Text

August 10, 2007 Mr. Michael D. Wadley Site Vice President Prairie Island Nuclear Generating Plant Nuclear Management Company, LLC 1717 Wakonade Drive East Welch, MN 55089

SUBJECT:

PRAIRIE ISLAND NUCLEAR GENERATING PLANT, UNITS 1 AND 2 -

ISSUANCE OF AMENDMENTS RE: MISCELLANEOUS TECHNICAL SPECIFICATION IMPROVEMENTS (TAC NOS. MD2822 AND MD2823)

Dear Mr. Wadley:

The Commission has issued the enclosed Amendment No. 180 to Facility Operating License No. DPR-42 and Amendment No. 170 to Facility Operating License No. DPR-60 for the Prairie Island Nuclear Generating Plant (PINGP), Units 1 and 2, respectively. The amendments consist of changes to the Technical Specifications (TSs) in response to your application dated August 14, 2006, as supplemented by [[letter::L-PI-07-060, Supplement to License Amendment Request (LAR) for Miscellaneous Technical Specification (TS) Improvements (TAC Nos. MD 2822 and MD 2823)|letter dated July 16, 2007]].

The amendments make miscellaneous improvements to the TSs for PINGP, Units 1 and 2.

The amendments revise TS 1.3, Completion Times; TS 3.1.4, Rod Group Alignment Limits; TS 3.3.7, Spent Fuel Pool Special Ventilation System (SFPSVS) Actuation Instrumentation; TS 3.7.10, Control Room Special Ventilation System (CRSVS); and TS Chapter 4.0, Design Features.

A copy of our related safety evaluation is also enclosed. The Notice of Issuance will be included in the Commissions biweekly Federal Register notice.

Sincerely,

/RA/

Mahesh L. Chawla, Project Manager Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-282 and 50-306

Enclosures:

1. Amendment No. 180 to DPR-42
2. Amendment No. 170 to DPR-60
3. Safety Evaluation cc w/encls: See next page

Mr. Michael D. Wadley Site Vice President Prairie Island Nuclear Generating Plant Nuclear Management Company, LLC 1717 Wakonade Drive East Welch, MN 55089

SUBJECT:

PRAIRIE ISLAND NUCLEAR GENERATING PLANT, UNITS 1 AND 2 -

ISSUANCE OF AMENDMENTS RE: MISCELLANEOUS TECHNICAL SPECIFICATION IMPROVEMENTS (TAC NOS. MD2822 AND MD2823)

Dear Mr. Wadley:

The Commission has issued the enclosed Amendment No. 180 to Facility Operating License No. DPR-42 and Amendment No. 170 to Facility Operating License No. DPR-60 for the Prairie Island Nuclear Generating Plant (PINGP), Units 1 and 2, respectively. The amendments consist of changes to the Technical Specifications (TSs) in response to your application dated August 14, 2006, as supplemented by [[letter::L-PI-07-060, Supplement to License Amendment Request (LAR) for Miscellaneous Technical Specification (TS) Improvements (TAC Nos. MD 2822 and MD 2823)|letter dated July 16, 2007]].

The amendments make miscellaneous improvements to the TSs for PINGP, Units 1 and 2.

The amendments revise TS 1.3, Completion Times; TS 3.1.4, Rod Group Alignment Limits; TS 3.3.7, Spent Fuel Pool Special Ventilation System (SFPSVS) Actuation Instrumentation; TS 3.7.10, Control Room Special Ventilation System (CRSVS); and TS Chapter 4.0, Design Features.

A copy of our related safety evaluation is also enclosed. The Notice of Issuance will be included in the Commissions biweekly Federal Register notice.

Sincerely,

/RA/

Mahesh L. Chawla, Project Manager Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-282 and 50-306

Enclosures:

1. Amendment No. 180 to DPR-42
2. Amendment No. 170 to DPR-60
3. Safety Evaluation cc w/encls: See next page DISTRIBUTION PUBLIC LPL3-1 r/f RidsNrrDorlLpl3-1 RidsNrrPMMChawla RidsNrrLATHarris RidsOGCRp RidsAcrsAcnwMailCenter RidsNrrDirsltsb G. Hill, OIS RidsRgn3MailCenter RidsNrrDorlDpr ADAMS ACCESSION NO: ML071660005, Package ML071660002,

TS Pages ML072220040

  • per Memo dated January 31, 2007 OFFICE NRR/LPL3-1 NRR/LPL3-1/PM NRR/LPL3-1/LA NRR/ITSB OGC NRR/LPL3-1/(A)BC NAME JPoole MChawla THarris TKobetz*

