Loss of Vital AC Power with Subsequent Reactor Coolant System Heat-UpML031130253 |
Person / Time |
---|
Site: |
Beaver Valley, Millstone, Hatch, Monticello, Calvert Cliffs, Dresden, Davis Besse, Peach Bottom, Browns Ferry, Salem, Oconee, Nine Mile Point, Palisades, Palo Verde, Perry, Indian Point, Fermi, Kewaunee, Catawba, Harris, Wolf Creek, Saint Lucie, Point Beach, Oyster Creek, Watts Bar, Hope Creek, Grand Gulf, Cooper, Sequoyah, Byron, Pilgrim, Arkansas Nuclear, Three Mile Island, Braidwood, Susquehanna, Summer, Prairie Island, Columbia, Seabrook, Brunswick, Surry, Limerick, North Anna, Turkey Point, River Bend, Vermont Yankee, Crystal River, Haddam Neck, Ginna, Diablo Canyon, Callaway, Vogtle, Waterford, Duane Arnold, Farley, Robinson, Clinton, South Texas, San Onofre, Cook, Comanche Peak, Yankee Rowe, Maine Yankee, Quad Cities, Humboldt Bay, La Crosse, Big Rock Point, Rancho Seco, Zion, Midland, Bellefonte, Fort Calhoun, FitzPatrick, McGuire, LaSalle, Fort Saint Vrain, Shoreham, Satsop, Trojan, Atlantic Nuclear Power Plant |
---|
Issue date: |
04/16/1990 |
---|
From: |
Rossi C Office of Nuclear Reactor Regulation |
---|
To: |
|
---|
References |
---|
IN-90-025, NUDOCS 9004120133 |
Download: ML031130253 (8) |
|
Similar Documents at Beaver Valley, Millstone, Hatch, Monticello, Calvert Cliffs, Dresden, Davis Besse, Peach Bottom, Browns Ferry, Salem, Oconee, Nine Mile Point, Palisades, Palo Verde, Perry, Indian Point, Fermi, Kewaunee, Catawba, Harris, Wolf Creek, Saint Lucie, Point Beach, Oyster Creek, Watts Bar, Hope Creek, Grand Gulf, Cooper, Sequoyah, Byron, Pilgrim, Arkansas Nuclear, Three Mile Island, Braidwood, Susquehanna, Summer, Prairie Island, Columbia, Seabrook, Brunswick, Surry, Limerick, North Anna, Turkey Point, River Bend, Vermont Yankee, Crystal River, Haddam Neck, Ginna, Diablo Canyon, Callaway, Vogtle, Waterford, Duane Arnold, Farley, Robinson, Clinton, South Texas, San Onofre, Cook, Comanche Peak, Yankee Rowe, Maine Yankee, Quad Cities, Humboldt Bay, La Crosse, Big Rock Point, Rancho Seco, Zion, Midland, Bellefonte, Fort Calhoun, FitzPatrick, McGuire, LaSalle, Fort Saint Vrain, Shoreham, Satsop, Trojan, Atlantic Nuclear Power Plant |
---|
Category:NRC Information Notice
MONTHYEARInformation Notice 2020-02, Flex Diesel Generator Operational Challenges2020-09-15015 September 2020 Flex Diesel Generator Operational Challenges ML20225A0322020-09-0303 September 2020 NRC Choice Letter to NAC International with Attached Safety Inspection Report, IR 0721015/2020201, February 24-27, 2020 and July 22, 2020, Inspection of NAC International in Norcross, Georgia Information Notice 2012-09, PWROG-16043-NP-A, Revision 2, PWROG Program to Address NRC Information Notice 2012-09: Irradiation Effects on Fuel Assembly Spacer Grid Crush Strength for Westinghouse and CE PWR Fuel Designs.2019-11-30030 November 2019 PWROG-16043-NP-A, Revision 2, PWROG Program to Address NRC Information Notice 2012-09: Irradiation Effects on Fuel Assembly Spacer Grid Crush Strength for Westinghouse and CE PWR Fuel Designs. Information Notice 2011-20, NRC060 - NRC Information Notice 2011-20: Concrete Degradation by Alkali-Silica Reaction (Nov. 18, 2011)2019-07-24024 July 2019 NRC060 - NRC Information Notice 2011-20: Concrete Degradation by Alkali-Silica Reaction (Nov. 18, 2011) ML19196A2452019-07-15015 July 2019 Public Notice - Sequoyah Nuclear Plant, Unit 2 - Exigent Amendment to Facility Operating License Information Notice 2019-01, Inadequate Evaluation of Temporary Alterations2019-03-12012 March 2019 Inadequate Evaluation of Temporary Alterations ML16028A3082016-04-27027 April 2016 NRC Information Notice; IN 2016-05: Operating Experience Regarding Complications From a Loss of Instrumentation Air Information Notice 2015-05, Inoperability of Auxiliary and Emergency Feedwater Auto Start Circuits on Loss of Main Feedwater Pumps2015-05-12012 May 2015 Inoperability of Auxiliary and Emergency Feedwater Auto Start Circuits on Loss of Main Feedwater Pumps Information Notice 2015-05, Inoperability Of Auxiliary And Emergency Feedwater Auto Start Circuits On Loss Of Main Feedwater Pumps2015-05-12012 May 2015 Inoperability Of Auxiliary And Emergency Feedwater Auto Start Circuits On Loss Of Main Feedwater Pumps Information Notice 2013-20, OFFICIAL EXHIBIT - NYS000538-00-BD01 - NRC Information Notice 2013-20: Steam Generator