{{#Wiki_filter:Page 1 of 7 , Additions to the Program1.Pages 65 and 147.EECW check valves 2-67-872, 873, 876, and 877 to the , shutdown board room chillers.These check valves are being added to the 2 0 program to be tested in their respective safety positions.
{{#Wiki_filter:Page 1 of 7
Valves 2-67-873 and 876 have been added to relief request PV-14 to allow disassembly and inspection in lieu of inservice exercising, since no position indication exists for these valves.Pages 117 and 118.Scram discharge instrument volume drain isolation valves 85-37C, D, E, and F and 85-82, 82A, 83, and 83A.Fail-safe operation testing is being added for these valves.3~Page 39.Drywell compressor suction isolation valves 2-32-62 and 63.The program is being revised to reflect fail-safe testing performed on these valves.4.Pages 98, 99, 104, and 178.Residual heat removal (RHR)and core spray system valves 74-792, 802, 803, 804, and 75-606, 607, 609, and 610.Cold shutdown justification No.13.5.Pages 38 and 40.Control Air System containment isolation valves 2-32-2516 and 2521.These check valves have been added to the piping which supplies control air to the drywell.These check valves function as containment isolation valves and are being tested in accordance with Appendix J requirements.
, Additions to the Program
6.Pages 115, 164, and 175.Containment Atmosphere Dilution System'check valve 84-680.This new check valve performs as a containment isolation valve and is being added to the program and to Relief Request PV-30 and tested in accordance with Appendix J requirements in accordance with Cold Shutdown Justification No.9.7~Page 45a.Post-Accident Sampling System isolation valves FSV-43-40, 42, 50, 56, and 70.These new solenoid valves are being added to.the program.8.Page 34.Raw cooling water discharge valves 0-24-712A and B to the main control room chillers are now used to control EECW flow through the chillers.These valves are being added to the testing program.Deletions from the Program Page 58.EECW System check valves 1-67-556 and 2-67-556.These check valves have been replaced with manual butterfly valves which are provided for use during system maintenance.
: 1. Pages   65 and 147. EECW check valves 2-67-872, 873, 876, and 877 to the
Such valves do not perform a safety function and are exempt from testing by paragraph IWV-1200 of ASME Section XI.2.Pages 24 and 25.Diesel fuel transfer pump check valves 1-18-582A, B, C, and D;3-18-582A, B, C, and D;1-18-583A, B, C, and D;and 3-18-583A, B, C, and D.These check valves have been physically removed from the plant and the program is being updated to reflect this.,.9108160181 4, g1gp I" , 4 vp J Page 2 of 7 3.Pages 116 and 156.Control Rod Drive System valve 85-617.This valve is a manual valve which was mistakenly identified as a check valve.This ,valve is provided for use during system maintenance and has no testing requirements.
      , shutdown board room chillers. These check valves are being added to the program to be tested in their respective safety positions. Valves 2-67-873 and 876 have been added to relief request PV-14 to allow disassembly and inspection in lieu of inservice exercising, since no position indication exists for these valves.
This valve is being deleted from the program.Also, the reference to this valve is being deleted from PV-23.Pages 172,-89, and 91.Cold Shutdown Justification No.6 for the RHR System pressure isolation valves 74-53 and 74-67.It has been determined that the justification for cold shutdown testing status for these valves is no longer valid.The integrity of the upstream isolation valves is sufficient to prevent the exposure of lower pressure RHR piping to reactor coolant pressure during the quarterly testing of the pressure isolation valves.5.Page 33.RCW check valve 1-24-851.This check valve has been replaced with a manual valve.This valve'is provided for use during system maintenance and is therefore exempt from testing requirements by paragraph IWV-1200 of ASME Section XI.This valve is being deleted from the program.6.Page 34.RCW check valve 1-24-709.This check valve no longer performs a safety function and is being deleted from the program.The downstream manual valve 24-710 is relied upon to provide isolation between the RCW system and the EECW system.Plant operating instructions control the operation of the system separation valve.7.Page 59.EECW System discharge header check valve 2-67-598.This check valve has been replaced with a normally open manual isolation valve which does not perform a safety function.The new manual valve is provided for use during system maintenance and is therefore exempt from testing requirements by paragraph IWV-1200 of ASME Section XI.8.Pages 32 and 33.RCW System discharge check valves 1, 2, and 3-24-765., These check valves no longer perform a safety function of providing the discharge flow path for the EECW System.Hew seismically qualified discharge piping has been installed for the EECW System.These check valves are being deleted from the program.9~Page 63.EECW system check valve 1-67-785.This valve has been physically removed from the plant and is, therefore, being deleted from the program.10.Pages 75, 81, and 174.High-pressure coolant injection and reactor core isolation cooling system steam supply valves to the respective pump turbines, 71-2 and 3 and 73-2 and 3.These valves are listed as cold shutdown tested valves.It has been determined that the justification for the cold shutdown classification of these valves is too conservative.
20    Pages   117 and 118. Scram discharge instrument volume drain isolation valves   85-37C, D, E, and F and 85-82, 82A, 83, and 83A. Fail-safe operation testing is being added for these valves.
It is believed that these valves can be tested quarterly without risk of making the system inoperable.
3~   Page 39. Drywell compressor       suction isolation valves 2-32-62 and 63.
Therefore, Cold Shutdown Justification CSD-8 is being deleted from the program.
The program is being revised       to reflect fail-safe testing performed on these valves.
A I~g~'i/1 Page 3 of 711.Page 81.High-pressure coolant injection turbine steam drain level~control isolation valve 73-5.This valve is provided for system control only and is exempt from Section XI testing.This valve is being deleted'rom the testing program.12.Pages 70 and 71.EECW supply isolation valves to the unit 3 water chillers, 3-67-760, 763, 770, and 773, are now maintained in the open position and are used only for maintenance of the chiller packages.These valves are being deleted from the program.13.Pages 57 and 62.EECW supply isolation valves to the main control room chiller, 1-67-537 and 651, are now maintained in the open position and are used only for maintenance of the chiller package.These valves are being deleted from the program.Changes to the Program 1.Page 51.Primary to secondary containment vacuum relief valves 64-800 and 801.The program is being revised to reflect that these relief valves perform'safety functions in both the open and closed directions and are being tested accordingly.
: 4. Pages   98, 99, 104, and 178. Residual heat removal (RHR) and core spray system valves 74-792, 802, 803, 804, and 75-606, 607, 609, and 610. Cold shutdown justification No. 13.
2.Page 112.Spent fuel cooling water check valves 78-526 and 527.Due to f system modifications, these check valves no longer perform safety functions in the closed position.3.Page 112.RHR System to spent fuel pool valve 78-62.Motor-operated valve 78-62 has been modified to disable the motor-operator.
: 5. Pages   38 and 40. Control Air System containment isolation valves 2-32-2516 and 2521. These check valves have been added to the piping which supplies control air to the drywell. These check valves function as containment isolation valves and are being tested in accordance with Appendix J requirements.
This valve will be tested as a manual valve in the future and will not be str'oke timed.4.Page 78.RCIC discharge valve 71-39 is no longer a containment isolation valve.The leakage testing requirement for this valve is being deleted.5.Page 84.HPCI discharge valve 73-44 is no longer a containment isolation valve.The leakage testing requirement for this valve is being deleted.6.Pages 71 and 126.EECW control room chiller discharge isolation valves 3-67-769 and 779 are now used to control flow through the chiller and are no longer passive valves.These valves are being added to the active valve test listing and deleted from the passive valve listing.Corrections to the Program 1.Page 46.Add PV-32 in the Relief Request column for valves 63-514 and 516 to reflect their inclusion in this relief request.2.Pages 63 and 64.Add PV-33 in the Relief Request column for valves 1-67-787 and 789 to reflect their inclusion in this relief request.3.Page 101.Delete the reference to relief request PV-21 for valve 75-57 t to reflect the removal of this valve from the relief request.4.Page 91.Change the valve type designation for RHR check valve 74-68, which has mistakenly identified in the program as a gate valve.1310C 0 W)',~ll Cl Page 4 of 7 5.Pages 114 and 115.Correct the cold shutdown justification reference for'alves 84-600, 601, 602, 603, and 617 from CSD-10 to CSD-9.6.Pages 116 and 156.Delete relief request reference PV-25 from valves 85-39A and 39B.7.Page 26.Valves 1-23-56 and 2-23-56 were deleted from the program in the program revision dated June 22, 1989.The enclosed page 26 reflects this deletion.8.Page 82.Valves 73-8 and 19 were deleted from the program in the program revision dated June 22, 1989.The enclosed page 82 reflects this deletion.The fail-safe testing performed on valve 73-18 is also reflected on this new page 82.9.Page 85.The safety-related position of valve 73-609 was corrected from'open/closed'o
: 6. Pages   115, 164, and 175. Containment Atmosphere Dilution System 'check valve 84-680. This new check valve performs as a containment isolation valve and is being added to the program and to Relief Request PV-30 and tested in accordance with Appendix J requirements in accordance with Cold Shutdown   Justification   No. 9.
'closed'nly, in the June 22, 1989 program revision.This new page 85 reflects this change.10.Page 137.Correct the page reference from page 11 to page 12.Page 116.program i positions 12.Page 112.reference 527'ontrol Rod Drive cooling water inlet check valve 85-597.The s being changed to reflect the correct normal and safety for this valve.PV-22 was deleted in the June 22, 1989 program revision.The-'o this relief request was not deleted for valves 78-526 and 1310C bi 4(t Page 5 of 7 Revision of Relief Request PV-6 Relief Request PV-6 deals with the testing of the main steam safety relief valves (SRVs)(1-5, 19, 22, 30, 31, 34).The plant staff has determined that with presently installed instrumentation, no means exists to verify that the main steam SRVs each stroke within two seconds as stated under alternative testing in the current relief request.The only existing position indicating instrumentation consists of a series of LEDs on the main control room valve acoustic monitoring panel.The acoustic monitoring LEDs indicate noise levels downstream of the SRVs and are very sensitive to background noise as well as steam flow through the SRVs.Since no means exists to measure the stroke time for the main steam SRVs, the alternate testing description i.n the request for relief is being revised to remove the less than two second stroke time testing.The technical specification reference which requires the manual exercising of each SRV each operating cycle is being corrected from 4.5.G to 4.6.D.0902C (I
7 ~   Page 45a. Post-Accident Sampling System isolation valves FSV-43-40, 42, 50, 56, and 70. These new solenoid valves are being added to. the program.
1 Jj Page 6 of 7R li f R N mber PV-6 Page 139 Page 1 of 1 System: Main Steam Drawing: Valves: 47W801-1 1-5, 1-19, 1-22, 1-30, 1-31, 1-34 Category', C Class: Function: ADS Valve, Code Safety/Relief Valve Impractical Test Requirement:
: 8. Page 34. Raw cooling water discharge valves 0-24-712A and B to the main control   room chillers are now used to control EECW flow through the chillers. These valves are being added to the testing program.
Exercise valve once every three months.Basis for Relief: The six safety relief valves assigned to the ADS system'perform an essential safety function when operated by the pneumatic actuator with gas supplied through the ADS solenoid valves.Operation of'these valves is not practical during power operations because this action will vent main steam to the suppression pool, inducing a transient condition and increasing the potentiality for an open failure of a safety relief valve..Also, no stroke timing is practical as these are pneumatic'ssisted SRVs.Since"position indication" of the SRVs is provided by acoustic monitors attached to the valve discharge piping, exercising during cold shutdown cannot be accomplished because of lack of steam flow (and attendant noise).Alternative Testing: The ADS valves will be exercised once each operating cycle in accordance with Technical Specification 4.6.D which provides manual opening of each ADS valve and observing indication of steam flow through each valve.0902C
Deletions from the Program Page 58. EECW System check valves 1-67-556 and 2-67-556. These check valves have   been replaced with manual butterfly valves which are provided for use   during system maintenance. Such valves do not perform a safety function and are exempt from testing by paragraph IWV-1200 of ASME Section XI.
: 2. Pages 24 and 25. Diesel fuel transfer pump check valves 1-18-582A, B, C, and D; 3-18-582A, B, C, and D; 1-18-583A, B, C, and D; and 3-18-583A, B, C, and D. These check valves have been physically removed from the plant and the program is being updated to reflect this.
              ,. 9108160181


Page 7 of 7l Sh wn ifi ion No 1 System: Residual Heat Removal (74)Core Spray (75)Drawing: 47W811-1 47W814-1 Valves: 74 792 802~803 i 804 75-606, 607, 609, 610 Category: Class: Function: Provides isolation between the safety system and the non-safety system which is used to fill the safety system and maintain it filled while it is in the standby status.Justification:
4, g1 gp I"
The valve'lignments which is necessary to provide positive indication of the full, or partial exercising of these check valves requires that the safety system be declared inoperable during the testing procedure.
            ,
Normal testing of these valves during unit operation would require placing the plant in limiting condition operation (LCO)on a quarterly basis for the testing of each valve.As required by paragraph IWV-3522 of the Code, these valves will be full stroke exercised on a cold shutdown basis.0902C
4 vp J
~4 I ENCLOSURE-2 (48 pages)


System: Fuel Oil (18)TENNESSEE VA THORITY Browns Ferry r Plant Units 1, , and 3 Inservice Testing Program Drawing No.47M84D-1 Page 1 of 2 Val ve Number Function ASNE Cl ass Drawing Coordtn.Sect.XI Valve Category Size (in.)Val ve Type Actuator Normal Type Positn.Safety-Related Posi tn.Testing Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)Page 24
Page 2  of 7
: 3. Pages 116 and 156. Control Rod Drive System valve 85-617. This valve              is a manual valve which was mistakenly identified as a check valve. This
      ,valve is provided for use during system maintenance and has no testing requirements. This valve is being deleted from the program.              Also, the reference to this valve is being deleted from PV-23.
Pages 172, -89, and 91. Cold Shutdown Justification No. 6 for the RHR System pressure isolation valves 74-53 and 74-67.            It has been determined that the justification for cold shutdown testing status for these valves is no longer valid. The integrity of the upstream isolation valves is sufficient to prevent the exposure of lower pressure RHR piping to reactor coolant pressure during the quarterly testing of the pressure isolation valves.
: 5. Page 33. RCW check valve 1-24-851.          This check valve has been replaced with  a manual valve. This valve'is provided for use during system maintenance and is therefore exempt from testing requirements by paragraph IWV-1200 of ASME Section XI. This valve is being deleted from the program.
: 6. Page 34. RCW  check valve 1-24-709.        This check valve no longer performs a safety  function  and  is being deleted from the program. The downstream manual valve 24-710    is relied upon to provide isolation between the RCW system and the EECW    system. Plant operating instructions control the operation of the system separation        valve.
: 7. Page 59. EECW  System discharge header check valve 2-67-598. This check valve has been replaced with a normally open manual isolation valve which does not perform a safety function. The new manual valve is provided for use during system maintenance and is therefore exempt from testing requirements by paragraph IWV-1200 of ASME Section XI.
: 8. Pages 32 and 33. RCW System discharge check valves 1, 2, and 3-24-765.
    ,
These check valves no longer perform a safety function of providing the discharge flow path for the EECW System. Hew seismically qualified discharge piping has been installed for the EECW System. These check valves are being deleted from the program.
9 ~    Page 63. EECW  system check valve 1-67-785.          This valve has been physically  removed from the      plant  and  is, therefore,    being deleted from the program.
: 10. Pages  75, 81, and 174. High-pressure coolant injection and reactor core isolation cooling    system steam supply valves to the respective pump turbines, 71-2 and 3 and 73-2 and 3. These valves are listed as cold shutdown tested valves.       It  has been determined that the justification for the cold shutdown      classification    of these valves is too conservative. It  is  believed  that  these  valves can be tested quarterly without risk of making      the system  inoperable. Therefore, Cold Shutdown Justification  CSD-8  is  being  deleted  from  the  program.


