ML20198C036

From kanterella
Jump to navigation Jump to search
Rev 11 to ECA-0.2, Loss of All AC Power Recovery with SI Required
ML20198C036
Person / Time
Site: Ginna 
Issue date: 12/14/1998
From:
ROCHESTER GAS & ELECTRIC CORP.
To:
Shared Package
ML17265A479 List:
References
ECA-.2, ECA-0.2, NUDOCS 9812210279
Download: ML20198C036 (10)


Text

_

~ - - - - -

E0P:

TITLE:

REV: 11

.ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI REQUIRED PAGE 1 of 9 O(_f ROCHESTER GAS AND ELECTRIC CORPORATION GINNA STATION CONTROLLED COPY NUMBER b

e RESPONSIBLE)hANAGER j

JR -H4f EFFECTIVE DATE CATEGORY 1.0 REVIEWED BY:

U 9812210279 981214 I PDR ADOCK 05000244, t-1 P

PDR Q

... ~ -...

~.. ~

~

. -. ~... -.

4 l

E0P:

TITLE:

l ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI REV: 11 REQUIRED PAGE 2 of 9 iIO lJ A.

PURPOSE - This procedure provides actions to use engineered safeguards systems to recover plant conditions following restoration of AC emergency power.

B.

ENTRY CONDITIONS / SYMPTOMS 1.

ENTRY CONDITIONS - This procedure is entered from:

l a.

ECA-0.0, LOSS OF ALL AC POWER, when AC emergency l

power is restored and SI is required.

l b.

ECA-0.1, LOSS OF ALL AC POWER RECOVERY WITHOUT SI REQUIRED, if SI is required.

I h

l O

l l

l

E0P:

TITLE:

REV: 11 ECA-0*2 LOSS OF ALL AC POWER RECOVERY WITH SI 4

REQUIRED TAGE 3 of 9 GV ACTION / EXPECTED RESPONSE RESPONSENOTUBTi.1NEDl STEP NOTE: o CSFSTs should be monitored for information only.

FR procedures should not be implemented prior to completion of Step 10.

l o

Adverse CNMT values should be used whenever CNMT pressure is greater than 4 psig or CNMT radiation is greater than 10+05 R/hr.

1 Reset SI 2 Check RCP CCW Isolation Status:

a. CCW pumps - BOTH PUMPS OFF
a. Go to Step 3.

l

b. RCP CCW return valves - CLOSED
b. Manually close valves as l

necessary:

i MOV-759A e

i'

. MOV-759B o RCP CCW thermal barrier j

outlet valves l

l

-OR-l' o RCP CCW supply valves e MOV-749A e MOV-749B i

i i

3 Check RWST Level - GREATER Co to ES-1.3. TRANSFEP. TO COLD LEG THAN 28%

RECIRCULATION, Step 1.

l l

l l

I i

l a

LOP:

'ilI LE:

REV: 11 LOSS OF ALL AC' POWER RECOVERY WITH SI ECA-0.2 4

REQUIRED PAGE 4 of 9 O

ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP F_QIB: SI actuation to establish safeguards valve alignment is not recommended.

4 Manually Align SI And RHR Pumps To Establish SI Injection:

a. SI pump suction valves from RWST
a. Ensure at least one SI pump

- OPEN suction valve from RWST open.

. MOV-825A e MOV-825A

= MOV-825B e MOV-825B

b. Verify SI pump C discharge
b. Manually open valves as valves - OPEN necessary.

. MOV-871A e MOV-871B

c. RHR pump discharge to Rx vessel
c. Ensure at least one deluge valve O

deluge - OPEN open.

. MOV-852A e MOV-852A MOV-852B e MOV-852B e

O

E0P:

TITLE:

ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI REV: 11 REQUIRED PAGE 5 of 9 p

V ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP CAUTION THE LOADS PLACED ON THE ENERGIZED AC EMERGENCY BUS SHOULD NOT EXCEED THE CAPACITY OF THE POWER SOURCE.

5 Manually Load Following Safeguards Equipment On AC Emergency Bus:

1

a. Start all SI pumps
a. Perform the following:
1) Start available SI pumps.
2) H SI pump A or B M available. THEN verify SI pump C aligned as follows:

o H SI pump A M available. THEN ensure MOV-871B closed, o H SI pump B M available. THEN ensure MOV-871A closed,

b. Check RCS pressure:
b. Manually start both RHR pumps and go to Step Sd.

o Pressure - GREATER THAN 250 psig [465 psig adverse CNMT) o Pressure - STABLE OR INCREASING

c. Place RHR pump switches in AUTO
d. Start all available CNMT RECIRC fans

-a L

z_ -....

