ML060540467

From kanterella
Revision as of 22:50, 28 October 2018 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search

Sequoyah Nuclear Plant (Sqn) - Response to Request for Additional Information Regarding Unit 2 Steam Generator (SG) Reports from Cycle 13 Refueling Outage (TAC MC8118)
ML060540467
Person / Time
Site: Sequoyah Tennessee Valley Authority icon.png
Issue date: 02/22/2006
From: Pace P L
Tennessee Valley Authority
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
TAC MC8118
Download: ML060540467 (19)


Text

February 22, 2006

U.S. Nuclear Regulatory Commission

ATTN: Document Control Desk

Washington, D.C. 20555

Gentlemen:

In the Matter of ) Docket No. 50-328 Tennessee Valley Authority )

SEQUOYAH NUCLEAR PLANT (SQN) - RESPONSE TO REQUEST FOR

ADDITIONAL INFORMATION REGARDING UNIT 2 STEAM GENERATOR (SG)

REPORTS FROM CYCLE 13 REFUELING OUTAGE (TAC NO. MC8118)

Reference:

NRC letter to TVA dated January 13, 2006, "Sequoyah Nuclear Plant, Unit 2 - Request for

Additional Information Regarding the 15-Day and

90-Day Steam Generator Tube Inservice Inspection

Reports for the End-of-Cycle 13 Refueling Outage

in 2005 (TAC No. MC8118)"

The enclosure to this letter provides additional information

requested by the referenced letter. The additional

information supports the basis for certain conclusions and

statements in the SQN Unit 2 SG reports and results from

detailed review of the SG tube inspection data from the SQN

Unit 2 Cycles 12 and 13 refueling outages.

Please direct questions concerning this issue to me at

(423) 843-7170 or J. D. Smith at (423) 843-6672.

Sincerely, Original signed by James D. Smith for:

P. L. Pace

Manager, Site Licensing and

Industry Affairs

Enclosure

cc: See page 2 U.S. Nuclear Regulatory Commission Page 2 February 22, 2006

cc (Enclosure):

Mr. Douglas V. Pickett, Senior Project Manager

U.S. Nuclear Regulatory Commission

Mail Stop O8G-9a

One White Flint North

11555 Rockville Pike

Rockville, Maryland 20852-2739 NRC Resident Inspector

Sequoyah Nuclear Plant

2600 Igou Ferry Road

Soddy-Daisy, Tennessee 37379-3624

Regional Administrator

U.S. Nuclear Regulatory Commission

Region II

61 Forsythe St., SW, Suite 23T85

Atlanta, Georgia 30303-3415

E1-1 ENCLOSURE TENNESSEE VALLEY AUTHORITY (TVA)

SEQUOYAH NUCLEAR PLANT (SQN)

UNIT 2 RESPONSE TO REQUEST FOR ADDITIONAL INFORMATION REGARDING

STEAM GENERATOR REPORTS FROM CYCLE 13 REFUELING OUTAGE NRC Question 1 On Page 4-6 (of Westinghouse Report SG-SGDA-05-29, Rev.0), it was stated that only one indication was 2-volts or greater out of the

302 (sizing sample) indications at the end-of-cycle (EOC) 13 that

were tested with a worn probe during the EOC 12 inspection. With

this information, you concluded that probe wear has no

significant effect on the population of indications. In

addition, it was stated that out of 365 (population sample)

indications at the EOC 13 only 81 were inspected with a worn

probe during the EOC 12 inspection. You further concluded that

this information indicates that tubes inspected with worn probes

do not contain a larger number of new indications. The basis for

these statements is not clear to the staff, therefore, please

provide justification for these statements.