System: Fuel Oil (18)TENNESSEE VA UTHORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program Drawing No.47M840-1 Page 2 of 2 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size (in.)Valve Type Actuator Normal Type Positn.Saf ety-Related Positn.Testing Req'd.Relief Req./Cold Shutdn.Testing Justifictn.
I A
Performed (if applic.)(if diffrnt.)Page 25
    ~ g~ 'i
/ 1


System: Residual Heat Removal Service Water (23)TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, 3 Inservice Testing Program Drawing No.47W858-1 Page 1 of 6 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category.Size (in.)Valve.Type Actuator Normal Type Positn.Safety-Related Positn.Testing'eq'd.Relief Req./Cold Shutdn.3ustifictn.(if applic.)Testing Performed (if diffrnt.)23-34 23-40 23-46, 23-52 RHR Htx A Cooling Wtr Outlet RHR Htx C Cooling Wtr Outlet RHR Htx B Cooling Wtr Outlet RHR Htx D Cooling Wtr Outlet C-1 A-1 12 12 12 12 GL GL GL=GL TH TH TH TH Q ST Q ST Q ST Q ST PV-12 PV-12 PV-12 PV-12 a~Page 26 ir'I t System: Raw Cooling Water (24)TENNESSEE VAL THORITY Browns Ferry Plant Units 1, 3 Inservice Testing Program 0 Drawing No.47W844-2 Page 1 of 2 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size (in.)Valve Actuator Normal Type Type Positn.Safety-Related Positn.Testing Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)1-24-707 2-24-707 3-24-707 1-24-730 2-24-730 3-24-730 Supply to EECW Check Supply to EECW Check Supply to EEOf Check Supply to EECW Check Supply to EECW Check Supply to EECW Check B-1 C-7 C-9 3 B-6 B-8 6-10/11 CK SELF.CK SELF CK SELF CK SELF CK SELF CK SELF CV CV a CV CV CV Page 32 0
Page 3 of  7
System: Raw Cooling Water (24)TENNESSEE VA THORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program Drawing No.47W844-2 Page 2 of 2 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI'alve Category Size (in.)Valve Actuator Normal Type Type Positn.Safety-Related Positn.Testing Req'd..Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)3-24-796 3-24-798 HVAC RH A Supply Check HVAC RH A Supply Check D-12 0-12 CK SELF CK SELF CV CV PV-14 PV>14 RR RR Page 33
: 11. Page 81. High-pressure coolant injection turbine steam drain level
      ~
control isolation valve 73-5. This valve is provided for system control only and is exempt from Section XI testing. This valve is being deleted
      'rom the testing program.
: 12. Pages  70 and 71. EECW supply isolation valves to the unit 3 water chillers,   3-67-760, 763, 770, and 773, are now maintained in the open position and are used only for maintenance of the chiller packages.
These valves are being deleted from the program.
: 13. Pages  57 and 62. EECW supply isolation valves to the main control room chiller,    1-67-537 and 651, are now maintained in the open position and are used only for maintenance of the chiller package. These valves are being deleted from the program.
Changes    to the Program
: 1. Page  51. Primary to secondary containment vacuum relief valves 64-800 and 801. The program is being revised to reflect that these relief valves perform 'safety functions in both the open and closed directions and are being tested accordingly.
: 2. Page 112. Spent  fuel cooling water check valves 78-526 and 527.         Due  to f system modifications, these check valves no longer perform safety functions in the closed position.
: 3. Page 112. RHR System to spent fuel pool valve 78-62.        Motor-operated valve  78-62  has  been  modified to  disable  the  motor-operator. This valve will be tested as a manual valve in the future and will not be str'oke timed.
: 4. Page 78. RCIC  discharge valve 71-39 is no longer a containment isolation valve. The leakage    testing requirement for this valve is being deleted.
: 5. Page 84. HPCI discharge valve 73-44 is no longer a containment        isolation valve. The leakage testing requirement for this valve is being        deleted.
: 6. Pages  71 and 126. EECW control room chiller discharge isolation valves 3-67-769 and 779 are now used to control flow through the chiller and are no longer passive valves.      These valves are being added to the active valve test listing and deleted from the passive valve listing.
Corrections to the Program
: 1. Page 46. Add PV-32 in the Relief Request        column  for valves  63-514 and 516 to reflect their inclusion in this        relief  request.
: 2. Pages  63 and 64. Add PV-33  in the Relief Request column for valves 1-67-787 and 789 to reflect      their inclusion in this relief request.
t  3.
4.
1310C Page 101.
to reflect Page 91.
Delete the reference to relief request PV-21 for valve 75-57 the removal of this valve from the relief request.
Change  the valve type designation for RHR check valve 74-68, which has mistakenly identified in the program as a gate valve.


System: Raw Cooling Mater (24)TENNESSEE VA UTHORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program Drawing No.47W859-1 Page 1 of 1 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size (in.)Valve Actuator Normal Type Type Positn.Safety-Related Positn.Testing Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Per f ormed (if diffrnt.)0-24-712A 0-24-7128 Wtr Chiller A discharge isolation Wtr Chiller B discharge isolation NNCC NNCC A-1 A-1 0/C 0/C 0/C 0/C Page 34
0 W) '
  ~
,
ll Cl


System: Control Air (32)TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, 3 Inservice Testing Program Drawing No.47W2847-5 Page 1 of 1 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size (in.)Valve Type Actuator Normal Type Positn.Safety-Related Positn.Testing Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)2-32-336 2-32-2521 Outbd DW Check DW Check NNCC 0-7 AC AC 1/2 CK CK SELF SELF 0/C 0/C CV LT CV LT PV-24 I PV-24 RR LT RR LT Page 38
Page 4  of  7
: 5. Pages  114 and 115. Correct the cold shutdown    justification  reference for
    'alves    84-600, 601, 602, 603, and 617 from CSD-10        to CSD-9.
: 6. Pages  116 and 156. Delete  relief  request reference PV-25 from valves 85-39A and 39B.
: 7. Page 26. Valves 1-23-56 and 2-23-56 were deleted from the program in the program revision dated      June 22, 1989. The enclosed page 26 reflects this deletion.
: 8. Page  82. Valves 73-8 and 19 were deleted from the program        in the  program revision dated June 22, 1989. The enclosed        page 82 reflects this deletion. The fail-safe testing performed        on valve 73-18 is also reflected on this new page 82.
: 9. Page 85. The  safety-related position of valve 73-609      was corrected from
      'open/closed'o      'closed'nly, in      the June 22, 1989 program revision.
This  new page 85    reflects this  change.
: 10. Page 137. Correct the page reference from page      11  to page 12.
          'ontrol Page 116.
program  is Rod Drive being changed positions for this valve.
cooling to reflect water inlet check valve 85-597.
the correct normal and safety The
: 12. Page 112. PV-22 was  deleted in the June 22, 1989 program revision. The this relief request was not deleted for valves 78-526 and
                                                                                            -'o reference 527 1310C


System: Control Air (32)TENNESSEE VALL THORITY Browns Ferry Plant Units 1, 3 Inservice Testing Program Drawing No.47W2847-8 Page 1 of 1 Val ve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size Valve Actuator (in.)Type Type Normal Posi tn.Safety-Related Testing Positn.Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)2-32-62 2-32-63 DW Cmpsr Suction Isol DW Cmpsr Suction Isol B-9 B-9 PL PL AO AO Q ST LT FS Q ST LT FS Page 39
bi 4(t


System: Control Air (32)TENNESSEE VAL THORITY Drowns Ferry r Plant Units 1, d 3 Inservice Testing Program Drawing No.47W2847-9 Page 1 of 1 Valve Number 2-32-2163 2-32-2516 Function Inbd DW Check Inbd DW Check ASHE Class NNCC Drawing Coordtn.C-2 C-3 Sect.XI Valve Category AC AC Size Valve (in.)Type 3/4 CK 3/4 CK Actuator Type SELF SELF Normal Positn.0/C 0/C Safety-Related Testing Posi tn.Req'd.CV LT CV LT Relief Req./Cold Shutdn.3ustifictn.(if applic.)PV-24 PV-24 Testing Performed (if diffrnt.)RR LT RR LT Page 40
Page 5 of 7 Revision of Relief Request PV-6 Relief Request  PV-6 deals with the testing of the main steam safety relief valves (SRVs) (1-5, 19, 22, 30, 31, 34). The plant staff has determined that with presently installed instrumentation, no means exists to verify that the main steam SRVs each stroke within two seconds as stated under alternative testing in the current relief request. The only existing position indicating instrumentation consists of a series of LEDs on the main control room valve acoustic monitoring panel. The acoustic monitoring LEDs indicate noise levels downstream of the SRVs and are very sensitive to background noise as well as steam flow through the SRVs.
Since no means exists to measure the stroke time for the main steam SRVs, the alternate testing description i.n the request for relief is being revised to remove the less than two second stroke time testing. The technical specification reference which requires the manual exercising of each SRV each operating cycle is being corrected from 4.5.G to 4.6.D.
0902C


System: Sampling and Water ()vali ty TENNESSEE VAL THORITY Browns Ferry r Plant, Units 1, 3 Inservice Testing ProgramDrawing No.47E867-3 Page 1 of 1 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size Valve Actuator (in.)Type Type Normal Positn.Relief Req./Safety-Cold Shutdn.Related Testing 3ustifictn.
(
Positn.Req'd..(if applic.)Testing Performed (if diffrnt.)FSV-43-40 FSV-43-42 FSV-43-50 FSV-43-56 FSV-43-70 Primary Containment Isolation Primary Containment Isolation Primary Containment Isolation Primary Containment Isolation Primary Containment Isolation F-2 F-2 G-2 G-2 B-2 1/2 GL 1/2 GL 1/2 GL 1/2 GL 1/2" GL S LT LT LT LT LT Page 45a
I


System:-Standby Liquid Control,(63)
1 Jj Page  6 of 7 Page  139 R  li f  R        N mber PV-6            Page 1 of 1 System:            Main Steam Drawing:            47W801-1 Valves:            1-5, 1-19, 1-22, 1-30, 1-31, 1-34 Category',              C Class:
TENNESSEE VA THORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program Drawing No.47W854-1 Page 1 of 1 Valve Number.Function ASME Class Drawing Coordtn.Sect.XI Valve Category Size Valve (in.)Type Actuator Type Normal Posi tn.Safety-Related Testing Posi tn.Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Perf ormed (if diffrnt.)63-BA 63-88 63-512 63-513 63-514 63-516 63-525 63-526 A Inj ec ti on 8 In j ec ti on A Pump Relief B Pump Relief A Pump Disch Check B Pump Disch Check Cont Isol Check Cont Isol Check C-3 D-3 D-5 0-6 D-6 D-2 E-2 AC AC l-l/2 GA 1-1/2 GA RV RV 1-1/2 CK 1-1/2 CK 1-1/2 CK 1-1/2 CK SELF SELF SELF SELF SELF SELF 0/C 0/C 0/C 0/C DT DT RV RV CV CV CV LT CV LT PV-32 PV-32 PV-9 PV-9 RR/PV-32 RR/PV-32 RR LT RR LT Page 46 Cl TENNESSEE VAL UTHORITY Browns Ferry r Plant Units 1, 3 Inservice Testing Program System: Reactor Building Heating, Ventilation, and Air Conditioning (64)Drawing No.47W865-1 Page 3 of 3 Valve Number Function ASHE Cl ass Drawing Coordtn.Sect.XI Valve Category Size Valve Actuator (in.)Type Type Normal Positn.Safety-Related Testing Positn.Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)64-32 64-33 64-34 PSC Exhaust Inbd Isol PSC Exhaust Outbd Isol PSC SBGT Inbd Isol G-9 F-9 G-10 18 BF 18 BF 2 BF AO AO AO Q ST LT Q ST LT Q ST LT 64-800 64-801 PSC Vac Rel i e f Ck PSC Vac Relief Ck G-3 G-3 20 CK SELF 20 CK SELF 0/C 0/C CV LT CV LT Page 51 0~e~r%PI System: Emergency Equipment Cooling Water (67)TENNESSEE VAL'HORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program Drawing No.47W859-1 Page 5 of 13 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size (in.)Valve Type Actuator Normal Type Positn.Safety-Related Positn.Testing Req'd.Rel i e f Req./Cold Shutdn.3ustifictn.(if applic.)Testing Performed (if diffrnt.)0-67-521 0-67-522 0-67-528 0-67-529 0-67-538 0-67-539 1B OG Cooler S Hdr Check 18 DG Cooler S Hdr Check lA OG Cooler S Hdr Check lA OG Cooler S Hdr Check Control Rm Chiller S Hdr Supply Check Control Rm Chiller S Hdr Supply Check D-1 D-1 C-1 C-1 8-2 8-2 C CK CK CK.CK CK CK SELF 0/C SELF 0/C SELF 0/C SELF 0/C SELF SELF 0/C 0/C 0/C 0/C 0/C 0/C CV CV CV CV CV PV-14 PV-14 PV-14 PV-14 PV-33 PV-33 RR RR RR RR~RR/PV-3 RR/PV-3 Page 57
Function:          ADS  Valve, Code Safety/Relief Valve Impractical Test Requirement:        Exercise valve once every three months.
Basis  for Relief: The six safety relief valves assigned to the ADS system
                        'perform an essential safety function when operated by the pneumatic actuator with gas supplied through the ADS solenoid valves. Operation of'these valves is not practical during power operations because this action will vent main steam to the suppression pool, inducing a transient condition and increasing the potentiality for an open failure of a safety relief valve.. Also, no stroke timing is practical as these are pneumatic'ssisted SRVs.
Since "position indication" of the SRVs is provided by acoustic monitors attached to the valve discharge piping, exercising during cold shutdown cannot be accomplished because of lack of steam flow (and attendant noise).
Alternative Testing:            The ADS    valves  will be  exercised once each operating cycle in accordance with Technical Specification 4.6.D which provides manual opening of each ADS valve and observing indication of steam flow through each valve.
0902C


System: Emergency Equipment Cooling Water (67)TENNESSEE VA THORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program Drawing No.47W859-1 Page 6 of 13 Val ve Number Functi on ASHE Class Drawing Coordtn.Sect.XI Valve Category Size (in.)Valve Type Actuator Normal Type Positn.Safety-Rel ated Posi tn.Testing Req'd.Relief Req./Cold Shutdn.Testing Justifictn.'erformed (if applic.)(if diffrnt.)67-541 67-542 67-558 Loop I Supply Loop I Supply CS Rm Cooler S Hdr Check RHR Rm Cooler S Hdr Check Loop I CS Rm Cooler S Hdr Supply Check C-3 C-3 2-1/2 2-1/2 CK CK CK SELF 0/C SELF 0/C SELF 0/C 0/C 0/C 0/C CV CV CV PV-14 PV-14 PV-14 RR RR RR67-559 Loop I RHR Rm Cooler S Hdr Supply Check CK SELF 0/C'/C CV PV-14 RR Page 58 System: Emergency Equipment Cooling Water (67)TENNESSEE VAL THORITY Drowns Ferry r Plant Units 1, d 3 Inservice Testing Program Drawing No.47W859-1 Page 7 of 13 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size (in.)Valve Actuator Normal Type Type Positn.Safety-Related Positn.Testing Req'd..Relief Req./Cold Shutdn.3ustifictn.(if applic.)Testing Performed (if diffrnt.)67-584 67-585 67-600 67-601 0-67-619 Loop II CS Rm Cooler S Hdr Supply Check Loop II CS Rm Cooler S Hdr Supply Check Loop II RHR Rm Cooler S Hdr Supply Check Loop II RHR Rm Cooler S Hdr Supply Check S Hdr Check F-5 F-5 G-12 2-1/2 2-1/2 18 CK SELF CK SELF 0/C 0/C CK SELF CK SELF 0/C 0/C CK SELF 0/C 0/C 0/C 0/C 0/C 0/C CV CV CV CV CV PV-14 PV-14 PV.-14 PV-14 PV-14 RR RR~RR RR Page 59
Page 7 of 7 l  Sh    wn    ifi ion No  1 System:       Residual Heat Removal (74)
Core Spray (75)
Drawing:      47W811-1 47W814-1 Valves:        74 792 802 803 i 804
                            ~
75-606, 607, 609, 610 Category:
Class:
Function:      Provides  isolation between the safety system and the non-safety system which is used to it fill the safety system  and maintain  it  filled while is in the standby status.
Justification: The valve'lignments which is necessary to provide positive indication of the full, or partial exercising of these check valves requires that the safety system be declared inoperable during the testing procedure. Normal testing of these valves during unit operation would require placing the plant in limiting condition operation (LCO) on a quarterly basis for the testing of each valve. As required by paragraph IWV-3522 of the Code, these valves will be full stroke exercised on a cold shutdown basis.
0902C
 
