Potential Electrical Equipment ProblemsML031180481 |
Person / Time |
---|
Site: |
Beaver Valley, Millstone, Hatch, Monticello, Calvert Cliffs, Dresden, Davis Besse, Peach Bottom, Browns Ferry, Salem, Oconee, Mcguire, Nine Mile Point, Palisades, Palo Verde, Perry, Indian Point, Fermi, Kewaunee, Catawba, Harris, Wolf Creek, Saint Lucie, Point Beach, Oyster Creek, Watts Bar, Hope Creek, Grand Gulf, Cooper, Sequoyah, Byron, Pilgrim, Arkansas Nuclear, Three Mile Island, Braidwood, Susquehanna, Summer, Prairie Island, Columbia, Seabrook, Brunswick, Surry, Limerick, North Anna, Turkey Point, River Bend, Vermont Yankee, Crystal River, Haddam Neck, Ginna, Diablo Canyon, Callaway, Vogtle, Waterford, Duane Arnold, Farley, Robinson, Clinton, South Texas, San Onofre, Cook, Comanche Peak, Yankee Rowe, Maine Yankee, Quad Cities, Humboldt Bay, La Crosse, Big Rock Point, Rancho Seco, Zion, Midland, Bellefonte, Fort Calhoun, FitzPatrick, McGuire, LaSalle, 05000000, Zimmer, Fort Saint Vrain, Shoreham, Satsop, Trojan, Atlantic Nuclear Power Plant |
---|
Issue date: |
01/11/1989 |
---|
From: |
Cunningham R NRC/NMSS/IMNS |
---|
To: |
|
---|
References |
---|
IN-89-003, NUDOCS 8901050122 |
Download: ML031180481 (11) |
|
Similar Documents at Beaver Valley, Millstone, Hatch, Monticello, Calvert Cliffs, Dresden, Davis Besse, Peach Bottom, Browns Ferry, Salem, Oconee, Mcguire, Nine Mile Point, Palisades, Palo Verde, Perry, Indian Point, Fermi, Kewaunee, Catawba, Harris, Wolf Creek, Saint Lucie, Point Beach, Oyster Creek, Watts Bar, Hope Creek, Grand Gulf, Cooper, Sequoyah, Byron, Pilgrim, Arkansas Nuclear, Three Mile Island, Braidwood, Susquehanna, Summer, Prairie Island, Columbia, Seabrook, Brunswick, Surry, Limerick, North Anna, Turkey Point, River Bend, Vermont Yankee, Crystal River, Haddam Neck, Ginna, Diablo Canyon, Callaway, Vogtle, Waterford, Duane Arnold, Farley, Robinson, Clinton, South Texas, San Onofre, Cook, Comanche Peak, Yankee Rowe, Maine Yankee, Quad Cities, Humboldt Bay, La Crosse, Big Rock Point, Rancho Seco, Zion, Midland, Bellefonte, Fort Calhoun, FitzPatrick, McGuire, LaSalle, 05000000, Zimmer, Fort Saint Vrain, Shoreham, Satsop, Trojan, Atlantic Nuclear Power Plant |
---|
Category:NRC Information Notice
MONTHYEARInformation Notice 2020-02, Flex Diesel Generator Operational Challenges2020-09-15015 September 2020 Flex Diesel Generator Operational Challenges ML20225A0322020-09-0303 September 2020 NRC Choice Letter to NAC International with Attached Safety Inspection Report, IR 0721015/2020201, February 24-27, 2020 and July 22, 2020, Inspection of NAC International in Norcross, Georgia Information Notice 2012-09, PWROG-16043-NP-A, Revision 2, PWROG Program to Address NRC Information Notice 2012-09: Irradiation Effects on Fuel Assembly Spacer Grid Crush Strength for Westinghouse and CE PWR Fuel Designs.2019-11-30030 November 2019 PWROG-16043-NP-A, Revision 2, PWROG Program to Address NRC Information Notice 2012-09: Irradiation Effects on Fuel Assembly Spacer Grid Crush Strength for Westinghouse and CE PWR Fuel Designs. Information Notice 2011-20, NRC060 - NRC Information Notice 2011-20: Concrete Degradation by Alkali-Silica Reaction (Nov. 18, 2011)2019-07-24024 July 2019 NRC060 - NRC Information Notice 2011-20: Concrete Degradation by Alkali-Silica Reaction (Nov. 18, 2011) ML19196A2452019-07-15015 July 2019 Public Notice - Sequoyah Nuclear Plant, Unit 2 - Exigent Amendment to Facility Operating License Information Notice 2019-01, Inadequate Evaluation of Temporary Alterations2019-03-12012 March 2019 Inadequate Evaluation of Temporary Alterations ML16028A3082016-04-27027 April 2016 NRC Information Notice; IN 2016-05: Operating Experience Regarding Complications From a Loss of Instrumentation Air Information Notice 2015-05, Inoperability of Auxiliary and Emergency Feedwater Auto Start Circuits on Loss of Main Feedwater Pumps2015-05-12012 May 2015 Inoperability of Auxiliary and Emergency Feedwater Auto Start Circuits on Loss of Main Feedwater Pumps Information Notice 2015-05, Inoperability Of Auxiliary And Emergency Feedwater Auto Start Circuits On Loss Of Main Feedwater Pumps2015-05-12012 May 2015 Inoperability Of Auxiliary And Emergency Feedwater Auto Start Circuits On Loss Of Main Feedwater Pumps Information Notice 2013-20, OFFICIAL EXHIBIT - NYS000538-00-BD01 - NRC Information Notice 2013-20: Steam Generator Channel Head and Tubesheet Degradation (October 3, 2013) (ML13204A143)2013-10-0303 October 2013 OFFICIAL EXHIBIT - NYS000538-00-BD01 - NRC Information Notice 2013-20: Steam Generator Channel Head and Tubesheet Degradation (October 3, 2013) (ML13204A143) Information Notice 2013-20, Official Exhibit - NYS000538-00-BD01 - NRC Information Notice 2013-20: Steam Generator Channel Head and Tubesheet Degradation (October 3, 2013) (ML13204A143)2013-10-0303 October 2013 Official Exhibit - NYS000538-00-BD01 - NRC Information Notice 2013-20: Steam Generator Channel Head and Tubesheet Degradation (October 3, 2013) (ML13204A143) Information Notice 2013-11, OFFICIAL EXHIBIT - NYS000551-00-BD01 - NRC Information Notice 2013-11: Crack-Like Indication at Dents/Dings and in the Freespan Region of Thermally Treated Alloy 600 Steam Generator Tubes (July 3, 2013)2013-07-0303 July 2013 OFFICIAL EXHIBIT - NYS000551-00-BD01 - NRC Information Notice 2013-11: Crack-Like Indication at Dents/Dings and in the Freespan Region of Thermally Treated Alloy 600 Steam Generator Tubes (July 3, 2013) Information Notice 2013-11, Official Exhibit - NYS000551-00-BD01 - NRC Information Notice 2013-11: Crack-Like Indication at Dents/Dings and in the Freespan Region of Thermally Treated Alloy 600 Steam Generator Tubes (July 3, 2013)2013-07-0303 July 2013 Official Exhibit - NYS000551-00-BD01 - NRC Information Notice 2013-11: Crack-Like Indication at Dents/Dings and in the Freespan Region of Thermally Treated Alloy 600 Steam Generator Tubes (July 3, 2013) Information Notice 2010-12, Intervenors' Fifth Motion to Amend and/or Supplement Proposed Contention No. 5 (Shield Building Cracking). Appendix VI: NRC FOIA Responses (B-51 Through B-53); Turkey Point Event Report; NRC Information Notice 2010-12: Contain2012-08-17017 August 2012 Intervenors' Fifth Motion to Amend and/or Supplement Proposed Contention No. 5 (Shield Building Cracking). Appendix VI: NRC FOIA Responses (B-51 Through B-53); Turkey Point Event Report; NRC Information Notice 2010-12: Containment Liner Cor Information Notice 2010-12, Intervenors' Fifth Motion to Amend and/or Supplement Proposed Contention No. 5 (Shield Building Cracking). Appendix VI: NRC FOIA Responses (B-51 Through B-53); Turkey Point Event Report; NRC Information Notice 2010-12: Con2012-08-17017 August 2012 Intervenors' Fifth Motion to Amend and/or Supplement Proposed Contention No. 5 (Shield Building Cracking). Appendix VI: NRC FOIA Responses (B-51 Through B-53); Turkey Point Event Report; NRC Information Notice 2010-12: Containment Liner Cor Information Notice 2010-12, Intervenors' Fifth Motion to Amend And/Or Supplement Proposed Contention No. 5 (Shield Building Cracking). Appendix VI: NRC FOIA Responses (B-51 Through B-53); Turkey Point Event Report; NRC Information Notic2012-08-17017 August 2012 Intervenors' Fifth Motion to Amend And/Or Supplement Proposed Contention No. 5 (Shield Building Cracking). Appendix VI: NRC FOIA Responses (B-51 Through B-53); Turkey Point Event Report; NRC Information Notice 2010-12: Containment Liner Cor Information Notice 2012-13, Boraflex Degradation Surveillance Programs and Corrective Actions in the Spent Fuel Pool2012-08-10010 August 2012 Boraflex Degradation Surveillance Programs and Corrective Actions in the Spent Fuel Pool Information Notice 2012-13, Boraflex Degradation Surveillance Programs And Corrective Actions In The Spent Fuel Pool2012-08-10010 August 2012 Boraflex Degradation Surveillance Programs And Corrective Actions In The Spent Fuel Pool Information Notice 2012-11, Age Related Capacitor Degradation2012-07-23023 July 2012 Age Related Capacitor Degradation ML12031A0132012-02-0606 February 2012 U.S. Nuclear Regulatory Commission Investigation Report No. 2-2010-058, Cpn International, Inc Information Notice 2011-19, Licensee Event Reports Containing Information Pertaining to Defects to Basic Components2011-09-26026 September 2011 Licensee Event Reports Containing Information Pertaining to Defects to Basic Components Information Notice 2011-15, Steel Containment Degradation and Associated License Renewal Aging Management Issues2011-08-0101 August 2011 Steel Containment Degradation and Associated License Renewal Aging Management Issues Information Notice 2011-17, Calculation Methodologies for Operability Determinations of Gas Voids in Nuclear Power Plant Piping2011-07-26026 July 2011 Calculation Methodologies for Operability Determinations of Gas Voids in Nuclear Power Plant Piping Information Notice 2011-13, Official Exhibit - NYS000329-00-BD01 - NRC Information Notice 2011-13, Control Rod Blade Cracking Resulting in Reduced Design Lifetime (Jun 29, 2011) (NRC in 2011-13)2011-06-29029 June 2011 Official Exhibit - NYS000329-00-BD01 - NRC Information Notice 2011-13, Control Rod Blade Cracking Resulting in Reduced Design Lifetime (Jun 29, 2011) (NRC in 2011-13) Information Notice 2011-13, Official Exhibit - Nys000329-00-Bd01 - NRC Information Notice 2011-13, Control Rod Blade Cracking Resulting in Reduced Design Lifetime (Jun 29, 2011) (Nrc in 2011-13)2011-06-29029 June 2011 Official Exhibit - Nys000329-00-Bd01 - NRC Information Notice 2011-13, Control Rod Blade Cracking Resulting in Reduced Design Lifetime (Jun 29, 2011) (Nrc in 2011-13) Information Notice 2011-13, OFFICIAL EXHIBIT - NYS000329-00-BD01 - NRC Information Notice 2011-13, Control