This justification should include a comparison of the percentage

of new indications at the EOC 13 that were inspected with a worn

probe during the EOC 12 inspection to the percentage of new

indications that were inspected with a good probe during the EOC

12 inspection. In addition, please compare the percentage of new

indications greater than or equal to 0.5-volts at the EOC 13 that

were inspected with a worn probe during the EOC 12 inspection to

the percentage of new indications greater than or equal to 0.5-

volts at EOC 13 that were inspected with a good probe during the

EOC 12 inspection. If there are significant differences, please

provide an assessment of the adequacy of the probe wear criteria

and its impact on your operational assessment for EOC 14. A

value of 0.5-volts was chosen to be consistent with the NRC

staff's approval of the alternate probe wear criterion (refer to

NRC letter to the Nuclear Energy Institute dated February 9, 1996). TVA Response.

In response to this question, the NDE data was reviewed in

detail. The study reported here includes all tubes in all

calibration groups that were reported out of calibration.

E1-2 The indication data reported in the EOC-13 90 Day Report (Westinghouse Report SG-SGDA-05-29, Rev.0) and the EOC-12 90 Day

Report (Westinghouse Report SG-SGDA-03-55, Rev.0), were compared

to identify the new indications. From the EOC-12 NDE data, all

tubes which were in calibration groups that were reported out of

calibration are identified by comparing the NDE data list with

the list of calibration groups that were reported out of

calibration. Then, both new and previously existing indications

can be identified as having been tested with a worn probe at EOC-

12 or not, and the total number of tubes which were tested with a

worn probe can also be determined. The results of this data

sorting procedure are given in the Tables below.

Sequoyah Unit 2 Tube Status Prior to 2005 Inspection (EOC 13)

SG Original Tubes Number plugged at EOC 13 Number of open tubes at EOC 13 1 3388 71 3317 2 3388 158 3230 3 3388 114 3274 4 3388 111 3277 Results of NDE Data Review Steam Generator 1 Number of new indications in EOC-13 56 Worn Probe in EOC-12 Number of new indications tested with worn probe in EOC-12 21 Number of these equal to or greater than 0.5 V in EOC-13 5 Number of tubes tested with worn probe 1578 Good Probe in EOC-12 Number of new indications tested with good probe in EOC-12 35 Number of these equal to or greater than 0.5 V in EOC-13 16 Number of tubes tested with good probe 1739 Ratio of new indications in tubes tested with worn probe to number of tubes tested with a worn probe 21/1578 = 0.0133 Ratio of new indications in tubes tested with good probe to number of tubes tested with a good probe 35/1739 = 0.0201 Percentage of new indications equal to or greater than 0.5 V in tubes tested with worn probe 5/21 = 24%

Percentage of new indications equal to or greater than 0.5 V in tubes tested with good probe 16/35 = 46%

Steam Generator 1 Number of previous indications in EOC-13 238 Worn Probe in EOC-12 Number of prev indications tested with worn probe in EOC-12 89 Number of these exceeding 2.0 V in EOC-13 0 Highest voltage indication of these in EOC-13 1.16 V E1-3 Steam Generator 2 Number of new indications in EOC-13 65 Worn Probe in EOC-12 Number of new indications tested with worn probe in EOC-12 16 Number of these equal to or greater than 0.5 V in EOC-13 5 Number of tubes tested with worn probe 1290 Good Probe in EOC-12 Number of new indications tested with good probe in EOC-12 49 Number of these equal to or greater than 0.5 V in EOC-13 14 Number of tubes tested with good probe 1940 Ratio of new indications in tubes tested with worn probe to number of tubes tested with a worn probe 16/1290 = 0.0124 Ratio of new indications in tubes tested with good probe to number of tubes tested with a good probe 49/1940 = 0.0253 Percentage of new indications equal to or greater than 0.5 V in tubes tested with worn probe 5/16 = 31%

Percentage of new indications equal to or greater than 0.5 V in tubes tested with good probe 14/49 = 29%

Steam Generator 2 Number of previous indications in EOC-13 240 Worn Probe in EOC-12 Number of prev indications tested with worn probe in EOC-12 90 Number of these exceeding 2.0 V in EOC-13 0 Highest voltage indication of these in EOC-13 1.97V

