MONTHYEARLR-N13-0064, Request for Relief from ASME Code Defect Removal for Service Water Buried Piping2013-04-0303 April 2013 Request for Relief from ASME Code Defect Removal for Service Water Buried Piping Project stage: Request LR-N13-0058, Request for Relief from ASME Code Pressure Test for Service Water Supply Buried Piping2013-04-11011 April 2013 Request for Relief from ASME Code Pressure Test for Service Water Supply Buried Piping Project stage: Request ML13137A4882013-06-0505 June 2013 Request for Additional Information Relief Request SC-l4R-133 Project stage: RAI LR-N13-0171, Response to Request for Additional Information on Relief Request SC-I4R-133, Alternative Repair for Service Water System Piping2013-08-15015 August 2013 Response to Request for Additional Information on Relief Request SC-I4R-133, Alternative Repair for Service Water System Piping Project stage: Response to RAI ML13304B9362013-10-29029 October 2013 Request for Additional Information: Salem Units 1 and 2 - Relief Request SC-14R-133 Repair of Service Water Piping (TAC MF1375 & 1376) Project stage: RAI ML13330A5672013-11-22022 November 2013 Request for Additional Information: Salem Units 1 and 2 - Relief Request SC-14R-133 Repair of Service Water Piping (TAC MF1375 & 1376) Project stage: RAI LR-N13-0302, Response to Request for Additional Information (RAI 31 and RAI 32) - Relief Request SC-14R-1 33, Alternative Repair for Service Water System Piping2014-01-0808 January 2014 Response to Request for Additional Information (RAI 31 and RAI 32) - Relief Request SC-14R-1 33, Alternative Repair for Service Water System Piping Project stage: Response to RAI ML14041A0262014-02-0606 February 2014 NRR E-mail Capture - Request for Additional Information: Salem Units 1 and 2 - Relief Request SC-14R-133 Repair of Service Water Piping (TAC MF1375 & 1376) Project stage: RAI LR-N14-0047, Response to Request for Additional Information (RA133 - RAI36)- Relief Request SC-14R-133, Alternative Repair for Service Water System Piping2014-02-27027 February 2014 Response to Request for Additional Information (RA133 - RAI36)- Relief Request SC-14R-133, Alternative Repair for Service Water System Piping Project stage: Response to RAI ML14078A3352014-03-19019 March 2014 NRR E-mail Capture - Request for Additional Information: Salem Units 1 and 2 - Relief Request SC-14R-133 Repair of Service Water Piping (TAC MF1375 & 1376) Project stage: RAI LR-N14-0092, Response to RAI 37 - Relief Request SC-I4R-133, Alternative Repair for Service Water System Piping2014-03-26026 March 2014 Response to RAI 37 - Relief Request SC-I4R-133, Alternative Repair for Service Water System Piping Project stage: Response to RAI ML14097A0292014-04-0808 April 2014 Safety Evaluation of Relief Requested No. SC-1-l4-R-133 for the Alternative Repair for Service Water System Piping Project stage: Approval 2013-08-15
[Table View] |
Similar Documents at Salem |
---|
Category:Letter
MONTHYEARIR 05000272/20230042024-02-0505 February 2024 Integrated Inspection Report 05000272/2023004 and 05000311/2023004 ML24009A1022024-01-26026 January 2024 Exemption from Select Requirements of 10 CF Part 73 (EPID L-2023-LLE-0045 (Security Notifications, Reports, and Recordkeeping and Suspicious Activity Reporting)) IR 05000272/20234012024-01-22022 January 2024 Material Control and Accounting Program Inspection Report 05000272/2023401 and 05000311/2023401 ML24004A1542024-01-0808 January 2024 Notification of Conduct of a Fire Protection Team Inspection LR-N23-0079, Special Report 23-02-00 Pursuant to the Requirements of Salem Unit 1 Technical Specification 3.3.3.7, Action 10, for the Unit 1 Main Steam Line Rad Monitor Inoperable for Greater than Seven Days2023-12-0707 December 2023 Special Report 23-02-00 Pursuant to the Requirements of Salem Unit 1 Technical Specification 3.3.3.7, Action 10, for the Unit 1 Main Steam Line Rad Monitor Inoperable for Greater than Seven Days ML23270C0072023-11-29029 November 2023 Notice of Proposed Amendment to Decommissioning Trust Agreement LR-N23-0077, Loss of Coolant Accident Peak Cladding Temperature Margin Tracking - Annual Report 2023 & 30 Day Report for Salem Unit 1 Upflow Conversion2023-11-29029 November 2023 Loss of Coolant Accident Peak Cladding Temperature Margin Tracking - Annual Report 2023 & 30 Day Report for Salem Unit 1 Upflow Conversion ML23324A3072023-11-17017 November 2023 Request for Exemption from Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Implementation IR 05000272/20230032023-11-13013 November 2023 Integrated Inspection Report 05000272/2023003 and 05000311/2023003 LR-N23-0072, Core Operating Limits Report Cycle 