Rod Blade Cracking Resulting in Reduced Design Lifetime (Jun 29, 2011) (NRC in 2011-13)2011-06-29029 June 2011 OFFICIAL EXHIBIT - NYS000329-00-BD01 - NRC Information Notice 2011-13, Control Rod Blade Cracking Resulting in Reduced Design Lifetime (Jun 29, 2011) (NRC in 2011-13) Information Notice 2011-04, IN: Contaminants and Stagnant Conditions Affecting Stress Corrosion Cracking in Stainless Steel Piping in Pressurized Water Reactors2011-02-23023 February 2011 IN: Contaminants and Stagnant Conditions Affecting Stress Corrosion Cracking in Stainless Steel Piping in Pressurized Water Reactors Information Notice 2011-04, In: Contaminants and Stagnant Conditions Affecting Stress Corrosion Cracking in Stainless Steel Piping in Pressurized Water Reactors2011-02-23023 February 2011 In: Contaminants and Stagnant Conditions Affecting Stress Corrosion Cracking in Stainless Steel Piping in Pressurized Water Reactors Information Notice 2011-04, in: Contaminants and Stagnant Conditions Affecting Stress Corrosion Cracking in Stainless Steel Piping in Pressurized Water Reactors2011-02-23023 February 2011 in: Contaminants and Stagnant Conditions Affecting Stress Corrosion Cracking in Stainless Steel Piping in Pressurized Water Reactors Information Notice 2010-26, New England Coalition'S Motion for Leave to Reply to NRC Staff'S Objection to Nec'S Notification of Information Notice 2010-26 and Entergy'S Response to the Supplement to Nec'S Petition for Commission Review of LBP-10-2010-12-30030 December 2010 New England Coalition'S Motion for Leave to Reply to NRC Staff'S Objection to Nec'S Notification of Information Notice 2010-26 and Entergy'S Response to the Supplement to Nec'S Petition for Commission Review of LBP-10-19 Information Notice 2010-26, New England Coalition'S Motion for Leave to Reply to NRC Staff'S Objection to Nec'S Notification of Information Notice 2010-26 and Entergy'S Response to the Supplement to Nec'S Petition for Commission Review2010-12-30030 December 2010 New England Coalition'S Motion for Leave to Reply to NRC Staff'S Objection to Nec'S Notification of Information Notice 2010-26 and Entergy'S Response to the Supplement to Nec'S Petition for Commission Review of LBP-10-19 Information Notice 2010-26, 2010/12/21-NRC Staff'S Objection to Nec'S Notification of Information Notice 2010-262010-12-21021 December 2010 2010/12/21-NRC Staff'S Objection to Nec'S Notification of Information Notice 2010-26 ML13066A1872009-12-16016 December 2009 Draft NRC Information Notice 2009-xx - Underestimate of Dam Failure Frequency Used in Probabilistic Risk Assessments ML1007804482009-11-23023 November 2009 Email from Peter Bamford, NRR to Pamela Cowan, Exelon on TMI Contamination Control Event Information Notice 2009-11, NSP000059-Revised Prefiled Testimony of Northard/Petersen/Peterson-NRC Information Notice 2009-112009-07-0707 July 2009 NSP000059-Revised Prefiled Testimony of Northard/Petersen/Peterson-NRC Information Notice 2009-11 Information Notice 2009-10, Official Exhibit - NYS000019-00-BD01- NRC Information Notice 2009-10, Transformers Failures - Recent Operating Experience (Jul. 7, 2009) (NRC in 2009-10)2009-07-0707 July 2009 Official Exhibit - NYS000019-00-BD01- NRC Information Notice 2009-10, Transformers Failures - Recent Operating Experience (Jul. 7, 2009) (NRC in 2009-10) Information Notice 2009-09, Improper Flow Controller Settings Renders Injection Systems Inoperable and Surveillance Did Not Identify2009-06-19019 June 2009 Improper Flow Controller Settings Renders Injection Systems Inoperable and Surveillance Did Not Identify Information Notice 2008-12, Reactor Trip Due to Off-Site Power Fluctuation2008-07-0707 July 2008 Reactor Trip Due to Off-Site Power Fluctuation Information Notice 2008-11, Service Water System Degradation at Brunswicksteam Electric Plant Unit 12008-06-18018 June 2008 Service Water System Degradation at Brunswicksteam Electric Plant Unit 1 Information Notice 2008-04, Counterfeit Parts Supplied to Nuclear Power Plants2008-04-0707 April 2008 Counterfeit Parts Supplied to Nuclear Power Plants Information Notice 1991-09, Counterfeiting of Crane Valves2007-09-25025 September 2007 Counterfeiting of Crane Valves Information Notice 2007-28, Potential Common Cause Vulnerabilities in Essential Service Water Systems Due to Inadequate Chemistry Controls2007-09-19019 September 2007 Potential Common Cause Vulnerabilities in Essential Service Water Systems Due to Inadequate Chemistry Controls Information Notice 2007-29, Temporary Scaffolding Affects Operability of Safety-Related Equipment2007-09-17017 September 2007 Temporary Scaffolding Affects Operability of Safety-Related Equipment Information Notice 2007-14, Loss of Offsite Power and Dual-Unit Trip at Catawba Nuclear Generating Station2007-03-30030 March 2007 Loss of Offsite Power and Dual-Unit Trip at Catawba Nuclear