ML20052G045

From kanterella
Jump to navigation Jump to search
LER 82-001:on 820225,discovered That Potential for Allowing Contaminated Air from Fuel Handling Bldg to Area Served by Control Room Ventilation Sys Exists Due to Ductwork Penetrating Wall Between Control & Fuel Handling Bldgs
ML20052G045
Person / Time
Site: Three Mile Island Constellation icon.png
Issue date: 02/25/1982
From: Toole R
GENERAL PUBLIC UTILITIES CORP.
To: Haynes R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
LER-82-001, LER-82-1, NUDOCS 8205140263
Download: ML20052G045 (1)


Text

____- _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _

. . z c w s _

,:' ; . i .

2 N -G. $

4l%t- ,

  • N , yi GPU Nuclear f

_. A g g{ P.O Box 480 i

Route 441 South Mrddietown, Pennsylvania 17051 717 948-8000 TELEX 842 386 ,

February 25, 1982 * '

. Y Mr. Rouald C. Ha ..es, Director *

~

Office of Inspection and Enforcement Region 1

  • Nuclear Regulatory Commission

' 6 31 P.s t k Ave nue "

King of Prunnin, PA 19406 >

Subjcet: Licennec Event Report No.82-001 I

Dear Mr. llaynes:

Re: Ope. rating Licensee DPR-50 .

Decket 50-289 8

This telecopy is to confirm the conversation between Mt. D. R. Haverkamp, Region - - -

1 f.'RC and Mr. R. .I. Toole, Operations & Maintenance Director, TML 1, at 1535 hours0.0178 days <br />0.426 hours <br />0.00254 weeks <br />5.840675e-4 months <br /> on February 25, 1982, that an item van discovered which is considered prompt '

reportable per TMT 1 Technical Specification 6.9.2.A.(9).

  • 7hc cociputer room air conditioning unit (AH-E-108) ductwork penetrates the vall
  • between the Control Building and the Fuel Handling Building at Elevation 335. .'

The unit and the ductuork penetrating the wall have not been seismically qualified,  :

and there are no radiation interlocks to close the dampers or shut down the fan unit. '

Therefore, there appears to be a potential for this installation to allow contamin-

  • ated air from the Tuc1 !!andling Building to enter the area served by the Control Room Ventilation System, assuming an airborne contamination event in the Fuel Handling Building.

. Additional infornstion and proposed corrective action will be forwarded in the '.

following report within 14 days.

g k .

R. J. Toole Operations & Ksintenance *

'[*

  • ej Director, DfI 1
  • s.

R.1T/ MAN /acih .

s cc Mr. lake Rarrett, Deputy Program Director NRC TMI Program Office . -

U.S. NRC P.O. Box 311 7 i Middletown, PA 17057 e 8205140263 820225 PDR ADOCK 05000289 Ibgg I S PDR h [h> '.c." '

ll