302023-11-0101 November 2023 Core Operating Limits Report Cycle 30 IR 05000272/20230102023-10-12012 October 2023 Biennial Problem Identification and Resolution Inspection Report O5000272/2023010 and 05000311/2023010 IR 05000272/20234022023-10-12012 October 2023 and Salem Nuclear Generating Station, Units 1 and 2 - Security Baseline Inspection Report 05000354/2023402, 05000272/2023402 and 05000311/2023402 (Cover Letter Only) LR-N23-0045, and Peach Bottom Atomic Power Station, Units 2 and 3 - Notice of Proposed Amendment to Decommissioning Trust Agreement2023-09-0808 September 2023 and Peach Bottom Atomic Power Station, Units 2 and 3 - Notice of Proposed Amendment to Decommissioning Trust Agreement ML23249A2612023-09-0606 September 2023 License Amendment Request to Modify the Salem and Hope Creek Exclusion Area Boundary IR 05000272/20230052023-08-31031 August 2023 Updated Inspection Plan for Salem Nuclear Generating Station, Units 1 and 2 (Reports 05000272/2023005 and 05000311/2023005) ML23233A0762023-08-21021 August 2023 Requalification Program Inspection ML23192A8212023-08-14014 August 2023 and Salem Nuclear Generating Station, Unit Nos. 1 and 2 - Issuance of Amendment Nos. 234, 347, and 329 Revise Technical Specifications to Delete Meteorological Tower Location IR 05000272/20230022023-08-0909 August 2023 Integrated Inspection Report 05000272/2023002 and 05000311/2023002 LR-N23-0055, Special Report 272/23-01-00, Pursuant to the Requirements of Technical Specification 3.3.3.1, Action 23, for the Vent Noble Gas Rad Monitor Inoperable for Greater than Seven Days2023-08-0303 August 2023 Special Report 272/23-01-00, Pursuant to the Requirements of Technical Specification 3.3.3.1, Action 23, for the Vent Noble Gas Rad Monitor Inoperable for Greater than Seven Days IR 05000354/20230022023-08-0303 August 2023 Integrated Inspection Report 05000354/2023002 and Independent Spent Fuel Storage Installation Inspection Report 07200048/2023001 LR-N23-0054, In-Service Inspection Activities2023-07-26026 July 2023 In-Service Inspection Activities LR-N23-0046, Emergency Plan Document Revisions Implemented June 28, 20232023-07-10010 July 2023 Emergency Plan Document Revisions Implemented June 28, 2023 LR-N23-0005, License Amendment Request to Amend Technical Specifications (TS) 6.8.4.f for Permanent Extension of Type a and Type C Leak Rate Test Frequencies2023-06-23023 June 2023 License Amendment Request to Amend Technical Specifications (TS) 6.8.4.f for Permanent Extension of Type a and Type C Leak Rate Test Frequencies ML23139A1472023-06-0505 June 2023 Relief Request Associated with Fourth Interval In-service Inspection Limited Examinations of Weld Coverage ML23096A1842023-05-0909 May 2023 Issuance of Amendment No. 328 Revise and Relocate Reactor Coolant System Pressure and Temperature Limits and Pressurizer Overpressure Protection System Limits to Pressure and Temperature Limits Report IR 05000272/20230012023-05-0303 May 2023 Integrated Inspection Report 05000272/2023001 and 05000311/2023001 ML23081A4662023-05-0202 May 2023 Issuance of Amendment Nos. 346 and 327 Revise Technical Specifications to Extend Allowable Outage Time for Inoperable Emergency Diesel Generator IR 05000272/20233012023-05-0101 May 2023 Initial Operator Licensing Examination Report 05000272/2023301 and 05000311/2023301 LR-N23-0034, 2022 Annual Radiological Environmental Operating Report (AREOR) - Salem Nuclear Generating Station, Unit Nos. 1 and 2 and Hope Creek Generating Station2023-04-27027 April 2023 2022 Annual Radiological Environmental Operating Report (AREOR) - Salem Nuclear Generating Station, Unit Nos. 1 and 2 and Hope Creek Generating Station LR-N23-0035, 2022 Annual Radioactive Effluent Release Report (ARERR)2023-04-27027 April 2023 2022 Annual Radioactive Effluent Release Report (ARERR) LR-N23-0033, Core Operating Limits Report Cycle 272023-04-26026 April 2023 Core Operating Limits Report Cycle 27 LR-N23-0010, License Amendment Request Revision of Technical Specification (TS) to Delete TS Section 5.5 - Meteorological Tower Location2023-04-21021 April 2023 License Amendment Request Revision of Technical Specification (TS) to Delete TS Section 5.5 - Meteorological Tower Location ML23089A0942023-04-17017 April 2023 NRC to PSEG Hope Creek, Transmittal of the National Marine Fisheries Service'S March 24, 2023, Biological Opinion GAR-2020-02842 Concerning Salem and Hope Creek ML23087A1492023-04-17017 April 2023 NRC to PSEG Salem, Transmittal of the National Marine Fisheries Service'S March 24, 2023, Biological Opinion GAR-2020-02842 Concerning Salem and Hope Creek ML23103A3232023-04-13013 April 2023 Submittal