lbf:
- llM, gl REV: 16 i
4 FR-C.1 RESPONSE TO INADEQUATE CORE COOLING 4
PAGE 1 of 18 OV ROCHESTER GAS AND ELECTRIC CORPORATION GINNA STATION CONTROLLED COPY NUMBER kb (Nblmh o
RESPONSIBLE @ AGER l2-/4-0f EFFECTIVE DATE CATEGORY 1.0 REVIEWED BY:
O D
9812210284 981214 PDR ADOCK 05000244 P
PDR L
_.. = = _ _
E0P:
TITLE:
REV: 16 FR-C.1 RESPONSE TO INADEQUATE CORE COOLING i
PAGE 2 of 18 O
A.
PURPOSE - This procedure provides actions to restore core cooling.
B.
ENTRY CONDITIONS / SYMPTOMS 1.
ENTRY CONDITIONS - This procedure is entered from:
I a.
F-0.2, CORE COOLING Critical Safety Function Status Tree, on a RED condition.
O
E0P:
TITLE:
REV: 16 ER-C.1 RESPONSE TO INADEQUATE CORE COOLING 1
PAGE 3 of 18 OO ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP NDIE: Adverse CNMT values should be used whenever CNMT pressure is greater than 4 psig or CNMT radiation is greater than 10+05 R/hr.
- 1 Monitor RWST Level - GREATER Perform the following:
THAN 28%
TRANSFER TO COLD LEO RECIRCULATION.
2 Verify SI Pump Suction Aligned to RWST:
- a. Verify SI pump suction valves
- MOV-825A
= MOV-825B e MOV-825B a
4
!b
E0P:
TITLE:
REV: 16 FR-C.1 RESPONSE TO INADEQUATE CORE COOLING S
PAGE 4 of 18 t' %
b ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP l
CAUTION RHR PUMPS SHOULD NOT BE RUN LONGER THAN 1 HOUR WITHOUT CCW TO THE RHR HEAT EXCHANGERS.
I 1
3 Verify SI Pump And RHR Pump Emergency Alignment:
- a. RHR pump discharge to Rx vessel
- a. Ensure at least one valve open.
i deluge - OPEN e MOV-852A
- MOV-852B l
- b. Verify both RHR pumps - RUNNING
- b. Manually start pumps
- c. Verify SI pump C - RUNNING
- c. Manually start pump on available
- bus,
- d. Verify SI pump A - RUNNING
- d. Perform the following:
O
- 1) Ensure SI pumps B and C running.
- 2) Ensure SI pump C aligned to discharge line A:
o MOV-871B closed l
o MOV-871A open
- 3) Go to Step 4.
- e. Verify SI pump B RUNNINC
- e. Perform the following:
- 1) Ensure SI pumps A and C l
running.
- 2) Ensure SI pump C aligned to discharge line B:
o MOV-871B open o MOV-871A closed l
- 3) Go to Step 4.
- f. Verify both SI pump C discharge
- f. Manually open valves as valves - OPEN necessary.
MOV-871A
. MOV-871B Os i
E0P:
TITLE:
REV: 16 FR-C.1 RESPONSE TO INADEQUATE CORE COOLING
-4 PAGE 5 of 18 ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP 4 Verify SI Flow In Both Trains:
Perform the following:
l o SI line loop A and B flow
- a. Manually start pumps and align i
indicators - CHECK FOR FLOW valves as necessary.
o RHR loop flow indicator - CHECK
- b. Establish maximum charging flow.
FOR FLOW J
l 5 Check RCP Support Conditions:
- a. Verify Bus 11A or 11B - ENERGIZED
- a. Restore power to Bus 11A or 11B d
(Refer to ER-ELEC.1, RESTORATION OF OFFSITE POWER).
- b. Check other RCP support
- b. Continue attempts to establish conditions (Refer to Attachment RCP support conditions.
RCP START) 6 Check SI ACCUM Discharge J.E SI ACCUM discharge valves closed i
J
. Valves - OPEN after ACCUM discharge, THEN go to Step 7.
IF NOT, THEN perform the l-
. MOV-841 following:
. MOV-865
- a. Dispatch A0 with locked valve key to locally close breakers for SI ACCUM discharge valves.
. MOV-841, MCC C position 12F MOV-865, MCC D position 12C e
- b. Open SI ACCUM discharge valves.
= ACCUM A. MOV-841
. ACCUM B, MOV-865 1
i C
Y 4
-. ~
E0P:
TITLE:
REV: 16 FR-C.1 RESPONSE TO INADEQUATE CORE COOLING 4.
