at 11.6 and 43.2 seconds, RETRAN tends to swing about the true level. Once the secondary pressure stabilized, the RETRAN predicted level closely follows test data. Figure 6.3-3 shows the pressurizer pressure response. RETRAN correctly predicts the initial pressure increase to the pressurizer spray setpoint. Once initiated, RETRAN calculated a slight depressurization due to the spray flow, but the full effectiveness of the spray in reducing the pressure was not seen. Ultimately, the spray could not check the increasing pressure due to level swell, and a scram on high pressure was reached. The scram on high pressure resulted in decreased core heat production and the reopening of the MSFCV. The increased heat transfer to the steam generator along with the decrease in core heat production lead to a swift depressurization of the l primary that did not stop until the MSFCV was again shut. RETRAN predicted a greater depressurization than was measured for two related reasons. First, the RETRAN scram is 4 seconds earlier than the LOFT scram, depriving the primary of a significant amount of energy needed to maintain 1 l pressure. Second, RETRAN calculates the MSFCV to remain open more than 1 - 112 -

7 seconds longer than was measured - resulting in a significant amount of energy removal from the primary. Once the MSFCV was closed, RETRAN calculated an increase in pressure consistent with that seen in the LOFT data, but again with the exception of the depressurization caused by the l unpredicted cycling of the MSFCV at 91.2 seconds. Figure 6.3-4 shows the pressurizer level response (the LOFT data is not density compensated). The RETRAN pressurizer level response agrees well with the LOFT data. Af ter scram, the RETRAN level decreases more than i the LOFT measured level because, as discussed for Figure 6.3-3, there is less energy in the primary system to keep temperature and specific volume up. Figure 6.3-5 shows the primary temperature response at the inlet plenum to the steam generator. The RETRAN results are well within the uncertainty band of the data (f_10.62 F). The RETRAN calculated temperature falls off faster than the measured data due to two factors: the early reactor trip calculated by RETRAN, and the response delay time of the LOFT temperature measurements. 6.3.4 RETRAN Sensitivity Study for LOFT Test L6-1 Two parameters were varied to study their effect on overall pressurizer pressure response in the simulation of L6-1. These parameters were the bubble rise velocity (VBUB) and the interface heat transfer coefficient (IHTC). The overall pressurizer performance was found to be more predictable and stable wher IHTC was the parameter being varied rather than VBUB. For the L6-1 transient, a pressurizer insurge followed by an outsurge with backup heaters on at time zero, it was critical that the !HTC be a very high value. - 113 -

The IHTC actually used in the RETRAN simulation was 27,500 2 BTU /HR-FT -F. Lower values for IHTC resulted in either a too rapid pressurization during the insurge portion of the transient or an underprediction of the value of the pressurizer spray or both. When a low 2 value of IHTC, like 10 BTU /HR-FT -F, is used in concert with a low value of VBUB like 0.6 F/sec (3.0 F/sec is normally recommended), there is some compensating effect on the pressure response to the insurging level. This may be due to the slower transport of the steam bubbles generated by the backup heaters to the pressurizer steam / liquid interfacing region. Once the backup heaters are turned off, the IHTC dominates. The more accurate LOFT RETRAN model uses a high value for IHTC and the normal value of 3.0 2 FT/sec. for VBUB. The values used for this transient,27,500 BTU /HR-FT _p and 3.0 FT/sec., provide good agreement with the LOFT data. 6.3.5 Summary of Results A simulation of the LOFT test L6-1 was performed using the RETRAN 02 Mod 3 computer code. Figures showing comparisons of RETRAN calculated and LOFT test measured data have been presented for the pressure in the steam generator dome, the steam generator level, the pressure in the pressurizer, the level in the pressurizer, and the temperature of the primary coolant in the steam generator outlet plenum. In every case, RETRAN calculated both the general trends and the relative magnitudes of the data within acceptable bounds. A sensitivity study was conducted to determine the best value of IHTC and VBUB in the pressurizer for this transient. - 114 -