~4 I ENCLOSURE-2 (48 pages)
 
TENNESSEE VA         THORITY Browns Ferry         r Plant Units 1,   , and 3 Inservice Testing Program System: Fuel  Oil (18)                                                                        Drawing No. 47M84D-1 Page 1 of 2 Relief Req./
Sect. XI                                    Safety-            Cold Shutdn. Testing Val ve                        ASNE  Drawing  Valve      Size    Val ve Actuator Normal  Related  Testing  Justifictn. Performed Number              Function  Cl ass Coordtn. Category    (in.)    Type  Type    Positn. Posi tn. Req'd.  (if applic.)  (if diffrnt.)
Page 24
 
TENNESSEE VA        UTHORITY Browns Ferry        r Plant Units 1,      d 3 Inservice Testing Program System: Fuel  Oil (18)                                                                      Drawing No. 47M840-1 Page 2  of 2 Relief Req./
Sect. XI                                    Saf ety-          Cold Shutdn. Testing Valve                        ASHE  Drawing  Valve      Size    Valve  Actuator Normal  Related  Testing  Justifictn. Performed Number             Function  Class Coordtn. Category    (in.)    Type  Type    Positn. Positn. Req'd.  (if applic.)  (if diffrnt.)
Page 25
 
TENNESSEE VAL        THORITY Browns  Ferry        r Plant Units 1,          3 Inservice Testing Program System:  Residual Heat Removal Service Water (23)                                                          Drawing No. 47W858-1 Page  1  of 6 Relief Req./
Sect. XI                                    Safety-          Cold Shutdn. Testing Valve                                      ASHE   Drawing  Valve      Size    Valve. Actuator Normal  Related Testing  3ustifictn. Performed Number                Function              Class Coordtn. Category.    (in.)    Type  Type    Positn. Positn. 'eq'd.    (if applic.)  (if diffrnt.)
23-34      RHR Htx A Cooling Wtr Outlet            C-1                    12    GL                      TH      Q        PV-12 ST 23-40      RHR Htx C  Cooling Wtr Outlet            A-1                    12    GL                      TH      Q        PV-12 ST 23-46,      RHR Htx B  Cooling Wtr Outlet                                    12    GL=                    TH      Q ST PV-12            a
                                                                                                                                                        ~
23-52      RHR Htx D  Cooling Wtr Outlet                                    12    GL                      TH      Q        PV-12 ST Page 26
 
ir
'I t
 
TENNESSEE VAL Browns Ferry Units 1, THORITY 3
Plant Inservice Testing Program 0
System:  Raw  Cooling Water (24)                                                                    Drawing No. 47W844-2 Page  1 of 2 Relief Req./
Sect. XI                                  Safety-          Cold Shutdn. Testing Valve                                      ASHE  Drawing   Valve      Size    Valve Actuator Normal  Related Testing  Justifictn. Performed Number                  Function          Class Coordtn. Category    (in.)    Type  Type  Positn. Positn. Req'd.  (if applic.)  (if diffrnt.)
1-24-707      Supply to  EECW  Check              B-1                          CK      SELF                    CV 2-24-707      Supply to  EECW  Check              C-7                        . CK      SELF                    CV a
3-24-707      Supply to EEOf Check                C-9                          CK      SELF                    CV 1-24-730      Supply to  EECW  Check        3    B-6                          CK      SELF                    CV 2-24-730      Supply to  EECW  Check              B-8                          CK      SELF                    CV 3-24-730      Supply to  EECW  Check              6-10/11                      CK      SELF Page 32
 
0 TENNESSEE VA            THORITY Browns Ferry            r Plant Units 1,          d 3 Inservice Testing Program System:  Raw Cooling Water (24)                                                                        Drawing No. 47W844-2 Page 2  of 2 Relief Req./
Sect. XI                                       Safety-          Cold Shutdn. Testing Valve                                     ASHE  Drawing            'alve Size    Valve Actuator Normal  Related Testing  Justifictn. Performed Number                  Function          Class Coordtn. Category       (in.)    Type  Type  Positn. Positn. Req'd..  (if applic.)  (if diffrnt.)
3-24-796      HVAC RH A  Supply Check            D-12                              CK      SELF                    CV        PV-14            RR 3-24-798      HVAC RH A  Supply Check            0-12                              CK      SELF                    CV        PV>14            RR Page 33
 
TENNESSEE VA        UTHORITY Browns Ferry        r Plant Units 1,      d 3 Inservice Testing Program System:  Raw  Cooling Mater (24)                                                                    Drawing No. 47W859-1 Page 1 of  1 Relief Req./
Sect. XI                                  Safety-          Cold Shutdn. Testing Valve                                      ASHE  Drawing  Valve      Size   Valve Actuator Normal  Related Testing  Justifictn.      f Per ormed Number                  Function          Class Coordtn. Category    (in.)   Type  Type  Positn. Positn. Req'd.  (if applic.)  (if diffrnt.)
0-24-712A      Wtr Chiller  A discharge isolation                    NNCC  A-1                                          0/C    0/C 0-24-7128      Wtr Chiller  B discharge isolation                    NNCC  A-1                                          0/C    0/C Page 34
 
TENNESSEE VAL        THORITY Browns Ferry          r Plant Units 1,        3 Inservice Testing Program System:    Control Air (32)                                                                    Drawing No. 47W2847-5  Page  1  of 1 Relief Req./
Sect. XI                                    Safety-          Cold Shutdn.      Testing Valve                                ASHE  Drawing  Valve      Size    Valve Actuator Normal  Related Testing  Justifictn.      Performed Number                  Function    Class Coordtn. Category    (in.)    Type   Type  Positn. Positn. Req'd.  (if applic.)  (if diffrnt.)
2-32-336      Outbd  DW Check                0-7        AC                CK      SELF  0/C              CV        PV-24              RR LT                          LT I
2-32-2521      DW Check              NNCC              AC        1/2      CK      SELF  0/C              CV        PV-24              RR LT                          LT Page 38
 
TENNESSEE VALL      THORITY Browns Ferry          Plant Units 1,        3 Inservice Testing Program System:  Control Air (32)                                                                      Drawing No. 47W2847-8  Page  1  of 1 Relief Req./
Sect. XI                                    Safety-          Cold Shutdn.      Testing Val ve                              ASHE  Drawing  Valve      Size    Valve  Actuator Normal   Related Testing  Justifictn.      Performed Number                Function      Class Coordtn. Category    (in.)    Type  Type   Posi tn. Positn. Req'd.  (if applic.)  (if diffrnt.)
2-32-62      DW Cmpsr Suction  Isol        B-9                          PL      AO                        Q ST LT FS 2-32-63      DW Cmpsr Suction  Isol        B-9                          PL      AO                        Q ST LT FS Page 39
 
TENNESSEE VAL        THORITY Drowns Ferry          r Plant Units 1,      d 3 Inservice Testing Program System:  Control  Air (32)                                                                    Drawing No. 47W2847-9  Page  1  of 1 Relief Req./
Sect. XI                                    Safety-           Cold Shutdn.      Testing Valve                                ASHE  Drawing  Valve      Size    Valve Actuator Normal  Related  Testing  3ustifictn.      Performed Number                  Function      Class Coordtn. Category    (in.)    Type  Type  Positn. Posi tn. Req'd.  (if applic.)  (if diffrnt.)
2-32-2163      Inbd DW Check                  C-2        AC        3/4      CK      SELF  0/C              CV        PV-24              RR LT                          LT 2-32-2516      Inbd DW Check          NNCC  C-3        AC        3/4      CK      SELF  0/C              CV        PV-24              RR LT                          LT Page 40
 
TENNESSEE VAL        THORITY Browns  Ferry        r Plant, Units 1,          3 Inservice Testing Program System:  Sampling and Water ()vali ty                                                                      Drawing No. 47E867-3 Page  1 of 1 Relief Req./
Sect. XI                                    Safety-          Cold Shutdn. Testing Valve                                            ASHE  Drawing  Valve      Size    Valve Actuator Normal  Related Testing  3ustifictn. Performed Number                  Function                Class Coordtn. Category    (in.)    Type  Type  Positn. Positn. Req'd..  (if applic.)  (if diffrnt.)
FSV-43-40      Primary Containment Isolation            F-2                  1/2      GL                              LT FSV-43-42      Primary Containment Isolation            F-2                  1/2      GL                              LT FSV-43-50      Primary Containment Isolation            G-2                  1/2      GL                              LT FSV-43-56      Primary Containment Isolation            G-2                  1/2      GL                              LT FSV-43-70      Primary Containment Isolation            B-2                  1/2  "  GL      S                      LT Page 45a
 
TENNESSEE VA        THORITY Browns Ferry        r Plant Units 1,      d 3 Inservice Testing Program System: - Standby Liquid Control,(63)                                                                      Drawing No. 47W854-1 Page  1  of 1 Relief Req./
Sect. XI                                    Safety-            Cold Shutdn. Testing Valve                                          ASME  Drawing  Valve      Size    Valve Actuator Normal  Related  Testing   Justifictn. Perf ormed Number .                  Function            Class Coordtn. Category    (in.)    Type  Type  Posi tn. Posi tn. Req'd.   (if applic.)  (if diffrnt.)
63-BA        A Injec ti on                            C-3                l-l/2    GA                                DT 63-88        8 In j ec ti on                          D-3                1-1/2    GA                                DT 63-512        A Pump    Relief                        D-5                          RV      SELF                      RV 63-513        B Pump    Relief                        0-6                          RV      SELF                      RV 63-514        A Pump Disch Check                                          1-1/2    CK      SELF            0/C      CV      PV-32      RR/PV-32 63-516        B Pump    Disch Check                    D-6                1-1/2    CK      SELF            0/C      CV      PV-32      RR/PV-32 63-525        Cont Isol Check                          D-2      AC      1-1/2    CK      SELF            0/C      CV      PV-9        RR LT                  LT 63-526        Cont  Isol  Check                      E-2      AC      1-1/2    CK      SELF            0/C      CV      PV-9        RR LT                    LT Page 46
 
Cl TENNESSEE VAL      UTHORITY Browns  Ferry        r Plant Units 1,        3 Inservice Testing Program System:  Reactor Building Heating, Ventilation, and  Air Conditioning (64)                                  Drawing No. 47W865-1 Page 3  of 3 Relief Req./
Sect. XI                                  Safety-          Cold Shutdn. Testing Valve                                      ASHE    Drawing    Valve      Size    Valve Actuator Normal  Related Testing  Justifictn. Performed Number              Function              Cl ass  Coordtn. Category    (in.)    Type  Type  Positn. Positn. Req'd.  (if applic.) (if diffrnt.)
64-32      PSC Exhaust Inbd    Isol                  G-9                    18    BF      AO                    Q ST LT 64-33      PSC Exhaust Outbd Isol                    F-9                    18    BF      AO                    Q ST LT 64-34      PSC SBGT  Inbd Isol                      G-10                    2    BF      AO                    Q ST LT 64-800      PSC Vac Rel i e f Ck                      G-3                    20    CK      SELF          0/C      CV LT 64-801      PSC Vac  Relief  Ck                      G-3                    20    CK      SELF          0/C      CV LT Page 51
 
0
    ~ e~r
%PI
 
TENNESSEE VAL      'HORITY Browns  Ferry        r Plant Units 1,        d 3 Inservice Testing Program System:    Emergency Equipment Cooling Water (67)                                                          Drawing No. 47W859-1      Page 5  of  13 Rel i e f Req./
Sect. XI                                    Safety-          Cold Shutdn.          Testing Valve                                          ASHE    Drawing  Valve      Size    Valve Actuator  Normal  Related Testing  3ustifictn.          Performed Number                  Function              Class  Coordtn. Category    (in.)    Type    Type  Positn. Positn. Req'd.  (if applic.)        (if diffrnt.)
0-67-521      1B OG  Cooler  S Hdr Check                D-1                          CK      SELF  0/C      0/C      CV      PV-14                  RR 0-67-522      18 DG  Cooler S Hdr Check                 D-1        C                  CK      SELF  0/C      0/C      CV      PV-14                  RR 0-67-528      lA OG  Cooler S Hdr Check                 C-1                          CK      SELF  0/C      0/C              PV-14                  RR 0-67-529 0-67-538 lA OG Control Cooler Rm S Hdr Check Chiller S Hdr C-1 8-2
                                                                                    . CK CK SELF SELF 0/C      0/C 0/C CV CV PV-14 PV-33 RR RR/PV-3
                                                                                                                                                              ~
Supply Check 0-67-539      Control  Rm  Chiller S Hdr                8-2                          CK      SELF          0/C     CV      PV-33              RR/PV-3 Supply Check Page 57
 
TENNESSEE VA        THORITY Browns Ferry        r Plant Units 1,      d 3 Inservice Testing  Program System:  Emergency Equipment Cooling Water (67)                                                            Drawing No. 47W859-1 Page 6  of  13 Relief Req./
Sect. XI                                    Safety-            Cold Shutdn. Testing Val ve                                      ASHE    Drawing  Valve      Size    Valve Actuator Normal  Rel ated Testing  Justifictn.'erformed Number                Functi on            Class  Coordtn. Category    (in.)    Type    Type  Positn. Posi tn. Req'd.  (if applic.) (if diffrnt.)
67-541      Loop I  CS Rm Cooler  S  Hdr            C-3                2-1/2     CK     SELF 0/C       0/C       CV      PV-14            RR Supply Check 67-542      Loop I  CS Rm  Cooler  S  Hdr            C-3                2-1/2    CK      SELF 0/C       0/C       CV      PV-14            RR Supply Check 67-558      Loop I  RHR Rm  Cooler  S  Hdr                                        CK      SELF  0/C     0/C       CV       PV-14             RR 67-559 Supply Check Loop I RHR Rm Supply Check Cooler   S Hdr                                       CK     SELF   0/C '/C         CV       PV-14             RR Page 58
 
TENNESSEE VAL       THORITY Drowns Ferry         r Plant Units 1,       d 3 Inservice Testing Program System:  Emergency Equipment Cooling Water (67)                                                          Drawing No. 47W859-1 Page 7 of 13 Relief Req./
Sect. XI                                  Safety-          Cold Shutdn. Testing Valve                                          ASHE  Drawing  Valve     Size    Valve Actuator Normal  Related Testing  3ustifictn. Performed Number                 Function               Class Coordtn. Category   (in.)   Type   Type   Positn. Positn. Req'd.. (if applic.)  (if diffrnt.)
67-584        Loop  II CS  Rm Cooler  S  Hdr                              2-1/2    CK      SELF  0/C    0/C    CV        PV-14            RR Supply Check 67-585        Loop  II CS  Rm Cooler  S  Hdr                              2-1/2    CK      SELF  0/C    0/C    CV        PV-14 Supply Check 67-600        Loop  II RHR Supply Check Rm Cooler  S  Hdr          F-5                        CK      SELF  0/C    0/C    CV        PV.-14            RR
                                                                                                                                                      ~
67-601        Loop  II RHR  Rm Cooler  S  Hdr          F-5                        CK      SELF  0/C    0/C    CV        PV-14            RR Supply Check 0-67-619      S  Hdr Check                              G-12                18    CK      SELF  0/C    0/C    CV        PV-14            RR Page 59
 
