SHOREHAM NUCLEAR POWER STATION L--
P.O. BOX 618, NORTH COUNTRY ROAO e WADING RIVER, N.Y.11792 August 26, 1982 SNRC-759 Mr. Ilarold R. Denton, Director Office of Nuclear Reactor Regulation U.S.
Nuclear Regulatory Commission Washington, D.C.
20555 PSI Relief Requests Shoreham Nuclear Power Station - Unit 1 Docket No. 50-322
Dear Mr. Denton:
Attached please find shoreham's relief requests for the Preservice Inspection Program.
It must be noted that the PSI Program imple-mentation is about 98% complete to date.
If the final completion of this program results in any additional relief requests, they will also be forwarded to you.
At present, it does not appear that additional relief will be required.
If you have any questions with respect to this matter, we will be happy to discuss them with you at your earliest convenience.
Very truly yours, Y
J. L.
Smith Manager, Special Projects Shoreham Nuclear Power Station CKS:mp 000 Attachment cc:
J.
Iliggins All parties 8208300137 820826
~
PDR ADOCK 05000322 D
s RELIEF REQUEST NO. 1 I.
IDENTIFICATION OF COMPONENTS:
Class I, Category J-1, pressure retaining welds in piping.
(See Attachment.)
II.
CODE REQUIREMENT Paragraph IS-232 of the ASME Code Section XI, 1971 Edition, requires that a volumetric examination of 100% of circumferential and longitudinal pipe welds, excluding.those welds exempt per IS-121, be performed completely (as preservice examination) prior to initial plant startup.
III. RELIEF DESCRIPTION Relief is required from the ASME Secti'on XI examinations noted on the attachment on the basis of partial inaccessibility of the weld and required volume due to plant design.
IV.
BASIS FOR RELIEF The basis for requesting relief from ASME Section XI examination requirements is as follows:
1.
The structural integrity of the piping pressure boundary was demonstrated during construction by meeting the requirements of the ASME Code Section III.
All welds were inspected in accordance with the appropriate Code requirements, weld techniques and
welders were qualified in accordance with code requirements and materials were purchased and traced;in accordance with the appropriate Code and NRC requirements and guidelines.
Finally, the pressure boundary was " proof tested" after installation by the application of a 1.25 times the design pressure hydrostatic test.
2.
Complete examinations meeting the requirements of'the ASME Code Section XI were performed on welds of similar configurations which utilized the same weld techniques,(
procedures and materials.
The inspected welds are subject to the same operating and environmental t.
4 conditions as the partially' inspected welds.
It is, therefore, reasonable to extend the acceptable results on the inspectable welbs to the partially inspectable welds.
-3.
Ninety percent (90%) or greater coverage of each of,the partially inspectable welds (see attachment) was achieved.
Since the'c'onstruction, operating conditions and environmental conditions on the non-inspected portion of the weld are identical to the inspected area, it is reasonable to extend the satisfactory results to the non-inspectec. areas.
s.
9
1
- s' i
}-
.a -
e t;-
v.
4j.
2
.L
+.
The-Edition'E,f-thesASME, Code.Section XI which.is 4.
currently-applicable'for Inservice Inspection actnally.
. : 4-
- c.D t
decreases the volume required. t_ o b e z-inspected.
- / i
.t Therefore, for s'ubsequent Inter'vice Inspection,. the
.3
~
_'c, s
- percentage of non-inspectable volume will either
-A f
. decrease or remain ' the same - (see attachment).
The effect will be to' improve Shoreham s conformance to
)e i
ASME Code'r'equirements for future Inse$vice gnspections.
j,,
i k'
f*
g y *,
W c
.e' s
~
L g
,j$
r
-i r
y A
g,
- s t
4 i.
s.
Y f
j.
>#p d
c 4
4
'k' L8 U
,,1
..),f -
4 m
e-
, t?
'r*
n i.
t 5
i;
-e 1
- 1
- t gy l.jkl
(.
,M
~
^
F,.