Table 6.3-1 Sequence of Events for Experiment L6-1* Time After Experiment Initiation RETRAN Time Event (seconds) (seconds) MSFCV closing initiated 0.0 0.0 Pressurizer backup heaters off 6.1 11 7.07 0 Pressurizer spray on 9.1 1,0.1 9.47 MSFCV closed 11.6 12 11.61 0 Reactor scrammed 21.3 12 17.67 0 Maximum PC5 pressure reached 22.0 12 IS 0 MSFCV opened 22.2 12 18.61 0 QSG > 9 26.5 15 25 0 core Pressurizer spray off 30.4 11 21.46 0 Pressurizer backup heaters on 32.5 11 23.8 0 MSFCV closed 40.6 12 43.23 0 MSFCV opened 91.2 12 0 MSFCV closed 104.4 12 0 Only the first 200 seconds are presented. Pressurizer liquid level at maximum.

      • This event not predicted by RETRAN.

- 115 -

s FIGURE 6.3-1 LOFT TEST L6-1 PRESSURE IN STEAM GENERATOR DOME 8 TEST DATA RETRAN 1100 4 I j. ~ j \\,. p 1000 s- \\ 2 4. .9

E

\\ ! E ~ t. e j 3 e I a E j 900 E i E 6 j l i i i 800 5 -50 0 50 100 150 200 Time After Initiation (s) - 116 - o 1

FIGURE 6.3-2 LOFT TEST L6-1 UQUID LEVEL IN STEAM GENERATOR SECONDARY SIDE 0.2 7 i WIDE RANGE 0.5 RETRAN I. I 0.0 o.o .lg I. i 1 ;. \\ l\\ I. \\ l-l \\. - - o.5 j ! O E - 0.2 j ! l 3 !i \\. 3 l j-i. - i.o \\ 3 '5 I- .E s cr 3 -o. s \\ i \\ -1.5 i i A

  1. .\\ A.

i. l - 0.6 i 1.-- - 2.0 l . ~

.\\!

I \\!i! - 2. 5 - o. a -50 0 So 10 0 15 o 200 Time After Initiation (s) - 117 -

FIGURE 6.'3-3 LOFT TEST L6-1 PRESSURE IN PRESSURIZER 16.0 i TEST DATA 2300 RETRAN l. 2 j i 15.5 j 2250 .i I-I l ,i l l }\\ 2200 I i i 15.0 j l I i O a bie h t.d k b .m. j 2150 -T,.,, i a e B 5 14.5 u$ 2100 i h I 2050 t. ./ p 14.0 ./ I-\\. .s- /.' f I. './ - 2000 \\-g.N.,,_,.j.,./ 13.5 e 1950 -50 0 50 100 15 0 200 Time After initiation (s) - 118 -

O FIGURE 6.3-4 LOFT TEST L6-1 LIQUID LEVEL IN PRESSURIZER 1.5 i TEST DATA 4.8 RETRAN g (\\ i\\ .i J.6 1.4 ' l \\ \\. E 4,4 i E j. a$ 1.3 j 4.2 3 .? -I cr a i i \\ 4.0 g 1.2 \\-g \\ l / '\\, l ' ~._.._._._.-.- ~, - 3.8 u -50 0 50 100 150 200 Time Af ter Initiation (s) 119 - i

4 FIGURE 6.3-5 LOFT TEST L6-1 COOLANT TEMPERATlJRE IN INTACT LOOP STEAM GENERATOR PRIMARY SIDE INLET PLENUM 575 i a i i TEST DATA RETRAN 3 ,/ I, 570 I1 ii f 570 C. j ~ k I, 560 f e 2 1-I, E 3 o a 3 565 - 1 2 ta \\ \\ \\ 8 C t. o o o k \\. U $50 560 - '-g ~ ~.~._._._._._ t 555 -50 0 50 100 150 200 / ' Time After Initiation (s) - 120 -