PAGE 6 of 18 i
O ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP 7 Check Core Exit T/Cs - LESS Go to Step 10.
THAN 1200 F 8 Check RVLIS Indication:
- a. RCPs - BOTH SECURED a.~ Return to procedure and step in effect
- b. RVLIS level - GREATER THAN 52%
- b. E RVLIS increasing. IILEN return
[55% adverse CNMT]
to Step 1.
IF NOT, IllEN go to Step 9.
j
- c. Return to procedure and step in i
effect 9 Check Core Exit T/Cs:
- a. Temperature - LESS THAN 700* F
- a. E decreasing, THEN return to O)
Step 1.
IF NOT, THEN go to
(
Step 10.
- b. Return to procedure and step in effect
.......................................c CAUTION IF OFFSITE POWER IS LOST AFTER 51 RESET. THEN SELECTED SW PUMPS AND ONE CCW PUMP WILL AUTO START ON EMERGENCY D/G. MANUAL ACTION WILL BE REQUIRED TO RESTART SAFEGUARDS EQUIPMENT.
10 Reset SI O
~
~-
l E0P:
TITLE:
l REV: 16 l
FR-C.1 RESPONSE TO INADEQUATE CORE COOLING l
PAGE 7 of 18 ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED l
STEP l
l t
11 Reset CI:
- a. Depress CI reset pushbutton l-
- b. Verify annunciator A-26 CNMT
- b. Perform the following:
l ISOLATION - EXTINGUISHED
- 1) Reset SI.
- 2) Depress CI reset pushbutton.
l NOTE: This procedure should be continued while obtaining CNMT hydrogen sample in Step 12.
12 Check CNMT Hydrogen Concentration:
['i
- b. Hydrogen concentration - LESS
- b. Consult TSC to determine if V
THAN 0.5%
hydrogen recombiners should be placed in service.
i l
l
{
6 I
l
E0P:
TITLE:
REV: 16 FR-C.1 RESPONSE TO INADEQUATE CORE COOLING PAGE 8 of 18 n
v ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP CAUTION o IF CST LEVEL DECREASES TO LESS THAN 5 FEET, THEN ALTERNATE WATER SOURCES FOR AFW PUMPS WILL BE NECESSARY (REFER TO ER-AFW.1, ALTERNATE WATER SUPPLY TO AFW PUMPS).
A FAULTED OR RUPTURED S/G SHOULD NOT BE USED IN SUBSEQUENT STEPS UNLESS NO o
INTACT S/G IS AVAILABLE.
HQIE: TDAFW pump flow control valves fail open on loss of IA.
- 13 Monitor Intact S/G Levels:
- a. Narrow range level - GREATER
- a. Maintain total feed flow greater THAN 5% [25% adverse CNMT) than 200 gpm until narrow range level greater than 5% [25%
adverse CNMT} in at least one
~
If total feed flow greater than 200 gpm can HQI be established, IHEH perform the following:
- 1) Continue attempts to establish a heat sink in at least one S/G (Refer to ER-AFW.1, ALTERNATE WATER SUPPLY TO AFW PUMPS).
- 2) Go to Step 23.
- b. Control feed flow to mainta2n narrow range level between 11%
[25% adverse CNMT] and 50%
/
O
E0P:
TITLE:
REV: 16 FR-C.1-RESPONSE TO INADEQUATE CORE COOLING l
s PAGE 9 of 18 l
.O V
ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP j
l CAUTION IF ANY PRZR PORV OPENS BECAUSE OF HIGH PRZR PRESSURE. IT SHOULD BE CLOSED AFTER PRESSURE DECREASES TO LESS THAN 2335 PSIG (REFER TO STEP 14B).
l l
14 Check RCS Vent Paths:
- a. Power to PRZR PORV block valves
- a. Restore power to block valves l
- AVAILABLE unless block valve was closed to isolate an open PORV:
l
. MOV-515. MCC D position 6C l
. MOV-516. MCC C position 6C l
- b. PORVs - CLOSED
- b. H PRZR pressure less than 2335 psig. THEN manually close PORVs.
! Q b
H any PORV can NOT be closed.
l THEN manually close its block valve.
- c. Block valves - AT LEAST ONE OPEN
- c. Open one block valve unless it was closed to isolate an open PORV.
- d. Rx vessel head vent valver.
- d. Manually close valves.
CLOSED
. S0V-590
. S0V-591
. S0V-592
. SOV-593 l
l i
i I
- - ~.
. ~ _. -.
_. -. _. =.
..____m.
