MONTHYEARML23151A5472023-06-0101 June 2023 Public Meeting Summary - 2022 Annual Assessment Meeting Regarding North Anna Power Station, Docket Nos. 50-338 and 50-339; and Surry Power Station ML22255A1862022-10-0303 October 2022 Tornado Classification of the Fuel Handling Trolley Support Structure License Amendment Request Audit Plan ML22130A1702022-05-20020 May 2022 Summary of April 21, 2022, Public Meeting to Discuss Potential Emergency Preparedness License Amendment Request ML22130A0332022-05-0909 May 2022 Public Meeting Summary 2021 Annual Assessment Meeting Regarding North Anna Power Station, Docket Nos. 50-338 and 50-339; and Surry Power Station, Docket Nos. 50-280 and 50-281, Meeting Number 20220349 ML22034A3932022-02-16016 February 2022 Calendar Year 2021 Security Baseline Completion Memo ML21293A0992021-12-10010 December 2021 Meeting Summary for Draft Supplemental Environmental Impact Statement Public Meeting ML21221A3012021-10-18018 October 2021 June 24, 2021, Meeting Summary: Discussion of Dominion'S Response to Select Staff Requests for Additional Information on Subsequent License Renewal Application (EPID No. L-2020-SLR-0000) - Memo ML21239A0642021-09-0202 September 2021 August 27, 2021, Summary: Discussion Between NRC and Dominion Regarding the NAPS Subsequent License Renewal - an Inconsistency in Documentation Regarding RCP Code Case N-481 (EPID No. L-2020-SLR-0000) - Memo ML21236A0512021-08-27027 August 2021 August 16, 2021, Meeting Summary: Discussion of Aging Management of Cyclic Fatigue in the Subsequent License Renewal Application (EPID No. L-2020-SLR-0000) - Memo ML21221A0262021-08-26026 August 2021 Meeting Summary Regarding Discussion of Dominion'S Response to Select Staff Requests for Additional Information on Subsequent License Renewal Application ML21221A1362021-08-10010 August 2021 Meeting Summary: Discussion of Dominion'S Response to Select Staff Requests for Additional Information on Subsequent License Renewal Application ML21145A2122021-06-0909 June 2021 Meeting Summary: Discussion of Dominion'S Response to Select Staff Requests for Additional Information on Subsequent License Renewal Application (EPID No. L-2020-SLR-0000) - Memoranda ML21131A1612021-05-11011 May 2021 Public Meeting Summary - 2020 Annual Assessment Meeting Regarding Virgil C. Summer Nuclear Station, Docket No. 50-395; North Anna Power Station, Docket Nos. 50-338 and 50-339; and Surry Power Station, Docket Nos. 50-280 and 50-281, Meeting ML21067A0922021-04-20020 April 2021 Documentation of Decision by NRC Staff That EPRI Report 3002012988, Alternative Approaches for Addressing Seismic Risk in 10 CFR 50.69 Risk-Informed Categorization, Meets Criteria for a Federal Record ML21027A0232021-01-28028 January 2021 Summary of January 26, 2021 Closed Meeting with Dominion Energy Regarding Performance of Force on Force Exercises in a Pandemic Environment ML20350B4562020-12-17017 December 2020 Summary of the Historic and Cultural Resources Environmental Audit Meeting Related to the Review of the Subsequent License Renewal Application for the North Anna Power Station, Units 1 and 2 ML20176A5632020-06-24024 June 2020 Reconciliation - Analysis for April 30, 2020 Surry, Units 1 and 2 for NRR Response, Subsequent License Renewal Letter ML20161A1922020-06-15015 June 2020 SLRA - Delay in Issuance of Surry Subsequent Renewed Licenses ML20136A1752020-05-15015 May 2020 Sur 2019 Aam Meeting Summary ML19304C1462019-11-20020 November 2019 Correction to Summary of August 13, 2019 Category 2 Public Meeting Related to the Safety Review of the Surry Power Station Units 1 and 2 SLRA ML19283B6222019-10-10010 October 2019 Subsequent License Renewal Application Safety Review - Documentation of Draft Third Round Requests for Additional Information ML19253D7082019-09-24024 September 2019 Summary of