Generating Station Information Notice 2007-06, Potential Common Cause Vulnerabilities in Essential Service Water Systems2007-02-0909 February 2007 Potential Common Cause Vulnerabilities in Essential Service Water Systems Information Notice 2007-05, Vertical Deep Draft Pump Shaft and Coupling Failures2007-02-0909 February 2007 Vertical Deep Draft Pump Shaft and Coupling Failures Information Notice 2006-31, Inadequate Fault Interrupting Rating of Breakers2006-12-26026 December 2006 Inadequate Fault Interrupting Rating of Breakers Information Notice 2006-29, Potential Common Cause Failure of Motor-operated Valves as a Result of Stem Nut Wear2006-12-14014 December 2006 Potential Common Cause Failure of Motor-operated Valves as a Result of Stem Nut Wear Information Notice 2006-29, Potential Common Cause Failure of Motor-operated Valves As a Result of Stem Nut Wear2006-12-14014 December 2006 Potential Common Cause Failure of Motor-operated Valves As a Result of Stem Nut Wear Information Notice 2006-13, E-mail from M. Mclaughlin on NRC, Regarding NRC Information Notice 2006-13: Groundwater Contamination2006-07-13013 July 2006 E-mail from M. Mclaughlin on NRC, Regarding NRC Information Notice 2006-13: Groundwater Contamination 2020-09-03 The following query condition could not be considered due to this wiki's restrictions on query size or depth: <code> [[:Beaver Valley]] OR [[:Millstone]] OR [[:Hatch]] OR [[:Monticello]] OR [[:Calvert Cliffs]] OR [[:Dresden]] OR [[:Davis Besse]] OR [[:Peach Bottom]] OR [[:Browns Ferry]] OR [[:Salem]] OR [[:Oconee]] OR [[:Mcguire]] OR [[:Nine Mile Point]] OR [[:Palisades]] OR [[:Palo Verde]] OR [[:Perry]] OR [[:Indian Point]] OR [[:Fermi]] OR [[:Kewaunee]] OR [[:Catawba]] OR [[:Harris]] OR [[:Wolf Creek]] OR [[:Saint Lucie]] OR [[:Point Beach]] OR [[:Oyster Creek]] OR [[:Watts Bar]] OR [[:Hope Creek]] OR [[:Grand Gulf]] OR [[:Cooper]] OR [[:Sequoyah]] OR [[:Byron]] OR [[:Pilgrim]] OR [[:Arkansas Nuclear]] OR [[:Three Mile Island]] OR [[:Braidwood]] OR [[:Susquehanna]] OR [[:Summer]] OR [[:Prairie Island]] OR [[:Columbia]] OR [[:Seabrook]] OR [[:Brunswick]] OR [[:Surry]] OR [[:Limerick]] OR [[:North Anna]] OR [[:Turkey Point]] OR [[:River Bend]] OR [[:Vermont Yankee]] OR [[:Crystal River]] OR [[:Haddam Neck]] OR [[:Ginna]] OR [[:Diablo Canyon]] OR [[:Callaway]] OR [[:Vogtle]] OR [[:Waterford]] OR [[:Duane Arnold]] OR [[:Farley]] OR [[:Robinson]] OR [[:Clinton]] OR [[:South Texas]] OR [[:San Onofre]] OR [[:Cook]] OR [[:Comanche Peak]] OR [[:Yankee Rowe]] OR [[:Maine Yankee]] OR [[:Quad Cities]] OR [[:Humboldt Bay]] OR [[:La Crosse]] OR [[:Big Rock Point]] OR [[:Rancho Seco]] OR [[:Zion]] OR [[:Midland]] OR [[:Bellefonte]] OR [[:Fort Calhoun]] OR [[:FitzPatrick]] OR [[:McGuire]] OR [[:LaSalle]] OR [[:05000000]] OR [[:Zimmer]] OR [[:Fort Saint Vrain]] OR [[:Shoreham]] OR [[:Satsop]] OR [[:Trojan]] OR [[:Atlantic Nuclear Power Plant]] </code>.
[Table view]The following query condition could not be considered due to this wiki's restrictions on query size or depth: <code> [[:Beaver Valley]] OR [[:Millstone]] OR [[:Hatch]] OR [[:Monticello]] OR [[:Calvert Cliffs]] OR [[:Dresden]] OR [[:Davis Besse]] OR [[:Peach Bottom]] OR [[:Browns Ferry]] OR [[:Salem]] OR [[:Oconee]] OR [[:Mcguire]] OR [[:Nine Mile Point]] OR [[:Palisades]] OR [[:Palo Verde]] OR [[:Perry]] OR [[:Indian Point]] OR [[:Fermi]] OR [[:Kewaunee]] OR [[:Catawba]] OR [[:Harris]] OR [[:Wolf Creek]] OR [[:Saint Lucie]] OR [[:Point Beach]] OR [[:Oyster Creek]] OR [[:Watts Bar]] OR [[:Hope Creek]] OR [[:Grand Gulf]] OR [[:Cooper]] OR [[:Sequoyah]] OR [[:Byron]] OR [[:Pilgrim]] OR [[:Arkansas Nuclear]] OR [[:Three Mile Island]] OR [[:Braidwood]] OR [[:Susquehanna]] OR [[:Summer]] OR [[:Prairie Island]] OR [[:Columbia]] OR [[:Seabrook]] OR [[:Brunswick]] OR [[:Surry]] OR [[:Limerick]] OR [[:North Anna]] OR [[:Turkey Point]] OR [[:River Bend]] OR [[:Vermont Yankee]] OR [[:Crystal River]] OR [[:Haddam Neck]] OR [[:Ginna]] OR [[:Diablo Canyon]] OR [[:Callaway]] OR [[:Vogtle]] OR [[:Waterford]] OR [[:Duane Arnold]] OR [[:Farley]] OR [[:Robinson]] OR [[:Clinton]] OR [[:South Texas]] OR [[:San Onofre]] OR [[:Cook]] OR [[:Comanche Peak]] OR [[:Yankee Rowe]] OR [[:Maine Yankee]] OR [[:Quad Cities]] OR [[:Humboldt Bay]] OR [[:La Crosse]] OR [[:Big Rock Point]] OR [[:Rancho Seco]] OR [[:Zion]] OR [[:Midland]] OR [[:Bellefonte]] OR [[:Fort Calhoun]] OR [[:FitzPatrick]] OR [[:McGuire]] OR [[:LaSalle]] OR [[:05000000]] OR [[:Zimmer]] OR [[:Fort Saint Vrain]] OR [[:Shoreham]] OR [[:Satsop]] OR [[:Trojan]] OR [[:Atlantic Nuclear Power Plant]] </code>. |
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF NUCLEAR MATERIAL SAFETY AND SAFEGUARDS
WASHINGTON, D. C. 20555 January 11, 1989 NRC INFORMATION NOTICE NO. 89-03: POTENTIAL ELECTRICAL EQUIPMENT PROBLEMS
Addressees
All Fuel Cycle and Major Nuclear Materials licensees.