6.4 LOFT Test L6-3 Comparison 6.4.1 LOFT Test L6-3 Transient Description Experiment L6-3 was an excessive load increase anticipated transient and was performed on October 9, 1930 (40). The experiment was initiated from a power level of 36.9 MW by ramping the MSFCV open at its maximum rate. Secondary steam flow increased and caused a cooldown in the primary coolant system. The cooldown and its associated primary coolant density increase caused reactor powe: to increase and pressurizer level to decreae. The decreasing level caused Primary Coolant System (PCS) pressure to drop and the reactor to trip on low pressure at 15.6 seconds. Pressure continaed to decrease and, at about 26.5 seconds, the HPSI pumps began to inject emergency core coolant into the cold leg. The PCS pressure reached a minimum at 26.3 seconds. The MSFCV was closed at 36.2 seconds. With core heat production exceeding secondary heat removal at 33 seconds, the PCS temperature and pressure began to rise. At about 48.6 seconds, the HPSI pumps were shut off by the operators. Pressurizer cycling heaters shut off at 154.9 seconds. To maintain pressurizer liquid temperature, the pressurizer backup heaters were turned on by the operators at 536.8 seconds. The operators turned the cycling heaters on at 554.0 seconds. The backup heaters and cycling heaters were turned off by the operators at 564.6 seconds and 565.4 seconds, respectively. The operators turned the backup heaters on again at 600.2 seconds. The experiment was terminated at 700 seconds. - 121 -

6.4.2 RETRAN Modeling for L6-3 Transient Simulation The base LO'FT deck was set up for the L6-1 transient. Few modifications were required to simulate the L6-3 test. The most prominent modification was the addition of a High Pressure Safety Injection (HPSI) system. This was modeled simply by connecting two fill junctions to the cold leg and regulating their flow with a pressure dependent

  • rip signal.

6.4.3 Comparison of RETRAN Reruits to LOFT Test Data The response of the LOFT facility to the L6-3 test initiator is detailed in Reference 40. Data from that document have been plotted with our RETRAN results and are presented here as Figures 6.4-1 through 6.4-5. Only the first 200 seconds of the transient were simulated. All important thermal-hydraulic phenomena occurred during that time period. The RETRAN calculated and test recorded event sequences have been tabulated and are presented as Table 6.4-1. There is generally good agreement in both the sequence and timing of significant events. RETRAN predicts an earlier reactor trip on low pressure in the hot leg, causing all subsequent RETRAN events to occur earlier than the corresponding L6-3 events. More detail on the significance of the event sequence is given in the discussion of the Figures. Figure 6.4-1 shows the pressure response in the steam generator dome. RETRAN correctly ca!culated both the rate and timing of the depressurization due to the opening of the MSFCV. The magnitude of the depressurization was underpredicted, but that can be attributed to the earlier RETRAN reactor trip signal and the resulting earlier closure of the MSFCV. - 122 -

As the MSFCV closes, the steam flow decreases and the secondary pressure increases. The RETRAN repressurization curve rises more gently and steadies at a lower pressure than the LOFT data. This behavior is partly because less energy is being deposited in the secondary due to the early scram, but mostly it is due to a somewhat higher terminal steam flow and feedwater flow in the PETRAN calculation. Figure 6.4-2 shows the steam generator level response (the LOFT wide range indication was used). RETRAN calculated both the trends and magnitudes of the level response reasonably well with the exception of a large level swing calculated to occur at 43.5 seconds. As explained in Section 6.3.3, this swing is an artifact of the secondary model. The level is calculated as an equivalent liquid level summing volumes 61 (the steam dome) and 73 (the downcomer). Af ter the MSFCV closes, the pressure builds up in the steam line (volume 64) and a reverse flo'v is calculated from the steam line to the steam dome. This results in a surge in the equivalent liquid level. As the pressure equilibrates, the level returns to normal. Figure 6.4-3 shows the pressurizer pressure response. RETRAN correctly predicts the initial pressure decrease due to the rapid cooldown and level shrink. The rate of depressurization is somewhat less than in the LOFT test because the RETRAN pressurizer was initialized at a slightly lower pressure (2143 psi). This pressure is below the setpoint for the backup heaters and so they came on at time zero. The energy delivered by the heaters in the first 10 seconds before the heaters came on in the LOFT test helped keep the pressure up. The additional heater input also contributed to the RETRAN minimum pressure being higher than the test minimum. Another reason for the higher minimum pressure is that the RETRAN HPSI pumps deliver flow i (on low pressure in the cold leg) about 3 ceconds earlier. The added flow - 123 -