E0P:
TITLE:
REV: 16 E'R-C.1 -
-RESPONSE TO INADEQUATE CORE COOLING PAGE 10 of 18 t-
/^
G' ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP 15 Establish Condenser Steam Dump Manual Control
- a. Verify condenser available:
- a. Place intact S/G ARV controller in MANUAL and go to Step 16.
o Intact S/G MSIV - OPEN o Annunciator G-15. STEAM DUMP ARMED - LIT
- b. Place steam dump mode selector switch in MANUAL
- c. Place steam dump controller in MANUAL l
N0IE.
Partial uncovering of S/G tubes is acceptable in the following steps.
Q 16 Depressurize All Intact S/Gs To 200 PSIG:
- a. Dump steam to condenser at
- a. Manually or locally dump steam maximum rate at maximum rate using S/G ARVs.
- b. Check S/G pressure LESS THAN
IF NOT. TEEN go to Step 23.
- c. Check RCS hot leg temperatures
IF NOT TEEN go to Step 23.
I
- d. Stop S/G depressurization i
i 1
C\\
U i
~
E0P:
TITLE:
REV: 16
.FR-C.1 RESPONSE TO INADEQUATE CORE COOLING PAGE 11 of 18 i G
.O ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP 17 Check If SI ACCUMs Should Be Isolated:
j
- a. RCS hot leg temperatures - BOTH
- a. Go to Step 23.
LESS THAN 400* F
- b. Dispatch A0 with locked valve key to locally close breakers i
for SI ACCUM discharge valves if l-necessary l
- c. Verify SI reset
- c. Manually reset SI.
- d. Close SI ACCUM discharge valves
- d. Perform the following:
- ACCUM A, MOV-841
- 1) Reset CI.
- 2) Ensure two air compressors running.
l-
l
- 4) Open vent valves for l
unisolated SI ACCUMs.
- 5) Open HCV-945.
l
- e. Locally reopen breakers for MOV-841 and MOV 865 t
i l
~....... -.
-. ~. - -
^*'
E0P:
TITLE:
REV: 16 FR-C.1' RESPONSE TO INADEQUATE CORE COOLING l
PAGE 12 of 18 i
v ACTION / EXPECTED RESPONSE RESPONSENOTOBTAINEDl j-STEP l
l 18'Stop Both RCPs 19 Dump Steam to Condenser At Manually or locally dump steam at Maximum Rate To Depressurize maximum rate using S/G ARVs.
All Intact S/Gs To Atmospheric Pressure 20 Verify SI Flow:
Perform the following:
i-o SI line loop A and B flow
- a. Continue efforts to establish SI indicators - CHECK FOR FLOW flow.
-OR-
- b. Try to establish charging flow.
o RHR loop flow indicator - CHECK
- c. J.E core exit T/Cs less than FOR FLOW 1200* F. THEN return to Step 19.
IF NOT, THEN go to Step 23.
21 Check Core Cooling:
- a. Core exit T/Cs - LESS THAN 1200* F
- a. Go to Step 23,
- b. RCS hot leg temperatures BOTH
- b. Return to Step 19.
LESS THAN 320*F
CREATER
- c. Return to Step 19.
THAN 77% [82% adverse CNMT]
l t
'AV c
l I
....-.. - - ~.
. ~.-.....-.
~. - -..
i E0P:
TITLE:
i REV: 16 FR-C.1 RESPONSE TO INADEQUATE CORE COOLING PAGE 13 of 18 ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP 1
4 s
I 22 Go to Appropriate Plant Procedure l
- a. Check RWST level - GREATER THAN
- a. Go to ES 1.3, TRANSFER TO COLD 28%
LEG RECIRCULATION, Step 1.
- b. Go to E-1 LOSS OF REACTOR OR SECONDARY COOLANT. Step 17 i
j i
)
l i.
1 i
i o 4
W n
i-O
E0P:
TITLE:
REV: 16 FR-C.1 RESPONSE TO INADEQUATE C3RE COOLING PAGE 14 of 18 g- -
(
j ACTION / EXPECTED RESPONSE RESPCNSE NOT OBTAINED STEP
}LQIE: Normal conditions are desired but not required for starting the RCPs.
23 Check If RCPs Should Be Started:
- a. Core Exit T/Cs - GREATER THAN
- a. Go to Step 24.
1200* F l
- b. Check if an idle RCS cooling
- b. Perform the following:
loop is available
- 1) Reset SI.
o Narrow range S/G 1evel -
GREATER THAN 5% (25% adverse
- 2) Reset CI.
CNMT]
l
- 3) Ensure two air compressors o RCP in associated loop -
running.