./
RELIEF REQUEST NO. 1 Attachment
^ '
WELD IDENTIFICATION ESTIMATED % OF PREDICTED % COMPLETION' NUMBER SYSTEM CONFIGURATION NATURE OF OBSTRUCTION SCAN COMPLETED OF SCAN FOR ISI B21-NS001-BW15 Main Steam Pipe to Valve Location of Branch Connection 97.5 98 B21-NS003-BW12 Main Steam Pipe to Valve Location of Branch Connection 97.5 98 B21-NS004-BW12 Main Steam Pipe to Valve Location of Branch Connection 97.5 98 E21-IC-173-FW6 Main Steam Pipe to Valve Location of-Branch Connection 97.0 100 B21-IC-175-FW6 Main Steam Pipe to Valve Location of Branch Connection 97.0 100 B21-IC-173-FW1 Main Steam Pipe to Valve Location of Branch Connection 95.5' 98 B21-IC-175-FW1 Main Steam Pipe to Valve Location of Branch Connection 94.9 98 RS-1-B2-A-U1 Recirc.
Longitudinal Geometry of Tee 90.0 90 Weld on Tee RS-1-B2-A-U2 Recirc.
Longitudinal
. Geometry of Tee 90.0 90 Weld on Tee B31-NS006-BWO2-dl Recire.
Longitudinal Geometry of Tee 90.0 90 Ueld on Tee B31-NS006-3WO2-d2 Recirc.
Longitudinal Geometry of Tee 90.0 90 Weld on Tee RD-1-D2-E-dl Recirc.
Longitudinal Geometry of Tee 90.0
'a0 RD-1-B2-E-d2 Weld on Tee RD-1-B3-E-ul Recirc.
Longitudinal Geometry of Cross 90.0 90 RD-1-B3-E-u2 Weld on Cross E41-986E HPCI Pipe to Nozzle Location of Branch 95.8 98 Connection RD-1-A2-E-dl Recirc Longitudinal Geometry of Tee 90.0 90 RD-1-A2-E-d2 Weld on Tee E41-IC182-FW3 IIPCI Pipe to Valve Location of Branch 96.2 98 Connection RD-1-A3-E-ul Recirc Longitudinal Geometry of Cross 90.0 90 RD-1-A3-E-u2 Weld on Cross E41-IC182-FW2
!!PCI Pipe to Valve Location of Branch 96.2 98 Connection
i RELIEF REQUEST NO. 2 I.
-IDENTIFICATION OF COMPONENTS:
Class I, Category J-1, pressure retaining welds in piping.
(See Attachment.)
II.
CODE REQUIREMENT:
Paragraph IS-232 of the ASME Code Section XI, 1971 Edition requires that a volumetric examination of 100% of circumferential and longitudinal pipe welds, excluding those welds exempt per IS-121, be performed completely (as a preservice examination) prior to initial plant startup.
III. RELIEF DESCRIPTION Relief is required from the ASME Section XI examina-tions noted on the attachment on the basis of partial inaccessi-bility of the weld and required volume due to. plant design.
17.
BASIS FOR RELIEF The justification for requesting relief from ASME Section XI examination requirements is as follows:
1.
The structural integrity of the piping pressure boundary was demonstrated during construction by meeting the requirements of the ASME Code Section III.
All welds were inspected in accordance with the L
-appropriate Code requirements,. weld-techniques and welders were qualified'in accordance with Code requirements:and' materials were purchased and traced in accordance with the appropriate Code and NRC requirements and-guidelines.
Finally, the pressure boundary was " proof tested" after installation by the application of.a 1.25 times the design pressure hydrostatic test.
~2.
Complete examinations meeting the requirements of the ASME Code Section XI were performed on welds of similar configurations which utilized the same weld techniques, procedures 1and materials.
The inspected welds are subject to-the same operating and environmental 4.
conditions as the partially inspected welds.
It is, therefore, reasonable to extend the acceptable results on the inspectable welds to the partially inspectable welds.
1 3.
A substantial percent coverage of each of the partialb inspectable welds (see attachment) was achieved.
Since the construction, operating conditions and environmental conditions on the non-inspectable portions of the weld are identical.to the inspected area, the satisfactory results of the. inspected areas i~
can be extended-to the non-inspected area.
5
-..--,..,.m,
,v.
,r.
-.v,;
.,.,.-,e.
w
,w,
-r s
4.-
' The Editiion of.the 'ASME ' Code Section XI which is currently' applicable-for Inservice Inspection actually; decreases,the volume required lto be inspected.
Therefore, for subsequent ~ Inservice Inspection, the i
- percentage ~of non-inspectable volume.will.either
' decrease or remain'the same (see. attachment). :The effect will-be to improve'Shoreham's conformance-to.
l ASME Code l requirements for future Inservice 1
Inspections.
'I I
e k
~
J r
4 i
T v 7p y
y->
9 3
, + +,.
,,m4 tr-r,-,,y.