helps to maintain pressurizer level and keep the pressure high. The last effect worth noting is that the pressure does not recover to the same level es found in the test data. In fact, the pressure does not quite reach the setpoint to reset the pressurizer heaters. The reason is the same as that given for the steam generator pressure recovery. A combination of decreased core power input and higher energy removal through the secondary (caused by increased steam flow and feedwater flow over that measured in the test) retards the peak pressure level. Figure 6.4-4 shows the pressurizer level response. The RETRAN pressurizer level response decreased at the same rate and reached a minimum at about the same time as measured in the experiment. The RETRAN minimum level is greater than the LOFT minimum because of the additional HPSI flow (as discussed for the pressurizer pressure). The RETRAN level does not recover to the same level as in the test because there is less expansion of the primary coolant due to a lessened primary side heatup. This is due to more energy being transferred to the secondary side and less overall heat input from the core. Figure 5.4.-5 shows the primary temperature response at the inlet plenum to the steam generator. RETRAN predicts the correct trend and the magnitude is within the uncertainty band of the cfata (1 10.62 F). The steeper slope of the RETRAN cooldown can be attributed primarily to the re.sponse delay time of the LOFT temperature measurements. 6.4.4 RETRAN Sensitivity Study for LOFT Test L6-3 The two sensitivity studies performed for LOFT Test L6-3 examined i various values of the IHTC, and the effect of HPSI delivery to both the cold leg and the hot leg as opposed to delivery to just the cold leg. - 124 -

For the IHTC investigation, the IHTC was varied from 10 to 30,000 2 BTU /HR-FT -F with a broad range of effects on both the pressurizer pressure and temperature. The value used for the final analysis was 400 2 BTU /HR-FT -F. For large values of IHTC, greater than about 6000 2 BTU /HR-FT -F, there is excessive heat transfer in the pressurizer and temperatures are depressed. A small value of IHTC will reduce the heat transfer in the pressurizer, thus leading to repressurization rates and i pressures that are consistent with the observed data for a transient in which there is: an initial outsurge, followed by an insurge into the pressurizer. Values which are too small, less than about 10 BTU /HR-FT'-F, lead to an overprediction of the repressurization rate and pressures. For the HPSI delivery location study, it was found that injecting cold HPSI flow into the hot leg volume upstream of the pressurizer caused excessive depressurization because some of the cold HPSI water entered the pressurizer. Injecting both the A and B HPSI pumps into the cold leg allowed the core to heat the water before entering the hot leg. This latter method was used in both the LOFT test and the RETRAN rimulation. 6.4.5 Summary of Results A simulation of the LOFT test L6-3 was performed using the RETRAN 02 Mod 3 computer code. Figures showing comparisons of RETRAN calculated and LOFT test measured data have been presented for the pressure in the steam generator dome, the steam generator level, the pressure in the pressurizer, the level in the pressurizer, and the temperature of the primary coolant in the steam generator and outlet plenum. In every case, RETRAN calculated both the general trends and the relative magnitudes of the data - 125 -

within acceptable bounds. A sensitivity study was conducted to determine the best value of pressurizer IHTC and HPSI injection loc:2 tion for this transient. - 126 -

Table 6.4-1 Sequence of Events for Experiment L6-3* Event LOFT Time RETRAN Time MSFCV Opening 0.0 0.0 Feedwater Flow Increased 1.4 12 0.0** Pressurizer Backup Heaters On 10.2 11 0.0 Maximum Reactor Power 15.612 14.13 Reactor Scrammed 15.612 14.13 Feedwater Flow Terminated 16.6 12 15.0 MSFCV Start Closing 17.3 12 15.0 HPSI Pump A On 26.4 12 13.5 HPSI Pump B On 26.6 +.2 13.5 Minimum PCS Pressure Reached 26.8 12 30.5 Qc<Q 33 1 1 32.25 3 core MSFCV Closed 36.2 12 34.00 HPSI Pump A Off 48.6 12 44.14 HPSI Pump B Off 50 12 44.14 Pressurizer Backup Heaters 'Off 105.4 11 i Pressurizer Cycling Heaters Off 154.9 11 Only events occuring in the first 200 seconds of the LOFT Test are presented. RETRAN Feedwater was delivered by a fill junction designed to match the LOFT data. Pressurizer liquid level at minimum. RETRAN did not predict this event. - 127 -