Channel Head and Tubesheet Degradation (October 3, 2013) (ML13204A143)2013-10-0303 October 2013 OFFICIAL EXHIBIT - NYS000538-00-BD01 - NRC Information Notice 2013-20: Steam Generator Channel Head and Tubesheet Degradation (October 3, 2013) (ML13204A143) Information Notice 2013-20, Official Exhibit - NYS000538-00-BD01 - NRC Information Notice 2013-20: Steam Generator Channel Head and Tubesheet Degradation (October 3, 2013) (ML13204A143)2013-10-0303 October 2013 Official Exhibit - NYS000538-00-BD01 - NRC Information Notice 2013-20: Steam Generator Channel Head and Tubesheet Degradation (October 3, 2013) (ML13204A143) Information Notice 2013-11, OFFICIAL EXHIBIT - NYS000551-00-BD01 - NRC Information Notice 2013-11: Crack-Like Indication at Dents/Dings and in the Freespan Region of Thermally Treated Alloy 600 Steam Generator Tubes (July 3, 2013)2013-07-0303 July 2013 OFFICIAL EXHIBIT - NYS000551-00-BD01 - NRC Information Notice 2013-11: Crack-Like Indication at Dents/Dings and in the Freespan Region of Thermally Treated Alloy 600 Steam Generator Tubes (July 3, 2013) Information Notice 2013-11, Official Exhibit - NYS000551-00-BD01 - NRC Information Notice 2013-11: Crack-Like Indication at Dents/Dings and in the Freespan Region of Thermally Treated Alloy 600 Steam Generator Tubes (July 3, 2013)2013-07-0303 July 2013 Official Exhibit - NYS000551-00-BD01 - NRC Information Notice 2013-11: Crack-Like Indication at Dents/Dings and in the Freespan Region of Thermally Treated Alloy 600 Steam Generator Tubes (July 3, 2013) Information Notice 2010-12, Intervenors' Fifth Motion to Amend and/or Supplement Proposed Contention No. 5 (Shield Building Cracking). Appendix VI: NRC FOIA Responses (B-51 Through B-53); Turkey Point Event Report; NRC Information Notice 2010-12: Contain2012-08-17017 August 2012 Intervenors' Fifth Motion to Amend and/or Supplement Proposed Contention No. 5 (Shield Building Cracking). Appendix VI: NRC FOIA Responses (B-51 Through B-53); Turkey Point Event Report; NRC Information Notice 2010-12: Containment Liner Cor Information Notice 2010-12, Intervenors' Fifth Motion to Amend and/or Supplement Proposed Contention No. 5 (Shield Building Cracking). Appendix VI: NRC FOIA Responses (B-51 Through B-53); Turkey Point Event Report; NRC Information Notice 2010-12: Con2012-08-17017 August 2012 Intervenors' Fifth Motion to Amend and/or Supplement Proposed Contention No. 5 (Shield Building Cracking). Appendix VI: NRC FOIA Responses (B-51 Through B-53); Turkey Point Event Report; NRC Information Notice 2010-12: Containment Liner Cor Information Notice 2010-12, Intervenors' Fifth Motion to Amend And/Or Supplement Proposed Contention No. 5 (Shield Building Cracking). Appendix VI: NRC FOIA Responses (B-51 Through B-53); Turkey Point Event Report; NRC Information Notic2012-08-17017 August 2012 Intervenors' Fifth Motion to Amend And/Or Supplement Proposed Contention No. 5 (Shield Building Cracking). Appendix VI: NRC FOIA Responses (B-51 Through B-53); Turkey Point Event Report; NRC Information Notice 2010-12: Containment Liner Cor Information Notice 2012-13, Boraflex Degradation Surveillance Programs and Corrective Actions in the Spent Fuel Pool2012-08-10010 August 2012 Boraflex Degradation Surveillance Programs and Corrective Actions in the Spent Fuel Pool Information Notice 2012-13, Boraflex Degradation Surveillance Programs And Corrective Actions In The Spent Fuel Pool2012-08-10010 August 2012 Boraflex Degradation Surveillance Programs And Corrective Actions In The Spent Fuel Pool Information Notice 2012-11, Age Related Capacitor Degradation2012-07-23023 July 2012 Age Related Capacitor Degradation ML12031A0132012-02-0606 February 2012 U.S. Nuclear Regulatory Commission Investigation Report No. 2-2010-058, Cpn International, Inc Information Notice 2011-19, Licensee Event Reports Containing Information Pertaining to Defects to Basic Components2011-09-26026 September 2011 Licensee Event Reports Containing Information Pertaining to Defects to Basic Components Information Notice 2011-15, Steel Containment Degradation and Associated License Renewal Aging Management Issues2011-08-0101 August 2011 Steel Containment Degradation and Associated License Renewal Aging Management Issues Information Notice 2011-17, Calculation Methodologies for Operability Determinations of Gas Voids in Nuclear Power Plant