Purpose
This information notice is being provided to advise certain NRC fuel cycle and
materials licensees of potential electrical equipment problems that may be
caused by inadequate maintenance, equipment component defects, or procurement
practices. It is expected that you will review this information for appli- cability, distribute it to responsible radiation safety, maintenance and
procurement staff, and consider actions, as appropriate, to avoid similar
problems. However, suggestions contained in this notice do not constitute
new NRC requirements; no written response is required.
Description of Circumstances
Concerns regarding electrical equipment problems with materials licensees
were prompted by recent inspection findings that counterfeit, substandard, or questionable electrical equipment or components had been used in nuclear
power reactors. The inspection findings indicated that the electrical equip- ment problems appeared to be significant and pervasive. As a result, several
NRC information notices were issued which reflected such equipment problems
involving nuclear utilities, equipment manufacturers, and vendors. Further- more, several electrical suppliers were identified as those associated in
refurbishing and sale of defective equipment components to nuclear and non- nuclear industries. Therefore, the electrical equipment problem does not
appear to be confined to nuclear power reactors or the nuclear industry.
Similar problems may also exist in non-nuclear medical and industrial
operations as well.
A review of previously published NRC information notices and bulletins ad- dressed to materials licensees revealed that there had been incidents which
involved failure of electrical equipment and components such as pressure
regulator switches, teletherapy timers, solid-state relays, and solenoid
valves, which could have resulted in radiation overexposures. A brief
description of the incidents is provided below:
IN 89-03 January 11, 1989 1. 1E Information Notice No. 84-77:
A defective solid-state relay in a circuit board of a teletherapy unit
caused the source unit to move to the exposed position. This could
cause both the teletherapy operator and the patient to receive excessive
radiation exposures. This incident also may have generic implications
because of the non-fail-safe design of the relay circuit.
2. IE Information Notice No. 85-54:
A failure of a pressure regulator switch on the pneumatic system to an
Atomic Energy of Canada, Ltd. (AECL) Theratron 60 teletherapy unit caused
an overpressure condition in the holding tank and prevented the source
drawer from immediately closing on command.
3. IE Bulletin No. 86-04:
The bulletin described how an operational malfunction of a teletherapy
timer could result in radiation misadministration to patients and possible
excessive radiation exposures to teletherapy operators.
4. NRC Information Notice No. 87-29:
The Notice described several related incidents at large irradiators.
One event involved an irradiator source unable to retract to its fully
shielded-posftion due-to-a-firozen lenoidva We.
Discussion:
Although these incidents apparently did not involve counterfeit equipment, these incidents illustrate the need for facility management to have
adequate maintenance and procurement program. Therefore, licensees anare
urged to thoroughly review their programs to ensure that the procedures
for operations, service, repair, or replacement are being followed properly.
Licensees should also review their procurement procedures and practices, especially in areas such as purchase orders, materials requirements, vendor
qualifications, and receipt inspections, to ensure quality control and
compliance.
IN 89-03 January 11, 1989 No specific action or written response is required by this information notice.
If you should have any questions about this matter, please contact the
the appropriate NRC regional office or the technical contact listed below.
Richard E. Cunningham, Director
Division of Industrial and
Medical Nuclear Safety
Office of Nuclear Material Safety
and Safeguards
Technical Contact:
K. C. Leu, NMSS
(301) 492-0696 Attachments:
1. List of Recently Issued NMSS Information Notices
2, List of All Recently Issued NRC Information Notices
Attafent Attachmnt 2 IN R'-03 1S89-03 Janu ryt" 11.1W January it. I9M5 rrI
i.qe I of I figs I of I
tlST or RECENTLY ISSUED tlST OFRECaTlLYISSUED
RPSSINFORAMTION NOIICS MACINfATlTIO NOTICE$
I-nssolo mro tenofoc
Infaretion Dr
I c Aa Subjact lossuance Issuod to NoticaeNm Subject Issulncs Issmedta
89-07 Criminol proscution et 01/009/09 All holders of mRC 89-02 Crtilnl Prsctite of 1/9/Si P All balders of a
license.s former president specific license Licensees Formr President d.S. mC sp*cific
for
Intent
ional safety for intentinal Safety licensa
violations Violatiose
88-1020 pllmranm of ondnnteadlng 12/23/U All Jar muclear 8-23. Potntial tor 6Us siding I/s/11I All hblders at Ots
bet NRCand 0MA rlting materials licensees Sup. I of Nigh-Pressure Safety oerCPsfr PuRs.
to eC-liernsed facilitls and utilities bolding lejectina Pep Earing a
(S3 Fi 43"O. October 31. 19A) CPSa.d Ots. tens-of-Coolant Accident
58-93 Telptherapy Foents 12/28U All WCwedical Ng-01 Valve 5e Erosion "a,"8 All holdes of OLS
licensees or CS for nuclear
powr reactors.
58-9e thmatiberiznd reunvol of 1112288 All Mlt licensees
1ndustriol nuclear qagn authorized to 3t-4'. Licensae RtPert of ollectivw 52/30/U All baldrs af Oas
posses. 9sr. Supp. 2 Refurbished Circuit Breakers or CPI ftr nuclear
manufacture. er pomr reactars.
distribute industrial
nuclear gawge 85-101 Sbipt mt Contamimatad 12/2181 Al I balder, of OS
£qui~pmnt b*taee NRclear or CPs for nuclear
1-616 Instrial radiography 08/22/8 All IC Industrial Phunr Stations powr reactors.