E1-4 Steam Generator 3 Number of new indications in EOC-13 119 Worn Probe in EOC-12 Number of new indications tested with worn probe in EOC-12 59 Number of these equal to or greater than 0.5 V in EOC-13 35 Number of tubes tested with worn probe 1583 Good Probe in EOC-12 Number of new indications tested with good probe in EOC-12 60 Number of these equal to or greater than 0.5 V in EOC-13 32 Number of tubes tested with good probe 1691 Ratio of new indications in tubes tested with worn probe to number of tubes tested with a worn probe 59/1583 = 0.0373 Ratio of new indications in tubes tested with good probe to number of tubes tested with a good probe 60/1691 = 0.0355 Percentage of new indications equal to or greater than 0.5 V in tubes tested with worn probe 35/59 = 59%

Percentage of new indications equal to or greater than 0.5 V in tubes tested with good probe 32/60 = 53%

Steam Generator 3 Number of previous indications in EOC-13 293 Worn Probe in EOC-12 Number of prev indications tested with worn probe in EOC-12 125 Number of these exceeding 2.0 V in EOC-13 1 Highest voltage indication of these in EOC-13 2.36V

E1-5 Steam Generator 4 Number of new indications in EOC-13 125 Worn Probe in EOC-12 Number of new indications tested with worn probe in EOC-12 81 Number of these equal to or greater than 0.5 V in EOC-13 31 Number of tubes tested with worn probe 1992 Good Probe in EOC-12 Number of new indications tested with good probe in EOC-12 44 Number of these equal to or greater than 0.5 V in EOC-13 16 Number of tubes tested with good probe 1285 Ratio of new indications in tubes tested with worn probe to number of tubes tested with a worn probe 81/1992 = 0.0407 Ratio of new indications in tubes tested with good probe to number of tubes tested with a good probe 44/1285 = 0.0342 Percentage of new indications equal to or greater than 0.5 V in tubes tested with worn probe 31/81 = 38%

Percentage of new indications equal to or greater than 0.5 V in tubes tested with good probe 16/44 = 36%

Steam Generator 4 Number of previous indications in EOC-13 711 Worn Probe in EOC-12 Number of prev indications tested with worn probe in EOC-12 428 Number of these exceeding 2.0 V in EOC-13 0 Highest voltage indication of these in EOC-13 1.74V

E1-6 All Steam Generators Combined Number of new indications in EOC-13 365 Worn Probe in EOC-12 Number of new indications tested with worn probe in EOC-12 177 Number of these equal to or greater than 0.5 V in EOC-13 76 Number of tubes tested with worn probe 6443 Good Probe in EOC-12 Number of new indications tested with good probe in EOC-12 188 Number of these equal to or greater than 0.5 V in EOC-13 78 Number of tubes tested with good probe 6655 Ratio of new indications in tubes tested with worn probe to number of tubes tested with a worn probe 177/6443 = 0.0275 Ratio of new indications in tubes tested with good probe to number of tubes tested with a good probe 188/6655 = 0.0282 Percentage of new indications equal to or greater than 0.5 V in tubes tested with worn probe 76/177 = 42.9%

Percentage of new indications equal to or greater than 0.5 V in tubes tested with good probe 78/188 = 41.5%

All Steam Generators Combined Number of previous indications in EOC-13 1482 Worn Probe in EOC-12 Number of prev indications tested with worn probe in EOC-12 732 Number of these exceeding 2.0 V in EOC-13 1 Highest voltage indication of these in EOC-13 2.36V The indications found in the current inspection that were tested with a worn probe in the previous (EOC-12) inspection were

identified as seen in the tables above. Of the 732 indications

found in the current inspection that were tested with a worn

probe in the previous inspection, only one was 2 volts or

greater. Of the 750 indications found in the current inspection

that were tested with a good probe in the previous inspection, two were 2 volts or greater. Therefore, there is no significant

difference in the number of repairable indications for tubes

previously tested with a worn probe.

As required by the NRC letter to the Nuclear Energy Institute

dated February 9, 1996, the number of new indications detected in

the present inspection in tubes that were inspected with a worn

probe in the last inspection was also determined. Out of a total

of 365 new indications reported in the current inspection, 177 E1-7 were in tubes inspected with a worn probe during the last inspection. Steam Generator 4 has the highest number of

indications and the highest ratio of new indications that were

identified in tubes tested with a worn probe in EOC-12 to the

number of tubes tested with a worn probe in EOC-12 of 0.0407.

The ratio of new indications that were identified in tubes tested

with a good probe in EOC-12 to the number of tubes tested with a

good probe in EOC-12 for Steam Generator 4 is 0.0342. The

percentage of new indications equal to or greater than 0.5 V in

tubes tested with a worn probe in SG 4 is 38%, and the percentage

of new indications equal to or greater than 0.5 V in tubes tested

with good probe in SG 4 is 36%. The similarity of these ratios

and percentages indicate that there is no significant difference

in the rate of occurrence or magnitude of new indications found

in the EOC-13 inspection due to testing with a worn probe in the

EOC-12 inspection. Thus, the requirements specified for applying

the alternate probe wear criteria are met.

NRC Question 2 In Section 6.4 of Enclosure 1 to your August 15, 2005, letter, it was indicated that the EOC 14 voltage distribution (using both

the Cycle 12 and Cycle 13 growth rates) are shown in Table 6-2

and in Figures 6-1 through Figure 6-4. In reviewing the table

and figures only one voltage distribution was provided for each

steam generator.

Please clarify whether the tables and graphs provided were

determined using the Cycle 12 or Cycle 13 voltage growth rate

distribution.

In addition, Section 6.4 indicates that the voltage distributions

predicted using both growth rates are similar, however, the

predictions using the Cycle 13 growth rates were populated with

somewhat greater frequency in the lower voltages and with higher

tail-end voltages. Since the most limiting voltage growth rate

distribution is the one that results in the highest projected

probability of burst and leakage, discuss how it was determined

that the Cycle 12 growth rate distribution was the most limiting.

The staff notes that sometimes the higher tail end voltages can

result in more limiting probability of burst or leakage estimates (i.e., the largest voltage indication may have a significant

effect on the leakage and burst calculations depending on the

distribution of indications).

TVA Response The Cycle 12 growth rate clearly has a longer upper tail due to the inclusion of the one large voltage indication found at EOC-

12. Only the results using the Cycle 12 growth rate were included

in the EOC-13 90 Day Report (Westinghouse Report SG-SGDA-05-29, Rev.0) since this did produce the more conservative results.

The Table 6-2 and Figures 6-1 to 6-4 and Table 6-3 all are

results using the Cycle 12 growth rate.

E1-8 The reference to using both growth rates is an editorial error.

The statement "voltage distributions predicted using both growth

rates are similar, however, the predictions using the Cycle 13

growth rates were populated with somewhat greater frequency in

the lower voltages and with higher tail-end voltages" is also an

editorial error.

In order to demonstrate that the Cycle 12 growth rate results in the more conservative predictions the predictive results of using

both the Cycle 12 and Cycle 13 growth rates are presented here.

The analyses clearly indicate that the Cycle 12 growth rate

results are more conservative. Therefore, the results in the

report are correct.

E1-9 Operational Assessment: Tube Leak Rate and Burst Probabilities at EOC-14 1. Analysis Approach The BOC-14 voltage distributions are developed, within the Cyclesim3.1 program, from the measured EOC-13 distribution by

considering the probability of detection (POD) and the indications

that are removed from service. The EOC-14 voltage distribution is

developed considering the NDE uncertainties and voltage growth

during the cycle. Both the bounding Cycle 12 growth rate and the

bounding Cycle 13 growth rate were used in these projections in

order to assure the more conservative results. The latest burst

and leakage correlations, are used for the EOC-14 predictions. The

burst probabilities and leak rates are computed using the computed

EOC-14 voltage predictions to address the acceptance criteria at

the end of the cycle.

