Corrects Typo in Second Interim Deficiency Rept 84-03 Re Installation of Butt Splices in Electrical Connectors.Rept Should Have Indicated That 564 Splices Documented But Not Inspected
ML19302F758
Person / Time
Site: Byron  
Issue date: 04/23/1985
From: Tramm T
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
0022K, 22K, 84-03, 84-3, NUDOCS 8505090517
Download: ML19302F758 (1)


Text

b L / f fS Docket No.:

50-206 August 5, 1985 LS05 85-08-002 DISTRIBUTION Central file Mr. Kenneth P. Baskin, Vice President

{.McVsenna v.

Grimes Nuclear Engineerira Safety ar.d Licensing Department h.

nski southern California Edison Company R. Oudley 2244 Walnut Grove Avenue Post Office Box 800 Rosemead, California 91770

Dear Mr. Baskin:

SUBJECT:

LTS SMAL'. BORE PIPING AND TUBING CRITERIA - SAN ONOFRE NUCLEAR GENERATING STATION, UNIT 1 By letter dated April 30, 1985, you submitted a report describing the proposed small bore pipir.g and tubing criteria for long-term service and supporting analyses.

Based on the staff's review of your submittal, we find that the items described in the enclosure to this letter require further clarification. We request that you be prepared to address these items during the staff audit review to be conducted the week of August 12-16, 1985.

ine reporting end/or recordkeeping reouirements contained in this letter affect fewer than ten respondents; therefore, OMB clearance is not required under P.L.96-511.

Sincerely, Or,inal signed by:

John A. Zwolinski, Chief Operating Reactors Branch 45 Division of Licensing

Enclosure:

As stated cc w/ enclosure:

See next page SEPB:DLc gy SEPB:

SEPB:D C.any Services Post Office Box 800 714 P Street, Office Bldg. 8 Rosemead, California 91770 Sacramento, California 95814 David R. Pigott Orrick, Herrington & Sutcliffe 600 Montgomery Street San Francisco, California 94111 Dr. Leu Bernath San Diego Gas & Electric Company P. O. Box 1831 San Diego, California 92112 Resident Inspector / San Onofre NPS c/o U.S. NRC P. O. Box 4329 San Clemente, California 92672 Maycr City of San Clemente San Clemente, California 92672 Chairnan Board of Supervisors County of San Diego San Diego, California 92101 Director Energy Facilities Siting Division Energy Resources Conservation &

Development Corcission 1516 - 9th Street Sacramento, California 95814 U.S. Environmental Protection Agency Region IX Office ATTN: Regional Radiation Representative 215 Freemont Street San Francisco, California 94105 John B. Martin, Regional Administrator Nuclear Regulatory Commission, Region V 1450 Maria Lane Walnut Creek, California 94596

COMMENTS CONCERNING SONGS 1 LTS SMALL BORE PIPING AND TUBING CRITERIA A review of the SONGS 1 LTS Small Bore Piping and Tubing Criteria (Impell Report No. 01-0310-1385, Rev. O, 4/85) has been performed. The criteria were found generally acceptable, except for the four items listed below:

1.

The allowable stress of 2 S proposed for the small bore criteria y

(Section 3.2) has been found unacceptable for the large bore piping.

Acceptance criteria for small bore piping and tubing should be consistent with those used for the large bore piping.

2.

The rules for out-of-plane support of valve operator (Section 7.2 and 7.3 of the Appendix) include two parameters (C) and C ) which p

have not yet been defined. These parameters should be defined.

3.

The rules for calculating seismic support loads (Section 10.0 of Appendix A) appear to involve an equivalent static calculation with an amplification / carryover factor of 1.2.

This value appears small and needs justification.

4 A correction factor 0.75 is used in defining acceptable span lengths for spans including elbows, tees or valves.

The basis for this factor should be provided.