Inspectin and enfarcomet radiography license.s
BS-10 feliran ot tUderstanding 12/23/8 All major nuclear
e42 lacnt findings coucerniog 018/12/1 All hialdes o NC betea NC aln OSKA intarials licensees
iwir anttlen of ewilty quality assurne Ralatina to EC-liceased and utilities balding
assufance progrinJ by sueplierts ro approveas for raclitisl 53 4so.
of transpart packages nd ctve material October 31. .S9e)
packages
E1111- DetacKtim Sen1Rnitaig 12/20/U All heldes af Oas
0-323 Rctm prubetr lfvolnng the 05/2flM All Agraonnnt States of Suddenand/or Rapidly or th far Puss.
model Spec 2-1 radilogralc and ItC licensees Increasing Priwry-ta- exposure device autherizad to Secondary Leaks"
manufacture. distribute
or operate Rwoo ElaCtrical belay llMditetm 1219/U All balders of Cs
radiographic exposure Cased by ODidatien of er CPsfor nuclear
devices and source Contact Surtaces pr reactors.
changers
R-7 Potentially Substandard 12/1/U All balder of Cta
3-32 Prot reatrIn ti NeCaf 01/25/Ui All RC materials alvo Replace"t Parts or Css for nuclear
si'nificant incidents Involving Icensees powr reactors.
radioactive interial
Ot - Operating ticense
Cr - Constnurtio" Per-It
Ot
CP* Construction P.rit
UNITED STATES FIRST CLASS MAIL
POSTAGE & FEES PAID
NUCLEAR REGULATORY COMMISSION USNRC
WASHINGTON, D.C. 20555 PERMIT No. 0-67 OFFICIAL BUSINESS
PENALTY FOR PRIVATE USE, $300
IN 89-03 January 11, 1989 No specific action or written response is required by this information notice.
If you should have any questions about this matter, please contact the
the appropriate NRC regional office or the technical contact listed below.
Richard E. Cunningham, Director
Division of Industrial and
Medical Nuclear Safety
Office of Nuclear Material Safety
and Safeguards
Technical Contact:
K. C. Leu, NMSS
(301) 492-0696 Attachments:
1. List of Recently Issued NMSS Information Notices
2. List of All Recently Issued NRC Information Notices
Ellen Kraus
reviewed 11/08/88 OFC :*IMIF :*IMIF :*IMAB :*IMIF :*IMSB :*DD/IMNS :*D/IMNS
NAME: KCLeu:lg/mh:FLBrown :MLamastra:JPRoberts:LCRouse :GLSjoblom :RECunningham
DATE: 12/ /88 :11/23/88:11/23/88 :11/23/88 :12/ /88 :12/ /88 :12/ /88 OFFICIAL RECORD COPY
IN 89- January , 1989 No specific action or written response is required by this Information Notice.
If you should have any questions about this matter, please contact the
Regional Administrator of the appropriate Regional Office or the technical
contact listed below.
Richard E. Cunningham, Director
Division of Industrial and
Medical Nuclear Safety
Office of Nuclear Material Safety
and Safeguards
Technical Contact:
K. C. Leu, NMSS
(301) 492-0696 Attachment: List of recently issued NRC Information Notices
Ellen Kraus reviewed 11/08/88 FR-:IMIF :*IMIF :*IMAB :*IMIF :I w :DD/IMNS :D/IMNS
_______------------------------------------- ---------------------------
NAME:KCI : lg/mh:FLBrown :MLamastra:JPRoberts:LtRo se :GLSjoblom:RECunningham
_______. ------------------------------------------------------------ _________
DATE:12/,,//88 :11/23/88:11/23/88 :11/23/88 :12/Z2/88:12/ /88 :12/ /88
____________OFI RECORD_______________
COPY_-__________________________________
OFFICIAL RECORD COPY
IN 88- November , 1988 No specific ction or written response is required by this Information Notice.
If you should ave any questions about this matter, please contact the
Regional Admin trator of the appropriate Regional Office or the technical
contact listed b low.
Richard E. Cunningham, Director
Division of Industrial and
Medical Nuclear Safety
Office of Nuclear Material Safety
and Safeguards
Technical Contact:
K. C. Leu, MSS
(301) 492-0 6 Attachment: List of recently issue NRC Information Notices
Ellen Kraus reviewed 11/08/88 OFC :IMIF :IMIF :IMAB :IMIF .MSB :DD/IMNS :D/IMNS
NAME:K Mu:lg/mh:F :n
MLa astra:JP e s:Louse :GLSjoblom:RECunningham
DATE:1V/88 88:11A 8 :11/A3/88 :11/ 88:11/ /88 :11/ /88
_____--------OFFICIAL -RECORD C ------------------------
OFFICIAL RECORDC
IN 88- November 1988 3. IE Information Notice No. 85-54:
A failureo a pressure regulator switch on the pneumatic system to an
Atomic Energ of Canada, Ltd. (AECL) Theratron 60 teletherapy unit caused
an overpressu condition in the holding tank and prevented the source drawer
from immediate closing on command.
4. IE Bulletin No. -04:
The Bulletin descr ed how an operational malfunction of a teletherapy
timer could result radiation misadministration to patients and possible
excessive radiation e osures to teletherapy operators.
5. NRC Information Notice . 87-29:
The Notice described seve 1 safety-related incidents at large irradiators.
One event involved an irra *ator source unable to retract to its fully
shielded position due to a ozen solenoid valve.
