ML20054K280

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 820329-0402
ML20054K280
Person / Time
Site: Saint Lucie NextEra Energy icon.png
Issue date: 04/28/1982
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20054K276 List:
References
50-389-82-13, NUDOCS 8207010384
Download: ML20054K280 (1)


Text

r APPENDIX A NOTICE OF VIOLATION Florida Power and Light Company Docket No. 50-389 St. Lucie 2 License No. CPPR-144 As a result of the inspection conducted on March 29 - April 2,1982, and in accordance with the NRC Enforcement Policy, 47 FR 9987 (March 9, 1982), the following violation was identified.

10 CFR 50.55.a(g), as implemented by paragraph 5.2.4 of the FSAR, requires in part that, ASME Code Class 1 components meet preservice (PSI) examina-tion requirements of Section XI of the ASME Boiler and Pressure Vessel Code (B&PV). Article 4 of ASME B&PV,Section V, referenced in Section XI, has been identified by the licensee as the applicable Code _ for PSI ultrasonic inspection (UT) of reactor coolant pressure boundary piping. Table T-434.1 and paragraph T-434.3 of ASME B&PV,Section V require that the thickness of the UT calibration block be within one inch of the thickness of the weld.

Contrary to the above, on April 27, 1981,. preservice inspection was not being performed in accordance with ASME B&PV,Section XI in that the thick-ness of the UT calibration block used for the 45 angle beam calibration for reactor coolant pressure boundary weld 123-2, zone 7, was not -within one inch of the thickness of the weld.

This is a Severity Level V Violation (Supplement II.E).

Pursuant to the provisions of 10 CFR 2.201, you are hereby required to submit to this office within thirty days of the date of this Notice, a written statement or explanation in reply, including: (1) admission or denial of the alleged viola-tion; (2) the reasons for the violation if admitted; (3) the corrective steps which have been taken and the results achieved; (4) corrective steps which will be taken to avoid further violations; and (5) the date when full compliance will be achieved. Consideration may be given to extending your response time for good cause shown.

Date: APR 2 81982 8207010304 820615 PDR ADOCK 05000389 G PDR

-. -- - - . . . - . - - - - . - - - , . . . . . - _ , . . - - -, - .--