TENNESSEE V        UTHORITY Drowns Ferry      ear Plant Units 1, 2, and  3 Inservice Testing Program System:  Emergency Equipment Cooling Water (67)                                                                      Drawing No. 47W859-1    Page 10  of  13 I
                                                                    / Sect. XI I
                                                                                /
I, I
I I        / Safety-f
(
Relief Req./
Cold Shutdn.
[
f    Testing Valve                                            / ASHE  / Drawing  /  Valve      Size  )Valve )Actuator]  Normal  / Related )Testing  (
Justifictn.  ]  Performed Number                Function                ./  Class / Coordtn. / Category  f (in.) [  Type ). Type  [ Positn. / Positn. [ Req'd . [ (if applic.) (if diffrnt.)
I 0-67-652  )  Control Rm Chillers    N  Hdr                  8-2                            CK      SELF              0/C  i  CV        PV-33            RR/PV-33
          ]  Supply Check I
0-67-653  )  Control Rm Chillers    N  Hdr                  8-2                            CK      SELF              0/C      'CV        PV-33            RR/PV-33
          ]  Supply Check I
67-656      [ Loop II CS Rm Cooler   N  Hdr               8-5          C      12-1/2      CK      SELF    . 0/C      0/C                PV-14              RR
          $  Supply Check I
I 67-657      ] Loop II CS Rm Cooler   N  Hdr               C-5        C      I 2-1/2 I  CK      SELF      0/C      0/C      CV        PV-14              RR
            ) Supply Check I
67-659      [ Loop II RHR Rm Cooler   N Hdr             8/C-5                          CK      SELF      0/C      0/C      CV        PV-14              RR
[ Supply Check I
Page 62
 
  .
Al
 
TENNESSEE VA        UTHORITY Browns Ferry          r Plant Units 1,        d 3 Inservice Testing Program System:    Emergency Equipment Cooling Water (67)                                                            Drawing No. 47W859-1 Page  11  of 13 Relief Req./
Sect. XI                                    Safety-          Cold Shutdn. Testing Valve                                          ASHE    Drawing  Valve      Si ze  Val ve  Actuator Normal  Related Testing  Justifictn. Performed Number                  Function              Class  Coordtn. Category    (in.)    Type    Type    Positn. Positn. Req'd.  (if applic.)  (if diffrnt.)
67-660        Loop II RHR Rm Cooler N Kdr            F-5                    3      CK      SELF    0/C    0/C      CV      PV-14            RR Supply Check 0-67-671      N Hdr Check                               G-12                  18      CK      SELF    0/C    0/C      CV      PV-14            RR 1-67-675      Units  182 Emerg  Cooling Unit          A-2                    4      GA Disch Isol 0-67-679      RSW  to  EECW Check                      F/G-5                     1    CK      SELF                    CV      PV-14 1-67-786      Emergency Control Bay Cooling            8-2                    4      GA Unit  N  Hdr Supply  Isol 1-67-787      Emergency Control Bay Cooling            8-2                     4      CK      SELF            0/C      CV      PV-33          RR/PV-33 Unit  N Hdr Supply Check Page 63
 
.
TENNESSEE VAL        THORITY Browns Ferry        r Plant Units 1,        3 Inservice Testing Program System:  Emergency Equipment Cooling Water (67)                                                            Drawing No. 47W859-1 Page  12  of 13 Relief Req./
Sect. XI                                    Safety-          Cold Shutdn. Testing Valve                                        ASHE    Drawing  Valve      Size    Valve Actuator Normal  Related Testing  Justifictn. Performed Number                  Function            Class  Coordtn. Category  ,(in.)    Type  Type  Posi tn. Positn. Req'd.  (if applic.)  (if diffrnt.)
1-67-788      Emergency Control Bay Cooling            B-2 Unit  S  Hdr Supply  Isol 1-67-789      Emergency Control Bay Cooling            B-2                           CK      SELF            0/C      CV      PV-33          RR/PV-33 Unit  S Hdr Supply Check 3-67-807      DG Rm  Cooler 1  Cooler 2             E-5 Crosstie 3-67-808      DG Rm  Cooler 1   Cooler 2 Crosstie 67-838        H202  Analyzer 25-340                                                  CK     SELF   0/C               CV Supply Check Page 64
 
Cl I ig ll
 
TENNESSEE VAL        THORITY Browns Ferry          r Plant Units 1,        d 3 Irscrvice Testing  Program System:  Emergency Equipment Cooling Water (67)                                                              Orawing No. 47W859-1  Page 13  of 13 Relief Req./
Sect. XI                                      Safety-            Cold Shutdn. Testing Valve                                        ASHE    Orawing  Valve      Si ze  Val ve  Actuator Normal  Related  Testing  Justifictn.        f Per ormed Number                  Function              Class  Coordtn. Category    (in.)    Type    Type  Posi tn. Posi tn. Req'd.  (if appli c.)  (if diffrnt.)
67-839        H202 AnalYzer 25-340                                            1      CK     SELF   0/C               CV Supply Check 67-843        H202  Analyzer 25-341                    0-7                    1      CK     SELF   0/C Supply Check 67-844        H202  Analyzer 25-341                    0-7                    1      CK      SELF    0/C Supply Check 2-67-872      Shutdown Bd  Rm  Crosstie Check          C-8                    3      CK      SELF    0/C 2-67-873      EECW/RCW  Supply Check                  C-8                    3      CK      SELF    0/C               CV       PV-14             PV-14 2-67-876 2-67-877 EECW/RCW  Supply Check
            ~Shutdown Bd  Rm  Crosstie Check  3  '8 0-8                    3 3
                                                                                  . CK CK SELF SELF 0/C 0/C CV CV PV-14             PV-14 Page 65
 
. Cl
                  ~ ~ ~
  ~ ~                  ~ ~    ~ ~
l  . ~
        ~ ~  ~ ~
                            ~ ~
~ ~
~ ~
~ ~
~ ~


