. _- - _

GULF STATES UTILITIES COMPANY l

, POST OFFICE GoX 2951 *DEAUMONT. TEXAS 77704 AREA COoE 713 838-6631 April 8, 1982 RBG- 12,429 File Nos. G9.5, G9.25.1.1 Mr. John T. Collins, Regional Administrator

  • A U. S. Nuclear Regulatory Commission #  %

Region IV, Office of Inspection and Enforcement 611 Ryan Plaza Drive, Suite 1000 p H2CEjygg' ,

Arlington, Texas 76011 -

~

APR 141993, c

Dear Mr. Collins:

h ,hpgg hCC River Bend Station Unit 1 .g f, Docket No. 50-458

~ g On March 8, 1982, Gulf States Utilities Company (GSU) notified Reigon IV of a deficiency potentially reportable under 10CFR50.55(e).

The deficiency concerned the amount of torque being applied to Power-Strut PS-10-RS spring nuts when the nuts were substituted as equivlent for Uni-Strut P1010 spring nuts. Each was being installed to the Uni-Strut requirement of 50 ft-lbs torque where Power-Strut spring nuts should have been installed to 60 ft-lbs torque.

GSU has not yet completed its investigation of the significance of this deficiency nor its evaluation whether the reporting criteria of 10CFR50.55(e) have been satisfied. GSU will provide a Status Report j of its investigation by May 28, 1982.

Sincerely, F 8crz1>

J. E. Booker l Manager-Engineering & Licensing River Bend Nuclear Group JEB/JE/kt 13 f -j cc: Director of Inspection & Enforcement s . . ,

U. S. Nuclear Regulatory Commission i '

Washington, D. C. 20555 I

g l plgg"7 1

k bla _

_-. Y

{

8204150521 820408 PDR ADOCK 05000458 hl Q 1 S PDR

/