E0P TITLE:

REV: 10 AP-RCS.2 LOSS OF REACTOR COOLANT FLOW PAGE 1 of 7 li (O j %-)

i i

i ROCHESTER GAS AND ELECTRIC CORPORATION

(.

GINNA STATION CONTROLLED COPY NUMBER l

l l

l l

O l

RESPONSIBLEIMNAGER

!j r\\

U l

id ->4-9f EFFECTIVE DATE l

l l

l CATEGORY 1.0 l

REVIEWED BY:

l l

l O

C/

9812210269 981214E PDR ADOCK 05000244 q

P PDRg

.. _ _ _. ~ _

I J

l E0P:

TITLE:

REV: 10 AP-RCS.2 LOSS OF REACTOR COOLANT PLOW l

PAGE 2 of 7 o

1 O 1

A.

PURPOSE - This procedure provides actions required to i

stabilize plant conditions following a loss of reactor coolant flow.

B.

ENTRY CONDITIONS / SYMPTOMS l

1.

SYMPTOMS - The symptoms of LOSS OF REACTOR COOLANT FLOW are:

l a.

Annunciator A-17, MOTOR OFF RCP CCWP, lit, or l

b.

Annunciator B-29, RCP BREAKER CHANNEL ALERT, lit, or I

Low RCS flow indicated in either or both loops and c.

verified by more than one indication, or l

d.

Steam flow rapidly decreasing in one loop and rapidly increasing i.n the other loop.

l e.

Annunciator B-27, (28), RCS Loop A(B) Lo Flow Channel Alert.

1 l

l l

i

~.

E0P -

TITLE:

REV: 10 AP-RCS.2 LOSS OF REACTOR COOLANT FLOW PAGE 3 of 7 pb ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP CAUTION IF, AT ANY. TIME DURING THIS PROCEDURE, A REACTOR TRIP OR SI OCCURS. E-0, REACTOR TRIP OR SAFETY INJECTION, SHALL BE PERFORMED.

1 Check RCS flows:

a. Verify at least one loop
a. E reactor trip breakers closed, operating:

THEN trip the reactor and go to E-0 REACTOR TRIP OR SAFETY o One RCP running INJECTION.

o Flow greater than 91% in one

1) H reactor trip breakers loop open, verify natural circulation per Attachment NC AND go to Step 2.
b. Verify two loops operating:
b. E power greater than 8%, THEN r

trip the reactor and go to E-0, o Both RCPs running REACTOR TRIP OR SAFETY INJECTION.

o Flow greater than 91% in both

1) H power less than 8%, THEN loops go to step 2.
c. Return to procedure and step in l

effect 2 Verify ROD CONTROL BANK Place R0D CONTROL BANK SELECTOR SELECTOR In MANUAL switch in MANUAL.

O

l' E0P:

TITLE:

~

REV: 10 AP-RCS.2 LOSS OF REACTOR COOLANT FLOW l

PAGE 4 of 7.

- O ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP CAUTION 1

IF ONLY ONE RCP IS LOST. THEN A DECREASS (SHRINK) IN IDLE S/G LEVEL COUPLED i

WITH AN INCREASE (SWELL) IN OPERATING S/G LEVEL SHOULD BE ANTICIPATED.

I j

3 Monitor S/G Levels - TRENDING Restore narrow range level to 52%.

TO 52%

1E S/G level can NOT be restored, THEN trip the reactor and go to a

E-0 REACTOR TRIP OR SAFETY

}

INJECTION.

1

)

l.-

1

!O i

/~N d

1

E0P:

TITLE:

REV: 10 AP-RCS.2 LOSS OF P' TACTOR COOLANT FLOW 2

PAGE 5 of 7 O

ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP m,-

F_0IE: Temperatures in the idle loop may not be indicative of true Tavg and Q

AT values and may affee automatic control systems operation.

Operating loop values should be used for control.

4 Establish Stable Plant Conditions:

a. Tavg - TRENDING TO TREF
a. Insert control rods or. if necessary decrease turbine load to match Tavg of the operating loop to Tref.
b. PRZR pressure - TRENDING T0
b. Verify proper operation of PRZR 2235 PSIG heaters and spray or take manual control of PRZR pressure controller 431K. E pressure can EQT be controlled, THEN refer to AP-PRZR.1, ABNORMAL PRESSURIZER PRESSURE.
c. PRZR level - TRENDING TO PROGRAM
c. Verify proper operation of charging pump speed controllers E take manual control of speed controllers to control PRZR level. H letdown isolation has occurred. THEN place Letdown Loop B Cold Leg to RHX A0V-427 to close.
d. Check S/G 1evels TRENDING T0
d. Control feed flow as necessary 52%

to restore both S/G 1evels to

$2%.

e. Steam dump valves - CLOSED
e. Ensure proper operation of steam dump control system.

O

' i-E0P:

TITLE:

l.

REV: 10 i

AP-RCS.2 LOSS OF REACTOR COOLANT FLOW I

PAGE 6 of 7 O'

l^

)

l-ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP 5 Check Letdown Status

a. Normal OR Excess Letdown in
a. GO TO Step 6.

service.

b. GO TO Step 7.

l 6 Establish Normal Letdown:

Perform the following steps in sequence to establish excess

a. Establish charging line flow to letdown:

REGEN Hx - GREATER THAN 20 GPM o Place excess letdown divert

b. Verify the following switches in valve. A0V-312. to NORMAL CLOSE:

o Ensure CCW from excess letdown Letdown orifice valve open. A0V-745-e (A0V-200A. A0V-200B and A0V-202) o Ensure RCP seal return isolation Loop B cold Icg to REGE!! Hx valve open. MOV-313 e

(q)

A0V-427 U

i o Open excess letdown isolation

c. Plece letdown controllers in valve. A0V-310 MANUAL at 40% open o Slowly open HCV 123 to maintain

. TCV-130 excess letdown temperature less e PCV-135 than 195'F and pressure less than 100 psig

d. Open A0V-427
e. Open letdown orifice valven as necessary
f. Place TCV-130 in AUTO at 105'F
g. Place PCV-135 in AUTO at 250 psig
h. Adjust charging pump speed and HCV-142 at. necessary l

l

l-E0P:

TITLE:

l REV: 10 AP-RCS.2 LOSS OF REACTOR COOIANT FLOW 3

l ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED STEP

.1 CAUTION SHUTDOWN MARGIN REQUIREMENTS SHOULD BE VERIFIED (REFER TO 0-3.1 BORON l

CONCENTRATION FOR XENON FREE ALL RODS IN MOST REACTIVE ROD STUCK OUT SHUTDOWN l

MARGIN).

1 l

l 7 Check Reactor Status:

Initiate plant shutdown (Refer to j

appropriate section of 0-2.1, l

o Reactor Trip Breakers open NORMAL SHUTDOWN TO HOT SHUTDOWN).

l NQIE: Refer to 0-9.3. NRC IMMEDIATE NOTIFICATION, for reporting i

requirements.

8 Notify Higher Supervision 9 Return To Procedure Or g

Guidance In Effect

-END-l I