FIGURE 6.4-1 LOFT TEST L6-3 PRESSURE IN STEAM GENERATOR DOME 6.5 3 TEST DATA _.. _ _. _. - RETRAN 900 6.0

5. 5 800 c2

~

s a

n "*~'_,.._.__.- -- l l 2 \\. E A 5.0 ),\\ \\ l 700 \\ i 1-\\- 4.5 \\ j/-l-v_ 600 4.0 -50 0 50 100 150 200 Time After Initiation (s) - 128 - 3

FIGUEE 6.4-2 LOFT TEST L6-3 LIQUID LEVEL IN STEAM GENERATOR SECONDARY SIDE 0.5 p, i\\ .i ! WIDE RANG 6 !1 RETRAN !i 1 I i .i \\. I i i 0.0 I j.\\ o G \\ u \\ O 'g-I !2 1 -i 3 3 s b i 3 i .7 - 0.5 l .I I I. -2 i1l\\ '\\.

i. l\\.x h

- -. -... _. - -3 - 1.0 -50 0 50 100 150 200 Time After initiation (s) - 129 -

h FIGURE 6.4-3 LOFT TEST L6-3 PRESSURE IN PRESSURIZER 16 ~ TEST DATA _._. _.- R ETR A N 4 2200 15 _. pp _, _ s a )

s

/.- 8 c. ~ e / 2100 5 / 2 ll: / 3 E i E I i E 1 i 14 j j \\ i \\ j 2000 g \\ I \\i \\iu 1900 e e 33 -50 0 50 100 150 200 Time After Initiat on (s) - 130 - ~ O

FIGURE 6.4-4 LOFT TEST L6-3 LIQUID LEVEL IN PRESSURIZER 1.2 1 i i \\ TEST DATA RETRAN 3.5 1.0 a E O g 3.0 }* i "2 y 5 t .E s \\. a \\ 'g O.8 / \\- j - 2.5 / 0.6 I -50 0 50 100 150 200 Time After Initiation (s) - 131 -

FIGURE 6.4-5 LOFT TEST L6-3 COOLANT TEMPERATURE IN INTACT LOOP STEAM GENERATOR PRIMARY SIDE INLET PLENUM 570 i i i i TEST DATA RETRAN 560 g i i i i i I 550 g 560 g I ~ e 2 i E I { Ts k j 540 a \\ t l 8 i e I V 550 } 530 0 - 520 \\ t, \\ 5 ~~~,,.. Ss0 \\ t i i 510 -50 0 50 100 15 0 200 Time After Initiation (s) - 132 -

7.0

SUMMARY

AND CONCLUSIONS In response to NRC Generic Letter 83-11 and as part of the Inhouse Safety Analysis Capability Development Project, BG&E has presented the results of nine analyses of Calvert Cliffs and the LOFT Facility vrith the RETRAN computer code in this topical report. These RETRAN calculations were compared to measured plant transient data, calculations performed with the TRAC advanced best estimate computer code, and LOFT test data. The matrix of the nine RETRAN analyses is delineated and cross-referenced in Table 7-1 to the applicable report section. The key simulation parameters; i.e, type of model used, transient time, and initial power level are presented for these nine analyses in Table 7-2. This table shows that each of the three Calvert Cliffs RETRAN models and the LOFT RETRAN model are utilized in at least two different analyses. Furthermore, simulation times of zero (steady state) to 192 minutes were required for the calculations in this report. Finally, these RETRAN models were initiated from 0%, 20%, 40%,74%,30% and 100% of full power. Table 7-3 delineates specific thermal-hydraulic phenomenology evaluated and tested in the nine RETRAN analyses of this report. The BG&E l CCNPP RETRAN model components verified in these analyses include: Reactor Coolant Pump, Steam Generator, Primary Coolant Loop, Pressurizer, ADV, TBV, PORV, SRV, HPSI, and Reactor Vessel. The RETRAN Calvert Cliffs model enhancements, refinements and insights which resulted from the analyses documented in this report are presented in Table 7-4. This topical report has demonstrated BG&E's capability to model the l Calvert Cliffs Nuclear Power Plant with the RETRAN computer code. BG&E has verified the accuracy of these RETRAN models by performing best - 133 -

estimate analyses of Calvert Cliffs and LOFT transient thermal-hydraulic behavior. This process has served to validate our models while substantiating i the capabilities of BG&E RETRAN code users. F e - 134 -