NLO/MPL TTate DATE 8/9/07 08/9/07 08/9/07 1/31/07 06/27/07 08/10/07 OFFICIAL RECORD COPY

NUCLEAR MANAGEMENT COMPANY, LLC DOCKET NO. 50-282 PRAIRIE ISLAND NUCLEAR GENERATING PLANT, UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 180 License No. DPR-42 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Nuclear Management Company, LLC (the licensee), dated August 14, 2006, as supplemented by [[letter::L-PI-07-060, Supplement to License Amendment Request (LAR) for Miscellaneous Technical Specification (TS) Improvements (TAC Nos. MD 2822 and MD 2823)|letter dated July 16, 2007]], complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (I) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commissions regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commissions regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. DPR-42 is hereby amended to read as follows:

Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. 180, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance and shall be implemented within 90 days.

FOR THE NUCLEAR REGULATORY COMMISSION

/RA/

Travis L. Tate, Acting Chief Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation

Attachment:

Changes to the Facility Operating License and Technical Specifications Date of Issuance: August 10, 2007

NUCLEAR MANAGEMENT COMPANY, LLC DOCKET NO. 50-306 PRAIRIE ISLAND NUCLEAR GENERATING PLANT, UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 170 License No. DPR-60 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Nuclear Management Company, LLC (the licensee), dated August 14, 2006, as supplemented by [[letter::L-PI-07-060, Supplement to License Amendment Request (LAR) for Miscellaneous Technical Specification (TS) Improvements (TAC Nos. MD 2822 and MD 2823)|letter dated July 16, 2007]], complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (I) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commissions regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commissions regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. DPR-60 is hereby amended to read as follows:

Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. 170, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance and shall be implemented within 90 days.

FOR THE NUCLEAR REGULATORY COMMISSION

/RA/

Travis L. Tate, Acting Chief Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation

Attachment:

Changes to the Facility Operating License and Technical Specifications Date of Issuance: August 10, 2007

ATTACHMENT TO LICENSE AMENDMENT NOS. 180 AND 170 FACILITY OPERATING LICENSE NOS. DPR-42 AND DPR-60 DOCKET NOS. 50-282 AND 50-306 Replace the following pages of the Facility Operating License No. DPR-42 and DPR-60 with the attached revised pages. The changed areas are identified by a marginal line.

REMOVE INSERT DPR-42, License Page 3 DPR-42, License Page 3 DPR-60, License Page 3 DPR-60, License Page 3 Replace the following pages of the Appendix A Technical Specifications with the attached revised pages. The revised pages are identified by amendment number and contain marginal lines indicating the areas of change.

REMOVE INSERT 1.3-11 1.3-11 3.1.4-4 3.1.4-4 3.3.7-4 3.3.7-4 3.7.10-2 3.7.10-2 3.7.10-3 3.7.10-3 4.0-4 4.0-4 (4)

Pursuant to the Act and 10 CFR Parts 30, 40, and 70, NMC to receive, possess and use in amounts as required any byproduct, source or special nuclear material without restriction to chemical or physical form, for sample analysis or instrument and equipment calibration or associated with radioactive apparatus or components; (5)

Pursuant to the Act and 10 CFR Parts 30 and 70, NMC to possess but not separate, such byproduct and special nuclear materials as may be produced by the operation of the facility; (6)

Pursuant to the Act and 10 CFR Parts 30 and 70, NMC to transfer byproduct materials from other job sites owned by Northern States Power Company for the purpose of volume reduction and decontamination.

C.

This amended license shall be deemed to contain and is subject to the conditions specified in the following Commission regulations in 10 CFR Chapter l: Part 20, Section 30.34 of Part 30, Sections 50.54 and 50.59 of Part 50, and Section 70.32 of Part 70; is subject to all applicable provisions of the Act and to the rules, regulations, and orders of the Commission now or hereafter in effect; and is subject to the additional conditions specified or incorporated below:

(1)

Maximum Power Level NMC is authorized to operate the facility at steady state reactor core power levels not in excess of 1650 megawatts thermal.

(2)

Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. 180, are hereby incorporated in the license. NMC shall operate the facility in accordance with the Technical Specifications.

(3)

Physical Protection NMC shall fully implement and maintain in effect all provisions of the Commission-approved physical security, guard training and qualification, and safeguards contingency plans including amendments made pursuant to provisions of the Miscellaneous Amendments and Search Requirements revisions to 10 CFR 73.55 (51 FR 27817 and 27822) and to the authority of 10 CFR 50.90 and 10 CFR 50.54(p). The combined set of plans, which contains Safeguards Information protected under 10 CFR 73.21, is entitled: "Prairie Island Nuclear Generating Plant Security Plan, Training and Qualification Plan, Safeguards Contingency Plan, and Independent Spent Fuel Storage Installation Security Program," Revision 1, submitted by letters dated October 18, 2006, and January 10, 2007.