TENNESSEE V UTHORITY Drowns Ferry ear Plant Units 1, 2, and 3 System: Emergency Equipment Cooling Water (67)Inservice Testing Program Drawing No.47W859-1 Page 10 of 13 Valve Number Function I I/Sect.XI//ASHE/Drawing/Valve./Class/Coordtn./Category f I, I I I Size)Valve)Actuator]
Normal (in.)[Type).Type[Positn./Safety-/Related/Positn.f Relief Req./[(Cold Shutdn.f Testing)Testing (Justifictn.
]Performed[Req'd.[(if applic.))(if diffrnt.)0-67-652 0-67-653 67-656 67-657 67-659)Control Rm Chillers N Hdr]Supply Check I)Control Rm Chillers N Hdr]Supply Check I[Loop II CS Rm Cooler N Hdr$Supply Check I I]Loop II CS Rm Cooler N Hdr)Supply Check I[Loop II RHR Rm Cooler N Hdr[Supply Check I 8-2 8-2 8-5 C-5 8/C-5 C 12-1/2 C I 2-1/2 I CK CK CK CK CK SELF SELF SELF SELF SELF.0/C 0/C 0/C 0/C'CV 0/C 0/C CV 0/C CV I 0/C i CV PV-33 PV-33 PV-14 PV-14 PV-14 RR/PV-33 RR/PV-33 RR RR RR Page 62
.Al System: Emergency Equipment Cooling Water (67)TENNESSEE VA UTHORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program Drawing No.47W859-1 Page 11 of 13 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Si ze Val ve (in.)Type Actuator Type Normal Positn.Safety-Related Testing Positn.Req'd.Relief Req./Cold Shutdn.Testing Justifictn.
Performed (if applic.)(if diffrnt.)67-660 0-67-671 1-67-675 Loop II RHR Rm Cooler N Kdr Supply Check N Hdr Check Units 182 Emerg Cooling Unit Disch Isol 1-67-786 1-67-787 Emergency Control Bay Cooling Unit N Hdr Supply Isol Emergency Control Bay Cooling Unit N Hdr Supply Check 0-67-679 RSW to EECW Check F-5 G-12 A-2 F/G-5 8-2 8-2 3 CK 18 CK 4 GA 1 CK 4 GA 4 CK SELF SELF SELF SELF 0/C 0/C 0/C 0/C 0/C CV CV CV CV PV-14 PV-14 PV-14 PV-33 RR RR RR/PV-33 Page 63
.
.
System: Emergency Equipment Cooling Water (67)TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, 3 Inservice Testing Program Drawing No.47W859-1 Page 12 of 13 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size ,(in.)Valve Actuator Type Type Normal Posi tn.Safety-Related Testing Positn.Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)1-67-788 1-67-789 3-67-807 3-67-808 67-838 Emergency Control Bay Cooling Unit S Hdr Supply Isol Emergency Control Bay Cooling Unit S Hdr Supply Check DG Rm Cooler 1-Cooler 2 Crosstie DG Rm Cooler 1-Cooler 2 Crosstie H202 Analyzer 25-340 Supply Check B-2 B-2 E-5 CK SELF CK SELF 0/C 0/C CV CV PV-33 RR/PV-33 Page 64 Cl I ig ll System: Emergency Equipment Cooling Water (67)TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, d 3 Irscrvice Testing Program Orawing No.47W859-1 Page 13 of 13 Valve Number 67-839 67-843 67-844 Function H202 AnalYzer 25-340 Supply Check H202 Analyzer 25-341 Supply Check H202 Analyzer 25-341 Supply Check ASHE Class Orawing Coordtn.0-7 0-7 Sect.XI Valve Category Si ze Val ve (in.)Type 1 CK 1 CK 1 CK Actuator Type SELF SELF SELF Normal Posi tn.0/C 0/C 0/C Safety-Related Testing Posi tn.Req'd.CV Relief Req./Cold Shutdn.Justifictn.(if appli c.)Testing Per f ormed (if diffrnt.)2-67-872 2-67-873 2-67-876 2-67-877 Shutdown Bd Rm Crosstie Check EECW/RCW Supply Check EECW/RCW Supply Check~Shutdown Bd Rm Crosstie Check C-8 C-8 0-8 3'8 3 CK 3 CK 3.CK 3 CK SELF SELF SELF SELF 0/C 0/C 0/C 0/C CV CV CV PV-14 PV-14 PV-14 PV-14 Page 65
~ ~   ~ ~
.Cl
                                ~ ~       ~ ~ ~
~~~~~~~~~l.~~~~~~~~~~~~~~~  
                                  ~ ~
.
I   .   ~
~~~~~~~~~I.~~~~~~~~~~~~~~~'~~~~~~~~  
                                                  '
.4 System: Reactor Core Isolation Cooling (71)TENNESSEE VA UTHORITY Browns Ferry r Plant Units 1, nd 3 Inservice Testing Program Drawing No.47W813-1 Page 1 of 6'Val ve Number Function ASHE Class Drawing Coordtn.Sect.XI Val ve Category Size Valve (in.)Type Actuator Type Normal Posi tn.Safety-Related Positn.Testing Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)71-2 71-3 71-6A Steam Line Inbd Isol Steam Line Outbd Isol Steam Line to Cond Drain B-3 E-10 AO 0/C 0/C 0/C Q ST LT Q ST LT Q ST PV-21 ST LT (R)ST LT (R)Page 75
                                                ~
:  
            ~ ~ ~   ~ ~ ~
~~I~~~~~~~.~~~~~~~~~~~~~~~~~~  
                          ~ ~ ~       ~ ~
.0 Cl System: High Pressure Coolant Injection,(73)
    ~ ~
TENNESSEE VAL THORITY Browns Ferry Plant Units 1, d 3 Inservice Testing Program Drawing No.47W812-1'age 1 of 6 Val ve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Si ze Val ve (in.)Type Actuator Type Normal Posi tn.Safety-Related Testing Posi tn.Req'd.Relief Req./Cold Shutdn.Justifictn.
    ~ ~
'if applic.)Testing Per f ormed (if diffrnt.)73-2 73-3 73-6A Steam Line Inbd Isol Steam Line Ougbd Isol Steam Line to Cond Drain B-3 8-4 0-10 10 10 AO 0 0/C 0/C 0/C Q ST LT Q ST LT Q ST PV-21 ST LT (R)ST LT (R)Page 81 0 System: High Pressure Coolant Injection (73)TENNESSEE VA THORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program Drawing No.47M812-1 Page 2 of 6 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size (in.)Valve Type Actuator Type Normal Positn.Safety-Related Testing Positn.Req'd: Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Perf ormed (if diffrnt.)73-16 73-18 Turbine Steam Supply Turbine Stop 8-9 8-9 10 10 E/H Q ST Q ST FS PV-25 Page 82
    ~ ~
:  
    ~ ~
~~~~~~~~~'~~~~~~~I oo~~I tq1 Cl System: High Pressure Coolant Injection (73)TENNESSEE VAL THORITY Browns Ferry Plant Units 1, 3 Inservice Testing Program Drawing No.47W812-1 Page 5 of 6 Val ve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size (in.)Valve Actuator Normal Type Type Positn.Safety-Related Positn.Testing Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)73-506 73-517 73-559 73-574 73-603 73-609 Pump Suction Relief PSC Suction Check Hin Flow Bypass Check Cooling Water to Gland Seal Cond Relief Turb Exhaust Check Turb Exhaust Dr Check 8-6/7 F-5 F-7/8 E-2/3 E-4 AC AC AC 16 20 RV SELF CK SELF CK SELF RV SELF CK SELF CK SELF 0/C 0/C RV CV CV LT RV CV LT CV LT PV<0 PV-16 PV-18 PV-18 RR RR LT~RR LT RR LT Page 85 I I W%
 
System: Residual Heat Removal (74)TENNESSEE VAL THORITY Browns Ferry Plant Units 1, 3 In'service Testing Program Drawing No.47W811-1 Page 3 of 13 Val ve Number Function ASHE Class Drawing Coordtn., Sect.XI Valve Category Size (in.)Valve Type Actuator Type Normal Posi tn.Safety-Related Testing Posi tn.Req'd.Rel i e f Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)74-48 74-52 74-53 74-54 SD Cooling Inbd Isol Loop I Throttle Loop I Injection Loop I Testable Check C-6 AC 20 24 24 24 CK AO/SELF 0/C 0/C 0/C Q ST LT Q ST Q ST LT CV LT CSD3-5 PV-27 CSD ST LT ST LT CSD/PV-27 LT 74-57 Loop I PSC Return 8-2/3 18 GA 0/C Q ST LT Page 89-  
  .
4
 
                                                                                                                                                        '
TENNESSEE VA       UTHORITY Browns Ferry         r Plant Units 1,     nd 3 Inservice Testing Program System:    Reactor Core Isolation Cooling (71)                                                                Drawing No. 47W813-1 Page 1 of 6 Relief Req./
Sect. XI                                    Safety-          Cold Shutdn. Testing Val ve                                      ASHE    Drawing  Val ve     Size    Valve Actuator Normal  Related Testing  Justifictn. Performed Number               Function               Class   Coordtn. Category   (in.)   Type   Type   Posi tn. Positn. Req'd.   (if applic.) (if diffrnt.)
71-2       Steam Line Inbd Isol                       B-3                                                 0/C       Q       PV-21 ST                          ST LT                          LT (R) 71-3        Steam Line Outbd  Isol                                                                          0/C      Q ST                         ST LT                          LT (R) 71-6A      Steam  Line to Cond  Drain                  E-10                                AO              0/C      Q ST Page 75
:
                        ~ ~
    ~ . ~ ~ ~
I    ~ ~       ~ ~   ~ ~
                                    ~ ~
                                                ~   ~
              ~ ~ ~ ~ ~       ~ ~       ~ ~
~ ~
 
.0 Cl
 
TENNESSEE VAL       THORITY Browns Ferry           Plant Units 1,       d 3 Inservice Testing Program System:  High Pressure Coolant Injection,(73)                                                                Drawing No. 47W812-1 'age   1 of 6 Relief Req./
Sect. XI                                      Safety-            Cold Shutdn. Testing Val ve Number               Function ASHE Class Drawing Coordtn.
Valve Category Si ze (in.)
Val ve Type Actuator Normal Type   Posi tn.
Related Posi tn.
Testing Req'd. 'if applic.)
Justifictn. Per formed (if diffrnt.)
73-2       Steam Line Inbd  Isol                    B-3                 10                                0/C        Q        PV-21 ST                          ST LT                          LT  (R) 73-3        Steam Line Ougbd Isol                   8-4                 10                       0       0/C       Q ST                           ST LT                           LT (R) 73-6A      Steam Line to  Cond Drain                0-10                                  AO              0/C        Q ST Page 81
 
0                                                     TENNESSEE VA Browns Ferry Units 1, THORITY r Plant d 3 Inservice Testing Program System:  High Pressure Coolant Injection (73)                                                              Drawing No. 47M812-1 Page 2 of 6 Relief Req./
Sect. XI                                    Safety-          Cold Shutdn. Testing Valve                                       ASHE    Drawing  Valve      Size    Valve  Actuator Normal  Related Testing  Justifictn. Perf ormed Number               Function               Class   Coordtn. Category   (in.)   Type   Type   Positn. Positn. Req'd:   (if applic.) (if diffrnt.)
73-16       Turbine Steam Supply                     8-9                 10                                        Q ST 73-18      Turbine Stop                              8-9                 10             E/H                       Q       PV-25 ST FS Page 82
:
              ~ ~ ~
                        ~ ~     ~   ~   ~
                                  ~
                                      '
        ~ ~ ~       ~ ~     ~ ~
I   oo
  ~ ~ I
 
Cl tq1
 
TENNESSEE VAL       THORITY Browns Ferry           Plant Units 1,         3 Inservice Testing Program System:    High Pressure Coolant Injection (73)                                                              Drawing No. 47W812-1 Page 5 of 6 Relief Req./
Sect. XI                                    Safety-          Cold Shutdn. Testing Val ve                                       ASHE    Drawing  Valve      Size    Valve Actuator  Normal  Related Testing  Justifictn. Performed Number                 Function             Class   Coordtn. Category   (in.)   Type   Type   Positn. Positn. Req'd.   (if applic.) (if diffrnt.)
73-506     Pump  Suction Relief                      8-6/7                        RV      SELF                    RV 73-517     PSC  Suction Check                                            16      CK      SELF                    CV        PV<0            RR 73-559     Hin Flow Bypass Check                      F-5      AC                CK      SELF          0/C      CV        PV-16            RR 73-574      Cooling Water to Gland Seal Cond Relief F-7/8                       RV      SELF LT RV LT
                                                                                                                                                      ~
73-603      Turb Exhaust Check                        E-2/3     AC       20       CK       SELF           0/C     CV         PV-18          RR LT                         LT 73-609      Turb Exhaust Dr Check                      E-4      AC                  CK      SELF                    CV        PV-18           RR LT                         LT Page 85
 
I I W%
TENNESSEE VAL         THORITY Browns Ferry           Plant Units 1,         3 In'service Testing Program System:    Residual Heat Removal (74)                                                                          Drawing No. 47W811-1   Page 3 of 13 Rel i e f Req./
Sect. XI                                      Safety-            Cold Shutdn.      Testing Val ve                                       ASHE  Drawing    Valve      Size  Valve  Actuator Normal    Related  Testing  Justifictn.      Performed Number                 Function             Class Coordtn., Category     (in.)   Type   Type     Posi tn. Posi tn. Req'd.   (if applic.)     (if diffrnt.)
74-48       SD  Cooling Inbd Isol                    C-6                  20                                0/C        Q      CSD3-5              CSD ST                            ST LT                            LT 74-52      Loop I Throttle                                               24                                            Q ST 74-53      Loop I Injection                                             24                                0/C        Q ST                            ST LT                            LT 74-54      Loop I Testable   Check                           AC         24       CK     AO/SELF           0/C       CV         PV-27       CSD/PV-27 LT                            LT 74-57       Loop I PSC Return                     8-2/3                   18     GA                       0/C         Q ST LT Page 89-


System: Residual Heat Removal (74)TENNESSEE VAL THORITY Browns Ferry Plant Units 1, 3 Inservice Testing ProgramDrawing No.47W811-1 Page 5 of 13 Valve Number Function ASME Class Drawing Coordtn.Sect.XI Valve Category Size (in.)Valve Actuator Normal Type Type Positn.Safety-Related Positn.Testing Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Per f ormed (if diffrnt.)74-66 74-67 74-68 74-71 74-72 Loop II Throttle Loop II Injection Loop II Testable Check Loop II PSC Return Loop II PSC Spray 8-7 BC-7/8 C-7 8-9 C-9 AC A.24 24 24 18 CK AO/SELF C GL 0/C 0/C 0/C 0/C Q ST Q ST LT CV LT Q ST LT Q ST LT PV-27 ST LT CSD/PV-27 LT Page 91 f~l System: Residual Heat Removal (74)TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program Drawing No.47W811-1 Page 12 of 13 Valve Number 74-587A 74-5878 74-659 74-661 74-662 Function Loop I Disch Hdr Relief Loop II Disch Hdr Relief SD Cooling Supply Relief Thermal Relief Check Thermal Relief Check ASHE Class Drawing Coordtn.8-3 8-8 D-5 C-5 C-5 Sect.XI Valve Category AC AC Size (in.)3/4 3/4 Valve Type RV RV RV CK CK Actuator Normal Type Positn.SELF SELF SELF SELF SELF Safety-Related Positn.0/C 0/C Testing Req'd..RV RV RV CV LT CV LT Relief Req./Cold Shutdn.Justifictn.(if applic.)PV-30 PV-30 Testing Performed (if diffrnt.)RR~RR LT 74-722 74-792 PSC Drain Loop I Fill from Hd Tk D-7/8 A(P)AC CK SELF 0/C LT CV LT CSD3-13 CSD Page 98
TENNESSEE VAL         THORITY Browns Ferry           Plant Units 1,         3 Inservice Testing Program System:  Residual Heat Removal (74)                                                                      Drawing No. 47W811-1 Page 5 of 13 Relief Req./
'l System: Residual Heat Removal (74)TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, 3 Inservice Testing Prcgran Drawing No.47W811-1 Page 13 of 13 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size (in.)Valve Actuator Normal Type Type Positn.Safety-Related Posi tn.Testing Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)74-802 74-803 74-804 Loop II Fill from Hd Tk Loop II Fill from Hd Tk Loop I Fill from Hd Tk A-8 A-8 AC AC AC CK SELF CK SELF CK SELF 0/C 0/C 0/C CV LT CV LT CV LT CSD3-13 I CSD3-13 CSD3-13 CSD CSD cso~Page 99 WI System: Core Spray (75)TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, 3 Inservice Testing Program Drawing No.47W814-1 Page 2 of 5 Val ve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size (in.)Valve Actuator Normal Type Type Positn.Safety-Related Positn.Testing Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)75-50 75-51 75-53 75-54 75-57 Loop II Pump Test Loop II Injection Loop II Injection Loop II Testable Check Drain Pump A Inbd Isol 8-6 8-3 8-3 H-7 AC 10 12 12 12 GL CK AO/SELF C AO 0/C 0/C Q ST Q ST Q ST LT CV LT Q ST LT PV-27 CSD/PV-27 LT Q ST LT(R)Page 101
Sect. XI                                    Safety-          Cold Shutdn. Testing Valve                                       ASME  Drawing  Valve      Size    Valve Actuator  Normal  Related Testing  Justifictn. Per formed Number               Function             Class Coordtn. Category     (in.)   Type   Type   Positn. Positn. Req'd.   (if applic.) (if diffrnt.)
74-66       Loop II Throttle                        8-7                  24                                        Q ST 74-67       Loop II Injection                     BC-7/8                 24                               0/C       Q ST                         ST LT                         LT 74-68      Loop II Testable  Check               C-7        AC       24      CK    AO/SELF   C     0/C     CV         PV-27      CSD/PV-27 LT                        LT 74-71      Loop II PSC Return                    8-9                  18                              0/C       Q ST LT 74-72      Loop II PSC  Spray                      C-9        A.                 GL                     0/C       Q ST LT Page 91


System: Core Spray (75)TENNESSEE VAL THORITY Browns Ferry Plant Units 1, 3 Inservice Testing Program Drawing No.47M814-1 Page 5 of 5 Valve Number 75-606 75-607 75-609 75-610 Function Loop I Fill from Hd Tank Loop I Fill from Hd Tank Loop II Fill from Hd Tank Loop II Fill from Hd Tank ASHE Class Drawing Coordtn.Sect.XI Valve Category AC AC AC AC CK SELF 0/C CK SELF 0/C CK SELF~0/C CK SELF 0/C Si ze Valve Actuator Normal (in.)Type Type Posi tn.Safety-Related Positn.Testing Req'd.CV LT CV LT CV LT CV LT Relief Req./Cold Shutdn.Justifictn.(if applic.)CS03-13 CSOJ-13 CSOJ-13 CSD3-13 Testing Performed (if diffrnt.)CSD CSD cso~CSO Page 104
f ~l TENNESSEE VAL         THORITY Browns Ferry         r Plant Units 1,       d 3 Inservice Testing Program System:  Residual Heat Removal (74)                                                                      Drawing No. 47W811-1 Page 12  of 13 Relief Req./