Piping2011-07-26026 July 2011 Calculation Methodologies for Operability Determinations of Gas Voids in Nuclear Power Plant Piping Information Notice 2011-13, Official Exhibit - NYS000329-00-BD01 - NRC Information Notice 2011-13, Control Rod Blade Cracking Resulting in Reduced Design Lifetime (Jun 29, 2011) (NRC in 2011-13)2011-06-29029 June 2011 Official Exhibit - NYS000329-00-BD01 - NRC Information Notice 2011-13, Control Rod Blade Cracking Resulting in Reduced Design Lifetime (Jun 29, 2011) (NRC in 2011-13) Information Notice 2011-13, Official Exhibit - Nys000329-00-Bd01 - NRC Information Notice 2011-13, Control Rod Blade Cracking Resulting in Reduced Design Lifetime (Jun 29, 2011) (Nrc in 2011-13)2011-06-29029 June 2011 Official Exhibit - Nys000329-00-Bd01 - NRC Information Notice 2011-13, Control Rod Blade Cracking Resulting in Reduced Design Lifetime (Jun 29, 2011) (Nrc in 2011-13) Information Notice 2011-13, OFFICIAL EXHIBIT - NYS000329-00-BD01 - NRC Information Notice 2011-13, Control Rod Blade Cracking Resulting in Reduced Design Lifetime (Jun 29, 2011) (NRC in 2011-13)2011-06-29029 June 2011 OFFICIAL EXHIBIT - NYS000329-00-BD01 - NRC Information Notice 2011-13, Control Rod Blade Cracking Resulting in Reduced Design Lifetime (Jun 29, 2011) (NRC in 2011-13) Information Notice 2011-04, IN: Contaminants and Stagnant Conditions Affecting Stress Corrosion Cracking in Stainless Steel Piping in Pressurized Water Reactors2011-02-23023 February 2011 IN: Contaminants and Stagnant Conditions Affecting Stress Corrosion Cracking in Stainless Steel Piping in Pressurized Water Reactors Information Notice 2011-04, In: Contaminants and Stagnant Conditions Affecting Stress Corrosion Cracking in Stainless Steel Piping in Pressurized Water Reactors2011-02-23023 February 2011 In: Contaminants and Stagnant Conditions Affecting Stress Corrosion Cracking in Stainless Steel Piping in Pressurized Water Reactors Information Notice 2011-04, in: Contaminants and Stagnant Conditions Affecting Stress Corrosion Cracking in Stainless Steel Piping in Pressurized Water Reactors2011-02-23023 February 2011 in: Contaminants and Stagnant Conditions Affecting Stress Corrosion Cracking in Stainless Steel Piping in Pressurized Water Reactors Information Notice 2010-26, New England Coalition'S Motion for Leave to Reply to NRC Staff'S Objection to Nec'S Notification of Information Notice 2010-26 and Entergy'S Response to the Supplement to Nec'S Petition for Commission Review of LBP-10-2010-12-30030 December 2010 New England Coalition'S Motion for Leave to Reply to NRC Staff'S Objection to Nec'S Notification of Information Notice 2010-26 and Entergy'S Response to the Supplement to Nec'S Petition for Commission Review of LBP-10-19 Information Notice 2010-26, New England Coalition'S Motion for Leave to Reply to NRC Staff'S Objection to Nec'S Notification of Information Notice 2010-26 and Entergy'S Response to the Supplement to Nec'S Petition for Commission Review2010-12-30030 December 2010 New England Coalition'S Motion for Leave to Reply to NRC Staff'S Objection to Nec'S Notification of Information Notice 2010-26 and Entergy'S Response to the Supplement to Nec'S Petition for Commission Review of LBP-10-19 Information Notice 2010-26, 2010/12/21-NRC Staff'S Objection to Nec'S Notification of Information Notice 2010-262010-12-21021 December 2010 2010/12/21-NRC Staff'S Objection to Nec'S Notification of Information Notice 2010-26 ML13066A1872009-12-16016 December 2009 Draft NRC Information Notice 2009-xx - Underestimate of Dam Failure Frequency Used in Probabilistic Risk Assessments ML1007804482009-11-23023 November 2009 Email from Peter Bamford, NRR to Pamela Cowan, Exelon on TMI Contamination Control Event Information Notice 2009-11, NSP000059-Revised Prefiled Testimony of Northard/Petersen/Peterson-NRC Information Notice 2009-112009-07-0707 July 2009 NSP000059-Revised Prefiled Testimony of Northard/Petersen/Peterson-NRC Information Notice 2009-11 Information Notice 2009-10, Official Exhibit - NYS000019-00-BD01- NRC Information Notice 2009-10, Transformers Failures - Recent Operating Experience (Jul. 7, 2009) (NRC in 2009-10)2009-07-0707 July 2009 Official Exhibit - NYS000019-00-BD01- NRC Information Notice 2009-10, Transformers Failures - Recent Operating Experience (Jul. 7, 2009) (NRC in 2009-10) Information Notice 2009-09, Improper