Table 7-1 RETRAN ANALYSIS MATRIX REPORT SECTION TRANSIENT MODELED WITH RETRAN 4.1 CCNPP 2 Multiple secondary side malfunction event 4.2 CCNPPI Four reactor coolant pump coastdown test 4.3 CCNPPI Reactor coolant pump combination flow test 4.4 CCNPPI One reactor coolant pump coastdown test 4.5 CCNPPI Total loss of flow - natural circulation test 5.2 CCNPP Cooldown to RHR entry with ADVs and APS TRAC calculation 5.3 CCNPP Runaway main feedwater to one steam generator TRAC calculation 6.3 LOFT test L6-1 reduced secondary side heat removal 6.4 LOFT test L6-3 excessive secondary side heat removal - 135 -

Table 7-2 RETRAN ANALYSIS KEY MODELING PARAMETERS Transient Initial Power Level Percent of Repert Section RETRAN Model Used Time Megawatts Full Power I 4.1 Two Loop CCNPP 360 seconds 2700 100 I 3 4.2 One Loop CCNPP 55 seconds 512 20 I 3 Four Loop CCNPP 55 seconds 512 20 I 4.3 Four Loop CCNPP Steady State 0 0 I 3 4.4 Four Loop CCNPP 60 seconds 2043 30 I 3 4.5 Two Loop CCNPP 37 minutes 1024 40 I 5.2 One Loop CCNPP 192 minutes 2700 100 I 5.3 Two Loop CCNPP 60 minutes 2700 100 2 6.3 Two Loop LOFT 200 seconds 36.9 74 2 6.4 Two Loop LOFT 200 seconds 36.9 74 1 CCNPP = Calvert Cliffs Nuclear Power Plant Model 2 LOFT = Loss of Fluid Test Model 3 These tests were performed when the CCNPP licensed power level was 2560 MWt. - 136 -

Table 7-3 RETRAN ANALYSIS PHENOMENOLOGY Report Section

  • Event Symmetry Phenomenology Simulated and Evaluated 4.1 A

Pressurizer thermal-hydraulics, steam generator l heat transfer, moderate primary coolant system (PCS) cooldown and depressurization 4.2 S Four reactor coolant pump (RCP) coastdown, loop flow resistance 4.3 A/S Combinations of RCP operating loop resistance, abnormal, short-circuit and reverse flow paths in the l primary coolant system 4.4 A Single RCP coastdown and loop flow resistance 4.5 S Natural circulation flow and heat transfer in the primary and secondary system 5.2 S Steam generator heat transfer, atmospheric dump valve thermal-hydraulic performance, auxiliary pressurizer spray thermal-hydraulic performance, slow PCS cooldown and depressurization 5.3 A Normal and reverse steam generator heat transfer, rapid asymmetric PCS cooldown and depressurization, steam full and water solid pressurizer, steam generator upper tube voiding 6.3 S Pressurizer spray flow interaction, pressurizer thermodynamics, primary and secondary response to changing steam demands, primary to secondary heat transfer, reactor kinetics 6.4 S HPSI injection location, pressurizer level effect on pressure, primary and secondary response to changing steam demands, reactor kinetics A = Loop Asymmetric S = Loop Symmetric - 137 -