Sect. XI                                     Safety-          Cold Shutdn. Testing Valve                                       ASHE  Drawing  Valve      Size    Valve Actuator Normal Related Testing  Justifictn. Performed Number                Function              Class Coordtn. Category    (in. )   Type   Type   Positn. Positn. Req'd..  (if applic.)  (if diffrnt.)
74-587A      Loop  I Disch Hdr Relief                8-3                          RV      SELF                    RV 74-5878      Loop  II Disch Hdr  Relief              8-8                          RV      SELF                    RV 74-659      SD  Cooling Supply Relief              D-5                          RV      SELF                    RV 74-661 74-662 Thermal Thermal Relief Relief Check Check C-5 C-5 AC AC 3/4 3/4 CK CK SELF SELF 0/C 0/C CV LT CV PV-30 PV-30 RR RR
                                                                                                                                                    ~
LT                         LT 74-722      PSC  Drain                            D-7/8      A(P)                                                 LT 74-792      Loop  I Fill from  Hd Tk                          AC                CK      SELF    0/C              CV      CSD3-13         CSD LT Page 98


System: Fuel Pool Cooling System (78)TENNESSEE VA THORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program Drawing No.47W855-1 Page 1 of 1 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Si ze Val ve (in.)Type Actuator Type Normal Posi tn.Safety-Related Testing Positn.Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)78-61 78-62 78-526 78-527 RHR to FPC Supply RHR to FPC Supply To Pool Diffuser A To Pool Di f fuser B 3 A-5 A-6 A-7 CK CK SELF SELF 0 Q ST CV CV Page 112
'l TENNESSEE VAL        THORITY Browns Ferry          r Plant Units 1,        3 Inservice Testing Prcgran System:   Residual Heat Removal (74)                                                                        Drawing No. 47W811-1 Page 13  of 13 Relief Req./
:0~l*
Sect. XI                                    Safety-            Cold Shutdn. Testing Valve                                      ASHE  Drawing  Valve      Size    Valve  Actuator Normal  Related  Testing  Justifictn. Performed Number                Function              Class Coordtn. Category    (in.)    Type  Type    Positn. Posi tn. Req'd.  (if applic.)  (if diffrnt.)
System: Containment Atmosphere Dilution (84)TENNESSEE VAL THORITY Browns Ferry Plant Units 1, 3 Inservice Testing Program Drawing No.47W862-1 Page 2 of 3 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size Valve (in.)Type Actuator Type Normal Positn.Safety-Related Testing Posi tn.Req'd.'elief Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)84-20 84-600 84-601 84-602 DW/PSC Oisch to SBGT DW Supply Check A PSC Supply Check A DW Supply Check 8 8-3 0-2 D-2 CK CK CK AO SELF SELF SELF 0/C 0/C 0/C 0/C Q ST LT Q LT Q LT Q LT CSO-9 PV-30 CSO-9 PV-30 CSD-9 PV-30 CSD(0)RR(C)LT CSO(0)RR(C)LT CSO(0)RR(C)LT Page 114
74-802      Loop II Fill  from  Hd Tk              A-8        AC                CK      SELF    0/C              CV LT CSD3-13          CSD I
74-803      Loop II Fill  from  Hd Tk              A-8        AC                CK      SELF    0/C              CV LT CSD3-13          CSD 74-804      Loop I Fill  from  Hd Tk                          AC                CK      SELF    0/C              CV LT CSD3-13          cso
                                                                                                                                                      ~
Page 99
 
WI TENNESSEE VAL        THORITY Browns Ferry         r Plant Units 1,         3 Inservice Testing Program System:  Core Spray (75)                                                                          Drawing No. 47W814-1 Page of 5 Relief Req./
Sect. XI                                    Safety-          Cold Shutdn. Testing Val ve                              ASHE  Drawing  Valve      Size    Valve Actuator  Normal  Related Testing  Justifictn. Performed Number               Function       Class Coordtn. Category    (in.)    Type  Type    Positn. Positn. Req'd.  (if applic.)  (if diffrnt.)
75-50      Loop  II Pump Test              8-6                10        GL                                Q ST 75-51      Loop  II Injection                                  12                                          Q ST 75-53      Loop  II Injection              8-3                12                                0/C      Q ST LT 75-54      Loop  II Testable  Check        8-3      AC        12        CK    AO/SELF    C      0/C      CV        PV-27      CSD/PV-27 LT                        LT 75-57      Drain  Pump A Inbd Isol          H-7                                  AO                        Q                        Q ST                        ST LT                        LT(R)
Page  101
 
TENNESSEE VAL        THORITY Browns  Ferry          Plant Units 1,          3 Inservice Testing Program System:  Core Spray (75)                                                                              Drawing No. 47M814-1 Page 5  of 5 Relief Req./
Sect. XI                                       Safety-          Cold Shutdn. Testing Valve                                 ASHE  Drawing  Valve      Si ze   Valve Actuator  Normal  Related Testing  Justifictn. Performed Number              Function          Class Coordtn. Category    (in.)     Type   Type     Posi tn. Positn. Req'd.   (if applic.)  (if diffrnt.)
75-606      Loop I Fill from  Hd Tank                  AC                  CK      SELF    0/C              CV        CS03-13      CSD LT 75-607      Loop I Fill from  Hd Tank                    AC                  CK      SELF    0/C              CV        CSOJ-13      CSD LT 75-609      Loop II Fill  from Hd Tank                  AC                  CK      SELF ~  0/C              CV LT CSOJ-13      cso
                                                                                                                                                  ~
75-610      Loop II Fill  from Hd Tank                  AC                  CK      SELF    0/C              CV LT CSD3-13        CSO Page  104
 
TENNESSEE VA          THORITY Browns Ferry          r Plant Units 1,        d 3 Inservice Testing Program System:  Fuel Pool Cooling System (78)                                                                    Drawing No. 47W855-1 Page  1 of 1 Relief Req./
Sect. XI                                      Safety-          Cold Shutdn. Testing Valve                                      ASHE  Drawing  Valve      Si ze    Val ve Actuator Normal  Related Testing  Justifictn. Performed Number                Function              Class Coordtn. Category    (in.)    Type  Type    Posi tn. Positn. Req'd.  (if applic.) (if diffrnt.)
78-61       RHR to FPC Supply                     A-5                                                              Q ST 78-62      RHR to FPC Supply                     A-6 78-526      To Pool Diffuser   A                                                 CK      SELF              0      CV 78-527      To Pool Di ffuser  B             3   A-7                           CK     SELF                     CV Page   112
 
:0
~l*
 
TENNESSEE VAL       THORITY Browns Ferry           Plant Units 1,         3 Inservice Testing Program System:    Containment Atmosphere Dilution (84)                                                              Drawing No. 47W862-1 Page 2 of 3 Sect. XI                                  Safety-          'elief    Req./
Cold Shutdn. Testing Valve                                       ASHE    Drawing  Valve      Size    Valve Actuator Normal  Related  Testing  Justifictn. Performed Number               Function               Class   Coordtn. Category   (in.)   Type   Type   Positn. Posi tn. Req'd.   (if applic.)   (if diffrnt.)
84-20       DW/PSC Oisch to SBGT                     8-3                                  AO            0/C        Q ST LT 84-600      DW Supply Check A                         0-2                          CK      SELF          0/C                CSO-9          CSD(0)
Q        PV-30          RR(C)
LT                        LT 84-601      PSC Supply Check A                       D-2                         CK     SELF           0/C                 CSO-9          CSO(0)
Q      PV-30          RR(C)
LT                        LT 84-602      DW  Supply Check  8                                                    CK      SELF          0/C                 CSD-9          CSO(0)
Q        PV-30          RR(C)
LT                         LT Page  114
 
TENNESSEE VA        UTHORITY Browns Ferry          r Plant Units 1,        d 3 Inservice Testing Program System:  Containment Atmosphere Dilution (84)                                                                Drawing No. 478862-1 Page 3  of 3 Relief Req./
Sect. XI                                    Safety-           Cold Shutdn. Testing Val                                              ASHE    Drawing  Valve      Si ze    Valve Actuator Normal  Related  Testing  Justifictn. Performed ve'umber Function              Class  Coordtn. Category    (in.)    Type  Type  Posi tn. Posi tn. Req'd.  (if applic.)  (if diffrnt.)
84-603            PSC Supply Check  8                                                    CK      SELF            0/C                CSD-9         CSD(0)
PV-30        RR(C)
LT                       LT 84-617            Containment Isol Valve                    C-7                          CK      SELF            0/C        Q        PV-30        CSD(0)
LT        CSD-9        RR(C)
LT 84-680            Containment Isol Valv'e          NNCC    F-6      AC        1/2      CK      SELF            0/C        Q        PV-30        CSD(0)
                                                                                                                          .LT        CSD-9          RR(C)
LT Page   115


System: Containment Atmosphere Dilution (84)TENNESSEE VA UTHORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program Drawing No.478862-1 Page 3 of 3 Val ve'umber Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Si ze Valve Actuator (in.)Type Type Normal Posi tn.Safety-Related Testing Posi tn.Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)84-603 84-617 84-680 PSC Supply Check 8 Containment Isol Valve Containment Isol Valv'e NNCC C-7 F-6 AC CK SELF CK SELF 1/2 CK SELF 0/C 0/C 0/C LT Q LT Q.LT CSD-9 PV-30 PV-30 CSD-9 PV-30 CSD-9 CSD(0)RR(C)LT CSD(0)RR(C)LT CSD(0)RR(C)LT Page 115
.
.
System: Control Rod Drive (85)TENNESSEE VA UTHORITY Drowns Ferry r Plant Units 1, d 3 Inservice Testing Program Drawing No.47W820-2 Page 1 of 1 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size (in.)Valve Actuator Type Type Normal Positn..Safety-Related Testing Positn.Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)85-39A (1-185)85-398 (1-185)85-576 85-589 (1-185)85-597 (1-185)85-616 (1-185)Scram Inlet Scram Outlet Isol check to RWCU Charging Water Check Cooling Water Check Scram Outlet Check C-8 C-7 F-9 C-9 B-9 0-7 AC PL AO 3/4 PL AO CK SELF 1/2 CK SELF 1/2 CK SELF 3/4 CK SELF 0/C 0/C Q ST Q ST CV LT CV CV CV PV-23 I PV-23 PV-28 CSD-11 PV-23 PV-23 PV-23 Per PV-23 Per PV-23 RRCSD-11(C)PV-23(0)PV-23(0)PV-23(0)Page 116
TENNESSEE VA         UTHORITY Drowns Ferry         r Plant Units 1,         d 3 Inservice Testing Program System:    Control Rod  Drive (85)                                                                        Drawing No. 47W820-2 Page 1 of 1 Relief Req./
: L'liftpled System: Control Rod Drive (85)TENNESSEE VAL THORITY Browns Ferry Plant Units 1, 3 Inservice Testing Program A Page 1 of 2 Drawing No.47W820-6 (units 1&3)47W820-5 (unit 2)Valve Number Function ASHE Class Drawing Coordtn Sect.XI Valve Category Size (in.)Valve Type Actuator Type Normal Posi tn.Safety-Related Testing Posi tn.Req'd.Relief Req/Cold Shutdn.Justifictn.(if applic.)Testing Performed (if diffrnt.)85-37C 85-370 85-37E 85-37F 85-82 SDIV Drain Isol West SDIV Drain Isol West SDIV Drain Isol East SDIV Drain Isol East Scram Disch Header Vent West H-5 H-5 H-8 H-9 A-2 8 2.GL GL GL GL GL AO AO AO AO AO Q ST FS Q ST FS Q ST FS ST FS Q ST FS Page 117
Sect. XI                                      Safety-          Cold Shutdn. Testing Valve                                     ASHE  Drawing  Valve      Size    Valve Actuator  Normal  Related Testing  Justifictn. Performed Number                 Function           Class Coordtn. Category   (in.)     Type   Type   Positn.. Positn. Req'd.   (if applic.) (if diffrnt.)
85-39A       Scram  Inlet                          C-8                            PL      AO                      Q        PV-23      Per PV-23 (1-185)                                                                                                           ST I
85-398      Scram  Outlet                        C-7                3/4        PL      AO                      Q        PV-23      Per PV-23 (1-185)                                                                                                           ST 85-576      Isol check to RWCU                   F-9      AC                  CK      SELF  0/C               CV        PV-28          RR LT 85-589      Charging Water Check                  C-9                 1/2       CK     SELF           0/C     CV       CSD-11       CSD-11(C)
(1-185)                                                                                                                     PV-23         PV-23(0) 85-597      Cooling Water Check                  B-9                  1/2       CK      SELF                    CV        PV-23        PV-23(0)
(1-185) 85-616      Scram Outlet Check                  0-7                  3/4      CK      SELF                    CV (1-185)                                                                                                                      PV-23        PV-23(0)
Page   116
 
L'
:
:
System: Control Rod Drive (85)TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, 3 Inservice Testing Program Drawing No.47W820-6 Page 2 of 2 Valve Number Function ASHE Class Drawing Coordtn.Sect.XI Valve Category Size (in.)Valve Type Actuator Type Normal Positn.Safety-Related Testing Posi tn.Req'd.Relief Req./Cold Shutdn.Justifictn.(if applic.)Testing Perf ormed (if diffrnt.)85-82A 85-83 85-83A Scram Disch Header Vent Hest Scram Disch Header Vent East Scram Disch Header Vent East A-2 A-9/10 A-10 GL GL GL AO AO AO Q ST FS Q ST FS Q ST FS Page 118 1228C/COC3/TLH
lift pled
~~Page 126.CATEGORY B-PASSIVE VALVES System: EEIEWE7 Drawing No.~47W-i 67-504 67-505~P<<~ii42n Dr win or ins F-3 F-3 1303C
 
,b w, Page 137 Relief Re uest Number PV-5 Page 1 of 2 System: Drawing: Components:
TENNESSEE VAL         THORITY Browns Ferry             Plant Units 1,           3 Inservice Testing Program                                                       A Page  1 of 2 System:  Control Rod  Drive (85)                                                                        Drawing No. 47W820-6 (units 1  & 3) 47W820-5  (unit 2)
As listed on page 12 As listed on page Installed plant instrumentation used to measure pump parameters.
Relief Req  /
V Class: Function: 2, 3, and NC Measurement of pump parameters.
Sect. XI                                       Safety-            Cold Shutdn.      Testing Valve                                    ASHE  Drawing  Valve      Size    Valve  Actuator Normal  Related  Testing  Justifictn.      Performed Number              Function            Class Coordtn Category   (in.)     Type   Type   Posi tn. Posi tn. Req'd.   (if applic.)     (if diffrnt.)
Impractical Test Requirement:
85-37C      SDIV Drain Isol West                H-5                  2.      GL      AO                          Q ST FS 85-370      SDIV Drain Isol West                H-5                          GL      AO                          Q ST FS 85-37E      SDIV Drain Isol East                 H-8                          GL       AO                           Q ST FS 85-37F      SDIV Drain Isol East                H-9                          GL      AO ST FS 85-82      Scram Disch Header Vent West        A-2      8                  GL      AO                          Q ST FS Page  117
a.Instrument accuracy shall be within the limits of table IWP-4110-1, Paragraph IWP-3210, Allowable Ranges of Inservice Test Quantities and Paragraph IWP-4120, Full-Scale Range Requirement.
:
b.Velocity measurement shall be used instead of displacement as an alternative method of determining vibration amplitude.
TENNESSEE VAL      THORITY Browns Ferry        r Plant Units 1,        3 Inservice Testing Program System:  Control Rod  Drive (85)                                                                      Drawing No. 47W820-6 Page 2  of  2 Relief Req./
Basis for Relief: The accuracy of installed plant indicators is+2'L of full scale.However, the accuracy of installed transmitters and square rooters is 0.57.and, when these are taken into account, the i'nstrument loop accuracies are 2.5%and 3.0%for pressure loops and flow loops, respectively.
Sect. XI                                  Safety-           Cold Shutdn. Testing Valve                                      ASHE  Drawing  Valve      Size  Valve  Actuator Normal  Related  Testing  Justifictn. Perf ormed Number                Function            Class Coordtn. Category    (in.)  Type    Type  Positn. Posi tn. Req'd.  (if applic.)  (if diffrnt.)
