0 Battery Cell Parameters 3.8.6 SURVEILLANCE REgUIRB1ENTS SURVEILLANCE FRE(UENCY SR 3.8.6. I Verify electrolyte level of each connected battery cell is above the top of the plates and not overflowing.

31 days SR 3.8.6.2 Verify the float voltage of each connected battery cell is

> 2.07 V.

31 days SR 3.8.6.3 A, 1.<

Verify specific gravity of the desi n ted pilot cell in each battery is

.188 for a

ery A an atter 8 ~

31 days SR 3.8.6.4 Verify average electrolyte temperature of the designated pilot cell in each battery is > 55 F.

31 days SR 3.8.6.5 Verify average electrolyte temperature of every fifth cell of each battery is ) 55'F.

92 days SR 3.8.6.6 Verify specific gravity of each connected battery cell is:

a.

.Not more than 0.020 below average of all connected cells, and b.

, Avera e 'of all connected cells's 1.188 or a

ery an

~ 1.192 for

'ttery B.

~ /, le5; 92 days 9903i00125 99030f PDR ADQCK 05000244 P

PDR R.E. Ginna Nuclear Power Plant 3.8-19<

Amendment No.

61,

l

Attachment IV R.E. Ginna Nuclear Power Plant Proposed Ginna Station Technical Specifications Included pages:

3.&-19

attery Cell Parameters 3.8.6 SURVEILLANCE REgUIREPIENTS SURVEILLANCE FREQUENCY SR 3.8.6. 1 Verify electrolyte level of each connected battery cell is above the top of the plates and not overflowing.

31 days SR 3.8.6.2 Verify the float voltage of each connected battery cell is > 2.07 V.

31 days SR 3.8.6.3 Verify specific gravity of the designated I

pilot cell in each battery is ~ 1.195.

31 days SR 3.8.6.4 Verify average electrolyte temperature of the designated pilot cell in each battery is z 55'F.

31 days SR 3.8.6.5 Verify average electrolyte temperature of every fifth cell of each battery is z 55'F.

92 days SR 3.8.6.6 Verify specific gravity of each connected battery cell is:

a.

Not more than 0.020 below average of all connected cells, and b.

Average of all connected cells is z 1.195.

92 days R.E.

Ginna Nuclear Power Plant 3.8-19 Amendment No.

Pg

~

~

,h