Flow Controller Settings Renders Injection Systems Inoperable and Surveillance Did Not Identify2009-06-19019 June 2009 Improper Flow Controller Settings Renders Injection Systems Inoperable and Surveillance Did Not Identify Information Notice 2008-12, Reactor Trip Due to Off-Site Power Fluctuation2008-07-0707 July 2008 Reactor Trip Due to Off-Site Power Fluctuation Information Notice 2008-11, Service Water System Degradation at Brunswicksteam Electric Plant Unit 12008-06-18018 June 2008 Service Water System Degradation at Brunswicksteam Electric Plant Unit 1 Information Notice 2008-04, Counterfeit Parts Supplied to Nuclear Power Plants2008-04-0707 April 2008 Counterfeit Parts Supplied to Nuclear Power Plants Information Notice 1991-09, Counterfeiting of Crane Valves2007-09-25025 September 2007 Counterfeiting of Crane Valves Information Notice 2007-28, Potential Common Cause Vulnerabilities in Essential Service Water Systems Due to Inadequate Chemistry Controls2007-09-19019 September 2007 Potential Common Cause Vulnerabilities in Essential Service Water Systems Due to Inadequate Chemistry Controls Information Notice 2007-29, Temporary Scaffolding Affects Operability of Safety-Related Equipment2007-09-17017 September 2007 Temporary Scaffolding Affects Operability of Safety-Related Equipment Information Notice 2007-14, Loss of Offsite Power and Dual-Unit Trip at Catawba Nuclear Generating Station2007-03-30030 March 2007 Loss of Offsite Power and Dual-Unit Trip at Catawba Nuclear Generating Station Information Notice 2007-06, Potential Common Cause Vulnerabilities in Essential Service Water Systems2007-02-0909 February 2007 Potential Common Cause Vulnerabilities in Essential Service Water Systems Information Notice 2007-05, Vertical Deep Draft Pump Shaft and Coupling Failures2007-02-0909 February 2007 Vertical Deep Draft Pump Shaft and Coupling Failures Information Notice 2006-31, Inadequate Fault Interrupting Rating of Breakers2006-12-26026 December 2006 Inadequate Fault Interrupting Rating of Breakers Information Notice 2006-29, Potential Common Cause Failure of Motor-operated Valves as a Result of Stem Nut Wear2006-12-14014 December 2006 Potential Common Cause Failure of Motor-operated Valves as a Result of Stem Nut Wear Information Notice 2006-29, Potential Common Cause Failure of Motor-operated Valves As a Result of Stem Nut Wear2006-12-14014 December 2006 Potential Common Cause Failure of Motor-operated Valves As a Result of Stem Nut Wear Information Notice 2006-13, E-mail from M. Mclaughlin on NRC, Regarding NRC Information Notice 2006-13: Groundwater Contamination2006-07-13013 July 2006 E-mail from M. Mclaughlin on NRC, Regarding NRC Information Notice 2006-13: Groundwater Contamination 2020-09-03 The following query condition could not be considered due to this wiki's restrictions on query size or depth: <code> [[:Beaver Valley]] OR [[:Millstone]] OR [[:Hatch]] OR [[:Monticello]] OR [[:Calvert Cliffs]] OR [[:Dresden]] OR [[:Davis Besse]] OR [[:Peach Bottom]] OR [[:Browns Ferry]] OR [[:Salem]] OR [[:Oconee]] OR [[:Nine Mile Point]] OR [[:Palisades]] OR [[:Palo Verde]] OR [[:Perry]] OR [[:Indian Point]] OR [[:Fermi]] OR [[:Kewaunee]] OR [[:Catawba]] OR [[:Harris]] OR [[:Wolf Creek]] OR [[:Saint Lucie]] OR [[:Point Beach]] OR [[:Oyster Creek]] OR [[:Watts Bar]] OR [[:Hope Creek]] OR [[:Grand Gulf]] OR [[:Cooper]] OR [[:Sequoyah]] OR [[:Byron]] OR [[:Pilgrim]] OR [[:Arkansas Nuclear]] OR [[:Three Mile Island]] OR [[:Braidwood]] OR [[:Susquehanna]] OR [[:Summer]] OR [[:Prairie Island]] OR [[:Columbia]] OR [[:Seabrook]] OR [[:Brunswick]] OR [[:Surry]] OR [[:Limerick]] OR [[:North Anna]] OR [[:Turkey Point]] OR [[:River Bend]] OR [[:Vermont Yankee]] OR [[:Crystal River]] OR [[:Haddam Neck]] OR [[:Ginna]] OR [[:Diablo Canyon]] OR [[:Callaway]] OR [[:Vogtle]] OR [[:Waterford]] OR [[:Duane Arnold]] OR [[:Farley]] OR [[:Robinson]] OR [[:Clinton]] OR [[:South Texas]] OR [[:San Onofre]] OR [[:Cook]] OR [[:Comanche Peak]] OR [[:Yankee Rowe]] OR [[:Maine Yankee]] OR [[:Quad Cities]] OR [[:Humboldt Bay]] OR [[:La Crosse]] OR [[:Big Rock Point]] OR [[:Rancho Seco]] OR [[:Zion]] OR [[:Midland]] OR [[:Bellefonte]] OR [[:Fort Calhoun]] OR [[:FitzPatrick]] OR [[:McGuire]] OR [[:LaSalle]] OR [[:Fort Saint Vrain]] OR [[:Shoreham]] OR [[:Satsop]] OR [[:Trojan]] OR [[:Atlantic Nuclear Power Plant]] </code>.