The diesel fuel transfer pumps are not instrumented to measure flow other than a level gage on the day tank.'he plant installed instruments will continue to be used since any alternate method such as connecting instruments into the system-or replacing plant instrumentation will not significantly increase the repeatability of the instruments for trending.(.0302B s'l e System: Relief Re uest Number PV-14~Emergency Cooling Water (67)and Raw Cooling Water (24)Page 147 Page 1 of 1 Drawing: 47W859-1 47W859-2 47W866-7 Valves: 67-541, 542, 584, 585, 648, 649, 657, 558;559, 638, 639, 600, 601, 659, 660 528, 529, 634, 635, 521, 522, 630, 631 624, 625, 514, 515, 627, 628,.507, 508 502, 622, 619,'656, 671, 679, 638;873, 876 3-24-831, 833, 796, 798., 852 3-67-639, 694, 695, 696, 703, 704, 705, 706 715, 716, 713, 714, 723, 724, 725, 726 771, 772, 774, 775, 761, 762, 764, 765 737, 738, 735, 736 Function: EECW: Pass rated flow for the emergency coolers and prevent backflow from opposite header.RCW: Prevent backflow of EECW into RCW.Impractical Test Requirement:
85-82A        Scram Disch Header Vent Hest        A-2                        GL      AO                        Q ST FS 85-83        Scram Disch Header Vent East      A-9/10                        GL      AO                        Q ST FS 85-83A        Scram Disch Header Vent East        A-10                        GL      AO                        Q ST FS Page 118 1228C/COC3/TLH
Basis for Relief: Exercise valves closed every three months.System design prevents the valves from being verified closed by reverse flow or other conventional means.Therefore, an alternate test such as acoustic monitor verification'r disassembly will be required.Since the valves can be verified open quarterly by flow verification, apparent disc free movement will be indicated.
 
Alternative Testing: Valves will be proven to close once per refueling cycle by other positive means such as disassembly, acoustic monitoring techniques, or other proven methods.0302B I~
~
Relief Request Number PV-23 Page 1 of 2 System: Control Rod Drive Hydraulic (85)Drawing: 47H820-2 47820-5 (U2)47820-6 (U163)~e~r Valves: 85-39K (1-185)85-39B (1-185)85-589 (1-185)85-597(1-185) 85-616 (1-185)C Class: Function: Control Rod Scram Hater Flow Path Impractical Test Requirement:
    ~
Exercise once every three months and measure stroke times.Basis for Relief: These valves located on the dhydraulic control units for the 185 control rod drives function on a reactor scram signal from the reactor protection system to insert the control rods rapidly into the reactor core.Cycling these valves requires scramming a control rod.There are 185 control rods in the reactor.Scramming every rod once every three months is not practical for the followinq reasons: a.A power reduction is required to test the scram function.Reducing power for the length of time required to scram 185 rods is not practical.
Page 126
b.Fuel preconditioning must follow this power reduction to avoid possible fuel damage.The longer the reduction in power, the longer the preconditioning.
  . System: EEIEWE7 CATEGORY B  - PASSIVE VALVES Drawing No.  ~47W -i
Their proper functioning is most practically verified by an actual scram test.1310C
                          ~P<<~ii42n                  Dr win    or  ins 67-504                                                F-3 67-505                                                F-3 1303C
.;0'~&('
 
Page 164 RELIEF RE E T B R PV-Page 1 of 1 System: RHR (74)CAD (84)Drawing: 47W811-1 47W862-1 Valves: 74-661, 74-662 84-600, 601, 602, 603 84-617, 680 Class: RHRt 1 CAD!2 Function: RHR: Thermal Relief/Containment Isolation CAD: Containment Atmosphere Control MSRV Air Supply Impractical Test Requirement!
,b w, Page 137 Relief   Re  uest Number PV-5            Page 1  of 2 System:          As  listed  on page    12 Drawing:        As  listed  on page Components:      Installed plant instrumentation        used to measure  pump parameters.             V Class:          2, 3, and  NC Function:        Measurement    of pump  parameters.
Cycle valve quarterly.
Impractical Test Requirement:    a. Instrument accuracy shall      be  within the limits of table IWP-4110-1, Paragraph    IWP-3210, Allowable Ranges        of Inservice    Test Quantities and Paragraph IWP-4120, Full-Scale    Range  Requirement.
Basis for Relief: RHR: These valves provide thermal relief between the inboard and outboard shutdown cooling suction valves.Since these valves are in series with no isolation valve or test connection between them, they individually cannot be proven to close".Since these valves are located inside containment, access to perform testing during operation is impractical due to the drywell being inerted.Cycling by system manipulation is not possible during reactor operation due to pressure interlocks which prevent the suction valves from operating.
: b. Velocity  measurement  shall  be used  instead of displacement as an alternative method of determining vibration amplitude.
Alternative Testing: CAD: These valves provide an injection path when open and containment isolation when closed.Cycling the valve closed would require setup of temporary test equipment and abnormal valve lineups.l Proper valve opening will be proven by alternative test methods such as passing flow during CSD, assuming DW entry and adequate time.Proper valve closure will be verified by completion of local leak rate testing performed in accordance with'10 CFR 50 Appendix J.I 1310C Page 172 Cold Shutdown Justification Number 6 Deleted Page l.74 Cold Shutdown Justification Number 8 Deleted e 4'
Basis  for Relief:          The  accuracy of    installed plant indicators is      + 2'L of  full scale. However, the accuracy of installed transmitters and square rooters is 0.57. and, when these are taken into account, the i'nstrument loop accuracies are 2.5% and 3.0% for pressure loops and flow loops, respectively. The diesel fuel transfer pumps are not instrumented to measure flow other than a level gage on the day tank.'he plant installed instruments will continue to be used since any alternate method such as connecting instruments into the system -or replacing plant instrumentation will not significantly increase the repeatability of the instruments for trending.
~~'Page 175 ifi i n N System: Drawing: CAD (84)'-47W862-1 Valves: 84-600, 601, 602, 603, 617, and 680 Category: Class: Function: DW/PSC Supply Check Valves (CIV)Justification:
(.
Proving the valves open quarterly requires injection of nitrogen into the drywell which is not practical due to the effects on drywell pressure.0 1310C ri s~~C L Cl Page 7 of 7 1 h wn ifi i n N 1 Page 177b System: Residual Heat Removal (74)Core Spray (75)Drawing: 47W811-1 47W814-1 Valves: 74 792 802~803 i 804 75-606, 607, 609, 610 Category: Class: Function: Provides isolation between the safety system and the non-safety system which is used to fill the safety system and maintain it filled while it is in the standby status.-~Justification:
0302B
The valve alignments which is necessary to provide positive indication of the full, or partial exercising of these check valves requires that the safety system be declared inoperable during the testing procedure.
 
Normal testing of these valves during unit operation would require placing the plant in limiting condition operation (LCO)on a quarterly basis for the testing of each valve.As required by paragraph IWV-3522 of.the Code, these valves will be full stroke exercised on a cold shutdown basis.1310C I.L f 1I}}
s
'l
 
Page 147 e System:
Relief Re  uest Number PV-14 Emergency Cooling Water (67) and
                                                        ~
Page 1 of 1 Raw  Cooling Water (24)
Drawing:        47W859-1 47W859-2 47W866-7 Valves:
67-541, 542, 584, 585, 648, 649, 657, 558; 559, 638, 639, 600, 601, 659, 660 528, 529, 634, 635, 521, 522, 630, 631 624, 625, 514, 515, 627, 628,. 507, 508 502, 622, 619, '656, 671, 679, 638; 873, 876 3-24-831, 833, 796, 798., 852 3-67-639, 694, 695, 696, 703, 704, 705, 706 715, 716, 713, 714, 723, 724, 725, 726 771, 772, 774, 775, 761, 762, 764, 765 737, 738, 735, 736 Function:       EECW:   Pass rated flow for the emergency coolers and prevent backflow from opposite header.
RCW:   Prevent backflow of  EECW into RCW.
Impractical Test Requirement:    Exercise valves closed every three months.
Basis for Relief:          System design prevents the valves from being verified closed by reverse flow or other conventional means.
Therefore, an alternate test such as acoustic monitor verification'r    disassembly  will be  required. Since the valves can be  verified  open quarterly by flow verification, apparent disc free movement will be indicated.
Alternative Testing:        Valves  will be  proven to close once per refueling cycle by other positive means such as disassembly, acoustic monitoring techniques, or other proven methods.
0302B
 
I~
Relief Request  Number PV-23      Page 1  of 2 System:          Control  Rod Drive Hydraulic (85)
Drawing:         47H820-2 47820-5 (U2) 47820-6 (U163)
                                                            ~e~r Valves:          85-39K (1-185) 85-39B (1-185) 85-589 (1-185)                                C 85-597(1-185) 85-616 (1-185)
Class:
Function:        Control  Rod Scram  Hater Flow Path Impractical Test Requirement:    Exercise once every three months and measure stroke times.
Basis  for Relief:          These valves located on the dhydraulic control units for the 185 control rod drives function on a reactor scram signal from the reactor protection system to    insert the control rods rapidly into the reactor core.
Cycling these valves requires scramming a    control rod.
There are 185 control rods in the reactor.      Scramming every rod once every three months    is not practical for the followinq reasons:
: a. A power  reduction is required to test the scram function. Reducing power for the length of time required to scram 185 rods is not practical.
: b. Fuel preconditioning must follow  this power reduction to avoid possible fuel damage. The longer the reduction in power, the longer the preconditioning.
Their proper functioning is most practically verified by an actual scram test.
1310C
 
      .;0
    '
~&
(  '
 
Page 164 RELIEF RE E  T    B R PV-            Page 1  of 1 System:         RHR  (74)
CAD  (84)
Drawing:        47W811-1 47W862-1 Valves:          74-661, 74-662 84-600, 601, 602, 603 84-617, 680 Class:          RHRt  1 CAD!  2 Function:        RHR:  Thermal Relief/Containment Isolation CAD:  Containment Atmosphere Control MSRV Air Supply Impractical Test Requirement!    Cycle valve quarterly.
Basis  for Relief:         RHR:   These valves provide thermal relief between the inboard and outboard shutdown cooling suction valves. Since these valves are in series with no isolation valve or test connection between them, they individually cannot be proven to close". Since these valves are located inside containment, access to perform testing during operation is impractical due to the drywell being inerted. Cycling by system manipulation is not possible during reactor operation due to pressure interlocks which prevent the suction valves from operating.
CAD:  These valves provide an injection path when open and containment isolation when closed. Cycling the valve closed would require setup of temporary test equipment and abnormal valve lineups.                                            l Alternative Testing:         Proper valve opening will be proven by alternative test methods such as passing flow during CSD, assuming DW entry and adequate time. Proper valve closure will be verified by completion of local leak rate testing performed in accordance with'10  CFR 50 Appendix J.
I 1310C
 
Page 172 Cold Shutdown Justification Number 6 Deleted
 
Page l.74 Cold Shutdown Justification Number 8 Deleted
 
e 4'
~ ~ '
Page 175 ifi i n  N System:          CAD  (84)
Drawing:      '-47W862-1 Valves:          84-600, 601, 602, 603, 617, and 680 Category:
Class:
Function:        DW/PSC  Supply Check Valves (CIV)
Justification:  Proving the valves open quarterly requires injection of nitrogen into the drywell which is not practical due to the effects on drywell pressure.
0 1310C
 
ri  s ~ ~
C L
Cl
 
Page 7 of 7 1    h      wn  ifi i n  N  1        Page 177b System:        Residual Heat Removal (74)
Core Spray (75)
Drawing:      47W811-1 47W814-1 Valves:        74 792  802 ~  803 i  804 75-606, 607, 609, 610 Category:
Class:
Function:      Provides isolation between the safety system and the non-safety system which is used to it fill the safety system and maintain  it  filled while is in the standby status.
Justification: The  valve alignments which is necessary to provide positive indication of the full, or partial exercising of these check valves requires that the safety system be declared inoperable during the testing procedure. Normal testing of these valves during unit operation would require placing the plant in
-
  ~                limiting condition operation (LCO) on a quarterly basis for the testing of each valve. As required by paragraph IWV-3522 of. the Code, these valves cold shutdown basis.
will be full stroke exercised on a 1310C
 
I. L f
1 I}}

Revision as of 00:30, 22 October 2019

Forwards Description of Changes & Corrections to ASME Section XI Pump & Valve Test Program & Associated Implementing Surveillance Procedures,In Ref to NRC Info Notice 88-070.Revised Program Pages Also Encl
ML18036A321
Person / Time
Site: Browns Ferry  Tennessee Valley Authority icon.png
Issue date: 08/09/1991
From: Zeringue O
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
IEIN-88-070, IEIN-88-70, TAC-11324, TAC-11325, TAC-11326, NUDOCS 9108160181
Download: ML18036A321 (107)


Text

Page 1 of 7

, Additions to the Program

1. Pages 65 and 147. EECW check valves 2-67-872, 873, 876, and 877 to the

, shutdown board room chillers. These check valves are being added to the program to be tested in their respective safety positions. Valves 2-67-873 and 876 have been added to relief request PV-14 to allow disassembly and inspection in lieu of inservice exercising, since no position indication exists for these valves.

20 Pages 117 and 118. Scram discharge instrument volume drain isolation valves85-37C, D, E, and F and 85-82, 82A, 83, and 83A. Fail-safe operation testing is being added for these valves.

3~ Page 39. Drywell compressor suction isolation valves 2-32-62 and 63.

The program is being revised to reflect fail-safe testing performed on these valves.

4. Pages 98, 99, 104, and 178. Residual heat removal (RHR) and core spray system valves74-792, 802, 803, 804, and 75-606, 607, 609, and 610. Cold shutdown justification No. 13.
5. Pages 38 and 40. Control Air System containment isolation valves 2-32-2516 and 2521. These check valves have been added to the piping which supplies control air to the drywell. These check valves function as containment isolation valves and are being tested in accordance with Appendix J requirements.
6. Pages 115, 164, and 175. Containment Atmosphere Dilution System 'check valve 84-680. This new check valve performs as a containment isolation valve and is being added to the program and to Relief Request PV-30 and tested in accordance with Appendix J requirements in accordance with Cold Shutdown Justification No. 9.

7 ~ Page 45a. Post-Accident Sampling System isolation valves FSV-43-40, 42, 50, 56, and 70. These new solenoid valves are being added to. the program.

8. Page 34. Raw cooling water discharge valves 0-24-712A and B to the main control room chillers are now used to control EECW flow through the chillers. These valves are being added to the testing program.

Deletions from the Program Page 58. EECW System check valves 1-67-556 and 2-67-556. These check valves have been replaced with manual butterfly valves which are provided for use during system maintenance. Such valves do not perform a safety function and are exempt from testing by paragraph IWV-1200 of ASME Section XI.

2. Pages 24 and 25. Diesel fuel transfer pump check valves 1-18-582A, B, C, and D; 3-18-582A, B, C, and D; 1-18-583A, B, C, and D; and 3-18-583A, B, C, and D. These check valves have been physically removed from the plant and the program is being updated to reflect this.

,. 9108160181

4, g1 gp I"

,

4 vp J

Page 2 of 7

3. Pages 116 and 156. Control Rod Drive System valve 85-617. This valve is a manual valve which was mistakenly identified as a check valve. This

,valve is provided for use during system maintenance and has no testing requirements. This valve is being deleted from the program. Also, the reference to this valve is being deleted from PV-23.

Pages 172, -89, and 91. Cold Shutdown Justification No. 6 for the RHR System pressure isolation valves 74-53 and 74-67. It has been determined that the justification for cold shutdown testing status for these valves is no longer valid. The integrity of the upstream isolation valves is sufficient to prevent the exposure of lower pressure RHR piping to reactor coolant pressure during the quarterly testing of the pressure isolation valves.

5. Page 33. RCW check valve 1-24-851. This check valve has been replaced with a manual valve. This valve'is provided for use during system maintenance and is therefore exempt from testing requirements by paragraph IWV-1200 of ASME Section XI. This valve is being deleted from the program.
6. Page 34. RCW check valve 1-24-709. This check valve no longer performs a safety function and is being deleted from the program. The downstream manual valve 24-710 is relied upon to provide isolation between the RCW system and the EECW system. Plant operating instructions control the operation of the system separation valve.
7. Page 59. EECW System discharge header check valve 2-67-598. This check valve has been replaced with a normally open manual isolation valve which does not perform a safety function. The new manual valve is provided for use during system maintenance and is therefore exempt from testing requirements by paragraph IWV-1200 of ASME Section XI.
8. Pages 32 and 33. RCW System discharge check valves 1, 2, and 3-24-765.

,

These check valves no longer perform a safety function of providing the discharge flow path for the EECW System. Hew seismically qualified discharge piping has been installed for the EECW System. These check valves are being deleted from the program.

9 ~ Page 63. EECW system check valve 1-67-785. This valve has been physically removed from the plant and is, therefore, being deleted from the program.