A

-...A

._.A

.m.R h

E0P:

TITLE:

ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI REV: 11 j

4 REQUIRED PAGE 6 of 9

('~\\

I

(_ /

ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP l

CAUTION o IF CST LEVEL DECREASES TO LESS TRAN 5 FEET. THEN ALTERNATE WATER SOURCES FOR AFW PUMPS WILL BE NECESSARY (REFER TO ER-AFW.I. ALTERNATE WATER SUPPLY TO AFW PUMPS).

I IF S/G NR LEVEL DECREASES TO LESS THAN 5% [25% ADVERSE CNMT] AND FEED FLOW o

IS LESS THAN 200 GPM, THEN THE MDAFW PUMPS SHOULD BE MANUALLY LOADED ON AC EMERGENCY BUS TO SUPPLY WATER TO THE S/G(S).

4 If MDAFW pump operation is not required, pump switches should be NOTE: o maintained in PULL-STOP to prevent automatic start.

TDAFW pump flow control valves fail open on loss of IA.

o

  • 6 Monitor Intact S/G Levels:

fx i()

a. Narrow range level - GREATER
a. Maintain total feed flow greater THAN 5% [25% adverse CNMT]

than 200 gpm until narrow range level greater than 5% [25%

adverse CNMT] in at least one S/G.

IE feed flow less than 200 gpm, THEN perform the following:

1) Verify MDAFW pump discharge valve to intact S/G(s) open.

. S/G A, MOV-4007 S/G B, MOV-4008 e

2) Manually start MDAFW pumps as necessary (228 KW).
b. Control feed flow to maintain narrow range level between 17%

l

[25% adverse CNMT] and 50%

,T U

f i

LOP:

TITLE:

ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI REV: 11 REQUIRED PAGE 7 of 9 b'i l

O ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP l

7 Verify CI And CVI:

1

a. CI and CVI annunciators - LIT
a. Depress manual CI pushbutton.
b. Verify CI and CVI valve status
b. Manually close CI and CVI lights - BRIGHT valves. IE valves can EI be verified closed by MCB indication THEN dispatch A0 to locally close valves (Refer to Attachment CI/CVI).
c. CNMT RECIRC fan coolers SW
c. Dispatch A0 to locally fail apen outlet valve status lights -

valves.

BRIGHT i

A0V-4561 e

e A0V-4562 i

b[h 1

I

LOP:

ilTLE:

RW: 11 ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI 4

REQUIRED PAGE 8 of 9

.O V

ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP 8 Verify CNMT Spray Not IE CNMT pressure is less than 28 Required:

psig. THEN perform the following:

o Annunciator A-27. CNMT SPRAY -

a. Reset CNMT spray.

EXTINGUISHED

b. Place CNMT spray pump dinharge o CNMT pressure - LESS THAN 28 PSIG valve switches to CLOSE to deenergize open contactor.

IF NOT, THEN perform the following:

a. Depress manual CNMT spray pushbuttons (2 of 2).
b. Ensure CNMT spray pump discharge valves open.

o CNMT spray pump A:

  • MOV-860A e MOV-860B o CNMT spray pump B:
  • MOV-8600 e MOV-860D c'. Ensure NaOH tank outlet valves open.
d. Start both CNMT spray pumps.
e. Go to step 10.

OO

(

~.. -. _ - _ -..

se E0P:

TITLE:

REV: 11 LOSS OF ALL AC POWER RECOVERY WITH SI ECA-0.2 i

REQUIRED PAGE 9 of 9 0

ACTION / EXPECTED RESPONSE STEP RESPONSE NOT OBTAINED 9 Place CNMT Spray Pumps In AUTO 10 Check RCP Seal Injection Locally close valves before Needle Valves - CLOSED starting charging pump.

e V-300A

= V-300B HQI_E: FR procedures may now be implemented as necessary.

11 Go to E-1, LOSS OF REACTOR OR SECONDAR'I COOLANT, Step 1

-END-O i

l a

p 4

I

r... _.__ _

.. ~.

u E0P:

TITLE:

REV: 11 ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI 9

REQUIRED PAGE 1 of 1 l

ECA-0.2 APPEND 1X LIST TITLE 1)

ATTACHMENT CI/CVI

( ATI-3. 0)

I l

L

. m

.