Unit 1 Amendment No. 180 (5)

Pursuant to the Act and 10 CFR Parts 30 and 70, NMC to possess but not separate, such byproduct and special nuclear materials as may be produced by the operation of the facility; (6)

Pursuant to the Act and 10 CFR Parts 30 and 70, NMC to transfer byproduct materials from other job sites owned by Northern States Power Company for the purposes of volume reduction and decontamination.

C.

This amended license shall be deemed to contain and is subject to the conditions specified in the following Commission regulations in 10 CFR Chapter l: Part 20, Section 30.34 of Part 30, Sections 50.54 and 50.59 of Part 50, and Section 70.32 of Part 70; is subject to all applicable provisions of the Act and to the rules, regulations, and orders of the Commission now or hereafter in effect; and is subject to the additional conditions specified or incorporated below:

(1)

Maximum Power Level NMC is authorized to operate the facility at steady state reactor core power levels not in excess of 1650 megawatts thermal.

(2)

Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. 170, are hereby incorporated in the license. NMC shall operate the facility in accordance with the Technical Specifications.

(3)

Physical Protection NMC shall fully implement and maintain in effect all provisions of the Commission-approved physical security, guard training and qualification, and safeguards contingency plans including amendments made pursuant to provisions of the Miscellaneous Amendments and Search Requirements revisions to 10 CFR 73.55 (51 FR 27817 and 27822) and to the authority of 10 CFR 50.90 and 10 CFR 50.54(p). The combined set of plans, which contains Safeguards Information protected under 10 CFR 73.21, is entitled:

Prairie Island Nuclear Generating Plant Security Plan, Training and Qualification Plan, Safeguards Contingency Plan, and Independent Spent Fuel Storage Installation Security Program, Revision 1, submitted by letters dated October 18, 2006, and January 10, 2007.

Unit 2 Amendment No. 170

SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO AMENDMENT NO. 180 TO FACILITY OPERATING LICENSE NO. DPR-42 AND AMENDMENT NO. 170 TO FACILITY OPERATION LICENSE NO. DPR-60 NUCLEAR MANAGEMENT COMPANY, LLC PRAIRIE ISLAND NUCLEAR GENERATING PLANT, UNITS 1 AND 2 DOCKET NOS. 50-282 AND 50-306

1.0 INTRODUCTION

By application dated August 14, 2006 (Agency Documents Access and Management System (ADAMS) Accession No. ML062270248), as supplemented by [[letter::L-PI-07-060, Supplement to License Amendment Request (LAR) for Miscellaneous Technical Specification (TS) Improvements (TAC Nos. MD 2822 and MD 2823)|letter dated July 16, 2007]] (ADAMS Accession No. ML071980141), the Nuclear Management Company, LLC (the licensee),

requested an amendment to revise the Technical Specifications (TSs) for the Prairie Island Nuclear Generating Plant (PINGP), Units 1 and 2. The amendments would revise the wording in the section headers in TS 1.3, Completion Times; remove a Surveillance Note in TS 3.1.4, Rod Group Alignment Limits; remove applicable modes in TS 3.3.7, Spent Fuel Pool Special Ventilation System (SFPSVS) Actuation Instrumentation; clarify TS 3.7.10, Control Room Special Ventilation System (CRSVS); and update a reference in TS 4.0, Design Features.

The licensees supplement dated July 16, 2007, provided additional information that clarified the application, did not expand the scope of the application as originally noticed, and did not change the Nuclear Regulatory Commission (NRC) staffs original proposed no significant hazards consideration determination as published in the Federal Register on November 21, 2006 (71 FR 67397).

2.0 REGULATORY EVALUATION

Section 182a of the Atomic Energy Act (Act) requires applicants for nuclear power plant operating licenses to include TSs as part of the license. These TSs are derived from the plant safety analyses.

The NRC staff reviewed the proposed revisions for compliance with Title 10 of the Code of Federal Regulations (10 CFR) Section 50.36 and agreement with the precedent as established in NUREG-1431, Standard Technical Specifications Westinghouse Plants. In general, licensees cannot justify TS changes solely on the basis of adopting the model Standard Technical Specifications (STS). To ensure this, the NRC staff makes a determination that proposed revisions maintain adequate safety. Changes that result in relaxation (less restrictive condition) of current TS requirements require detailed justification.

