E0P:
TITLE:
REV: 11
.ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI REQUIRED PAGE 1 of 9 O(_f ROCHESTER GAS AND ELECTRIC CORPORATION GINNA STATION CONTROLLED COPY NUMBER b
e RESPONSIBLE)hANAGER j
JR -H4f EFFECTIVE DATE CATEGORY 1.0 REVIEWED BY:
U 9812210279 981214 I PDR ADOCK 05000244, t-1 P
PDR Q
... ~ -...
~.. ~
~
. -. ~... -.
4 l
E0P:
TITLE:
l ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI REV: 11 REQUIRED PAGE 2 of 9 iIO lJ A.
PURPOSE - This procedure provides actions to use engineered safeguards systems to recover plant conditions following restoration of AC emergency power.
B.
ENTRY CONDITIONS / SYMPTOMS 1.
ENTRY CONDITIONS - This procedure is entered from:
l a.
ECA-0.0, LOSS OF ALL AC POWER, when AC emergency l
power is restored and SI is required.
l b.
ECA-0.1, LOSS OF ALL AC POWER RECOVERY WITHOUT SI REQUIRED, if SI is required.
I h
l O
l l
l
E0P:
TITLE:
REV: 11 ECA-0*2 LOSS OF ALL AC POWER RECOVERY WITH SI 4
REQUIRED TAGE 3 of 9 GV ACTION / EXPECTED RESPONSE RESPONSENOTUBTi.1NEDl STEP NOTE: o CSFSTs should be monitored for information only.
FR procedures should not be implemented prior to completion of Step 10.
l o
Adverse CNMT values should be used whenever CNMT pressure is greater than 4 psig or CNMT radiation is greater than 10+05 R/hr.
1 Reset SI 2 Check RCP CCW Isolation Status:
- a. CCW pumps - BOTH PUMPS OFF
- a. Go to Step 3.
l
- b. Manually close valves as l
necessary:
i MOV-759A e
i'
. MOV-759B o RCP CCW thermal barrier j
outlet valves l
- A0V-754B l
l
-OR-l' o RCP CCW supply valves e MOV-749A e MOV-749B i
i i
3 Check RWST Level - GREATER Co to ES-1.3. TRANSFEP. TO COLD LEG THAN 28%
RECIRCULATION, Step 1.
l l
l l
I i
l a
LOP:
'ilI LE:
REV: 11 LOSS OF ALL AC' POWER RECOVERY WITH SI ECA-0.2 4
REQUIRED PAGE 4 of 9 O
ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP F_QIB: SI actuation to establish safeguards valve alignment is not recommended.
4 Manually Align SI And RHR Pumps To Establish SI Injection:
- a. Ensure at least one SI pump
- OPEN suction valve from RWST open.
. MOV-825A e MOV-825A
= MOV-825B e MOV-825B
- b. Verify SI pump C discharge
- b. Manually open valves as valves - OPEN necessary.
. MOV-871A e MOV-871B
- c. RHR pump discharge to Rx vessel
- c. Ensure at least one deluge valve O
deluge - OPEN open.
. MOV-852A e MOV-852A MOV-852B e MOV-852B e
O
E0P:
TITLE:
ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI REV: 11 REQUIRED PAGE 5 of 9 p
V ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP CAUTION THE LOADS PLACED ON THE ENERGIZED AC EMERGENCY BUS SHOULD NOT EXCEED THE CAPACITY OF THE POWER SOURCE.
5 Manually Load Following Safeguards Equipment On AC Emergency Bus:
1
- a. Start all SI pumps
- a. Perform the following:
- 1) Start available SI pumps.
o H SI pump A M available. THEN ensure MOV-871B closed, o H SI pump B M available. THEN ensure MOV-871A closed,
- b. Check RCS pressure:
- b. Manually start both RHR pumps and go to Step Sd.
o Pressure - GREATER THAN 250 psig [465 psig adverse CNMT) o Pressure - STABLE OR INCREASING
- c. Place RHR pump switches in AUTO
- d. Start all available CNMT RECIRC fans
-a L
z_ -....