of Updated Final Safety Analysis Report, Rev. 26, Summary of Revised Regulatory Commitments for Hope Creek, Summary of Changes to PSEG Nuclear LLC, Quality Assurance Topical Report, NO-AA-10, Rev. 89 ML23095A3682023-04-12012 April 2023 and Salem Nuclear Generating Station, Unit Nos. 1 and 2 - Threshold Determination for Proposed Transfer of Land Ownership LR-N23-0006, Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations2023-03-24024 March 2023 Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations ML23086A0912023-03-24024 March 2023 NMFS to NRC, Transmittal of Biological Opinion for Continued Operations of Salem and Hope Creek Nuclear Generating Stations RS-23-049, Constellation Energy Generation, LLC, Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations2023-03-23023 March 2023 Constellation Energy Generation, LLC, Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations LR-N23-0019, and Salem Generating Station, Units 1 and 2 - Guarantees of Payment of Deferred Premiums2023-03-21021 March 2023 and Salem Generating Station, Units 1 and 2 - Guarantees of Payment of Deferred Premiums ML23044A1052023-03-13013 March 2023 Issuance of Amendment Nos. 345 and 326 Relocate Technical Specifications Requirements for Reactor Head Vents to Technical Requirements Manual ML23037A9712023-03-0909 March 2023 and Salem Nuclear, Unit Nos. 1 and 2 Issuance of Amendment Nos. 233, 344, and 325 Relocate Technical Specification Staff Qualification Requirements to the PSEG Quality Assurance Topical Report IR 05000272/20230112023-03-0707 March 2023 Comprehensive Engineering Team Inspection Report 05000272/2023011 and 05000311/2023011 IR 05000272/20220062023-03-0101 March 2023 Annual Assessment Letter for Salem Nuclear Generating Station, Units 1 and 2 (Reports 05000272/2022006 and 05000311/2022006) LR-N23-0016, and Salem Generating Station, Units 1 and 2 - Report of Changes, Tests, and Experiments2023-02-28028 February 2023 and Salem Generating Station, Units 1 and 2 - Report of Changes, Tests, and Experiments LR-N23-0012, Annual Property Insurance Status Report2023-02-24024 February 2023 Annual Property Insurance Status Report LR-N23-0014, Stations Submittal of 2022 Annual Report of Fitness for Duty Performance Data Per 10 CFR 26.203(e) and 10 CFR 26.7172023-02-23023 February 2023 Stations Submittal of 2022 Annual Report of Fitness for Duty Performance Data Per 10 CFR 26.203(e) and 10 CFR 26.717 ML23034A1532023-02-0909 February 2023 Operator Licensing Examination Approval ML23019A3482023-02-0202 February 2023 Issuance of Relief Request No. SC-I5R-221 for the Alternative Repair for Service Water System Piping LR-N23-0003, Response to Requests for Additional Information Salem Unit 2 Relief Request S2-I4R-2112023-02-0101 February 2023 Response to Requests for Additional Information Salem Unit 2 Relief Request S2-I4R-211 2024-02-05
[Table view] Category:Request for Additional Information (RAI)
MONTHYEARML22333A9022022-11-29029 November 2022 NRR E-mail Capture - Final Iolb RAI - Salem 1 and 2 LAR to Revise TS to Extend Allowed Outage Time for Inoperable EDG ML22318A1062022-11-14014 November 2022 Information Request for Quadrennial Baseline Comprehensive Engineering Team Inspection; Notification to Perform Inspection 05000272/2023011 and 05000311/2023011 ML22290A2202022-10-17017 October 2022 NRR E-mail Capture - Final RAI - Salem 1 and 2 LAR to Revise TS to Extend Allowed Outage Time for Inoperable EDG ML22055A0702022-02-22022 February 2022 NRR E-mail Capture - Final RAI - Salem 1-Relief Request Associated with Fourth Inservice Inspection (ISI) Interval Limited Examinations (L-2021-LLR-0085) ML21256A1902021-09-10010 September 2021 NRR E-mail Capture - Exelon Generation Company, LLC - Request for Additional Information Regarding License Transfer Application ML21144A2132021-05-24024 May 2021 NRR E-mail Capture - Exelon Generation Company, LLC - Request for Additional Information Regarding License Transfer Application ML21068A4142021-03-0909 March 2021 NRR E-mail Capture - Final RAI for Salem Unit 1 LAR to Revise and Relocate Pressurizer Overpressure Protection System Limits to Pressure and Temperature Limits Report ML21043A1442021-02-11011 February 2021 NRR E-mail Capture - Salem - Final RAI Alternative for Examination of ASME Section XI, Category B-B, Item Number B2.11and B2.12 (L-2020-LRR-0103) ML21021A2592021-01-21021 January 2021 NRR E-mail Capture - Final RAI - Salem 1 - Steam Generator Tube Inspection Report ML20281A5172020-10-13013 October 2020 Notification of Conduct of a Fire Protection Team Inspection ML18267A1712018-09-21021 September 2018 NRR E-mail Capture - Final