Proposed Tech Spec Table 3.14-1 Concerning Fire Detection Instruments for Computer Room
ML17251A584
Person / Time
Site: Ginna Constellation icon.png
Issue date: 02/12/1986
From:
ROCHESTER GAS & ELECTRIC CORP.
To:
Shared Package
ML17251A581 List:
References
NUDOCS 8602190177
Download: ML17251A584 (8)


Text

AttachmentARevisetheTechnicalSpecificationpagesasfollows:Remove3.14-7Insert3.14-78602i90i778602i2'DRADOCK05000244PPDR 1p 4(~Table3.14-1FIREDETECTIONIhSTRUEKNTSInstnmentLocationMinimumInstrumentsrab]e***2.3.4.5.7.8.9.Containment"A"Post-AccidentCharcoalBank(Z09.Z10)"B"Post-AccidentCharcoalBank(Z11,Z12)"A"Aux.FilterCharcoalBank(Z06)"B"Aux.FilterCharcoalBank(Z07)CableTraysBasementElev.(Z08)CableTraysIntermed.El'.(Z15)CableTraysOperatingFloor(Z16)"A"RCPIntermediateFloor(Z13)"B"RCPIntermediateFloor(Z14)AreaDetectionOperatingFloor(Z16)ControlRoanAreaandCabinet(Z19)ControlRoan/Turb.Bldg.Wall(S29)RelayRoan(Z18,S08)CanputerRoanCeiling(S07)BatteryRoans(ASB)(PyrotronicsZone8)ControlBuildingAirHandlingRoan(S06)DieselGenerator"A"GeneratorRoan(S12)"A"GeneratorVault(Z20)nBnGeneratorRoan(S13)"B"GeneratorVault(Z21)IntermediateBuildingMotorDrivenAux.Fd.PumpArea(Z22)Turb.DrivenAux.Fd.Pump6Res.(S14),CableTraysBasementNorth(S15)"A"PurgeFilterElev.315'-4"(Z23)"B"PurgeFilterElev.315-4"(Z24)ScreenHouseAreaDetectionServ.WaterPumpandBusArea(Z26)CableTraysBasement(S17)Heat3*3*1**2**1%'*1%'*1%*N/A14N/AN/AN/A2N/A2N/AN/A1N/AN/AN/AN/AN/ASmokeN/AN/AN/AN/AN/AN/AN/AN/AN/A717N/A163N/A1N/A19N/A14111143.14-7 I)31kANJ,lp

~,AttachmentBRochesterGasandElectricCorporation(RGGE)willinstallanewplantprocesscomputersystem(PPCS)atGinnaintheSpringof1986.ThePPCSisnecessarytosupportthenewSafetyAssessmentSystemrequiredbyNUREG-0737.AsaresultofthePPCSinstallation,theexistingcomputerroomfloorwillbemodified.TheraisedfloorwillberemovedandwiresforthecomputerwillberelocatedtoawirewayunderthenewPPCS.ThecurrentTechnicalSpecificationsspecifytwofiredetectionzonesinthecomputerroom,ZoneS07undertheraisedfloorandzoneZ17attheceiling.CurrentlyZ17,theceilingzone,isonlyusedtoactuateanalarm.Theunder-floorzone,S07,isusedtoactuatetheHalonsystem.ModificationstotheroomtoaccommodatethePPCSwillresultintheHalonsystembeingactuatedbytheceilingzone.Theundertheraisedfloordetectionzonewillberemovedalongwiththeraisedfloor.Theceilingzonewillberelabled(S07).NeithertheamountofHaloninjectednortheconcentrationwillbeaffectedbythismodification.SincetheTechnicalSpecificationsspecifydetectionzonesthatwillbemodifiedaSpecificationchangeisrequired.TheplannedmodificationwillnotdecreasetheleveloffireprotectionbecausedetectionandautomaticactuationofHalonsuppressionwillberetained.Xnaccordancewith10CFR50.91,thischangetoTechnicalSpecificationshasbeenevaluatedagainstthreecriteria'todetermineiftheoperationofthefacilityinaccordancewiththeproposedamendmentwould:1.involveasignificantincreaseintheprobabilityorsequencesofanaccidentpreviouslyevaluated;orI2.createthepossibilityofanewordifferentkindofaccidentfromanyaccidentpreviouslyevaluated;or3.involveasignificantreductioninamarginofsafety.ThemodificationchangesthezonethatactuatestheHalon,however,itdoesnotdecreasetheamountofHaloninjectednordoesitdecreasetheconcentrationofHalonintheroom.Theactuationwillstillbebasedon2outof4logic,therefore,theprobabilityoffailureremainsunchanged.SincetheconcentrationofHalonintheroomisnotdecreasedandthefailureprobabilityisunchangedthemodificationdoesnot'increasetheprobabilityorconsequencesofanaccident.ChangingtheHalonactuationzonedoesnotcreateanewordifferentkindofaccidentthanwaspreviouslyevaluatedbecausethechangeonlyinvolveschangingtheactuationfromthefloortotheceiling.

llll SincetheEIalonconcentrationisnoteffectedbythemodification,andtheleveloffireprotectionisnotchangedthereisnoreductioninamarginofsafety.Therefore,anosignificanthazardsfindingiswarrantedfortheproposedchange.

l0~~~aL~-~lJLJIrtIJ