e U.S. NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT

REGION II

Report No. 50-281/79-59 Docket No. 50-281 License No. DPR-37 Licensee:

Virginia Electric and Power Company P. 0. Box 26666 Richmond, VA 23261 Facility Name:

Surry Power Station, Unit 2 Inspection At:

Surry Site near Williamsburg, Virginia Inspection Conducted:

July 9-12, 1979 Inspector:

Approved By: 1>>;1,i(.'.:_..,._:,~-l?-r:-~--

D. H. Danielson, Chief Engineering Support Section 2, RIII

,

1;1e,, lrlt ~I/;

~~ ~~~rW, Chief

'B/2/79 Engineering Support Section 1, RII ~'

Inspection Summary Inspection on July 9-12, 1~79 (Report No. 50-281/79-59)

Areas Inspected:

Observation of fit up and welding of steam generator shells, cleanliness and preheat practices, weld repair, NCR system, and NDE of primary coolant hot and cold leg fitting The inspection involved a total of 24 inspector-hours on site by one NRC RIII inspecto Results:

No items of noncompliance or deviations were identifie e e

DETAILS Persons Contacted Licensee Personnel (VEPCo)

W. L. Stewart, Site Manager J. L. Wilson, Superintendent Operations T. A. Peebles, Superintendent Technical Services E. P." Nottingham, III, Assistant Supervisor Health Physics R. L. Baldwin, Supervisor Administrative Services D. Kildoo, Station Quality Control W.R. Skelly, Jr., SGRP Staff Assistant E. P. Dewandel, Station Engineering Services D. A. Christian, Supervisor Engineering Services W. Davidson, Corporate T. Simpson, Corporate

  • C. Embler, Welding Engineer
  • C. W. Rhodes, Resident Engineer, Construction Chicago Bridge and Iron Company (CBI)
  • J. Edgar, QA Superintendent Daniel Construction Company (DCC)
  • R. Davis, QC Supervisor
  • R. Yuhasz, QC Inspector Technical Services Laboratory (TSL)
  • D. Councill, NDE Inspector, Level II
  • Denotes those present at the exit intervie Functional or Program Areas Inspected Welding and Related Activities for Steam Generator Shells Conditions of fit up and cleanliness of the weld area were observed for the "C" generator prior to the start of weldin Preheat temper-atures were also checked and found to be acceptable to specificatio The "A" generator was upended and placed in position for welding the girth sea The fit up and cleanliness were acceptabl The "B" generator welding of shells was nearly complete and will be

given a post weld heat treat (PWJIT) at 1100-1200 F when heating equipment is place *

e CBI weld procedure E8018 NM/91534 is used to weld the shells togethe The sequence is to weld in the areas where a root gap exists and then to bring out the weld evenly around the entire girth using from 2 to 6 welder Issuance of electrode was controlled and scrap electrodes were being collected properl The following NDT is performed on each generator girth wel. MT weld prep (Y6 adjustable yoke).

UT for lamination MT and hot UT first 1/3 thickness of wel Back gouge weld from inside MT insid Finish weld from insid MT inside wel Weld to 2/3 thickness and MT and hot U Finish weld0 MT and hot UT Soak at 400 for 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> Cool dow Radiograph using Cobalt and panoramic exposur Repair if necessar Final radiography as in step The weld procedure specification conforms to ASME Section III, 1974 Edition, 1976 Winter Addenda and to ASME Section IX, 1977 Edition, 1978 Summer Addend The base materials covered are plate to SA533, Grade A, Class 1, and forgings to SA508, Class 2, and SA508, Class 2 These analyses are classified in ASME Section IX as P3, Grade No items of noncompliance or deviations were identifie Observation of Hot and Cold Leg Fittings, ETA 40004 Grinding and weld repair operations were witnesse NCR 79-141 covering handling marks on cold leg piece No. EP3-8, U2A was examined and found to be acceptabl A weld repair build up was being made on the inside diameter of EP-In all cases of repair, care was being exercised to maintain minimum wal Piece No. EP-4 cold leg fitting has been welded to all three steam generator Grinding was complete and radiography was acceptable, but was for information onl However, penetrant indications on the W buttered (generator) side of the weld joint were being evaluated and blende No items of noncompliance or deviations were identifie I

" Radiography of Welds and Weld Buildup, ETA 40004 Radiographic film and procedure for the build up on weld No. 2 of EP-3, U2A was examine Procedure RT-A-Z-77VS was used by Technical Service Lab (TSL) to do this wor The following information was taken from the radiographic data sheet.

. Source SFD Type Exposure Thickness Film Pene 18\\"

8 films, panorama 3"

EKC-T

.45 This weld build up which was deposited by sub-arc welding, showed slag (0-15) which was rejected and repaire Radiographs of two welds EP4-U2C and EP4-U2A representing welds of a cold leg fitting to generators 2C and 2A were examine Information taken from the radiographic data sheet is listed belo These welds were made with the Dimetrics Automatic GTAW welde Weld EP-4, U2C EP-4, U2A Source IR-192,9SCi IR-192,94Ci SFD 18\\"

18\\"

Type Exposure panorama, 8 films panorama, 8 films Film Pene EKC-T

.SO EKC-T

.SO The above two welds are information welds since further repair, due to PT indications at the edge of the weld must be mad No items of noncompliance or deviations were identifie.

Housekeeping On Tuesday, July 10, rubber gloves, shoe covers and tape were lying around in the walkway between the change room and containmen This condition was reported to SGRP personnel and the condition was much improved the next da On Wednesday, July 11, when descending the spiral staircase between 2B and 2C generators, a loud speaker at approximately the 32 foot level was noticed to be full of tape and other assorted pape This item was reported to the the licensee at the exit intervie Exit Interview The inspector met with site staff representatives (denoted in the Persons Contacted paragraph) at the conclusion of the inspection on July 12, 197 The inspector summarized the scope and findings of the inspection, which were acknowledged by the license