RAI from PRA Branch: Revise Technical Specifications to Increase Inverter AOT Extension (L-2018-LLA-0140) ML18264A0122018-09-20020 September 2018 NRR E-mail Capture - Final RAI from I&C Branch: Revise Technical Specifications to Increase Inverter AOT Extension (L-2018-LLA-0140) ML18250A3132018-09-0606 September 2018 NRR E-mail Capture - Final RAI: Revise Technical Specifications to Increase Inverter AOT Extension (L-2018-LLA-0140) ML18171A3212018-06-20020 June 2018 NRR E-mail Capture - Final RAI: Revise Technical Specifications to Adopt TSTF-411 and 418 (L-2017-LLA-0442) ML18094B0832018-04-0505 April 2018 Enclosurequest for Additional Information (Letter to P. Duke RAI Regarding Entergy Operations, Inc.'S Decommissioning Funding Plan Update for Salem and Hope Creek, and Peach Bottom ISFSIs Docket Nos. 72-48 and 72-29) ML18067A1482018-03-0808 March 2018 Enclosurequest for Additional Information (Letter to P. R. Simpson Request for Additional Information Regarding Exelon Generating Company, Llc'S Decommissioning Funding Plan Update for Independent Spent Fuel Storage Installation) ML17212B1152017-07-31031 July 2017 Request for Additional Information - Salem Units 1 and 2 - Containment Fan Coil Unit Allowed Outage Time Amendment Request (CACs MF9364 and MF9365) ML17199A1122017-07-18018 July 2017 Request for Additional Information - Salem Units 1 and 2 - Accident Monitoring Instrumentation License Amendment Request (CAC Nos. MF8859 & MF8860) ML17192A1672017-07-11011 July 2017 Request for Additional Information - Salem Unit 1 - Steam Generator Tube Inspection Report ML17115A4032017-05-0909 May 2017 Request for Additional Information Regarding Relief Request SC-14R-171 - Use of Code Cases N-695-1 and N-696-1 ML16321A4642016-11-21021 November 2016 and Salem Nuclear Generating Station, Unit Nos. 1 and 2 - Request for Additional Information Regarding License Amendment Request to Remove Certain Training Requirements ML16218A0052016-08-11011 August 2016 Request for Additional Information Concerning Request for an Extension to Enforcement Guidance Memorandum 12-001 ML16195A4492016-07-14014 July 2016 Request for Additional Information Regarding Chilled Water System Modifications ML16188A4152016-07-0707 July 2016 Request for Additional Information Aging Management Program Plan for Reactor Vessel Internals ML16124A5802016-05-0303 May 2016 and Salem Nuclear Generating Station, Unit Nos. 1 and 2 - Redacted - Request for Additional Information Review of Security Plan Revision 17 Changes ML16013A1592016-02-17017 February 2016 Request for Additional Information Regarding Chilled Water System Modifications ML15287A1412015-11-0202 November 2015 Request for Additional Information License Amendment Request Regarding Replacement of Source Range and Intermediate Range Neutron Monitoring Systems ML15287A1052015-11-0202 November 2015 Request for Additional Information License Amendment Request to Isolate Unborated Water Sources and Use Gamma-Metrics Post-Accident Neutron Monitors During Mode 6 (Refueling) (CAC Nos. MF5831 & MF5832) ML15299A3832015-10-29029 October 2015 Supplemental Information Needed for Acceptance of Requested Licensing Action Amendment Request Regarding Chilled Water System Modification ML15069A1812015-03-31031 March 2015 Request for Additional Information Aging Management Program Plan for Reactor Vessel Internals (TAC Nos. MF5149 and MF5150) ML15075A2602015-03-24024 March 2015 Request for Additional Information Spring 2014 Steam Generator Tube Inspections ML15055A3772015-03-10010 March 2015 and Salem Nuclear Generating Station, Unit Nos. 1 and 2, Request for Additional Information Request to Update Appendix B to Renewed Facility Operating License DPR-70, DPR-75 and NPF-57 ML14197A6192014-07-24024 July 2014 and Salem Nuclear Generating Station, Units 1 and 2 - Request for Additional Information Regarding Cyber Security Plan Milestone 8 Implementation Schedule (Tac Nos. MF3384, MF3385 and MF3386) ML14168A2422014-06-28028 June 2014 Request for Additional Information Regarding Flooding Hazard Reevaluation ML14135A2912014-06-0202 June 2014 RAI Regarding Request for Relief SC-I4R-140 from American Society of Mechanical Engineers Boiler & Pressure Vessel Code, Section XI Requirements Regarding the Reactor Vessel Head Flange Seal Leak Detection ML14086A6362014-04-30030 April 2014 Request for Additional Information Regarding Core Operating Limits Report ML14066A2952014-03-0606 March 2014 Licensed Operator Positive Fitness-For-Duty-Test (FY14) ML13330A5672013-11-22022 November 2013 Request for Additional Information: Salem Units 1 and 2 - Relief Request SC-14R-133 Repair of Service