A
-...A
._.A
.m.R h
E0P:
TITLE:
ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI REV: 11 j
4 REQUIRED PAGE 6 of 9
('~\\
I
(_ /
ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP l
CAUTION o IF CST LEVEL DECREASES TO LESS TRAN 5 FEET. THEN ALTERNATE WATER SOURCES FOR AFW PUMPS WILL BE NECESSARY (REFER TO ER-AFW.I. ALTERNATE WATER SUPPLY TO AFW PUMPS).
I IF S/G NR LEVEL DECREASES TO LESS THAN 5% [25% ADVERSE CNMT] AND FEED FLOW o
IS LESS THAN 200 GPM, THEN THE MDAFW PUMPS SHOULD BE MANUALLY LOADED ON AC EMERGENCY BUS TO SUPPLY WATER TO THE S/G(S).
4 If MDAFW pump operation is not required, pump switches should be NOTE: o maintained in PULL-STOP to prevent automatic start.
TDAFW pump flow control valves fail open on loss of IA.
o
- 6 Monitor Intact S/G Levels:
fx i()
- a. Narrow range level - GREATER
- a. Maintain total feed flow greater THAN 5% [25% adverse CNMT]
than 200 gpm until narrow range level greater than 5% [25%
adverse CNMT] in at least one S/G.
IE feed flow less than 200 gpm, THEN perform the following:
- 1) Verify MDAFW pump discharge valve to intact S/G(s) open.
. S/G A, MOV-4007 S/G B, MOV-4008 e
- 2) Manually start MDAFW pumps as necessary (228 KW).
- b. Control feed flow to maintain narrow range level between 17%
l
[25% adverse CNMT] and 50%
,T U
f i
LOP:
TITLE:
ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI REV: 11 REQUIRED PAGE 7 of 9 b'i l
O ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP l
7 Verify CI And CVI:
1
- a. CI and CVI annunciators - LIT
- a. Depress manual CI pushbutton.
- Annunciator A-26. CNMT ISOIATION
- Annunciator A-25. CONTAINMENT VENTILATION ISOLATION i
- b. Verify CI and CVI valve status
- b. Manually close CI and CVI lights - BRIGHT valves. IE valves can EI be verified closed by MCB indication THEN dispatch A0 to locally close valves (Refer to Attachment CI/CVI).
- c. Dispatch A0 to locally fail apen outlet valve status lights -
valves.
BRIGHT i
A0V-4561 e
e A0V-4562 i
b[h 1
I
LOP:
ilTLE:
RW: 11 ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI 4
REQUIRED PAGE 8 of 9
.O V
ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP 8 Verify CNMT Spray Not IE CNMT pressure is less than 28 Required:
psig. THEN perform the following:
o Annunciator A-27. CNMT SPRAY -
- a. Reset CNMT spray.
EXTINGUISHED
- b. Place CNMT spray pump dinharge o CNMT pressure - LESS THAN 28 PSIG valve switches to CLOSE to deenergize open contactor.
IF NOT, THEN perform the following:
- a. Depress manual CNMT spray pushbuttons (2 of 2).
- b. Ensure CNMT spray pump discharge valves open.
o CNMT spray pump A:
- MOV-860A e MOV-860B o CNMT spray pump B:
- MOV-8600 e MOV-860D c'. Ensure NaOH tank outlet valves open.
- d. Start both CNMT spray pumps.
- e. Go to step 10.
OO
(
~.. -. _ - _ -..
se E0P:
TITLE:
REV: 11 LOSS OF ALL AC POWER RECOVERY WITH SI ECA-0.2 i
REQUIRED PAGE 9 of 9 0
ACTION / EXPECTED RESPONSE STEP RESPONSE NOT OBTAINED 9 Place CNMT Spray Pumps In AUTO 10 Check RCP Seal Injection Locally close valves before Needle Valves - CLOSED starting charging pump.
e V-300A
= V-300B HQI_E: FR procedures may now be implemented as necessary.
11 Go to E-1, LOSS OF REACTOR OR SECONDAR'I COOLANT, Step 1
-END-O i