[Table view]The following query condition could not be considered due to this wiki's restrictions on query size or depth: <code> [[:Beaver Valley]] OR [[:Millstone]] OR [[:Hatch]] OR [[:Monticello]] OR [[:Calvert Cliffs]] OR [[:Dresden]] OR [[:Davis Besse]] OR [[:Peach Bottom]] OR [[:Browns Ferry]] OR [[:Salem]] OR [[:Oconee]] OR [[:Nine Mile Point]] OR [[:Palisades]] OR [[:Palo Verde]] OR [[:Perry]] OR [[:Indian Point]] OR [[:Fermi]] OR [[:Kewaunee]] OR [[:Catawba]] OR [[:Harris]] OR [[:Wolf Creek]] OR [[:Saint Lucie]] OR [[:Point Beach]] OR [[:Oyster Creek]] OR [[:Watts Bar]] OR [[:Hope Creek]] OR [[:Grand Gulf]] OR [[:Cooper]] OR [[:Sequoyah]] OR [[:Byron]] OR [[:Pilgrim]] OR [[:Arkansas Nuclear]] OR [[:Three Mile Island]] OR [[:Braidwood]] OR [[:Susquehanna]] OR [[:Summer]] OR [[:Prairie Island]] OR [[:Columbia]] OR [[:Seabrook]] OR [[:Brunswick]] OR [[:Surry]] OR [[:Limerick]] OR [[:North Anna]] OR [[:Turkey Point]] OR [[:River Bend]] OR [[:Vermont Yankee]] OR [[:Crystal River]] OR [[:Haddam Neck]] OR [[:Ginna]] OR [[:Diablo Canyon]] OR [[:Callaway]] OR [[:Vogtle]] OR [[:Waterford]] OR [[:Duane Arnold]] OR [[:Farley]] OR [[:Robinson]] OR [[:Clinton]] OR [[:South Texas]] OR [[:San Onofre]] OR [[:Cook]] OR [[:Comanche Peak]] OR [[:Yankee Rowe]] OR [[:Maine Yankee]] OR [[:Quad Cities]] OR [[:Humboldt Bay]] OR [[:La Crosse]] OR [[:Big Rock Point]] OR [[:Rancho Seco]] OR [[:Zion]] OR [[:Midland]] OR [[:Bellefonte]] OR [[:Fort Calhoun]] OR [[:FitzPatrick]] OR [[:McGuire]] OR [[:LaSalle]] OR [[:Fort Saint Vrain]] OR [[:Shoreham]] OR [[:Satsop]] OR [[:Trojan]] OR [[:Atlantic Nuclear Power Plant]] </code>. |
. * - *
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF NUCLEAR REACTOR REGULATION
WASHINGTON, D.C. 20555 April 16, 1990
NRC INFORMATION NOTICE NO. 90-25: LOSS OF VITAL AC POWER WITH SUBSEQUENT
REACTOR COOLANT SYSTEM HEAT-UP
Addressees
All holders of operating licenses or construction permits for nuclear power
reactors.
Purpose
This information notice is being provided to inform addressees of a significant
operating event which occurred at the Georgia Power Company's Vogtle Nuclear
Plant on March 20, 1990. The event took place while Unit 1 was in mid-loop
in operational mde 6 and demonstrates the need for operating personnel to be
prudent in removing equipment from service or establishing atypical equipment
alignments during shutdown. It is expected that recipients will review the
information for applicability to their facilities and consider actions, as
appropriate,.to avoid similar problems. However, suggestions contained in
this information notice do not constitute NRC requirements; therefore, no
specific action or written response is required.
Description of Circumstances
On March 20, 1990, a loss of vital ac power occurred while Vogtle Unit 2 was
operating at 100 percent power and Unit 1 had been in a refueling outage for
about 4 weeks. Unit 1 was in mid-loop in operational mode 6 with plant equip- ment conditions as follows:
o The Unit 1 B reserve auxiliary transformer (RAT) was tagged out of
service for maintenance
o The Unit 1 B emergency diesel generator (EDG) was tagged out of
service and disassembled for maintenance
o The Unit 1 A RAT was supplying offsite power to the crosstied Unit 1 A and B vital buses
o The reactor coolant system (RCS) temperature was being maintained at
around 90 degrees Fahrenheit (F) via the train A residual heat removal
(RHR) pump, the-train B pump was in standby
o The vessel head was in place with the bolts not fully tensioned
o The pressurizer manway cover was removed
_ __ Al e,
IN 90-25 April 16, 1990 o The manways for steam generators 2 and 3 were partially bolted in place
and the manways for steam generators 1 and 4 were in place with bolts
fully tensioned
o The inboard charging line check valve and an accumulator isolation
valve were open for inspection
o The containment equipment hatch and the containment personnel hatch
were open
At about 9:20 a.m., a truck carrying fuel and lubricants in the plant low
voltage switchyard backed into a support column for the feeder line supplying
power to the Unit 1 A RAT and the Unit 2 B RAT. The insulator for the C phase
of the feeder line fractured and initiated a phase-to-ground electrical fault.
The fault resulted in a loss of power to the Unit 1 A RAT and the Unit 2 B RAT.