Water Piping (TAC MF1375 & 1376) ML13304B4182013-11-0101 November 2013 Request for Additional Information Associated with Near-Term Task Force Recommendation 2.3, Seismic Walkdowns ML13304B9362013-10-29029 October 2013 Request for Additional Information: Salem Units 1 and 2 - Relief Request SC-14R-133 Repair of Service Water Piping (TAC MF1375 & 1376) ML13270A4142013-10-17017 October 2013 Interim Staff Evaluation and Request for Additional Information Regarding the Overall Integrated Plan for Implementation of Order EA-12-051, Reliable Spent Fuel Pool Instrumentation (TAC Nos. MF0913 and Mf ML13249A0112013-09-0505 September 2013 Weko Seal Relief Request RAI ML13196A3382013-07-15015 July 2013 2013 Decommissioning Fund Report RAI ML13192A2322013-07-11011 July 2013 Draft Request for Additional Information Overall Integrated Plan in Response to Order EA-12-051, Reliable Spent Fuel Pool Instrumentation. ML13186A1672013-07-11011 July 2013 Request for Additional Information Overall Integrated Plan for Reliable Spent Fuel Pool Instrumentation (Order Number EA-12-051) ML13179A3032013-06-28028 June 2013 RAIs for Salem Regarding Response to Order EA-12-051 (SFP Instrumentation) ML13137A4882013-06-0505 June 2013 Request for Additional Information Relief Request SC-l4R-133 ML13149A0862013-06-0505 June 2013 Request for Additional Information Decommissioning Funding Status Report ML13102A2752013-04-25025 April 2013 Request for Additional Information Change to PSEG Emergency Plan to Remove the Backup R45 Plant Vent Radiation Monitor Indications ML13063A7172013-03-11011 March 2013 Second Request for Additional Information Deletion of Condition for Inoperable Control Area Air Condition System/Control Room Emergency Air Conditioning System Isolation Dampers 2022-02-22
[Table view] |
Text
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 June 5, 2013 Mr. Thomas Joyce President and Chief Nuclear Officer PSEG Nuclear LLC P.O. Box 236, N09 Hancocks Bridge, NJ 08038
SUBJECT:
SALEM NUCLEAR GENERATING STATION, UNITS 1 AND 2 REQUEST FOR ADDITIONAL INFORMATION RE: RELIEF REQUEST SC-14R-133 (TAC NOS. MF1375 AND MF1376)
Dear Mr. Joyce:
By letter dated April 3, 2013,1 PSEG Nuclear, LLC (the licensee) requested the Nuclear Regulatory Commission's (NRC's) approval of proposed relief request SC-14R-133 for Salem Nuclear Generating Station, Units 1 and 2 (Salem). The proposed relief will allow Salem to repair bell-and-spigot joints in the buried portions of Service Water System piping in lieu of defect removal requirements in the ASME Code,Section XI, IWA-4422.1. The NRC staff has reviewed the request submitted by the licensee and has determined that additional information is required, as provided in the enclosure, in order to complete its review.
The draft questions were sent to Ms. Emily Bauer of your staff, to ensure that the questions were understandable, the regulatory basis for the questions was clear, and to determine if the information was previously docketed. On June 4, 2013, Ms. Bauer indicated that the licensee will submit a response by August 16, 2013.
If you have any questions, please contact me at (301) 415-3204 or via e-mail at John.Hughey@nrc.gov.
Sincerely, tMAW
\o5ohn D. Hughey, Project Manager Plant licensing Branch 1-2 Division of Operating Reactor licensing Office of Nuclear Reactor Regulation Docket Nos. 50-272 and 50-311
Enclosure:
Request for Additional Information cc: Distribution via ListServ 1 Agencywide Documents and Access Management System (ADAMS) Accession No. ML13093A382.
REQUEST FOR ADDITIONAL INFORMATION OFFICE OF NUCLEAR REACTOR REGULATION RELIEF REQUEST SC-14R-133 ALTERNATIVE REPAIR FOR SERVICE WATER SYSTEM PIPING SALEM NUCLEAR GENERATING STATION. UNITS 1 AND 2 PSEG NUCLEAR LLC DOCKET NOS. 50-272 AND 50-311 By letter dated April 3, 2013, 1 PSEG Nuclear, LLC (the licensee) requested the Nuclear Regulatory Commission's (NRC's) approval of proposed relief request SC-14R-133 for Salem Nuclear Generating Station, Units 1 and 2 (Salem). The proposed relief will allow Salem to repair bell-and-spigot jOints in the buried portions of Service Water System piping in lieu of defect removal requirements in the ASME Code,Section XI, IWA-4422.1. To complete its review, the NRC staff requests the following additional information.
Design RAI 1 Provide legible design drawings that show plant-specific dimensions of the items (components) of the bell-and-spigot joint before and after the repair using the WEKO seal. If available, provide 3-dimensional perspective drawings to help the NRC staff to visualize the joint configuration. The drawing should also include the harness assembly.