AVAILABLE AND NOT OPERATING l
- 5) Open all PRZR PORVs and block valves a) H any block valve can NOI be opened. THEN ensure f-power supplied to block valve.
l b) H IA NOT available. TjiEN refer to Attachment N2 PORVS.
l
- 6) H core e.'it T/Cs remain greater than 1200*F. THEN l
open Rx vessel head vent valves.
SOV-590
. SOV-591 S0V-592 S0V-593
=
- 7) Go to Step 24.
- d. Return to Step 23a l
E0P:
TITLE:
1 REV: 16 FR-C.1 RESPONSE TO INADEQUATE CORE COOLING, PAGE 15 of 18
-a
.p t
ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP 24 Try To Locally Depressurize Use faulted or ruptured S/G.
All Intact S/Gs To Atmospheric Pressure:
o Use intact S/G(s) ARVs 0R-o Open TDAFW pump steam supply valve from intact S/G(s)
. S/G A, MOV-3505A j
S/G B, MOV-3504A e
-0R-Perform the following:
o
- a. Open intact S/G MSIV bypass valves
- b. Open both priming air ejector i
steam inlet valves
)
. V-3580 e V-3581 25 Check Core Exit T/Cs - LESS J_E core exit temperatures THAN 1200 F decreasing. THEN return to step 23.
lE core exit temperatures increasing. THEN go to SACRG-1.
SEVERE ACCIDENT CONTROL ROOM GUIDELINE INITIAL RESPONSE step 1.
-(
.~
(
TOP:
TITLE.:
REV: 16 FR-C.1 RESPONSE TO INADEQUATE CORE COOLING PAGE 16 of 18 ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP 26 Check If SI ACCUMs Should Be Isolated:
l l
- a. RHR loop flow indicator - AT.
- a. Return to Step 23.
LEAST INTERMITTENT FLOW
- b. Dispatch A0 with locked valve key to locally close breakers for SI ACCUM discharge valves if necessary
. MOV-841 MCC C position 12F
= MOV-865 MCC D position 12C
- c. Reset SI.
l I
- d. Close SI ACCUM discharge valves
- d. Perform the following:
l t
= ACCUM A. MOV-841
- 1) Reset CI.
l
- ACCUM B. MOV-865 lt
- 2) Ensure two air compressors l
running.
L
- 4) Open vent valves for unisolated SI ACCUMs.
i l'
= ACCUM A. A0V-834A
- ACCUM B. A0V-834B l
l
- 5) Open HCV-945.
- e. Locally reopen breaker.n for MOV-841 and MOV 865 i-l l
I i
l l
i LO
_. ~,.
E0P:
TITLE:
REV: 16 FR-C.1 RESPONSE TO INADEQUATE CORE COOLING j,
PAGE 17 of 18 ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP 27 Check If RCPs Should Be Stopped:
- a. Both RCS hot leg temperatures -
- a. Go to Step 28.
LESS THAN 320'W
Perform the following:
o SI line loop A and B flow
- a. Continue efforts to establish SI indicators - CHECK FOR FLOW flow.
-OR-
- b. Try to establish charging flow, o RHR loop flow indicator CHECK
- c. Return to Step 23.
FOR FLOW O%
29 Check Core Cooling:
- a. RCPs - BOTH SECURED
- a. Return to Step 23.
- b. RCS hot leg temperatures LESS
- b. Return to Step 23.
THAN 320'F
- c. RVLIS level CREATER THAN 71%
- c. Return to Step 23.
(82% adverse CNMTl i
l l
.__.__._._..__.._._._...._.m.
E0P:
TITt.E:
REV: 16 FR-C.1 RESPONSE TO INADEQUATE CORE COOLING PAGE 18 of 18
- O ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP t
1 30 Go to Appropriate Plant Procedure
- a. IE PRZR FORVs and head vents were opened in Step 23.
THEN consult TSC.to evaluate long 4
term status AND continue with l
transitions.
1 i
- b. Check RWST level - GREATER THAN
- b. Go to ES-1.3, TRANSFER TO COLD l
28%
LEG RECIRCULATION. Step 1.
4
- c. Go to E-1. LOSS OF REACTOR OR SECONDARY COOLANT, Step 17.
I
-CND-I i
4 O
4 t
i 1
i 5
J
. -... -.... - -.. ~.. ~ - -. ~. - - - -., -
l l'
E0P:
TITLE:
REV: 16 FR-C.1 RESPONSE TO INADEQUATE CORE COOLING PAGE 1 of 1 i
FR-C.1 APPENDIX LIST
)
TITLE 1)
ATTACHMENT RCP START (AU-15.0)
- 2). ATTACHMENT N2 PORVS (AM-12.0) l l
O i