The Unit 2 B EDG started and loaded to the deenergized Unit 2 B vital bus. How- ever, a Unit 2 turbine trip and reactor trip occurred because of an improperly
connected (wrong tap) differential current transformer (DCT). The DCT initiated
the trip when the current surge associated with the phase-to-ground fault was
sensed. The Unit 2 trip was uncomplicated.
Because both of the Unit 1 vital buses were crosstied and being supplied by
the Unit 1 A RAT, the loss of the transformer deenergized both vital buses.
Deenergizing these buses resulted in the loss of power to the operating RHR
pump. Since the Unit 1 B EDG was tagged out of service and disassembled for
maintenance, the emergency power supply for the B vital bus was unavailable
and the standby B RHR pump could not be started.
The available Unit 1 A EDG started on bus undervoltage, but for unknown reasons, it shut down automatically after 1 minute and 20 seconds. At 9:40 a.m., plant
operators declared a site area emergency. A loss of all onsite and offsite ac
power at Vogtle for more than 15 minutes is classified as a site area emergency.
The licensee made their declaration because all vital ac power was lost for
greater than 15 minutes. Approximately 18 minutes after the first start of
the A EDG, the operators locally reset the load sequencer which automatically
restarted the A EDG on undervoltage. However, after 1 minute and 10 seconds, the diesel again shut down automatically. At 9:56 a.m., plant operators per- formed an "emergency" manual start of the diesel, which bypassed most of the
diesel's protective trips. The diesel started and loaded to the bus, the A
RHR pump was restarted, and core cooling was reestablished to Unit 1. With
the start of the diesel, the site area emergency was downgraded to an "alert"
at 10:15 a.m. Containment integrity was established at 11:03 a.m.
Plant personnel returned the Unit 1 B RAT to service after completing formal
tagout removal procedures. However, attempts to energize the transformer were
delayed for several minutes because of a sticking mechanical interlock in the
control circuitry for a motor-operated disconnect switch on the high side of
the B RAT. Power was restored to the B vital bus via the B RAT at 11:40 a.m.
At 12:38 a.m., core cooling was shifted to the B RHR train to facilitate sub- sequent electrical alignment changes.
e. v - %
IN 90-25 April 16, 1990 According to control roon indication, RCS temperature increased from 90 to
136 degrees F during the 36 minutes required to reenergize the A bus (1.3 degrees F/min).
Throughout the event, non-vital power was continuously provided to Unit 1 from
offsite sources, via backfeed through the main generator transformer. Also, the Unit 2 electrical distribution system remained energized (aside from the
momentary loss of power before the reactor trip). However, the Vogtle electrical
system was not designed to permit easy interconnection of the Unit 1 vital buses
to nonvital power or to the Unit 2 electrical buses. Therefore, there were no
procedures in place to provide guidance on interconnecting the Unit 1 vital and
nonvital buses or for interconnecting the Unit 1 electrical distribution system
with the distribution system at Unit 2. (There are no regulatory requirements
that direct the licensee to develop Interconnection procedures.)
Discussion:
The NRC has previously identified concerns with the operability of necessary
equipment in shutdown modes. In Information Notice (IN)80-2O, "Loss of Decay
Heat Removal Capability at Davis-Besse Unit 1 While in a Refueling Mode" an
extended loss of decay heat removal capability was attributed to a number of
factors, including inadequate procedures, inadequate administrative controls, and the conduct of extensive maintenance activities.
Information Notice 84-42, "Equipment Availability for Conditions During Outages
Not Covered by Technical Specifications," describes an event at the Palisades
Nuclear Plant involving the total loss of all ac power. The Palisades event
was precipitated by personnel performing actions during a refueling outage
without an appreciation for the effect of those actions on the plant as it
was configured. Many pieces of equipment were tagged out of service for
maintenance. Personnel intentionally interrupted offsite power. This action
caused the loss of the only available service water pump. As a result, cooling
water was interrupted to the only available (and operating) diesel generator.
The diesel overheated and was manually tripped. As a result, all station ac
power was interrupted, causing the loss of fuel pool cooling. (The reactor
had been defueled, and its fuel was being stored in the spent fuel pool).
The recent Vogtle event reemphasizes the need for careful planning of equipment
outages during shutdown. Licensees, in general, have considerable latitude in
removing equipment from service and altering normal system lineups while in
shutdown modes if only the minimum technical specification requirements are
considered. The desire to return nuclear units to service as quickly as
possible can result in maintenance being conducted on redundant, safety- related systems, concurrently. The appropriateness of conducting parallel
maintenance activities should be considered in light of the availability of
alternate equipment and procedures to mitigate the consequences of potential
operational problems. It is important that plant outage plans assure that
an adequate complement of equipment capable of responding to potential events
remains available throughout the outage. Particular care is needed when the
reactor pressure boundary is not intact or the reactor coolant system is at
mid-loop.
IN 90-25 April 16, 1990 A special investigation of the Vogtle event is being conducted by an NRC
Incident Investigation Team (1IT). The information contained in this notice
is preliminary and is subject to change, pending the findings made by the IIT.
This Information notice requires no specific action or written response. If
you have any questions about the information in this notice, please contact
one of the technical contacts listed below or the appropriate NRR project
manager.