RAI2 Provide a detailed drawing of the square head set screws (bolts) and the spigot gasket (not a part of the WEKO seal) showing how the bell and spigot are connected to each other. These drawings will help the NRC staff understand how the pipe loading is distributed and evaluate any potential leak path through the joint.
RAI3 Figures 1 and 2 show a spigot gasket that is located near the set screws and a fillet weld connecting the bell to the steel cylinder.
- a. Discuss the gasket material and its potential degradation mechanism.
- b. Discuss whether the spigot gasket will be replaced when the bell thickness is reduced due to corrosion because the ground water may leak into the pipe through the gap that may be created between the gasket and the reduced bell thickness.
1 Agencywide Documents and Access Management System (ADAMS) Accession No. ML13093A382.
Enclosure
- 2
- c. Specify the size of the fillet weld.
RAI 4 The fillet weld is sandwiched and enclosed between the concrete and mortar coating.
- a. Discuss whether the fillet weld has ever been examined. If not, discuss how the fillet weld can be ensured to maintain its structural integrity to support the piping loads without nondestructive examinations.
- b. What would the implications on structural integrity be if the fillet weld could not be relied upon?
RAI 5 Figures 1 and 2 identify an area in the joint as "Bell core hold-back shape assumed 1" offset." It appears that the 1-inch gap would form an enclosure once the WEKO seal is installed. The ground water may leak into the 1-inch gap space and eventually leak into the crevice between the stainless steel backing plate and the inside pipe wall. This may cause corrosion of the stainless steel backing plate underneath the rubber seal. The stainless steel is susceptible to stress-corrosion cracking in chlorine and high-stressed environment. Discuss whether the WEKO seal design has considered the potential for the ground water leaking into the pipe through the degraded joint and cause corrosion of the backing plate of the WEKO seal.
RAI 6 Section 4 states that the degradation of the joint is due to corrosion of the carbon steel bell and spigot components caused by exposure to either service water or ground water.
- a. List specific joint items (e.g., set screws, wires, gasket, and steel cylinder) besides the bell and spigot that could be degraded and their potential degradation mechanism.
- b. Provide the average and maximum corrosion rate of the bell-and-splgot joint based on operating experience in the nuclear and non-nuclear industry in the similar operating conditions.
RAI 7 Section 5.2 states that joints with bell wall thickness less than 0.1 inches are required to be repaired and that if the bell thickness is between 0.042 inches and 0.1 inches, a WEKO seal with backing plate will be used to perform the repair, altho~gh inspection of the harness assembly for axial capacity is not required.
Section 5.2 further states that if the bell thickness is below 0.042 inches, the WEKO seal with backing plate will be installed and the harness assembly is required to be inspected.
- a. Justify why the harness assembly does not need to be inspected for axial capacity if the bell thickness is between 0.042 inches and 0.1 inches.
The NRC staff finds that when the bell thickness is degraded, the harness assembly needs to be ensured to carry the axial pipe load to maintain a defense-in-depth protection.
- b. Justify why the WEKO seal can be used to repair the joint when the bell thickness falls below 0.042 inches.
- 3
- c. Discuss the bell thickness beyond which the WEKO seal cannot be used to repair a degraded joint.
- d. Discuss how the bell thickness is measured during an inspection.
- e. Discuss the design and nominal thickness of the bell and spigot.
- f. Discuss whether the above acceptance criterion (0.1 and 0.042 inches) also applies to the spigot wall thickness. That is, if the spigot thickness is reduced to the acceptance limit (even if the bell thickness is not reduced to the acceptance limit), is the joint required to be repaired?
- g. If the bell or spigot thickness is reduced, discuss whether the bell bolts (set screws) need to be re-torqued to reduce the gap between the bell and spigot.
- h. Discuss whether the proposed WEKO seal can only be applied at the bell-and-spigot joint of the pre-stressed concrete cylinder pipe (PCCP) and not on any other area or region of the PCCP.
RAI 8 The WEKO seal is attached to the inside surface of the pipe by the retaining bands which may degrade and lose their strength overtime. As a consequence, the retaining bands, the rubber gasket and backing plate may fall from the pipe inside wall into the flow stream.
- a. Discuss the safety consequences of the loose WEKO seal parts in the flow stream that may either block the water flow or damage downstream equipment or components.
- b. Identify the potential safety-related systems and non-safety-related systems that support the safety-related systems downstream of the service water piping that may be affected by the loose seal parts.
- c. Discuss how the operator can determine if the service water flow has been changed as a result of loose WEKO seal parts falling in the flow stream.
RAI 9 Figure 1 identifies an item as "Cylinder to spigot connection Unknown, assumed butt welded." However, Section 5.1.1, page 3 states that the spigot is welded to the cylinder. Clarify how the steel cylinder is connected to the spigot.
Analysis RAI10 Provide NRC staff access to References 7.3,7.4,7.5, 7.6, 7.7, 7.8, 7.9, 7.10 and 7.11.