August 13, 2019, Category 2 Public Meeting Related to the Safety Review of the Surry Power Station, Units 1 and 2, Subsequent License Renewal Application ML19253A7002019-09-0606 September 2019 (FEMA Letter to NRC 09-06-19) Preliminary Capabilities Assessment (PCA) for the Surry Power Station ML19219A2842019-08-13013 August 2019 July 29, 2019, Summary of Category 2 Public Meeting Related to the Safety Review of the Surry Power Station, Units 1 and 2, Subsequent License Renewal Application ML19190A2862019-07-16016 July 2019 Summary of July 7, 2019, Public Meeting with Dominion to Discuss Open Phase Condition RAI Responses ML19165A1122019-06-14014 June 2019 Memoranda to File Environmental Assessment and Finding of No Significant Impact for the Virginia Electric and Power Company, Dominion Energy Kewaunee, Inc., and Dominion Nuclear Connecticut, Inc.'S Decommissioning Funding Plans Submitted ML19128A3432019-05-0808 May 2019 Public Meeting Summary - 2018 Annual Assessment Public Meeting Regarding North Anna Power Station, Docket Nos. 50-338 and 50-339 ML19128A3372019-05-0808 May 2019 Public Meeting Summary - 2018 Annual Assessment Public Meeting Regarding Surry Power Station Docket Nos. 50-280 and 50-281 ML18151A4682018-05-29029 May 2018 Public Meeting Summary - 2017 Annual Assessment Public Meeting Regarding North Anna Power Station, Docket Nos. 50-338 and 50-339 ML18144A0712018-05-23023 May 2018 Summary of Annual Assessment Public Meeting Regarding Surry Power Station ML18129A3142018-05-16016 May 2018 04/17/2018 Summary of Pre-Application Meeting with Dominion Energy Regarding the Surry, Units 1 and 2, Subsequent License Renewal Application ML18057A2752018-03-0101 March 2018 February 7, 2018, Summary of Pre-Application Meeting with Dominion Energy Regarding the Surry Power Station, Units 1 and 2 Subsequent Renewal Application ML17209A7652017-08-0303 August 2017 Fire Protection Input for Millstone Power Station Unit 2 Exemption from Title 10 of the Code of Federal Regulations Part 50, Appendix R, Section Iii.G, Fire Protection of Safe Shutdown Capability, for Use of Operator Manual Actions ML17137A0932017-05-17017 May 2017 Request for Additional Information, Alternative to Reactor Vessel Threads in Flange Examination Requirements ML17123A1162017-05-0303 May 2017 Summary of Meeting to Discuss Annual Assessment of the Surry Power Station, Units 1 and 2 with the Public for Period of January 01, 2016 Through December 31, 2016 ML17123A2092017-05-0303 May 2017 Summary of Meeting to Discuss Annual Assessment of the North Anna Power Station, Units 1 and 2 with the Public for the Period of January 1, 2016 Through December 31, 2016 ML16215A0752016-08-24024 August 2016 North Anna Power Station - Audit Report for Proposed License Amendment to Revise the Technical Specifications to Address the Issue Identified in Westinghouse Documents NSAL-09-5. Rev. 1 and NSAL-15-I ML16209A4132016-07-27027 July 2016 Safety Evaluation For North Anna Power Station, Units 1 And 2, Proposed License Amendment To Revise The Technical Specifications To Address The Issue Identified In Westinghouse Documents NSAL-09-5. Rev. 1 and NSAL-15-I (TAC No. MF7186 and MF7187) ML16139A5892016-05-23023 May 2016 North Anna Trip Report, April 11, 2016 ML16124A7582016-05-0303 May 2016 April 14, 2016, Summer of Public Meeting - North Anna, Units 1 and 2 ML16098A5302016-04-14014 April 2016 Audit Plan - Application for Amendment North Anna Power Station, Units 1 and 2. the Proposed License Amendment Revises the Issues Identified in Westinghouse Documents NSAL-09-5, Rev 1 and NSAL-15-1 ML16088A2042016-03-28028 March 2016 Memo T Bowers from s Ruffin, Technical Assistance Requests - Review 2015 Tri-Annual Decommissioning Funding Plans for Multiple Independent Spent Fuel Storage Installations W/ Encl 2 (Template) ML16088A2052016-03-28028 