Table 7-4 Calvert Cliffs RETRAN ModelImprovements and Lessons Learned REPORT SECTION REFINEMENTS, ENHANCEMENTS OR INSIGHTS 4.1 For a rapid pressurizer insurge transient, High IHTC, Surgeline Loss Factor, Initial Spray Line Temperature and Two Node Pressurizer significantly affect pressure and level response. Spray junction model, rainout velocity and pressurizer heat slabs have no significant effect. Non-condensible gases and normal operational spray flow, heater operation and ambient heat losses don't affect pressurizer performance. Uncertainties in actual spray flow rate and performance can significantly affect pressurizer response. 4.2 The RETRAN Four Loop model predicts a slightly closer four RCP coastdown than the One Loop model in comparison to plant data. 4.3 Downcomer crossflow junction and accurate RCP locked rotor reverse flow pressure loss coefficient are important for less than four RCP operation steady state loop flow calculations. The value of downcomer crossflow junction loss coefficient does not significantly affect (4-N) RCP operation. Three abnormal loop flow paths were identified for (4-N) RCP operation. 4.4 Varying RCP moment of inertia and rated torque significantly affect flow coastdown. Larger values of moment of inertia have the same effect as smaller values of torque. Downcomer crossflow and RCP locked rotor reverse flow loss coefficient do not significantly affect flow coastdown. 4.5 Early post trip primary and secondary thermal-hydraulic response is affected by the timing of TSV closure and ADV/TBV opening. 5.2 The rate of pressurizer depressurization is strongly dependent on pressurizer spray flow. For cooldowns using the ADVs, it is important to model the ADV mass flow accurately. For long cooldown and depressurization transients, the value of IHTC has no effect. 5.3 A large SG tube volume with the bubble rise model and enthalpy transport turned off in the SG allows simulation of SG tube voiding. Pressurizer model IHTC does not affe-t pressurizer outsurge transients. 6.3 A high value for the IHTC is needed to properly model the pressure and level response of a pressurizer undergoing an insurge transient (See 4.1). 6.4 For transients in which there is an initial outsurge followed quickly by an insurge into the pressurizer, the value of IHTC must be small to properly calculate the pressure and level response. - 138 -

8.0 REFERENCES

1. NUREG-0606 Volume 7 No. 2, " Unresolved Safety Issues Summary", Pressurized Thermal Shock Unresolved Safety Issue A-49, 2. NUREG-CR-4022 - ORNL/TM-9408, " Pressurized Thermal Shock Evaluation of the Calvert Cliffs Unit i Nuclear Power Plant", September,1985. 3. N. N. Nesselbeck, D. A. Prelewicz, A. Woodhouse (ENSA) and T. L. Cook and M. C. Key (BG& E), " Comparison of RETRAN-02 and TRAC-PF1 Simulations for a Steamline Break Overcooling Transient", International Nuclear Power Plant Thermal-Hydraulics and Operations Topical Meeting, Taipei, Taiwan October 22-24, 1984. 4. T. L. Cook, S. M. Mirsky and M. C. Key, "A RETRAN Analysis of Calvert Cliffs Feed and Bleed Capability", Winter ANS Meeting, Washington, D.C. (ANS Transactions Vol. 47), November 11-16, 1984. 5. USNRC Generic Letter No. 83-11, " Licensee Qualification for Performing Safety Analyses in Support of Licensing Actions", February 8,1983. 6. EPRI NP-408, "RETRAN - A Program for One-Dimensional Transient Thermal-Hydraulic Analysis of Complex Fluid Flow Systems", January,1977. 7. EPRI CCM-5, "RETRAN - A Program for One-Dimensional Transient Thermal-Hydraulic Analysis of Complex Fluid Flow Systems",1978. 8. EPRI CCM-5, Vol.1, "RETRAN - A Program for One-Dimensional Transient Thermal-Hydraulic Analysis of Complex Fluid Flow Systems",1978. 9. EPRI NP-1850-CCM, "RETRAN - A Program for Transient Thermal-Hydraulic Analysis of Complex Fluid Flow Systems", Volume 1 (Revision 2) - November,1984; Volume 2 - May,1981; Volume 3 - May,1981; Volume 4 - January,1983; Volume 5 (Draf t) - January,1983. 10. Letter to Dr. Thomas W. Schnatz, Chairman of Utility Group for Regulatory Application, from Cecil O. Thomas, Chief St.tndardization and Special Projects Branch, Division of Licensing, U.S. Nuclear Ryulatory Commission, September 4, 1984. 11. Memo from 3. E. Thorp to CCNPP POSRC, "14 Day Post Trip Review", October 24, 1983. 12. LER 83-54/3L, Docket No. 50-318, License No. DPR-69, Event Date - September 11, 1983 - Report Date - November 10,1983. 13. E. Imbro, USNRC AEOD Engineering Evaluation Report No. AEOD/E415, June 6, 1984. 14. Sang-Nyung Kim, PhD Thesis, MIT, "An Experimental and Analytical Model of a Pwr Pressurizer During Transients",1984. - 139 -