RAI11 Section 5.3.2 states that ethylene propylene diene monomer (EPDM) rubber sheet is aging resistant.
- a. Discuss how many years and under what pressure the EPDM rubber sheet is qualified (EPDM is qualified up to 200 degrees F).
- b. Provide the design and normal operation temperature and pressure of the service water supply and discharge piping.
-4 RAI12 The relief request states that the harness assembly and the bell bolts will provide longitudinal strength (axial loading) for the jOint. Identify which components of the joint support the hoop stresses (radial loadings).
RAI13 Section 5.3.1 states that axial piping loads due to internal pressure or seismic are carried by the external harness assembly and that the bell bolts provide axial restraint in the event of a failure of the harness assembly. The NRC staff believes that in addition to the bolts that provide axial restraint, the bolt holes in the bell, and the spigot (i.e., the bell cross-sectional thickness in the vicinity of the bolt holes) also provide axial restraint. If there is degradation on these components, how is the degradation assessed to ensure structural integrity?
RAI14 Section 5.3.1 states that the bell-and-spigot joints form the piping pressure boundary and are designed to provide 2 inches of axial deflection and one degree of articulation.
- a. Discuss if a 2-inch axial deflection occurs (the NRC staff interprets this as a 2-inch axial separation at the joint). whether water in the pipe would leak into or out of the joint.
- b. After the WEKO seal is placed in service, if the joint experiences 2 inches of axial deflection, discuss whether the WEKO seal will also be stretched for 2 inches along with the joint.
- c. If the pipe contracts after the expansion, discuss whether the WEKO seal will also contract (I.e., would the WEKO seal move axially with the jOint like an accordion?).
- d. In this scenario, a gap may be created between the WEKO seal and the concrete inside surface as a result of the joint expansion and contraction.
The ground water may leak into the pipe through the bell-and-spigot joint.
Discuss the potential for this scenario and the associated consequences.
RAI15 The last paragraph on page 10 states that WEKO seals have been installed as a preventive measure at all joints in the service water supply headers.
- a. Identify what inspections of the bell-and-spigot joints were conducted at the time of installation and the results of the inspections.
- b. Clarify whether the WEKO seals were credited as structural components for the joint or if they were preventive measures to reduce degradation of the bell-and-spigot joint.
- c. Provide the year when the WEKO seals were installed and how many seals were installed.
- d. Clarify whether the proposed alternative will be applied to the service water discharge piping only because the WEKO seals have already been installed at all bell-and-spigot joints in the service water supply headers.
- e. For WEKO seals that have already been installed, will they be removed and the bell-and-spigot components inspected to the proposed standards in this relief request and then reinstalled? If not, what is the plan for inspection of the existing seals and bell-and-spigot components?
-5
- f. Have there been inspections of the WEKO seals subsequent to their installation? If so, provide the inspection criteria and the results of the inspections.
RAI16 The fourth paragraph on page 10 states that the maximum shear stress in the push tab welds during installation is 66 percent of the allowable stress. Identify the push tab welds in the design drawings with respect to the WEKO seal assembly and provide a detailed sketch of the push tab itself.
RAI17 The WEKO seal has 4 retaining bands to attach the rubber gasket seal to the inside surface of the pipe.
- a. Provide the radial force that the retaining bands will exert to the inside surface of the pipe wall in order to attach the rubber gasket to the inside pipe wall.
- b. The retaining bands will exert a tensile load on the inside surface of the pipe, which is covered with concrete. Tensile loading is not favorable for concrete as concrete cannot support tensile loads. The pre-stressed wires that wrap the steel cylinder provide compressive load on the concrete. Demonstrate by analysis that the compressive loading of the wires exceed the tensile loading of the retaining bands such that the concrete would not be negatively affected by the tensile loading of the retaining bands.
Installation RAI18 Describe the installation of the WEKO seal in detail.
RAI19 Clarify whether a compound or coating is applied to the interface between the EPDM rubber gasket (edge) and the pipe inside surface to minimize leakage to the backing plate and through the seal assembly.
RAI20 The ends of the EPDM gasket have grooves. Discuss the function of these grooves.
RAI21 Clarify whether a sealant will be used between the backing plate and the pipe inside surface.
Examinations RAI22 Discuss the acceptance examination and associated acceptance criteria of the WEKO seal assembly.
- a. That is, what and how to examine the installed WEKO seal for acceptance?
- b. What are the criteria to accept or reject an installed WEKO seal for service?
-6 RAI23 Section 5.4 discusses post-installation pressure testing.
- a. Provide the pressure that will be used in the pressure testing and the associated hold time.
- b. Clarify whether a visual examination of the repaired joint will be performed as part of the pressure testing.
- c. List the subarticle(s) of the ASME Code,Section XI, that the pressure testing will be performed in accordance with.
RAI24 Section 5.4 states that periodic inspections of the degraded joint and the installed WEKO seal will be performed in conjunction with Generic Letter (GL) 89-13, "Service Water System Problems Affecting Safety-Related Equipment".2
- a. Clarify whether after installing the WEKO seal, the degraded portion of the buried pipe will be exposed (i.e., the excavation will not be backfilled) so that the repaired joint is accessible for periodic inspections for the remaining life of the repair.