3.0 TECHNICAL EVALUATION

The licensees TS revision proposes to make four revisions that are editorial, administrative, or provide clarification and one revision that is more restrictive.

The licensee proposes to revise the following PINGP TSs:

3.1 TS 1.3, Completion Times TS 1.3 uses examples to provide guidance on the use of completion times. The discussion of Example 1.3-4 is carried over from page 1.3-10 to page 1.3-11, however, the text header on page 1.3-11 is erroneously identified as Example 1.3-5." This proposed revision corrects the header reference to Example 1.3-4. The NRC staff concludes that this revision is acceptable since it is an administrative change that conforms with the format guidance of NUREG-1431, and clarifies the example.

3.2 TS 3.1.4, Rod Group Alignment Limits The surveillance requirement (SR) 3.1.4.1 Note directs the operators to Limiting Condition for Operation (LCO) 3.1.7, Rod Position Indication, when an Individual Rod Position Indicator (RPI) and the group demand position differ by more than 12 steps. This may lead to confusion, since the RPI is operable when the RPI and the group demand position differ by more than 12 steps, if the rod position is < 30 or > 215 steps. Moreover, the requirements of LCO 3.1.7 must always be met in Modes 1 and 2 when LCO 3.1.4 is applicable. The licensee proposed to remove the Note to eliminate the potential confusion. Removing the Note does not result in any technical changes since SR 3.1.4 still requires that the rod positions are verified to be within the alignment limits. The NRC staff concludes that this revision is acceptable since removing the Note does not change the TS requirements, and is also consistent with the content guidance of NUREG-1431, which does not include a Note in SR 3.1.4.1.

3.3 TS 3.3.7, Spent Fuel Pool Special Ventilation System (SFPSVS) Actuation Instrumentation The SFPSVS ensures that radioactive materials in the fuel pool enclosure atmosphere following a fuel-handling accident are filtered and absorbed prior to exhausting to the environment. The system is not credited for filtering post-LOCA ECCS leakage and thus, in accordance with the content guidance of NUREG-1431, MODES 1, 2, 3, and 4 should not be included in the Applicable MODES of Specified Conditions column. The system actuation instrumentation initiates the SFPSVS automatically following receipt of a high radiation signal. The licensee proposed to remove MODES 1, 2, 3, and 4 from the Applicable Modes or Specified Conditions column in Table 3.3.7-1 for the radiation monitors which actuate the SFPSVS. With this change, the SFPSVS is required to be operable during movement of irradiated fuel assemblies which encompasses all the operating conditions of the design-basis fuel-handling accident. The design-basis fuel-handling accident is independent of the plant operating Modes; therefore, removing MODES 1, 2, 3, and 4 from the Applicable Modes or Specified Conditions column does not effect the TS requirements. The NRC staff concludes that removing MODES 1, 2, 3, and 4 from the Applicable Modes or Specified Conditions column is acceptable because the TS requirements remain applicable during the required conditions (during movement of irradiated fuel assemblies in the fuel pool enclosure).

3.4 TS 3.7.10, Control Room Special Ventilation System (CRSVS)

When the Required Actions and Completion Times of Condition B are not met, TS 3.7.10 does not provide any further guidance, thus the operators are required to apply LCO 3.0.3. The licensee proposed to add or B to Condition C in TS 3.7.10 which provides shutdown requirements which are consistent with the guidance in NUREG-1431. Under the TS rules of use, when no guidance is provided, the operators are required to apply LC 3.0.3 which requires the plant to initiate action within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> to shutdown, be in Mode 3 within 7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br />, be in Mode 4 within 13 hours1.50463e-4 days <br />0.00361 hours <br />2.149471e-5 weeks <br />4.9465e-6 months <br /> and be in Mode 5 within 37 hours4.282407e-4 days <br />0.0103 hours <br />6.117725e-5 weeks <br />1.40785e-5 months <br />. The shutdown requirements of Specification 3.7.10 Condition C are more restrictive than LCO 3.0.3 in that the plant will be required to be in Mode 3 within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in Mode 5 within 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. The NRC staff concludes that adopting the shutdown requirements of Condition C is acceptable because the Condition C shutdown requirements are more restrictive than the present shutdown requirements in LCO 3.0.3.

The licensee proposed to revise SR 3.7.10.4 to state, Verify each CRSVS train in the Emergency Mode delivers 3600 to 4400 cfm through the associated CRSVS filter. Currently, SR 3.7.10.4 requires verification that the CRSVS fan for each train delivers the specified flow.

The system design does not include any fan that is designated as the CRSVS fan.