March 2016 Enclosure 1 - (72.30 DFP Reviews to Be Completed 2015) - Memo T Bowers from s Ruffin, Technial Assistance Requests - Review 2015 Tri-Annual Decommissioning Funding Plans for Multiple Independent Spent Fuel Storage Installations ML15253A4032016-03-11011 March 2016 Recommendation for Dispositioning Proposed Generic Issue on the Effects of Downstream Dam Failures on Nuclear Power Plants ML15281A2672015-10-28028 October 2015 Reassignment of U.S. Nuclear Regulatory Commission Branch Chief ML15232A8112015-08-24024 August 2015 Evaluation of Information Related to Commitments 6 and 8 from Confirmatory Action Letter No. NRR-2011-002 ML15238B5922015-08-17017 August 2015 Review of Commitment Action Completion Confirmation Action Letter Regarding Earthquake in 2011 ML15230A2162015-08-13013 August 2015 Review of Commitment Actions in Confirmatory Action Letter Regarding Earthquake in 2011 ML15132A2642015-05-11011 May 2015 EOC 2014 Public Meeting Memo - Spring 2015 2023-06-01
[Table view] |
Text
August 27, 2002 MEMORANDUM TO: File FROM: Omid Tabatabai, Project Manager /RA/
License Renewal Section License Renewal and Environmental Impacts Program Division of Regulatory Improvement Programs Office of Nuclear Reactor Regulation
SUBJECT:
DOMINIONS ADDITIONAL INFORMATION ON THE EVALUATION OF SURRY REACTOR VESSEL MATERIALS SURVEILLANCE DATA On August 23, 2002, Mike Henig of Virginia Electric and Power Company (VEPCo) transmitted an electronic mail (e-mail) to Omid Tabatabai and provided additional information related to the evaluation of Surry reactor vessel materials surveillance data. VEPCos e-mail is attached to this memo.
Attachment:
As Stated cc: PUBLIC Docket Nos. 50-338, 50-339, 50-280, and 50-281 Package: ML022400102
From: <Michael_Henig@dom.com>
To: <OTY@nrc.gov>
Date: 8/23/02 10:06AM
Subject:
Dominion Letter 99-452A
- Omid, See Attached Letter 99-452A.
(See attached file: NRC Ltr 99-452A.pdf)
Michael W. Henig Phone: 804-273-2237 Fax: 804-273-3554 Email: Michael_Henig@dom.com
Forwarded by Michael Henig/NUC/VANCPOWER on 08/23/02 10:00 AM -----
Michael Henig To: OTY@nrc.gov 08/22/02 05:52 cc: Bill Corbin/NUC/VANCPOWER@VANCPOWER, Julius PM Wroniewicz/NUC/VANCPOWER@VANCPOWER, David Roth/NUC/VANCPOWER@VANCPOWER, David Hostetler/NUC/VANCPOWER@VANCPOWER, Paul Aitken/NUC/VANCPOWER@VANCPOWER, David_Lewis@shawpittman.com, Tom Snow/NUC/VANCPOWER@VANCPOWER, Diane Aitken/NUC/VANCPOWER@VANCPOWER, Marc Hotchkiss/NUC/VANCPOWER@VANCPOWER, Lillian Cuoco/MILLSTONE/VANCPOWER@VANCPOWER, Paul Aitken/NUC/VANCPOWER@VANCPOWER bcc:
Subject:
NRC Letter 99-452A
- Omid,
Attached below is additional RV embrittlement data per your request.
Should you have any additional questions, please advise.
Michael W. Henig Phone: 804-273-2237 Fax: 804-273-3554 Email: Michael_Henig@dom.com
Forwarded by Michael Henig/NUC/VANCPOWER on 08/22/02 05:49 PM -----
David Lippard To: Michael Henig/NUC/VANCPOWER@VANCPOWER 08/22/02 05:31 cc: John Harrell/NUC/VANCPOWER@VANCPOWER PM
Subject:
NRC Letter 99-452A Attached is the letter that was requested in our 8/22/02 phone call.
Page 6 of 12 has a discussion of the Lower Shell Longintudinal Weld L2 (Heat No. 299L44). The normalization method of the data is provided in this discussion.
Pages 21 through 24 of Appendix A has the credibility assessment.
Individual capsule T-cold temperatures are given on Page 21, Table 2.
The W1 capsule that was irradiated in Surry 2 is included in the data table of the attached letter. Please understand, however, that the data from Capsule W1 was not used in the results that were presented on behalf of the license renewal assessment. In other words, only 8 capsules were considered in the evaluation of the weld heat 299L44 material.
(Embedded image moved to file: pic24479.pcx)
(Embedded image moved to file: pic15230.pcx)