- b. Discuss the inspection techniques that will be used in the periodic inspections of the repaired joint and the WEKO seal, what items will be inspected, whether the inspection will be performed from the inside or outside surface of the pipe, and what are the acceptance criteria of the inspection.
- c. Provide references for the acceptance criteria to disposition the inservice inspection results.
- d. Discuss how often the repaired joint will be inspected as part of the GL 89-13 inspections.
RAI25 The NRC staff finds that it is appropriate to inspect the harness assembly when the WEKO seals are installed, and periodically thereafter.
- a. Provide the plans for future inspections of the harness assembly after the seals are installed.
- b. Provide justification if this is not an examination requirement of the proposed alternative.
RAI26 Section 5.4 states that the external harness assembly will also be periodically inspected in the area of the repaired joint, if credited for axial load carrying capability.
- a. If degradation of the harness assembly exists, what are the criteria used to accept for further use?
- b. Does this criterion take into account degradation that exists in the bell and-spigot joint? If not, justify.
2 ADAMS Accession No. ML031150348.
-7 RAI27 The NRC staff finds that if both the harness assembly and the joint are degraded, there is no defense-in-depth to maintain the structural integrity of the joint. As stated in the relief request, the WEKO seal does not carry pipe axial loads.
- a. Discuss what instances the harness assembly is not credited for axial load carrying capability.
- b. Justify why the WEKO seal can be used at a location when both the bell and-spigot joint and harness assembly are degraded.
RAI28 Section 5.4 states that VT-2 examination of the exposed portion of piping is to be performed any time external harness assembly inspections are performed.
- a. Explain how often the harness assembly is inspected.
- b. Discuss what the harness assembly inspection criteria and acceptance criteria are for the harness assembly inspection.
Regulatory Issues RAI29 The NRC staff understands that for Unit 2, the fourth 10-year inservice inspection (lSI) interval starts on November 27,2013, and ends on November 27,2023, as stated in the licensee's fourth 10-year lSI submittal dated June 7, 2012. 3 Provide the beginning and end dates for the fourth 10-year lSI interval for Unit 1.
RAI30 Confirm that the proposed relief request will be effective starting the fourth 10 year lSI interval at both units.
3 ADAMS Accession 1\10. ML12159A084.
Mr. Thomas Joyce June 5, 2013 President and Chief Nuclear Officer PSEG Nuclear LLC P.O. Box 236, N09 Hancocks Bridge, NJ 08038 SUB~IECT: SALEM NUCLEAR GENERATING STATION, UNITS 1 AND 2 - REQUEST FOR ADDITIONAL INFORMATION RE: RELIEF REQUEST SC-14R-133 (TAC NOS. MF1375 AND MF1376)
Dear Mr. Joyce:
By letter dated April 3, 2013,1 PSEG Nuclear, LLC (the licensee) requested the Nuclear Regulatory Commission's (NRC's) approval of proposed relief request SC-14R-133 for Salem Nuclear Generating Station, Units 1 and 2 (Salem). The proposed relief will allow Salem to repair bell-and-spigot joints in the buried portions of Service Water System piping in lieu of defect removal requirements in the ASME Code,Section XI, IWA-4422.1. The NRC staff has reviewed the request submitted by the licensee and has determined that additional information is required, as provided in the enclosure, in order to complete its review.
The draft questions were sent to Ms. Emily Bauer of your staff, to ensure that the questions were understandable, the regulatory basis for the questions was clear, and to determine if the information was previously docketed. On June 4, 2013, Ms. Bauer indicated that the licensee will submit a response by August 16, 2013.
If you have any questions, please contact me at (301) 415-3204 or via e-mail at John.Hughey@nrc.gov.
Sincerely, IRAJ Jeffrey Whited for John D. Hughey, Project Manager Plant Licensing Branch 1-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-272 and 50-311
Enclosure:
Request for Additional Information cc: Distribution via ListServ 1 Agencywide Documents and Access Management System (ADAMS) Accession No. ML13093A382.
DISTRIBUTION:
RidsNrrPMSalem Resource RidsNrrLAABaxter Resource RidsNrrDorlDpr Resource RidsRgn1 MailCenter Resource RidsNrrDorlLpl1-2 Resource LPLI-2 R/F RidsNrrDeEpnb Resource RidsAcrsAcnw MailCTR Resource PUBLIC D. Alley, NRR J. Tsao, NRR - J. Whited, NRR ADAMS Accession No' .. ML13137A488 *via e-mail dated OFFICE LPL1-2/PM LPL1-2/LA EPNB/BC* LPL 1-2/BC (A) LPL1-2/PM JHughey NAME JWhited ABaxter TLupold VRodriguez (JWhited for)
DATE OS/29/2013 OS/29/2013 04/26/2013 06/05/2013 06/05/2013 OFFICIAL RECORD COpy