Discussion
The above described incidents at mate als license facilities illustrate the
need for facility management to have a adequate maintenance and procurement
program. Therefore, you are urged to r view thoroughly your management controls
program, to ensure that the procedures f r facility equipment controls, equipment
operations, service, repair, or replaceme t are being followed properly. You
should also review your procurement proced es and practices, especially in
areas such as purchase orders, materials re irements, vendor qualifications, and receipt inspections, to ensure quality c pliance and facility safe operation.
No specific action or written response is requ ed by this Information Notice.
If you should have any questions about this mat er, please contact the
Regional Administrator of the appropriate Region Office or the technical
contact listed below.
Richard E. Cunningh , Director
Division of Industrial and
Medical Nuclear Safety
Office of Nuclear Material Safety
and Safeguards
Technical Contact:
K. C. Leu, NMSS
(301) 492-0696 Attachment: List of recently issued NRC Information Notices
Ellen Kraus reviewed 11/08/8_
FIF : :IMA :I C :IMSB
vMI :DD/IMNS :D/IMNS
NAME:KW 4 lg/mh:_ own :MLamastra:JPR e'rts:LCRouse :GLSjoblom:RECunningham
wet-- -z-- f ------
- ----- - _I---- --- ---- -------------- -------
DATE:ll /88 : t/88:11 /88 :11/10/88 :11/ /88:11/ /88 :11/ /88 OFFICIAL RECORD COPY
IN 89- January , 1989 No specific action or written response is required by this Information Notice.
If you should have any questions about this matter, please contact the
the appropriate NRC Regional Office or the technical contact listed below.
Richard E. Cunningham, Director
Division of Industrial and
Medical Nuclear Safety
Office of Nuclear Material Safety
and Safeguards
Technical Contact:
K. C. Leu, NMSS
(301) 492-0696 Attachment:
1. List of recently issued NMSS Information Notices
2. List of all recently issued NRC Information Notices
Ellen Kraus
reviewed 11/08/88 OFC :*IMIF :*IMIF :*IMAB :*IMIF :*IMSB :*DD/IMNS :*D/IMNS
NAME: KCLeu:lg/mh:FLBrown :MLamastra:JPRoberts:LCRouse :GLSjoblom :RECunningham
DATE: 12/ /88 :11/23/88:11/23/88 :11/23/88 :12/ /88 :12/ /88 :12/ /88
-_- _- ___-__-__-_ -__ -__ -_____ -_ -_-_-_-__
-_- _- _- _____________- _- ___- __
OFFICIAL RECORD COPY
IN 89- January , 1989 No pecific action or written response is required by this Information Notice.
If u should have any questions about this matter, please contact the
the a ropriate NRC Regional Office or the technical contact listed below.
Richard E. Cunningham, Director
Division of Industrial and
Medical Nuclear Safety
Office of Nuclear Material Safety
and Safeguards
Technical Contact:
K. Leu, NMSS
(301) 492-0696 Attachment: List of recentl issued NRC Information Notices
Ellen Kraus
reviewed 11/08/88
-_ -_-_-_-_-_-_- -_ _-_- _- _ -_
OFC :*IMIF :*IMIF :*IMAB :*IMIF :*IMSB :DD/IMNS ,zD/IMNS A
t1 L -- - ---
NAME: KCLeu:lg/mh:FLBrown :MLamastra:JPRoberts:LCRouse :GL bqom:RECunningham
________________-_- - -
__- - - - -- - - - - - -------- ; ------- m o- - - - -
DATE: 12/ /88 :11/23/88:11/23/88 :11/23/88 :12/ /88 %>J/88:21/oJ'/8V
OFFICIAL RECORD COPY
IN 89- January , 1989 o specific action or written response is required by this Information Notice.
r\,you should have any questions about this matter, please contact the
the\a opriate NRC Regional Office or the technical contact listed below.
Richard E. Cunningham, Director
Division of Industrial and
Medical Nuclear Safety
Office of Nuclear Material Safety
and Safeguards
Technical Contact:
K. C. Leu,'NMSS
(301) 492-0696 Attachment: List of recently issued NRC Information Notices
Ellen Kraus reviewed 11/08/88 DFR:IMIF :*IMIF :*IMAB :*IMIF :IMSB :DD/IMNS :D/IMNS
_________________________________________
NAME:KCLeu:lg/mh:FLBrown. :MLamastra:JPRoberts:LCRouse :GLSjoblom:RECunningham
_________________________________________
DATE:12/ /88 :11/23/88:11/23/88 :11/23/88 :12/ /88:12/ /88 :12/ /88
_________________________________________
OFFICIAL RECORD COPY
|
---|
|
list | - Information Notice 1989-01, Valve Body Erosion (4 January 1989)
- Information Notice 1989-02, Criminal Prosecution of Licensee'S Former President for Intentional Safety Violations (9 January 1989)
- Information Notice 1989-03, Potential Electrical Equipment Problems (11 January 1989)
- Information Notice 1989-04, Potential Problems from the Use of Space Heaters (17 January 1989)
- Information Notice 1989-05, Use of Deadly Force by Guards Protecting Nuclear Power Reactors Against Radiological Sabotage (19 January 1989)
- Information Notice 1989-06, Bent Anchor Bolts in Boiling Water Reactor Torus Supports (24 January 1989)
- Information Notice 1989-07, Failures of Small-Diameter Tubing in Control Air, Fuel Oil & Lube Oil Systems Render Emergency Diesel Generators Inoperable (25 January 1989)
- Information Notice 1989-08, Pump Damage Caused by Low-Flow Operation (26 January 1989)
- Information Notice 1989-09, Credit for Control Rods Without Scram Capability in the Calculation of Shutdown Margin (26 January 1989, Topic: Shutdown Margin)
- Information Notice 1989-10, Undetected Installation Errors in Main Steam Line Pipe Tunnel Differential Temperature-Sensing Elements at Boiling Water Reactors (27 January 1989)
- Information Notice 1989-11, Failure of DC Motor-Operated Valves to Develop Rated Torque Because of Improper Cable Sizing (2 February 1989, Topic: Shutdown Margin)