~6hfares Eossi, Director
Division of Operational Events Assessment
Office of Nuclear Reactor Regulation
Technical Contacts: N. Fields, NRR
(301) 492-1173 E. Trager, AEOD
(301) 492-4496 Attachment: List of Recently Issued NRC Information Notices
, 0 - -u
Attachment
IN 90-25 April 16, 1990 LIST OF RECENTLY ISSUED
NRC INFORMATION NOTICES
Intormation Date ot
Notice No. Subject Issuance Issued to
90-24 Transportation of Model 4/10/90 All NRC licensees
Spec 2-T Radiographic authorized to use, Exposure Device transport, or operate
radiographic exposure
devices and source
changers.
90-23 Improper Installation of 4/4/90 All holders of OLs
Patel Conduit Seals or CPs for nuclear
power reactors.
90-22 Unanticipated Equipment 3/23/90 All holders of OLs
Actuations Following or CPs for nuclear
Restoration of Power power reactors.
to Rosemount Transmitter
Trip Units
90-21 Potential Failure of Motor- 3/22/90 All holders of OLs
Operated Butterfly Valves or CPs for nuclear
to Operate Because Valve power reactors.
Seat Friction was Under- estimated
90-20 Personnel Injuries Resulting 3/22/90 All NRC licensees
from Improper Operation of who process or
Radwaste Incinerators incinerate radio- active waste.
90-19 Potential Loss of Effective 3/14/90 All holders of OLs
Volume for Containment or CPs for PWRs.
Recirculation Spray at
PWR Facilities
90-18 Potential Problems with 3/9/90 All holders of OLs
Crosby Safety Relief Valves or CPs for nuclear
Used on Diesel Generator power reactors.
Air Start Receiver Tanks
90-17 Weight and Center of 3/8/90 All holders of OLs
Gravity Discrepancies or CPs for nuclear
for Copes-Vulcan Valves power reactors.
OL = Operating License
CP = Construction Permit
tNOW,
IN 90-25
- -April 16, 1990 A special investigation of the Vogtle event is being conducted by an NRC
Incident Investigation Team (IIT). The information contained in this notice
is preliminary and is subject to change, pending the findings made by the IIT.
This information notice requires no specific action or written response. If
you have any questions about the information in this notice, please contact
one of the technical contacts listed below or the appropriate NRR project
manager.
Charles E. Rossi, Director
Division of Operational Events Assessment
Office of Nuclear Reactor Regulation
Technical Contacts: N. Fields, NRR
(301) 492-1173 E. Trager, AEOD
(301) 492-4496 Attachment: List of Recently Issued NRC Information Notices
- SEE PREVIOUS PAGE FOR CONCURRENCE
OFC *OEAB:DOEA *TECH ED *REGION I (IIT) *PD23 NAME NFields WLazarus TReed
DATE 4/11/90 4/11/90 4/11/90 4/11/90
OFC *OEAB:DOEA *C:OEAB:DOEA *C:GCB:DOEA
NAME DFISCHER PSwetland CBERLINGER
DATE 4/11/90 4/11/90 4/11/90 4/1 3/90
OFFICIAL RECORD COPY
OFFICIAL RECORD COPY
Document Name: VOGTLE
OFC O .DOEA p
NAME NFlelds
DATE yv"1/90
OFC O X -DOEA
NAME DFISCHER
DATE f /11/90
|
---|
|
list | - Information Notice 1990-01, Importance of Proper Response to Self-Identified Violations by Licensees (12 January 1990, Topic: Uranium Hexafluoride)
- Information Notice 1990-02, Potential Degradation of Secondary Containment (22 January 1990)
- Information Notice 1990-03, Malfunction of Borg-Warner Bolted Bonnet Check Valves Caused by Failure of the Swing Arm (23 January 1990, Topic: Liquid penetrant)
- Information Notice 1990-04, Cracking of the Upper Shell-to-Transition Cone Girth Welds in Steam Generators, (26 January 1990, Topic: Nondestructive Examination)
- Information Notice 1990-05, Inter-System Discharge of Reactor Coolant (29 January 1990)
- Information Notice 1990-06, Potential for Loss of Shutdown Cooling While at Low Reactor Coolant Levels (29 January 1990)
- Information Notice 1990-07, New Information Regarding Insulation Material Performance and Debris Blockage of PWR Containment Sumps (30 January 1990)
- Information Notice 1990-08, KR-85 Hazards from Decayed Fuel (1 February 1990)
- Information Notice 1990-08, KR-85 Hazards From Decayed Fuel (1 February 1990)
- Information Notice 1990-09, Extended Interim Storage of Low-Level Radioactive Waste by Fuel Cycle and Materials Licensees (5 February 1990, Topic: Decommissioning Funding Plan)
- Information Notice 1990-10, Primary Water Stress Corrosion Cracking (PWSCC) of Inconel 600 (23 February 1990, Topic: Boric Acid, Hydrostatic, Liquid penetrant)
- Information Notice 1990-10, Primary Water Stress Corrosion Cracking of Inconel 600 (23 February 1990, Topic: Boric Acid, Hydrostatic, Nondestructive Examination, Liquid penetrant)
- Information Notice 1990-11, Maintenance Deficiency Associated with Solenoid-Operated Valves (28 February 1990)
- Information Notice 1990-12, Monitoring or Interruption of Plant Communications (28 February 1990)
- Information Notice 1990-13, Importance of Review and Analysis of Safeguards Event Logs (5 March 1990)
