Reactor Protection & Control Process Instrumentation Replacement Project at DC Cook Nuclear Plant Units 1 & 2 Test Program Summary.
ML17329A719
Person / Time
Site: Cook  American Electric Power icon.png
Issue date: 12/10/1992
From:
AMERICAN ELECTRIC POWER SERVICE CORP.
To:
Shared Package
ML17329A705 List:
References
2985-BJB-01, 2985-BJB-01-R00, 2985-BJB-1, 2985-BJB-1-R, NUDOCS 9212180090
Download: ML17329A719 (7)


Text

REACTORPROTECTIONANDCONTROLPROCESSINSTRUMENTATIONREPLACEMENTPROJECTATDONALDC.COOKNUCLEARPLANTUNITS1AND2TESTPROGRAMSUMMARYREPORTNO.2985-BJB-01~REV0Preparedby:Date)2i>l.92Date/Z,.921210992121PGRpSi70&~P ReactorProtectionandControlProcessInstrumentationRelacementPro'ectatDonaldC.CookNuclearPlantUnits1and2TestProramSummar~Scoe:ReortNo.2985-BJB-01Rev0TheTestProgramconsistsofFactoryAcceptanceTests(FATs),IntegrationTests,InstallationTests,SurveillanceTestsandTimeResponseTestsfortheReactorProtectionandControlProcessInstrumentationReplacementProjectforDonaldC.CookNuclearPlantUnits1and2.TheoverallTestProgramdescribedbelowwillensurethereplacementequipmentwillperformit'intendedfunctionwithinit'sprescribedacceptancecriteria.ThisTestProgramdoesnotincludethevariousequipmentqualificationtests,suchasenvironmentalandseismictests.Thesequalificationtestsaredetailedelsewhere.Certaininspectionsarenotedinthetestsummarybelow.QualityControlandQualityAssuranceinspectionsperformedforthisprojectarecoveredundertheprojectQAprogramrequirementselsewhere.Overview:Testingwillperformedinhierarchialfashiontoensurethatanyproblemswhicharefoundcanberesolvedbeforetheequipmentproceedstothenextphaseoftheproject(FactoryFabrication,PlantInstallation,PlantOperation).Pre-installationtestingwillbedoneviaFactoryAcceptanceTestsandIntegrationTeststoensurethereplacementequipmentwillmeetit'srequiredfunctionpriortoactualinstallation.Installationtestswillensurethereplacementequipmentisinstalledaccordingtoapproveddesignandintegratedwiththeirexistingplantinterfaces,suchassensors,alarmsandtripfunctions,whicharenotbeingreplaced.Post-installationSurveillanceandTimeResponsetestswillbeperformedtoensurethereplacementequipmentwillmeettheplantTechnicalSpecificationrequirementsforsystemoperability.Thereplacementequipmentmustsatisfactorilypassallofitequiredtestsandallproblemssatisfactorilyresolvedbeforethesystemisdeclaredoperable.SummarDiscussion:TheTestProgramconsistsofFactoryAcceptanceTests(FATs),IntegrationTests,InstallationTests,SurveillanceTestsandTimeResponseTests.FactorAccetanceTestFATFactoryAcceptanceTestsarepre-installationtestswhichverifythereplacementequipment,includingpowersupplies,interposing Report2985-BJB-01,Rev0page2of5relays,rackwiring,inputandoutputmodulesandloopconfigurations,performtheirintendedfunctionasrequiredbyboththereplacementvendorandAEPdesignspecificationspriortoacceptancefordeliveryorinstallationoftheequipment.Thesetestsarewrittensuchthatacompletehistoryofeachtestisdocumented,includingalogofanydiscrepanciesfound,resolutionofthesediscrepancies,arecordoftestpersonnel,testequipment,testsetupandconfiguration.Thefinalfactoryassembledrackswhichwillbeinstalledattheplantaresubjectedtothetests.Temporary120vacpowerissuppliedtothepermanentrackpowersupplies.Thepermanentrackpowersuppliesareusedtopowerallinstrumentloops.Fieldinputstotherackanaloginputmodulesandoutputloadsfromtherackanalogoutputmodulesaresimulatedusingtestequipmentwhichmimicactualfieldconditions.Theloopsareconfiguredusingthecontrolledconfigurationdocumentswhichwillbeusedfortheactualinstallation.Allinputsandoutputsaretestedandtheoverallloopconfigurationisverified.Dynamicandcontrolalgorithmresponsetestsareperformedtoensuretheirresponsecharacteristicsmeettheplantspecificrequirements.Inaddition,timeresponsetestswillbeperformedtoensurethereplacementequipmentwillmeettheplantspecifictimeresponserequirements.Allrackworkmanship,materielconditionandwiringisalsoverified.TheFATproceduresaremeticulouslydetailed.Theirprimarypurposeistodetectanypotentialdesign,equipmentorperformanceproblemswhichwouldjeopardizeplantcontrolorprotectionsystemsfromperformingtheirintendedfunction.Allproblemsidentifiedwillberesolvedpriortoacceptanceofthereplacementequipmentandcommencement.oftheinstallationofthereplacementequipmentintheplant.InterationTestinTheIntegrationTestsarepre-installationtestswhichensuretheReactorProtectionGroupinstrumentationproperlyinterfaceswithControlGroupinstrumentationandviceversawithnoadverseinteraction.ThesetestsconnecttheReactorProtectionrackstotheControlGroupracksperthedesignwiringdiagramsandsimulatevariousanticipatedrackinteractionsandperturbations,includingadversepowerfailures,instrumentgroundingsorfailures.TheprimaryemphasisoftheIntegrationTestsistoensurethattheReactorProtectiongroupandtheControlgroupoperatetogetherwithoutadverseinteraction.Expectedresultswillbe Report2985-BJB-01,Rev0page3of5recordedandanyunexpectedresultswillbeinvestigatedandsatisfactorilyresolvedpriortoacceptanceofthereplacementequipmentandcommencementoftheinstallationofthereplacementequipmentintheplant.Thesetestsarewrittensuchthatacompletehistoryofeachtestisdocumented,includingalogofanydiscrepanciesfound,resolutionofthesediscrepancies,arecordoftestpersonnel,testequipment,testsetupandconfiguration.InstallationTestinInstallationTestsareperformedtoensurethereplacementequipmentisproperlyinstalledandwiredintotheirpermanentplantmountinglocations.Mostofthereplacementequipmentwillbemountedinexistingracksinthecontrolroom.Someofthereplacementequipmentwillbepanelmountedonthefrontcontrolpanels.Someofthereplacementequipmentwillbemountedinnewracks.Installationtestsconsistofinitialde-energizedwirecontinuitychecks,cablemeggeringandvisualinspectionstoensureallplantinterfacessuchaspower,grounding,fieldsensorinputs,trip,alarmandcomputeroutputsareproperlyconnectedwiththepermanentplantequipment.Onceinitialchecksarecomplete,theequipmentisenergized,calibratedandfunctionallytestedtoensureallplantinterfaceshavebeenproperlyintegrated.Inspectionoftheequipmentinstallationisdonetoensuretheequipmentismountedincompliancewiththeseismicallyqualifiedmountingdesign.AllinstallationtestsmustbesatisfactorilycompletedandanyproblemsresolvedbeforethesystemscanbedeclaredoperableorreleasedforSurveillanceTesting.ReplacementequipmentincriticalplantsystemswhoseoperabilityiscoveredbyTechnicalSpecificationswillnotbereleasedordeclaredoperableuntiltheirapplicableSurveillanceandTimeResponseTestsarecomplete.SurveillanceTestinOncetheequipmentisinstalledandInstallationTestinghasbeencompletedwithallproblemsresolved,SurveillanceTestswillbeperformedtoensureallapplicableTechnicalSpecificationsystemoperabilityrequirementsaremet.TheseSurveillanceTestsmustbesatisfactorilycompletedbeforethesystemcanbedeclaredoperable.TimeResonseTestinSomeofthereplacementequipmentisintegraltocriticalplant