, - - 9
,r,u,
,-3
--ww,g p,
.,e, y
,y,+
.,.v.
~#
-RELIEF REQUEST NO. 2 Attachment WELD IDENTIFICATION ESTIMATED % OF PREDICTED % COMPLETION NUMBER SYSTEM CONFIGURATION NATURE OF OBSTRUCTION SCAN COMPLETED OF SCAN FOR ISI B31-NS005-BW33
.Recirc.
Pipe Cap Part Geometry 77.7 98 B31-N5005-BW34 Recirc.
Pipe Cap Part Geometry 63.2; 98 B31-NS005-BW36 Recirc.
Pipe Cap Part Geometry 31.8 65 B31-NS005-BW37 Recire.
Pipe Cap Part Geometry 63.2 98-B31-NS006-BW40 Recirc.
Tee to Pipe Part Geometry 21 21 Ell-298D RHR Pipe to Elbow Part Geometry 81 100' B31-NS005-BW36 Recirc.
Tee to Pipe Part Geometry 64 64 Ell-303D RHR Pipe to Elbow Part Geometry 64 100.
B31-NS006-BW36 Recirc.
Tee to Pipe Part Geometry 63 63 Ell-290A RHR Pipe to Elbow Part Geometry 54 100 CS-2A Core Spray Safe end to Pipe Part Geometry 49 49 CS-2B Core Spray Safe end to Pipe Part Geometry 49.
49 G33-6137Q RWCU Pipe to Pipe Obstruction with CRD 85.0 85 Tube Bundle G33-6137C RWCU Pipe to Elbow Obstruction with CRD 85.0 85 Tube Bundle G33-IC1508-FW3 RWCU Pipe to Valve Part Geometry 76.2 95
RELIEF REQUEST NO. 3 I.
IDENTIFICATION OF COMPONENTS:
Augmented inspection on selected pressure retaining welds in Class 2 piping which were inspected to Class 2, Category J-l requirements using applicable PSI Program inspection procedures.
II.
CODE REQUIREMENT:
There is no Code requirement applicable to Shoreham for inspection of these welds under the PSI Program.
Inspection of these welds are a result of LILCO's intent to perform augmented examinations as described in appendices D-1, D-2, E-1 & E-2 in the PSI Program Plan.
III. GENERAL DESCRIPTION:
Relief is required from the augmented examinations on the basis of partial inaccessibility of the weld and required volume noted on the attachment due to plant design.
L
,i.'
I V...
BASIS-FOR RELIEF:
The basis-for: requesting relief from the augmented-examination is as follows:-
~
1.
The structural integrity of the piping pressure
~ boundary was demonstrated during construction by meeting the requirements of the.ASME Code Section III.
All welds were inspected in accordance with the appropriate Code requirements,. weld techniques and welders were qualified in accordance with Code require-ments and materials were purchased and traced in accordance with the appropriate Code and NRC require-ments and-guidelines.
Finally,.the pressure boundary was " proof tested".aftdr installation by the application of a-l.25 times the design pressure-hydrostatic test.
2.
Complete examinat' ions meeting'the requirements of the augmented examination were performed on welds of similar configurations which utilized the same weld techniques, procedures and materials.
The-inspected welds are subject to the same operating and environmental conditions as the partially inspected welds.
It is, therefore, reasonable to extend the acceptable results on the inspectable welds to the partially inspectable welds.
}
-s 4
? '
3.
- 1L substantial ~ percent cove' rage of each of the partially inspectable welds 1(see attachment) was achieved.
Since the construction,foperating conditions and environmen-tal conditions onfthe'non-inspectable portions of the-weld are identical to.the inspected area, the satisfactory results of.the inspected areas can be extended to the non-inspected. area.
4.
The Edition of the AStiE Code Section XI which is currently applicable for Inservice Inspection actually decreases the volume > required to be inspected,for the i
" break exclusion" weld.
Therefore, a larger percentage-of the weld will be inspectable to Code requirements, thus improving Shoreham's conformance.
.5.