- Information Notice 1990-14, Accidental Disposal of Radioactive Materials (6 March 1990, Topic: Brachytherapy)
- Information Notice 1990-15, Reciprocity Notification of Agreement State Radiation Control Directors Before Beginning Work in Agreement States (17 March 1990, Topic: Uranium Hexafluoride)
- Information Notice 1990-16, Compliance with New Decommissioning Rule (7 March 1990)
- Information Notice 1990-17, Weight and Center of Gravity Discrepancies for Copes-Vulcan Valves (8 March 1990, Topic: Earthquake)
- Information Notice 1990-18, Potential Problems with Crosby Safety Relief Valves Used on Diesel Generator Air Start Receiver Tanks (9 March 1990)
- Information Notice 1990-18, Potential Problems With Crosby Safety Relief Valves Used on Diesel Generator Air Start Receiver Tanks (9 March 1990)
- Information Notice 1990-19, Potential Loss of Effective Volume for Containment Recirculation Spray at PWR Facilities (14 March 1990)
- Information Notice 1990-20, Personnel Injuries Resulting from Improper Operation of Radwaste Incinerators (22 March 1990)
- Information Notice 1990-21, Potential Failure of Motor-Operated Butterfly Valves to Operate Because Valve Seat Friction was Underestimated (22 March 1990)
- Information Notice 1990-21, Potential Failure of Motor-Operated Butterfly Valves to Operate Because Valve Seat Friction Was Underestimated (22 March 1990)
- Information Notice 1990-22, Unanticipated Equipment Actuations Following Restoration of Power to Rosemount Transmitter Trip Units (23 March 1990, Topic: Reactor Vessel Water Level)
- Information Notice 1990-23, Improper Installation of Patel Conduit Seals (4 April 1990)
- Information Notice 1990-24, Transportation of Model Spec 2-T Radiographic Exposure Device (10 April 1990)
- Information Notice 1990-24, Transportation of Model SPEC 2-T Radiographic Exposure Device (10 April 1990)
- Information Notice 1990-25, Loss of Vital AC Power With Subsequent Reactor Coolant System Heat-Up (16 April 1990)
- Information Notice 1990-25, Loss of Vital AC Power with Subsequent Reactor Coolant System Heat-Up (16 April 1990)
- Information Notice 1990-26, Inadequate Flow of Essential Service Water to Room Coolers and Heat Exchangers for Engineered Safety-Feature Systems (24 April 1990)
- Information Notice 1990-27, Clarification of the Recent Revisions to the Regulatory Requirements for Packaging of Uranium Hexafluoride (UF6) for Transportation (30 April 1990)
- Information Notice 1990-28, Potential Error In High Steamline Flow Setpoint (30 April 1990)
- Information Notice 1990-28, Potential Error in High Steamline Flow Setpoint (30 April 1990)
- Information Notice 1990-29, Cracking of Cladding and Its Heat-Affected Zone in the Base Metal of a Reactor Vessel Head (30 April 1990, Topic: Nondestructive Examination, Liquid penetrant)
- Information Notice 1990-30, Ultrasonic Inspection Techniques for Dissimilar Metal Welds (1 May 1999, Topic: Dissimilar Metal Weld)
- Information Notice 1990-31, Update on Waste Form and High Integrity Container Topical Report Review Status, Identification of Problems with Cement Solidification, and Reporting of Waste Mishaps (4 May 1990, Topic: Process Control Program)
- Information Notice 1990-31, Update on Waste form and High Integrity Container Topical Report Review Status, Identification of Problems with Cement Solidification, and Reporting of Waste Mishaps (4 May 1990, Topic: Process Control Program)
- Information Notice 1990-32, Surface Crack and Subsurface Indications in the Weld of a Reactor Vessel Head (3 May 1990)
- Information Notice 1990-33, Sources of Unexpected Occupational Radiation Exposures at Spent Fuel Storage Pools (9 May 1990)
- Information Notice 1990-34, Response to False Siren Activations (10 May 1990)
- Information Notice 1990-35, Transportation of Type a Quantities of Non-Fissile Radioactive Materials (24 May 1990)
- Information Notice 1990-37, Sheared Pinion Gear-To-Shaft Keys in Limitorque Motor Actuators (24 May 1990)
- Information Notice 1990-38, License and Fee Requirements for Processing Financial Assurance Submittals for Decommissioning (6 November 1990, Topic: Authorized possession limits)
- Information Notice 1990-39, Recent Problems with Service Water Systems (1 June 1990)
- Information Notice 1990-40, Results of NRC-Sponsored Testing of Motor-Operated Valves (5 June 1990, Topic: Weak link)
- Information Notice 1990-41, Potential Failure of General Electric Magne-Blast Circuit Breakers and Ak Circuit Breakers (12 June 1990)
- Information Notice 1990-42, Failure of Electrical Power Equipment Due to Solar Magnetic Disturbances (19 June 1990)
- Information Notice 1990-43, Mechanical Interference with Thermal Trip Function in GE Molded-Case Circuit Breakers (29 June 1990)
... further results |
---|