2. POD The POD used is the NRC accepted value of 0.6 for all voltages.

The beginning of Cycle 14 (BOC-14) voltage distributions are

shown in Table 1.

Table 1: BOC-14 Voltage Distributions Volts SG 1 SG 2 SG 3 SG 4 0.1 0 0 0 0 0.2 13.33 21.67 15 33.33 0.3 68.33 53.33 59 137.33 0.4 83.33 89 68.33 212.33 0.5 70 95.67 97.33 224 0.6 60 51.67 76.67 193.33 0.7 59 61.67 91.67 158.33 0.8 45 49 72.33 119 0.9 35 25.67 40 110 1 18.33 19 38.33 72.33 1.1 16.67 10.67 31.67 43.33 1.2 11.67 8.33 28.33 30 1.3 3.33 10 21.67 18.33 1.4 0 1.67 13.33 11.67 1.5 1.67 0 10 8.33 1.6 0 3.33 7.33 8.33 1.7 1.67 0 1.67 7.33 1.8 0 0 5 0 1.9 0 0 0 0 2 1.67 0.67 0 0 2.1 0 0 1.33 0 2.2 0 0 0 0 2.3 0 0 0 0 2.4 0 0 0.67 0 2.5 0 0 0 0 Total 489 501.3 679.7 1387.3 E1-10 3. Voltage Growth Rates for Cycle 14 The Cycle 12 and Cycle 13 bounding voltage growth rates, shown in Figure 3-15 and Figure 3-16 of EOC-13 90 Day Report (Westinghouse

Report SG-SGDA-05-29, Rev.0), indicate that the Cycle 12 growth

rate is the more conservative. To assure the more conservative

results, both growth rates were used in these projections.

4. Prediction of Voltage Distributions at EOC-14 The prediction of the EOC-14 voltage distributions is based on the BOC-14 indications and the composite growth rate. The length

of Cycle 14 is established at 545 effective full power days (EFPD). The EOC-14 predicted voltage distributions (using both

the Cycle 12 and Cycle 13 growth rates) are shown in Table 2 and

in Figure 1 through Figure 4. The voltage distributions

predicted using both growth rates are similar, with the

predictions using the Cycle 13 growth rates populated with

somewhat greater frequency in the lower voltages and with higher

tail-end voltages as seen in Table 2.

