O PSEG kublic Service Electric and Gas Company P.O. Box E Hancocks Bridge, New Jersey 08038 Salem Generating Stat;on March 11, 1983 Mr.

R. C. Haynes Regional Administrator USNRC Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Haynes:

LICENSE NO. DPR-70 DOCKET.NO. 50-272 REPORTABLE OCCURRENCE 83-011/01T Pursuant to the requirements of Salem Generating Station Unit No. 1 Technical Specifications, Section 6.9.1.8.c, we are submitting Licensee Event Report for Reportable Occurrence 83-Oll/0lT.

This report is required within fourteen (14) days of the occurrence.

Sincerely yours, ll k '

H.

J.

Midura General Manager -

Salem Operations RF:ks

.CC:

Distribution 7

8303180319 830311 PDR ADOCK 05000272 h

g PDR The Energy People 7,21FJ f20M) 1181

p Report Number:

83-011/01T Report Date:

03-10-83 Occurrence Date:

02-25-83 Facility:

Salem Generating Station Unit 1 Public Service Electric & Gas Company Hancock's Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:

Reactor Trip System - Reactor Trip Breakers - Inoperable.

This report was initiated by Incident Report 83-034.

CONDITIONS PRIOR TO OCCURRENCE:

Mode 1 - RX Power 12 5 - Unit Load 70 MWe.

DESCRIPTION OF OCCURRENCE:

On February 25, 1983, during a routine startup of Salem Unit 1, both reactor trip breakers failed to open automatically on receipt of a valid Low-Low Steam Generator Level reactor trip signal.

The reactor was shutdown 25 seconds later using the manual trip on the control console.

Following the trip, the plant was placed in a stable shutdown condition.

A plant cooldown was subsequently performed, and the unit entered Mode 5 at 0254 hours0.00294 days <br />0.0706 hours <br />4.199735e-4 weeks <br />9.6647e-5 months <br />, February 26, 1983 Letters to the NRC dated March 1 and 8, 1983, provide documentation of the investigation of the incident and proposed corrective action.

A Supplemental Report will be submitted documenting the occurrence in detail.

FAILURE DATA:

Westinghcuse Electric Corp.

Air Circuit Breaker Model DB-50 Type A Prepared By R.

Frahm

/

G'eneral Manager -

Salem Operations SORC Meeting No.

83-031B