~~I~Report2985-BJB-Ol,Rev0page4of5systemswhicharerequiredtomeetspecifictimeresponsetestsperplantTechnicalSpecifications.TheseTimeResponseTestsmustalsobesatisfactorilycompletedbeforethesystemcanbedeclaredoperable.ForInstallation,SurveillanceandTimeResponseTests,specificplantproceduresareutilizedtoperformanddocumentthetests,andtoidentifyanddocumentresolutionofallproblems.Conclusion:TheabovesummarydescribesthevariousphasesoftheoverallTest,Program.Thesetestsareperformedinhierarchialfashiontoensurethatanyproblemswhicharefoundcanberesolvedbeforetheequipmentproceedstothenextphaseoftheproject.ThetestsareperformedtoensureproperoperationandintegrationofthereplacementequipmentincompliancewiththevendorandAEPdesignspecificationsandplantfunctionalandTechnicalSpecificationrequirements.

References:

1.FoxboroFactoryAcceptanceTestProcedurefortheUpgradeoftheReactorProtectionProcessInstrumentation-TP-150,DraftRev22.ElectricalInstallationandCheckoutProcedure-12IHP6030IMP.59VariousSurveillance/MaintenanceTestProcedures3.DT/TavgProtectionSetICalibration**2IHP6030IMP.1944;ReactorCoolantFlowProtectionSetICalibration**2IHP6030IMP.1995.SteamGeneratorLevelProtectionSetICalibration**2IHP6030IMP.2046.PressurizerLevelProtectionSetICalibration**2IHP6030IMP.2087.SteamGenerator1E2MismatchProtectionSetICalibration**2IHP6030IMP.2118.SteamGenerator3&4MismatchProtectionSetICalibration**2IHP6030IMP.2129.PressurizerPressureProtectionSetICalibration**2IHP6030IMP.215 Report2985-BJB-Ol,Rev0page5of510.LowerContainmentPressureProtectionSetICalibration**THP6030IMP.219TurbineImpulseChamberPressureProtectionSetICalibration**2IHP6030IMP.22312.13.ReactorCoolantWideRangeTemperatureCalibration**2IHP6030IMP.256AuxiliaryFeedwaterToSteamGenerator41FlowIndicationCalibration**2IHP6030IMP.26514.15.AuxiliaryFeedwaterToSteamGenerator$3FlowIndicationCalibration**2IHP6030IMP.267SteamGenerator162MismatchProtectionSetITransmitterCalibration**2IHP6030IMP.40016.SteamGenerator364MismatchProtectionSetITransmitterCalibration**2IHP6030IMP.40117.18.19.20.21.22.23.24.25.ReactorCoolantFlowProtectionSetISurveillanceTest(Monthly)**2IHP4030STP.101OvertemperatureandOverpowerProtectionSetISurveillanceTest(Monthly)**2IHP4030STP.104PressurizerLevelProtectionSetISurveillanceTest(Monthly)**2IHP4030STP.108PressurizerPressureProtectionSetISurveillanceTest(Monthly)**2IHP4030STP.111SteamGeneratorWaterLevelProtectionSetISurveillanceTest(Monthly)**2IHP4030STP.115SteamGenerator162MismatchProtectionSetISurveillanceTest(Monthly)**2IHP4030STP.119SteamGenerator3&4MismatchProtectionSetISurveillanceTest(Monthly)**2IHP4030STP.120ContainmentPressureProtectionSEtISurveillanceTest(Monthly)**2IHP4030STP.146ReactorProtection6EngineeredSafeguardsSystemTimeResponseTrainASurveillanceTestProcedures-**2IHP4030STP.100A

~I~V