U. S. NUCLEAR REGULATORY COMMISSION
'
..
REGION V
Report No. 50-508/86-06
,
!
l Docket No. 50-508-
!
Construction Permit No. CPPR-154
' Licensee: Washington Public Power Supply System (WPPSS)
P. O. Box.1223 Elma, Washington 98541
. Facility Name: - Washington-Nuclear Project 3 Inspection Conducted:
May~19-23, 1986 Inspector:
N 6 1- "
?
W. P. Ang, Project Inspector Date Signed Approved by:
N----EM v 6 NAG M. Mendonca, Chief-Date Signed Sammary:
i Inspection on May 19-23, 1986 (Report No. 50-508/86-06)
I Areas Inspected: Routine unannounced inspection by a regionally based
,
inspector of the readiness review program, construction assurance program, and site tour.
Inspection procedures 90703, 35060, and 46153'were used for guidance.
i Results:.Of the areas-inspected, no violations or deviations were, identified.
'
!
i
'
.
.
,.
,
)
hhokg PDR i
J
'
.
.
.
.
s DETAILS 1.
Persons Contacted a.
Washington Public Power Supply System
- R.
B. Glasscock, Director, Licensing and Assurance P. D. Olson, Program Director
- C.
E. Love, Deputy Program Director D. R. Coody, Project QA Manager
- R. L. Knawa, Construction Assurance Program Manager
- G. A. Block, Engineering Assursace Program Manager b.
Ebasco Services Inc.
- P. L. Pitman, Quality Program Site Manager (Acting)
c.
State of Washington
- M. Mills, Compliance Manager, EFSEC
- Attended exit interview at Richland.
- Attended exit interview at WNP-3.
2.
Unresolved Items
.
Unresolved items were not identified during this inspection.
3.
Independent Inspection Effort The inspectors conducted a general inspection of portions of the exterior and interior area of the reactor building and of the auxiliary building to observe plant preservation, housekeeping and storage.
The inspector observed significant corrosion of v' lve bon'het fasteners a-for the refueling water storage tank (RWST) piping adjacent to the RWSTs.
Similar corrosion was also observed in the piping. The licensee showed the inspector a memorandum that documented licensee walkdowns of the area that had previously identified the noted condition. However, the inspector was unable to verify that the corrosion had been identified as a nonconforming condition. Pending further NRC inspection, this was identified as inspector follow-up item 50-508/86-06-01.
No violations or deviations were identified.
4.
Readiness Review Program a.
Oversight Committee - The licensee's Engineering Assurance Program and Construction Assurance Program, that were accepted by the NRC on October 25, 1985, and February 25, 1985, respectively, committed to the formation and utilization of an " oversight committee". An inspection to confirm licensee's compliance with commitments
,
-
-
y
.
N
,
e
.
regarding the oversight committee was performed. The NRC~ inspector-reviewed statements of financial independence from WNP-3 activities for the members of-the oversight committee. The inspector reviewed and discussed with the licensee the oversight committee meeting-
>
minutes for their September 10, 1985, and January 21 andf22, 1986.
No violations or deviations were identified.
b.
Engineering Assurance Program (EAP) - The licensee had completed its reviews of Piping Stress Analysis problems and Pipe Support Design Calculations for the first EAP module.
The results of the review were transmitted to the WNP-3 Program Director for review and for transmittal to EBASCO for dispositioning of the items identified.
The transmittal memorandum stated that the reviews confirmed that piping and pipe support. design is in a preliminary status and significant work would be required to bring the design to a final auditable status. The review results identified several issues regarding design procedures, documentation of data used for-calculations, etc.
The issues are to be forwarded to EBASCO for resolution.
No violations or deviations were identified.
Construction Assurance Program (CAP) - The licensee had prepared and c.
issued a review plan, including review checklists, for the first CAP module, earthwork / soil compaction. The plan was reviewed and discussed with the licensee by the NRC inspector. The need for a thorough review and complete identification of FSAR commitments for the review topic was discussed with the licensee. The need for assurance that nonconforming conditions will-be identified on appropriate site nonconformance reports was also re-affirmed by discussion with the licensee.
Completed reviews of soil cement in place density tests and class
,
-
A-1 fill in place density tests were sampled, reviewed, and discussed with the licensee by the NRC inspector.
No violations or deviations were identified.
5.
Exit Interview The inspection scope and findings were summarized on May 20, 1986, and May 23, 1986,.with those persons indicated in paragraph 1.. The inspector described the areas inspected and discussed in detail the inspection-findings. No dissenting comments were received from the licensee. The licensee did not identify as proprietary any of the material which was provided to or reviewed by the inspector csting this inspection.
,
"%
+
,