ML20090K454

From kanterella
Revision as of 00:28, 6 May 2020 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Deficiency Rept Re Acceptability of Electrical Conductor Butt Splices.Initially Reported on 840510.Insp of Butt Splices Installed Prior to 840405 in safety-related Cables Scheduled to Begin by 840521
ML20090K454
Person / Time
Site: Byron  Constellation icon.png
Issue date: 05/17/1984
From: Farrar D
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
8666N, NUDOCS 8405240211
Download: ML20090K454 (3)


Text

. ._ . . _ _ _ - _ _ _ - _ - _ _ _

/

[ 9 OCommonwealth Edison f one First National Pitza, Chictgo. Illinois 4 g

C1 1 Addrtss R: ply to: Post Ofhce Box 767 y j Chicago, Illinois 60690 May 17, 1984 Mr. James G. Keppler, Regional Administrator United States Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 61037

SUBJECT:

Byron Generating Station Units 1 and 2 Electrical Conductor Butt Splices Docket Nos. 50-454 and 50-455 REFERENCE (a): Notification (Verbal) of Potential 50.55(e) to J. Hinds on May 10, 1984

Dear Mr. Keppler:

As a result of concerns raised at our LaSalle Station in early January, 1984, our Quality Assurance Department at Byron Station initiated a sampling review of electrical conductor butt splices in early March, 1984. This review consisted of:

(1) review of approximately 11,000 termination inspection reports to determine the practice of documenting installed / inspected butt splices, and a review of 646 specific inspection reports identified from the 11,000 for the detail of objective evidence associated with butt splice inspections.

(2) a physical surveillance of 221 installed butt splices to determine the existence / nature of any deviations from manufacturers' requirements.

As a result of the physical surveillances, a Nonconformance Report 899 was initiated to identify and evaluate various deviations from manufacturer's requirements.

Mr. R. Love of your staff reviewed this data during a recent inspection of April 23 to May 4,1984, and was concerned that we had yet to commit ourselves to a 100% review, by inspection, of butt splices installed prior to April 5, 1984. After consideration of conditions we, by reference (a), made notification to your staff; and hereby outline the activities to be undertaken te verify the acceptability of electrical conductor butt splices. i e405240211 e40517 gDRADOCK05000 L

..- o Mr. James G. Keppler May 17, 1984 Page 2 (1) We will inspect electrical conductor butt splices in safety-related cables in safety-related: panels, motor control centers, switchgear, and both sides of containment electrical penetrations. With the following exceptions and a refinements:

(a) For any two redundant cables found, both of which have butt splices installed on an individual conductor (s) and covered with either heat shrink material or nuclear splicing cement with insulating tape and jacketing tape, the covering material shall be removed from the butt splice (s) on one of the cables and the butt splice shall be inspected. As an alternative to removing the covering material at the time of locating, the existing butt splice may be cut out and tagged for later dissection and inspection, and a new butt splice installed, inspected, and covered.

(b) The redundant cable butt splices identified in item (a) above which are not inspected or removed / replaced, and any butt splices identified in conductors of non-redundant cables which are covered with heat shrink material or nuclear splicing cement and tape will have their location documented for possible inspection based on the results of item (2) below.

(c) For containment electrical penetrations, the cable conductor termination to penetration conductor will not be inspected, but the cable conductor will be inspected from this point to the point where exterior cable pulling jacket has been removed. If butt splices are present in this run of conductors which are not allowed by design documents, a nonconformance report will be initiated to identify condition for resolution. Those that are allowed by design documents will be inspected per (a) or (b) above, as appropriate.

(2) If the inspection results of the inspected butt splices from (1) above, show a greater than 10% rejection rate on a population sufficiently large enough to establish a trend, then all butt splices which have heat shrink coating or nuclear cement and tape will be replaced (i.e. the population of (b) above).

^

)

Mr. James G. Keppler May 17, 1984 Page 3 (3) A special instruction will be developed for these activities and submitted to your staff for review prior to implementation. Inspection personnel will be trained and qualified to this instruction. Craft personnel who are not presently qualified as quality control inspectors, will not subsequently be qualified to perform these special inspections.

We are preparing for implementation of these activities to begin May 21, 1984, and could possibly begin implementation May 19, 1984; however, we will not begin until your staff advises us as to the acceptability of the proposed activities. If you have any questions, please contact us.

Very truly yours, D. Farrar Director of Nuclear Licensing 8666N

- . _ _ . . _ _ _ _ _ _ __ _ _ _ _ , _ _ .