ML19344A448

From kanterella
Jump to navigation Jump to search
LER 80-024/03L-0:on 800718,during Normal Operation,Control Room Personnel Reported UPS-1B Trouble & Loss of Voltage to MC-89B.Caused by Failed Logic Power Supply Board. Component Replaced & Unit Operationally Tested
ML19344A448
Person / Time
Site: Vermont Yankee Entergy icon.png
Issue date: 08/15/1980
From: Murphy W
VERMONT YANKEE NUCLEAR POWER CORP.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML19344A447 List:
References
LER-80-024-03L, LER-80-24-3L, NUDOCS 8008200334
Download: ML19344A448 (1)


Text

I..

I (7 77)

LICENSEE EVENT REPORT LER 80-24/3L lh NTROL BLCCK: i l l l l l (PLEASE PRINT OR TYPE ALL REQUIRED INPORMATION) 1 6 ,

lo i t8 l3 l VILICENSEE 7

T! VICoCE YI Sl ll@l0 14 ts lo l- 10LICENSE lo lo lo lo l- l010 l@l4 IlLICENst NUMSER 25 26 11 IlTypeIl 40l@l57 CAT l' SSl @

CCN'T IoIiI lo'7;;$ l L )@l 0 l 5 l 0 l 0 l 0 l 2 l 7 l1 l@l 01711'l8 l8 l0 l@l0 74 75 l8RF.11 l 5 l8 lo80l@

PORT oATE 7 4 60 6' ooCKET NUMS ER 68 69 EV ENT o ATE EVENT DESCRIPTtCN AND PRC8ABLE CONSECUENCES h Iol2; I During normal operatioun Control Room persennel reported UPS-13 trouble and loss of I l o l a l l voltage to MCC-89B. MCC was energized by Maint. tie. Alternate testing began in l lo (4i laccordance with T. S. Sec. 3.10.3.4 and 3.5.A.4. Trouble shooting revealed a failed 1 I o i s i lf ogic power supply ocard. The compo'nent was replaced, the unit operationally tested l l o is i land returned to service within approx. 5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> af ter failure. The redundant UPS-1A l lol7l l was available and operable. There were no adverse affects ':o the public health and ,

l 4

a , a j l saf ety. There were no similar occurrences reported. l 7 e, n
  • SI:'E *[o'CE s E$$E CouroNENT Coof susC [C'E suYoIsE lo191 7 8 l El Dl@ l E lh l G lh l Gl El Nl El Rl Alh l F lh W h 9 10 11 12 12 18 19 20

. stoVENTIAL OCCUR RE NCE REPORT Revision EVENT YE A R R EPoRT No. CoCE TYPE No.

O"y"ggRRo u'yg af l 8l 0l l-l l0l2l4l l/l 10l3l l Ll l-l l0 l

_ 21 22 23 24 26 27 .1 29 30 31 32 TE N AC e o Pt NT ME woVRs 22 se1 Po 8. sVP L MA U AC RER lAl@lZl@ lZl@ lZl@ l010l010l lN l@ jY l@ lL l@ lE l3 l5 l5 l@

44 47 33 34 JS 36 37 40 el 42 43 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h li j ol l An Exide Power System. 250 KVA uninterruptible power supply had tripped because of a l 4

gi bicwn logic power supply fuse. This failure was caused by a failed diode which I m,,g blew the board fuse. The corrective action was to replace the circuit board and I i, i3i l operationally test the unit. l 1

11 141 l 80 7 8 9 ST  % POWER oTHER status NA ei o Y Operator Observation otsCoVERY oEsCRIPTioN h l lt 15 l l Elh l 0 l 9 l 9 l@l" ': "

l l Al@l

A!TiviTv C '4 toc 2TioNo,REttAst@

  • EttAsto 2.o TENT R uEAst AucuNT NA Q, ACriviTv @ l NA l l1 l6llZl h lZ' I@l "

l

,ERsoNN/tn, esses Nuo.ER Tv,E mCR,,no~@

I t i 7 l l 010 l 0 lhj Z lhi NA l

' ' ' ,ERsoN~ ENu' Ries 2 " '

Nuo.ER 2EsCR,. Tion @

NA l It la $l l9 Ol 01 Ol@l12 7 11 30 W55E a fs'C%',Ve'3 '"' @

NA l l i I 99 I9I Zl@l10 7

30

ssuED oE C I1 8 N hh -

IIIIIIiiIii!l, 1: I o I (Lj@l 00 NA 1 68 69 90 .

7 8 1 10 NAME CF PREPARER a en P. h d ? NE

. . . - - . . . . - . . , _ - - , - . - , - - . - - . - - _ - - . - . - - - - - . , - - - -