ML17265A548

From kanterella
Jump to navigation Jump to search
To EOP ATT-22.0, Attachment Restoring Feed Flow
ML17265A548
Person / Time
Site: Ginna 
Issue date: 02/12/1999
From: Sidelinger R
ROCHESTER GAS & ELECTRIC CORP.
To:
Shared Package
ML17265A547 List:
References
ATT-22.0, NUDOCS 9902250301
Download: ML17265A548 (4)


Text

EOP:

ATT-22%0 TITLE:

ATTACHMENT RESTORING FEED FLOW REV 1

PAGE 1 of 3 ROCHESTER GAS AND ELECTRIC CORPORATION GINNA STATION CONTROLLED COPY NUMBER RESPO BLE MANAGER EFFECTIVE DATE CATEGORY 1.0 REVIEWED BY:

VV02250SQZ e902<2 PDR ADQCK 05000244 F

PDR V

EOP:

'ATT-22.0 ATTACHMENT RESTORING FEED FLOW REV 1

PAGE 2.of 3 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED NOTE:

o This attachment provides the desired feed flow rate when restoring feed flow to a S/G during FR-H.1.

o IF feedwater is restored via main feedwater or condensate the following may be used to indicate flow to the S/G:

o S/G feedwater flow meters (MCB) o S/G feedwater flow recorders (MCB) o S/G feedwater flow (PPCS Point ID F0466,

F0467, F0476.,F0477) o S/G feedwater RTD temperature decrease (PPCS Point ID T2096, T2097) l Initiate Feed flow as follows:
a. Bleed and Feed initiated or required b.'Check RCS temp stable or decreasing
c. Establish less than or equal to 100 gpm feed flow to affected S/G.

WHEN S/G level greater than 35 inches (100 inches adverse CNMT), THEN fill as desired to restore narrow range greater than 5/. (25'/ adverse CNMT)

a. IF feedwater flow to affected S7G greater than 50 gpm OR affected SG level greater than 35 inches (100 inches adverse CNMT), THEN fillas desired to restore narrow range greater than
51. (25'/ adverse CNMT) and go to step 2 of this attachment.

IF NOT, THEN establish less than or equal to 100 gpm feed flow to affected S/G.

WHEN S/G level greater than 35 inches (100 inches adverse CNMT). THEN. fill as desired to restore narrow range greater than 5/o (25/.

adverse CNMT) and go to step 2

of this attachment.

b. Fill ONE S/G at the highest possible flow rate and go to step 2 of this attachment.

EOP:

ATT-22.0 TITLE:

ATTACHMENT RESTORING FEED FLOW REV:

1 PAGE 3 of 3 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED 2 Check RCS Loop Hot Legs BOTH HOT LEG TEMPERATURES DECREASING Return to step 1 of this attachment.

1 3 Verify affected S/G is not faulted or ruptured.

Return to step 1 of this-attachment and attempt to establish the intact S/G as heat sink.

Isolate feedwater and steam flow path to/from affected S/G.

jF neither S/G is intact, THEN establish a heat sink using the best available S/G.

-END-