Furthermore, the system design is complex in that no single system fan by itself provides the specified flow. Upon discussion with the NRC staff, the licensee submitted the supplement [[letter::L-PI-07-060, Supplement to License Amendment Request (LAR) for Miscellaneous Technical Specification (TS) Improvements (TAC Nos. MD 2822 and MD 2823)|letter dated July 16, 2007]], to revise the word filter to filters in order to more accurately describe the system design since each CRSVS train consists of a prefilter, high efficiency particulate air filter, and an activated charcoal adsorber section. The NRC staff concludes that this revision is acceptable since it is administrative and does not modify any requirements for system performance; it clarifies the requirements to be technically accurate.

3.5 TS 4.0 DESIGN FEATURES The licensee proposed to replace Reference 1 of TS 4.0 with the reference to an updated document which supersedes the current reference. The current TS 4.0 Reference 1 is a Westinghouse Calculation Note which supports the approved spent fuel pool criticality analyses and fuel storage configuration. The licensee proposes to replace the current reference with a reference to WCAP-16517-NP, Revision 0, Prairie Island Units 1 and 2 Spent Fuel Pool Criticality Analysis, dated November 2005 (WCAP-16517), which superseded the Calculation Note. The NRC staff concludes that this revision is acceptable because it is administrative and improves the accuracy of the TS.

4.0

SUMMARY

The licensees proposed revisions in this license amendment request reflect the current configuration of the plant and do not change the TS requirements. The NRC staff finds the proposed revisions are technically justified, comply with 10 CFR 50.36, and are consistent with the STS. On this basis, the NRC staff concludes that the proposed revisions to the TSs of PINGP, Units 1 and 2 are acceptable.

As part of the application for amendment, the licensee provided draft TS Bases pages which the licensee will incorporate into the licensee-controlled TS Bases document. The NRC reviewed these pages and found the changes consistent with the TS changes evaluated above.

5.0 STATE CONSULTATION

In accordance with the Commissions regulations, the Minnesota State official was notified of the proposed issuance of the amendment. The State official had no comments.

6.0 ENVIRONMENTAL CONSIDERATION

The amendments change the requirements with respect to installation or use of a facility component located within the restricted area as defined in 10 CFR Part 20 or change the SRs.

The NRC staff has determined that the amendments involve no significant increase in the amounts, and no significant change in the types, of any effluents that may be released offsite, and that there is no significant increase in individual or cumulative occupational radiation exposure. The Commission has previously issued a proposed finding that the amendments involve no significant hazards consideration and there has been no public comment on such finding (71 FR 67397). Accordingly, the amendments meet the eligibility criteria for categorical exclusion set forth in 10 CFR 51.22(c)(9). Pursuant to 10 CFR 51.22(b), no environmental impact statement or environmental assessment need be prepared in connection with the issuance of the amendments.

7.0 CONCLUSION

The Commission has concluded, based on the considerations discussed above, that: (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) such activities will be conducted in compliance with the Commission's regulations, and (3) the issuance of the amendment will not be inimical to the common defense and security or to the health and safety of the public.

Principal Contributor: Pete Hearn Date: August 10, 2007

Prairie Island Nuclear Generating Plant, Units 1 and 2 cc:

Jonathan Rogoff, Esquire Vice President, Counsel & Secretary Nuclear Management Company, LLC 700 First Street Hudson, WI 54016 Manager, Regulatory Affairs Prairie Island Nuclear Generating Plant Nuclear Management Company, LLC 1717 Wakonade Drive East Welch, MN 55089 Manager - Environmental Protection Division Minnesota Attorney Generals Office 445 Minnesota St., Suite 900 St. Paul, MN 55101-2127 U.S. Nuclear Regulatory Commission Resident Inspector's Office 1719 Wakonade Drive East Welch, MN 55089-9642 Regional Administrator, Region III U.S. Nuclear Regulatory Commission Suite 210 2443 Warrenville Road Lisle, IL 60532-4351 Administrator Goodhue County Courthouse Box 408 Red Wing, MN 55066-0408 Commissioner Minnesota Department of Commerce 85 7th Place East, Suite 500 St. Paul, MN 55101-2198 Tribal Council Prairie Island Indian Community ATTN: Environmental Department 5636 Sturgeon Lake Road Welch, MN 55089 Nuclear Asset Manager Xcel Energy, Inc.

414 Nicollet Mall, R.S. 8 Minneapolis, MN 55401 Michael B. Sellman President and Chief Executive Officer Nuclear Management Company, LLC 700 First Street Hudson, MI 54016 Douglas E. Cooper Senior Vice President and Chief Nuclear Officer Nuclear Management Company, LLC 700 First Street Hudson, WI 54016 July 2006