- Information Notice 1989-12, Dose Calibrator Quality Control (9 February 1989)
- Information Notice 1989-13, Alternative Waste Management Procedures in Case of Denial of Access to Low-Level Waste Disposal Sites (8 February 1989, Topic: Shutdown Margin, Authorized possession limits)
- Information Notice 1989-15, Second Reactor Coolant Pump Shaft Failure at Crystal River (16 February 1989, Topic: Shutdown Margin)
- Information Notice 1989-16, Excessive Voltage Drop in DC Systems (16 February 1989, Topic: Shutdown Margin, Battery sizing)
- Information Notice 1989-17, Contamination and Degradation of Safety-Related Battery Cells (22 February 1989)
- Information Notice 1989-18, Criminal Prosecution of Wrongdoing Committed by Suppliers of Nuclear Products or Services (24 August 1990)
- Information Notice 1989-20, Weld Failures in a Pump of Byron-Jackson Design (24 February 1989, Topic: Health Physics Network)
- Information Notice 1989-21, Changes in Performance Characteristics of Molded-Case Circuit Breakers (27 February 1989, Topic: Health Physics Network)
- Information Notice 1989-23, Environmental Qualification of Litton-Veam Cir Series Electrical Connectors (3 March 1989, Topic: Health Physics Network)
- Information Notice 1989-24, Nuclear Criticality Safety (6 March 1989, Topic: Health Physics Network)
- Information Notice 1989-25, Unauthorized Transfer of Ownership or Control of Licensed Activities (7 March 1989, Topic: Health Physics Network)
- Information Notice 1989-26, Instrument Air Supply to Safety-Related Equipment (7 March 1989, Topic: Health Physics Network)
- Information Notice 1989-27, Limitations on the Use of Waste Forms and High Integrity Containers for the Disposal of Low-Level Radioactive Waste (8 March 1989, Topic: Process Control Program)
- Information Notice 1989-28, Weight and Center of Gravity Discrepancies for Copes-Vulcan Air-Operated Valves (14 March 1989)
- Information Notice 1989-29, Potential Failure of Asea Brown Boveri Circuit Breakers During Seismic Event (15 March 1989)
- Information Notice 1989-30, High Temperature Environments at Nuclear Power Plants (1 November 1990)
- Information Notice 1989-31, Swelling and Cracking of Hafnium Control Rods (22 March 1989)
- Information Notice 1989-32, Surveillance Testing of Low-Temperature Overpressure-Protection Systems (23 March 1989, Topic: Stroke time)
- Information Notice 1989-33, Potential Failure of Westinghouse Steam Generator Tube Mechanical Plugs (23 March 1989)
- Information Notice 1989-34, Disposal of Americium Well-Logging Sources (30 March 1989)
- Information Notice 1989-35, Loss & Theft of Unsecured Licensed Material, Attachment 1 to NRC Information Notice 1990-014: Accidental Disposal of Radioactive Materials. (Also includes Attachments 2 & 3) (30 March 1989)
- Information Notice 1989-35, Loss & Theft of Unsecured Licensed Material, Attachment 1 to NRC Information Notice 1990-014: Accidental Disposal of Radioactive Materials. (Also Includes Attachments 2 & 3) (30 March 1989, Topic: Moisture-Density Gauge)
- Information Notice 1989-36, Excessive Temperatures in Emergency Core Cooling System Piping Located Outside Containment (4 April 1989)
- Information Notice 1989-37, Proposed Amendments to 40 CFR Part 61, Air Emission Standards for Radionuclides (4 April 1989)
- Information Notice 1989-38, Atmospheric Dump Valve Failures at Palo Verde Units 1, 2, and 3 (5 April 1989, Topic: Emergency Lighting)
- Information Notice 1989-39, List of Parties Excluded from Federal Procurement or Non-Procurement Programs (5 April 1989)
- Information Notice 1989-40, Unsatisfactory Operator Test Results and Their Effect on the Requalification Program (14 April 1989)
- Information Notice 1989-41, Operator Response to Pressurization of Low-Pressure Interfacing Systems (20 April 1989)
- Information Notice 1989-42, Failure of Rosemount Models 1153 and 1154 Transmitters (21 April 1989)
- Information Notice 1989-43, Permanent Deformation of Torque Switch Helical Springs in Limitorque SMA-Type Motor Operators (1 May 1989)
- Information Notice 1989-44, Hydrogen Storage on the Roof of the Control Room (27 April 1989, Topic: Coatings)
- Information Notice 1989-45, Metalclad, Low-Voltage Power Circuit Breakers Refurbished with Substandard Parts (8 May 1989, Topic: Commercial Grade Dedication, Coatings)
- Information Notice 1989-46, Confidentiality of Exercise Scenarios (11 May 1989, Topic: Coatings)
- Information Notice 1989-47, Potential Problems with Worn or Distorted Hose Clamps on Self-Contained Breathing Apparatus (18 May 1989, Topic: Coatings)
- Information Notice 1989-48, Design Deficiency in the Turbine-Driven Auxiliary Feedwater Pump Cooling Water Systems (22 May 1989, Topic: Coatings, Temporary Modification)
- Information Notice 1989-49, Failure to Close Service Water Cross-Connect Isolation Valves (22 May 1989, Topic: Coatings)
- Information Notice 1989-50, Inadequate Emergency Diesel Generator Fuel Supply (30 May 1989)
- Information Notice 1989-51, Potential Loss of Required Shutdown Margin During Refueling Operations (31 May 1989, Topic: Shutdown Margin, Coatings)
- Information Notice 1989-52, Potential Fire Damper Operational Problems (8 June 1989, Topic: Safe Shutdown, Shutdown Margin, Fire Barrier, Fire Protection Program)
... further results |
---|