13. Hamid Reza Saedi, MS. Thesis, MIT, "Insurge Pressure Response and Heat Transfer for Pwr Pressurizer," 1983. 16. Phone conversatiori between S. M. Mirsky and R. E. Denton (Calvert Cliffs), January 22,1985. 17. Phone Conversation between S. M. Mirsky and Elliott Johnson of Edwin L. Wiegand Company, January 22,1985. 18. Westinghouse Electric Corporation Power Generation Turbine First Stage Pressure Curve AF114-0338, June 19,1973. 19. Memo from R. B. Sydnor to Steve Mirsky, "TSC Point Tolerances and Response Times", December 23,1983. 20,

3. A. Redfield and S. G. Margolis, " TOPS - A FORTRAN Program for the Transient Thermodynamics fo Pressurizers", WAPD-TM-545, Section IV, App.1, December 1965.

21. Baltimore Gas and Electric Co., Calvert Cliffs Nuclear Power Plant, Unit i Startup Test Report, August 29,1975. 22. A. S. Pallotta and Z. A. Akcasa, " Transient Analysis of Feedwater Heaters," Nuclear Engineering Department, University of Michigan,1975. 23.

3. G. Collier, " Condensation", Brookhaven/ Hemisphere Two-Phase Course. October 30 through November 3,1978.

24. F. Kreith, Principles of Heat Transfer. (International Textbook Company, Scranton, PA,1961). 25. W. H. McAdams, Heat Transmission (McGraw Hill Book Company, New York, NY, 1954). 26.

3. P. Holman, Heat Transfer (McGraw Hill Book Company, New York, NY 1981).

27. P. Cohen, Water Coolant Technology of Power Reactors 1980, ANS. 28. Mark T. Leonard, PhD Thesis, MIT, "The Effects of a Non-condensible Gas on Pressurizer Insurge Transients," 1984. 29. Calvert Cliffs Final Safety Analysis Report. 30. Baltimore Gas and Electric Company Calvert Cliffs Nuclear Power Plant Unit 1, Startup Test Report, Docket No. 50-317, License No. DPR-33, August 29,1975. 31. "CESEC - Digital Simulation of a Combustion Engineering Nuclear Steam Supply System", Plant Systems Analysis, December,1981. 32. Letter to S. M. Mirsky (BG&E) from R. R. Mills (CE), BG&E-85-207,"Calvert Cliffs Reactor Coolant Pump Flow Factors", August 7,1985. - 140 -

33. Yoram Zvirin, "A Review of Natural Circulation Loops in Pressurized Water Reactors and Other Systems", Nuclear Engineering and Design, Volume 67,1981. 34. NUREC/CR-3567 LA-9944-MS TRAC-PFl: An Advanced Best-Estimate Coalputer Program for Pressurized Water Reactor Analysis, February,1984. 35. Gregory D. Spriggs, Jan E. Koenig, and Russell C. Smith, NUREG/CR-4109 LA-10321-MS TRAC PFI Analyses of Potential Pressurized-Thermal-Shock Transients at Calvert Cliffs / Unit 1 - A Combustion Engineering PWR, February 1985. 36. Richard P. Je'nks (LANL), LA-UR-84-3947, "Cooldown to Residual Heat Removal Entry Conditions Using Atmospheric Dump Valves and Auxiliary Pressurizer Spray Following a Loss-of-Offsite-Power at Calvert Cliffs - Unit 1". 37. N. N. Nesselbeck, D. A. Prelewicz, A. Woodhouse (ENSA) and T. L. Cook and M. C. Key (BG&E), " Comparison of RETRAN-02 and TRAC-PF1 Simulations for a Steamline Break Overcooling Transient", International Nuclear Power Plant Thermal-Hydraulics and Operations Topical Meeting, Taipei, Taiwan October 22-24, 1984. 38. Charles L. Nalezny, " Summary of Nuclear Regulatory Commission's LOFT Program Experiments", NUREG/CR-3214, EGG-2248, July,1983. 39. Douglas L. Reeder, " LOFT System and Test Description (5.5-ft. Nuclear Core ! Loces)", NUREG/CR-0247, TREE-1208, July,1978. 40. Doyle L. Batt and Janice M. Carpenter, " Experiment Data Report for LOFT Anticipated Transient Experiments L6-1, L6-2 and L6-3", NUREG/CR-1797, EGG-2067, December,1980. - 141 - _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _.}}