Table 2 EOC -14 Voltage Distributions Cycle 12 Growth Rate Cycle 13 Growth Rate EOC-14 Voltage Distributions EOC-14 Voltage Distributions Volts SG1 SG2 SG3 SG4 SG1 SG2 SG3 SG4 0.1 0.17 0.28 0.19 0.43 0.17 0.27 0.18 0.41 0.2 4.79 6.29 4.92 11.11 4.62 6.07 4.75 10.71 0.3 19.98 19.06 17.92 43.4 19.04 18.03 17.02 41.3 0.4 37.39 37.83 34.19 88.81 34.67 35.21 31.73 82.73 0.5 51.95 55.37 52.3 134.58 47.96 51.52 48.7 124.85 0.6 59.57 63.96 66.57 163.78 56.74 60.4 63.05 154.57 0.7 59.13 63.33 72.95 168.95 58.31 62.11 70.58 164.27 0.8 55.24 57.8 73.45 158.74 55.8 58.5 72.57 159.08 0.9 48.52 49.26 67.56 140.03 49.53 50.83 67.84 143.2 1 40.03 39.34 58.17 117.28 41.68 41.31 59.91 121.97 1.1 31.33 29.77 48.53 93.56 33.72 32.27 51.05 99.54 1.2 23.37 21.72 39.88 71.2 25.92 24.59 42.73 77.96 1.3 16.71 15.58 32.53 52.24 19.02 17.94 35.06 58.9 1.4 11.59 11.16 26.18 37.78 13.44 12.88 28.41 43.27 1.5 7.91 8.02 20.73 27.46 9.1 9.15 22.54 31.14 1.6 5.23 5.7 15.94 19.99 5.98 6.29 17.34 22.16 1.7 3.5 4.02 12.08 14.53 3.85 4.23 13 15.61 1.8 2.53 2.85 9 10.64 2.53 2.86 9.54 10.91 1.9 1.88 2.12 6.56 7.7 1.81 1.99 6.92 7.71 2 1.4 1.5 4.69 5.45 1.38 1.46 4.96 5.51 2.1 1.07 1.06 3.31 3.8 1.04 1.09 3.54 3.87 2.2 0.95 0.83 2.45 2.79 0.77 0.75 2.5 2.63 2.3 0.83 0.73 1.82 2.2 0.59 0.52 1.77 1.75 2.4 0.65 0.61 1.39 1.73 0.33 0.06 1.24 1.15 2.5 0.48 0.44 1.06 1.3 0 0.7 0.84 0.77 2.6 0.36 0.32 0.83 0.96 0.7 0 0.58 0.33 E1-11 Table 2 EOC -14 Voltage Distributions Cycle 12 Growth Rate Cycle 13 Growth Rate EOC-14 Voltage Distributions EOC-14 Voltage Distributions Volts SG1 SG2 SG3 SG4 SG1 SG2 SG3 SG4 2.7 0.27 0.24 0.63 0.7 0 0.3 0.31 0 2.8 0.19 0.17 0.45 0.52 0.3 0 0 0.7 2.9 0.13 0.11 0.32 0.37 0 0 0.7 0 3 0.08 0.07 0.24 0.25 0 0 0 0.3 3.1 0.06 0.05 0.17 0.17 0 0 0.3 0 3.2 0.03 0.03 0.13 0.11 0 0 0 0 3.3 0.02 0.02 0.09 0.07 489 501.35 679.66 1387.3 3.4 0.01 0.01 0.06 0.05 3.5 0.01 0.01 0.04 0.03 3.6 0 0.01 0.03 0.02 3.7 0 0 0.02 0.01 3.8 0 0 0.01 0.01 3.9 0 0 0.01 0 4 0 0 0 0 4.1 0 0 0 0 4.2 0 0 0 0 4.3 0 0 0 0 4.4 0 0 0 0 4.5 0 0 0 0 4.6 0 0 0 0 4.7 0 0 0 0 4.8 0 0 0 0 4.9 0 0 0 0 5 0 0 0 0 5.1 0 0 0 0 5.2 0 0 0 0 5.3 0 0 0 0 5.4 0 0 0 0 5.5 0 0 0 0 5.6 0 0 0 0 5.7 0 0 0 0 5.8 0 0 0 0 5.9 0 0 0 0 6 0 0 0 0 6.1 0 0 0 0 6.2 0 0 0 0 6.3 0 0 0 0 6.4 0 0 0 0 6.5 0 0 0 0 6.6 0 0 0 0 6.7 0 0 0 0 6.8 0 0 0 0 6.9 0 0 0 0 7 0 0 0 0 7.1 0 0 0 0 7.2 0 0 0 0 7.3 0 0 0 0 7.4 0 0 0 0 7.5 0 0 0 0 E1-12 Table 2 EOC -14 Voltage Distributions Cycle 12 Growth Rate Cycle 13 Growth Rate EOC-14 Voltage Distributions EOC-14 Voltage Distributions Volts SG1 SG2 SG3 SG4 SG1 SG2 SG3 SG4 7.6 0 0 0 0 7.7 0 0 0 0 7.8 0 0 0 0 7.9 0 0 0 0 8 0 0 0 0 8.1 0 0 0 0 8.2 0 0 0 0 8.3 0 0 0 0 8.4 0 0 0 0 8.5 0 0 0 0 8.6 0 0 0 0 8.7 0.05 0.07 0.06 0.13 8.8 0.21 0.18 0.18 0.44 8.9 0.26 0.28 0.24 0.67 9 0.09 0.13 0.29 0.71 9.1 0 0 0.28 0.63 9.2 0.7 0.7 0.2 0.52 9.3 0 0 0 0.41 9.4 0 0 0 0.07 9.5 0.3 0.3 0.7 0 9.6 0 0 0 0.7 9.7 0 0 0 0 9.8 0 0 0.3 0.3 9.9 0 0 0 0 489.00 501.35 679.66 1387.30 E1-13 0 10 20 30 40 50 60 70 800.10.30.50.70.91.11.31.51.71.9 2.12.32.52.72.93.13.33.53.73.98.78.99.19.39.59.79.9VoltsNumber of Indications .Using Cycle 12 Growth RateUsing Cycle 13 Growth Rate Figure 1: Predicted EOC-14 Voltage Distribution, SG1