The Edition of'the ASME' Cod'e'Section XI which is s
1 e
s currently" applicable'for Inservice Inspection does not-require the Class 2 welds listed on the attachment to i
be inspected.- Therefore, for Inservice Inspection, full compliance for these welds will-be achieved.
i a
c_,
RELIEF REQUEST NO. 3 Attachment WELD IDENTIFICATION ESTIMATED % OF PREDICTED % COMPLETION NUMBER SYSTEM-CONFIGURATION NATURE OF OBSTRUCTION SCAN COMPLETED OF SCAN FOR ISI N11-IC594-FW2 Main Steam Pipe to Tee Location of Branch 98 Connection E41-IC183-FW3 HPCI Pipe to Valve Location of Branch 96.8 Class 2 Connection N11-IC594-FW7 Main Steam Elbow to Valve Part Geometry 73.8 Class 2 Ell-IC62-FW6 RHR Pipe fo Reducer Location of Branch 83.8 Class 2 Connection E11-IC62-FW2O RHR Pipe to Reducer Location of Branch 87.5 Class 2 Connection IG33-IC1120-FW3 RWCU Pipe to Valve Location of Welded 55.4 80 Break Exclusion Attachment
- See " Basis for Relief Request," Item #5.
'.J 'l
~
,~
Y ? ^.
s-4
. RELIEF-REQUEST-NO. 4 I.
IDENTIFICATION'OF COMPONENTS:
~
Class'I, Category A reactor pressure vessel welds.
1 II.
CODE REQUIREMENT:
Paragraph'IS-232 of the ASME Section XI, 1981 edition-code. requires.that a volumetric examination of.100% of pressure containing weldscin reactor vessel belt line region be performed completely as a Preservice examination requirement prior-to initial plant'startup.
III. RELIEF DESCRIPTION Reli'ef is required.from the ASME Section XI examination:
requirements'on the basis of partial inaccessibility of the weld-and. required volume due to vessel design.
The Purchase Order date for.the : reactor pressure vessel, dated February, 1967,
- resulted in vessel design prior to issue of the ASME Section XI
-Code..
4
- t
-IV.
-BASIS FOR RELIEF:-
-The justification ~for' requesting relief from ASME
~
Section XI' examination requirements is as follows:
- 1. '
The structural integrity of the vessel pressure boundary is'not in question.
All of'the affected welds were subject.to examination and testing requirements of ASME Section III.
2.
Complete examinations meeting the. requirements of the ASME Code Section XI were performed on welds offsimilar-c configurations which. utilized the same weld. techniques, procedures and materials.
The inspected welds are subject to the same. operating and-; environmental conditions as the partially. inspected welds.
It is, therefore, reasonable to extend the acceptable results on-the inspectable welds to the partially inspectable welds.
3.
A substcntial percent coverage of each of the partially inspectable welds (see attachment) was achieved.
Since the construction, operating conditions and environmental conditions on the non-inspectable portions of the weld are identical to the inspected Jarea, the satisfactory results of the inspected areas can be extended to the non-inspected area.
8
-e y
.4- -
e r
-r-.
r
-,m
--r-
,.,,v, y.
,4
E RELIEF REQUEST # 4
, t Attachment WELD IDENTIFICATION ESTIMATED % OF NUMBER SYSTEM
-CONFICURATION NATURE OF OBSTRUCTION SCAN COMPLETED 1-308A RPV Shell Course Weld Vessel Nozzle 99 1-308E RPV Shell Course Weld Vessel Support Lug 97 t
1-308F RPV Shell Course Weld Vessel Geometry &
95 Support Lug 1-308G RPV Shell Course Weld Vessel Taper 99 1-308H RPV Shell Course Weld Vessel Taper 99 1-308J RPV Shell Course Weld Vessel Taper 99 1-313 RPV Shell Course Weld Vessel Taper 95 1-307B RPV Shell Course Weld Vessel Taper 97 1-307C RPV Shell Course Weld Vessel Taper 97 4-308A RPV Shell Course Weld Vessel Support Lug 93 4-308B RPV Shell Course Weld Tapered Transition 99 Between Plates 3-318 RPV Closure Head Weld Vessel Nozzle 89 1-318B RPV Closure Head Weld Vessel IIcad Lif ting Lug 98 1-318D RPV Closure Head Weld Vessel IIcad Lif ting' Lug 98 1-318F RPV Closure Head Weld Vessel Head Lifting Lug 98 1-318H RPV Closure Head Weld Vessel Head Lifting Lug 97 1-306D RPV Bottom Head Weld-Nozzle Pad 93 4-316A RPV
. Nozzle to Shell Instrument Nozzle Pads 85 4-316A-r RPV
. Nozzle Inner Radius
' Instrument Nozzle Pads 89 4-316C RPV Nozzle to Shell Instrument Nozzle Pads 85 4-316C-r RPV
' Nozzle' Inner Radius Instrument Nozzle Pads 89 m