E1-14 0 10 20 30 40 50 60 70 800.10.30.50.7 0.91.11.3 1.51.7 1.9 2.1 2.3 2.5 2.7 2.9 3.1 3.3 3.5 3.7 3.9 8.7 8.9 9.1 9.3 9.5 9.7 9.9VoltsNumber of Indications Using Cycle 12 Growth RateUsing Cycle 13 Growth Rate Figure 2: Predicted EOC-14 Voltage Distribution, SG2 E1-15 0 10 20 30 40 50 60 70 800.10.30.50.70.91.11.31.51.7 1.9 2.1 2.3 2.5 2.7 2.9 3.1 3.3 3.5 3.7 3.9 8.7 8.9 9.1 9.3 9.5 9.7 9.9VoltsNumber of Indications Using Cycle 12 Growth RateUsing Cycle 13 Growth Rate Figure 3: Predicted EOC-14 Vo ltage Distribution, SG 3 E1-16 0 20 40 60 80100 120140160180 0.1 0.30.50.70.9 1.1 1.31.51.7 1.92.12.3 2.52.72.9 3.1 3.3 3.5 3.7 3.9 8.7 8.9 9.1 9.3 9.5 9.7 9.9VoltsNumber of Indications Using Cycle 12 Growth RateUsing Cycle 13 Growth Rate Figure 4: Predicted EOC-14 Vo ltage Distribution, SG 4 E1-17 5. Prediction of Tube Leak Rates and Burst Probabilities at EOC-14 The Monte Carlo analysis results for predicted EOC-14 voltage distributions are shown in Tables 3A and 3B. One-quarter-million

Monte Carlo trials were performed for each steam generator in

this operational assessment. The leakage rate is the 95 th percentile evaluated at 95% confidence. The burst probability is

95% confidence based on the number of trials.

The predictions using the Cycle 12 growth rate distribution, Table 3A, results in significantly larger values for both the

burst probability and the bounding leak rate as would be expected

due to the longer tail of the voltage growth curve.

Table 3A: EOC-14 Predicted Results Using Cycle 12 Growth Rate SG Number of Monte Carlo

Trials Number of Indications Maximum Volts* Burst Probability 95% Confidence 95/95 SLB Leak Rate (gpm) 1 250,000 489.0 9.5 2.20 X 10

-3 0.519 2 250,000 501.3 9.5 2.47 X 10

-3 0.530 3 250,000 679.7 9.8 3.41 X 10

-3 0.874 4 250,000 1387.3 9.8 6.51 X 10

-3 1.47

  • Voltage where tail is accumulated to 0.3 indications Table 3B: EOC-14 Predicted Results Using Cycle 13 Growth Rate SG Number of Monte Carlo

Trials Number of Indications Maximum Volts* Burst Probability 95% Confidence 95/95 SLB Leak Rate (gpm) 1 250,000 489.0 2.8 6.79 X 10

-5 0.184 2 250,000 501.3 2.7 9.24 X 10

-5 0.182 3 250,000 679.7 3.1 1.90 X 10

-4 0.413 4 250,000 1387.3 3.0 1.86 X 10

-4 0.628

  • Voltage where tail is accumulated to 0.3 indications
6. Comparison with Acceptance Criteria All steam generators are below the burst acceptance criterion of 1.0 x 10-2 , and the Sequoyah Unit 2 leakage criterion of 3.7 gpm.