10. Pages 75, 81, and 174. High-pressure coolant injection and reactor core isolation cooling system steam supply valves to the respective pump turbines, 71-2 and 3 and 73-2 and 3. These valves are listed as cold shutdown tested valves. It has been determined that the justification for the cold shutdown classification of these valves is too conservative. It is believed that these valves can be tested quarterly without risk of making the system inoperable. Therefore, Cold Shutdown Justification CSD-8 is being deleted from the program.

I A

~ g~ 'i

/ 1

Page 3 of 7

11. Page 81. High-pressure coolant injection turbine steam drain level

~

control isolation valve 73-5. This valve is provided for system control only and is exempt from Section XI testing. This valve is being deleted

'rom the testing program.

12. Pages 70 and 71. EECW supply isolation valves to the unit 3 water chillers, 3-67-760, 763, 770, and 773, are now maintained in the open position and are used only for maintenance of the chiller packages.

These valves are being deleted from the program.

13. Pages 57 and 62. EECW supply isolation valves to the main control room chiller, 1-67-537 and 651, are now maintained in the open position and are used only for maintenance of the chiller package. These valves are being deleted from the program.

Changes to the Program

1. Page 51. Primary to secondary containment vacuum relief valves64-800 and 801. The program is being revised to reflect that these relief valves perform 'safety functions in both the open and closed directions and are being tested accordingly.
2. Page 112. Spent fuel cooling water check valves78-526 and 527. Due to f system modifications, these check valves no longer perform safety functions in the closed position.
3. Page 112. RHR System to spent fuel pool valve 78-62. Motor-operated valve 78-62 has been modified to disable the motor-operator. This valve will be tested as a manual valve in the future and will not be str'oke timed.
4. Page 78. RCIC discharge valve 71-39 is no longer a containment isolation valve. The leakage testing requirement for this valve is being deleted.
5. Page 84. HPCI discharge valve 73-44 is no longer a containment isolation valve. The leakage testing requirement for this valve is being deleted.
6. Pages 71 and 126. EECW control room chiller discharge isolation valves 3-67-769 and 779 are now used to control flow through the chiller and are no longer passive valves. These valves are being added to the active valve test listing and deleted from the passive valve listing.

Corrections to the Program

1. Page 46. Add PV-32 in the Relief Request column for valves63-514 and 516 to reflect their inclusion in this relief request.
2. Pages 63 and 64. Add PV-33 in the Relief Request column for valves 1-67-787 and 789 to reflect their inclusion in this relief request.

t 3.

4.

1310C Page 101.

to reflect Page 91.

Delete the reference to relief request PV-21 for valve 75-57 the removal of this valve from the relief request.

Change the valve type designation for RHR check valve 74-68, which has mistakenly identified in the program as a gate valve.

0 W) '

~

,

ll Cl

Page 4 of 7

5. Pages 114 and 115. Correct the cold shutdown justification reference for

'alves84-600, 601, 602, 603, and 617 from CSD-10 to CSD-9.

6. Pages 116 and 156. Delete relief request reference PV-25 from valves85-39A and 39B.
7. Page 26. Valves 1-23-56 and 2-23-56 were deleted from the program in the program revision dated June 22, 1989. The enclosed page 26 reflects this deletion.
8. Page 82. Valves 73-8 and 19 were deleted from the program in the program revision dated June 22, 1989. The enclosed page 82 reflects this deletion. The fail-safe testing performed on valve 73-18 is also reflected on this new page 82.
9. Page 85. The safety-related position of valve 73-609 was corrected from

'open/closed'o 'closed'nly, in the June 22, 1989 program revision.

This new page 85 reflects this change.

10. Page 137. Correct the page reference from page 11 to page 12.

'ontrol Page 116.

program is Rod Drive being changed positions for this valve.

cooling to reflect water inlet check valve 85-597.

the correct normal and safety The

12. Page 112. PV-22 was deleted in the June 22, 1989 program revision. The this relief request was not deleted for valves78-526 and

-'o reference 527 1310C

bi 4(t

Page 5 of 7 Revision of Relief Request PV-6 Relief Request PV-6 deals with the testing of the main steam safety relief valves (SRVs) (1-5, 19, 22, 30, 31, 34). The plant staff has determined that with presently installed instrumentation, no means exists to verify that the main steam SRVs each stroke within two seconds as stated under alternative testing in the current relief request. The only existing position indicating instrumentation consists of a series of LEDs on the main control room valve acoustic monitoring panel. The acoustic monitoring LEDs indicate noise levels downstream of the SRVs and are very sensitive to background noise as well as steam flow through the SRVs.

Since no means exists to measure the stroke time for the main steam SRVs, the alternate testing description i.n the request for relief is being revised to remove the less than two second stroke time testing. The technical specification reference which requires the manual exercising of each SRV each operating cycle is being corrected from 4.5.G to 4.6.D.

0902C

(

I

1 Jj Page 6 of 7 Page 139 R li f R N mber PV-6 Page 1 of 1 System: Main Steam Drawing: 47W801-1 Valves: 1-5, 1-19, 1-22, 1-30, 1-31, 1-34 Category', C Class:

Function: ADS Valve, Code Safety/Relief Valve Impractical Test Requirement: Exercise valve once every three months.

Basis for Relief: The six safety relief valves assigned to the ADS system

'perform an essential safety function when operated by the pneumatic actuator with gas supplied through the ADS solenoid valves. Operation of'these valves is not practical during power operations because this action will vent main steam to the suppression pool, inducing a transient condition and increasing the potentiality for an open failure of a safety relief valve.. Also, no stroke timing is practical as these are pneumatic'ssisted SRVs.

Since "position indication" of the SRVs is provided by acoustic monitors attached to the valve discharge piping, exercising during cold shutdown cannot be accomplished because of lack of steam flow (and attendant noise).

Alternative Testing: The ADS valves will be exercised once each operating cycle in accordance with Technical Specification 4.6.D which provides manual opening of each ADS valve and observing indication of steam flow through each valve.

0902C

Page 7 of 7 l Sh wn ifi ion No 1 System: Residual Heat Removal (74)

Core Spray (75)

Drawing: 47W811-1 47W814-1 Valves: 74 792 802 803 i 804

~

75-606, 607, 609, 610 Category:

Class:

Function: Provides isolation between the safety system and the non-safety system which is used to it fill the safety system and maintain it filled while is in the standby status.

Justification: The valve'lignments which is necessary to provide positive indication of the full, or partial exercising of these check valves requires that the safety system be declared inoperable during the testing procedure. Normal testing of these valves during unit operation would require placing the plant in limiting condition operation (LCO) on a quarterly basis for the testing of each valve. As required by paragraph IWV-3522 of the Code, these valves will be full stroke exercised on a cold shutdown basis.

0902C

~4 I ENCLOSURE-2 (48 pages)

TENNESSEE VA THORITY Browns Ferry r Plant Units 1, , and 3 Inservice Testing Program System: Fuel Oil (18) Drawing No. 47M84D-1 Page 1 of 2 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Val ve ASNE Drawing Valve Size Val ve Actuator Normal Related Testing Justifictn. Performed Number Function Cl ass Coordtn. Category (in.) Type Type Positn. Posi tn. Req'd. (if applic.) (if diffrnt.)

Page 24

TENNESSEE VA UTHORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program System: Fuel Oil (18) Drawing No. 47M840-1 Page 2 of 2 Relief Req./

Sect. XI Saf ety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Positn. Positn. Req'd. (if applic.) (if diffrnt.)

Page 25

TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, 3 Inservice Testing Program System: Residual Heat Removal Service Water (23) Drawing No. 47W858-1 Page 1 of 6 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve. Actuator Normal Related Testing 3ustifictn. Performed Number Function Class Coordtn. Category. (in.) Type Type Positn. Positn. 'eq'd. (if applic.) (if diffrnt.)

23-34 RHR Htx A Cooling Wtr Outlet C-1 12 GL TH Q PV-12 ST 23-40 RHR Htx C Cooling Wtr Outlet A-1 12 GL TH Q PV-12 ST 23-46, RHR Htx B Cooling Wtr Outlet 12 GL= TH Q ST PV-12 a

~

23-52 RHR Htx D Cooling Wtr Outlet 12 GL TH Q PV-12 ST Page 26

ir

'I t

TENNESSEE VAL Browns Ferry Units 1, THORITY 3

Plant Inservice Testing Program 0

System: Raw Cooling Water (24) Drawing No. 47W844-2 Page 1 of 2 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Positn. Positn. Req'd. (if applic.) (if diffrnt.)

1-24-707 Supply to EECW Check B-1 CK SELF CV 2-24-707 Supply to EECW Check C-7 . CK SELF CV a

3-24-707 Supply to EEOf Check C-9 CK SELF CV 1-24-730 Supply to EECW Check 3 B-6 CK SELF CV 2-24-730 Supply to EECW Check B-8 CK SELF CV 3-24-730 Supply to EECW Check 6-10/11 CK SELF Page 32

0 TENNESSEE VA THORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program System: Raw Cooling Water (24) Drawing No. 47W844-2 Page 2 of 2 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing 'alve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Positn. Positn. Req'd.. (if applic.) (if diffrnt.)

3-24-796 HVAC RH A Supply Check D-12 CK SELF CV PV-14 RR 3-24-798 HVAC RH A Supply Check 0-12 CK SELF CV PV>14 RR Page 33

TENNESSEE VA UTHORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program System: Raw Cooling Mater (24) Drawing No. 47W859-1 Page 1 of 1 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. f Per ormed Number Function Class Coordtn. Category (in.) Type Type Positn. Positn. Req'd. (if applic.) (if diffrnt.)

0-24-712A Wtr Chiller A discharge isolation NNCC A-1 0/C 0/C 0-24-7128 Wtr Chiller B discharge isolation NNCC A-1 0/C 0/C Page 34

TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, 3 Inservice Testing Program System: Control Air (32) Drawing No. 47W2847-5 Page 1 of 1 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Positn. Positn. Req'd. (if applic.) (if diffrnt.)

2-32-336 Outbd DW Check 0-7 AC CK SELF 0/C CV PV-24 RR LT LT I

2-32-2521 DW Check NNCC AC 1/2 CK SELF 0/C CV PV-24 RR LT LT Page 38

TENNESSEE VALL THORITY Browns Ferry Plant Units 1, 3 Inservice Testing Program System: Control Air (32) Drawing No. 47W2847-8 Page 1 of 1 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Val ve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Posi tn. Positn. Req'd. (if applic.) (if diffrnt.)

2-32-62 DW Cmpsr Suction Isol B-9 PL AO Q ST LT FS 2-32-63 DW Cmpsr Suction Isol B-9 PL AO Q ST LT FS Page 39

TENNESSEE VAL THORITY Drowns Ferry r Plant Units 1, d 3 Inservice Testing Program System: Control Air (32) Drawing No. 47W2847-9 Page 1 of 1 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing 3ustifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Positn. Posi tn. Req'd. (if applic.) (if diffrnt.)

2-32-2163 Inbd DW Check C-2 AC 3/4 CK SELF 0/C CV PV-24 RR LT LT 2-32-2516 Inbd DW Check NNCC C-3 AC 3/4 CK SELF 0/C CV PV-24 RR LT LT Page 40

TENNESSEE VAL THORITY Browns Ferry r Plant, Units 1, 3 Inservice Testing Program System: Sampling and Water ()vali ty Drawing No. 47E867-3 Page 1 of 1 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing 3ustifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Positn. Positn. Req'd.. (if applic.) (if diffrnt.)

FSV-43-40 Primary Containment Isolation F-2 1/2 GL LT FSV-43-42 Primary Containment Isolation F-2 1/2 GL LT FSV-43-50 Primary Containment Isolation G-2 1/2 GL LT FSV-43-56 Primary Containment Isolation G-2 1/2 GL LT FSV-43-70 Primary Containment Isolation B-2 1/2 " GL S LT Page 45a

TENNESSEE VA THORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program System: - Standby Liquid Control,(63) Drawing No. 47W854-1 Page 1 of 1 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASME Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Perf ormed Number . Function Class Coordtn. Category (in.) Type Type Posi tn. Posi tn. Req'd. (if applic.) (if diffrnt.)

63-BA A Injec ti on C-3 l-l/2 GA DT 63-88 8 In j ec ti on D-3 1-1/2 GA DT 63-512 A Pump Relief D-5 RV SELF RV 63-513 B Pump Relief 0-6 RV SELF RV 63-514 A Pump Disch Check 1-1/2 CK SELF 0/C CV PV-32 RR/PV-32 63-516 B Pump Disch Check D-6 1-1/2 CK SELF 0/C CV PV-32 RR/PV-32 63-525 Cont Isol Check D-2 AC 1-1/2 CK SELF 0/C CV PV-9 RR LT LT 63-526 Cont Isol Check E-2 AC 1-1/2 CK SELF 0/C CV PV-9 RR LT LT Page 46

Cl TENNESSEE VAL UTHORITY Browns Ferry r Plant Units 1, 3 Inservice Testing Program System: Reactor Building Heating, Ventilation, and Air Conditioning (64) Drawing No. 47W865-1 Page 3 of 3 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Cl ass Coordtn. Category (in.) Type Type Positn. Positn. Req'd. (if applic.) (if diffrnt.)

64-32 PSC Exhaust Inbd Isol G-9 18 BF AO Q ST LT 64-33 PSC Exhaust Outbd Isol F-9 18 BF AO Q ST LT 64-34 PSC SBGT Inbd Isol G-10 2 BF AO Q ST LT 64-800 PSC Vac Rel i e f Ck G-3 20 CK SELF 0/C CV LT 64-801 PSC Vac Relief Ck G-3 20 CK SELF 0/C CV LT Page 51

0

~ e~r

%PI

TENNESSEE VAL 'HORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program System: Emergency Equipment Cooling Water (67) Drawing No. 47W859-1 Page 5 of 13 Rel i e f Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing 3ustifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Positn. Positn. Req'd. (if applic.) (if diffrnt.)

0-67-521 1B OG Cooler S Hdr Check D-1 CK SELF 0/C 0/C CV PV-14 RR 0-67-522 18 DG Cooler S Hdr Check D-1 C CK SELF 0/C 0/C CV PV-14 RR 0-67-528 lA OG Cooler S Hdr Check C-1 CK SELF 0/C 0/C PV-14 RR 0-67-529 0-67-538 lA OG Control Cooler Rm S Hdr Check Chiller S Hdr C-1 8-2

. CK CK SELF SELF 0/C 0/C 0/C CV CV PV-14 PV-33 RR RR/PV-3

~

Supply Check 0-67-539 Control Rm Chiller S Hdr 8-2 CK SELF 0/C CV PV-33 RR/PV-3 Supply Check Page 57

TENNESSEE VA THORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program System: Emergency Equipment Cooling Water (67) Drawing No. 47W859-1 Page 6 of 13 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Val ve ASHE Drawing Valve Size Valve Actuator Normal Rel ated Testing Justifictn.'erformed Number Functi on Class Coordtn. Category (in.) Type Type Positn. Posi tn. Req'd. (if applic.) (if diffrnt.)67-541 Loop I CS Rm Cooler S Hdr C-3 2-1/2 CK SELF 0/C 0/C CV PV-14 RR Supply Check 67-542 Loop I CS Rm Cooler S Hdr C-3 2-1/2 CK SELF 0/C 0/C CV PV-14 RR Supply Check 67-558 Loop I RHR Rm Cooler S Hdr CK SELF 0/C 0/C CV PV-14 RR 67-559 Supply Check Loop I RHR Rm Supply Check Cooler S Hdr CK SELF 0/C '/C CV PV-14 RR Page 58

TENNESSEE VAL THORITY Drowns Ferry r Plant Units 1, d 3 Inservice Testing Program System: Emergency Equipment Cooling Water (67) Drawing No. 47W859-1 Page 7 of 13 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing 3ustifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Positn. Positn. Req'd.. (if applic.) (if diffrnt.)67-584 Loop II CS Rm Cooler S Hdr 2-1/2 CK SELF 0/C 0/C CV PV-14 RR Supply Check 67-585 Loop II CS Rm Cooler S Hdr 2-1/2 CK SELF 0/C 0/C CV PV-14 Supply Check 67-600 Loop II RHR Supply Check Rm Cooler S Hdr F-5 CK SELF 0/C 0/C CV PV.-14 RR

~

67-601 Loop II RHR Rm Cooler S Hdr F-5 CK SELF 0/C 0/C CV PV-14 RR Supply Check 0-67-619 S Hdr Check G-12 18 CK SELF 0/C 0/C CV PV-14 RR Page 59

TENNESSEE V UTHORITY Drowns Ferry ear Plant Units 1, 2, and 3 Inservice Testing Program System: Emergency Equipment Cooling Water (67) Drawing No. 47W859-1 Page 10 of 13 I

/ Sect. XI I

/

I, I

I I / Safety-f

(

Relief Req./

Cold Shutdn.

[

f Testing Valve / ASHE / Drawing / Valve Size )Valve )Actuator] Normal / Related )Testing (

Justifictn. ] Performed Number Function ./ Class / Coordtn. / Category f (in.) [ Type ). Type [ Positn. / Positn. [ Req'd . [ (if applic.) ) (if diffrnt.)

I 0-67-652 ) Control Rm Chillers N Hdr 8-2 CK SELF 0/C i CV PV-33 RR/PV-33

] Supply Check I

0-67-653 ) Control Rm Chillers N Hdr 8-2 CK SELF 0/C 'CV PV-33 RR/PV-33

] Supply Check I

67-656 [ Loop II CS Rm Cooler N Hdr 8-5 C 12-1/2 CK SELF . 0/C 0/C PV-14 RR

$ Supply Check I

I 67-657 ] Loop II CS Rm Cooler N Hdr C-5 C I 2-1/2 I CK SELF 0/C 0/C CV PV-14 RR

) Supply Check I

67-659 [ Loop II RHR Rm Cooler N Hdr 8/C-5 CK SELF 0/C 0/C CV PV-14 RR

[ Supply Check I

Page 62

.

Al

TENNESSEE VA UTHORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program System: Emergency Equipment Cooling Water (67) Drawing No. 47W859-1 Page 11 of 13 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Si ze Val ve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Positn. Positn. Req'd. (if applic.) (if diffrnt.)67-660 Loop II RHR Rm Cooler N Kdr F-5 3 CK SELF 0/C 0/C CV PV-14 RR Supply Check 0-67-671 N Hdr Check G-12 18 CK SELF 0/C 0/C CV PV-14 RR 1-67-675 Units 182 Emerg Cooling Unit A-2 4 GA Disch Isol 0-67-679 RSW to EECW Check F/G-5 1 CK SELF CV PV-14 1-67-786 Emergency Control Bay Cooling 8-2 4 GA Unit N Hdr Supply Isol 1-67-787 Emergency Control Bay Cooling 8-2 4 CK SELF 0/C CV PV-33 RR/PV-33 Unit N Hdr Supply Check Page 63

.

TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, 3 Inservice Testing Program System: Emergency Equipment Cooling Water (67) Drawing No. 47W859-1 Page 12 of 13 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category ,(in.) Type Type Posi tn. Positn. Req'd. (if applic.) (if diffrnt.)

1-67-788 Emergency Control Bay Cooling B-2 Unit S Hdr Supply Isol 1-67-789 Emergency Control Bay Cooling B-2 CK SELF 0/C CV PV-33 RR/PV-33 Unit S Hdr Supply Check 3-67-807 DG Rm Cooler 1 Cooler 2 E-5 Crosstie 3-67-808 DG Rm Cooler 1 Cooler 2 Crosstie 67-838 H202 Analyzer 25-340 CK SELF 0/C CV Supply Check Page 64

Cl I ig ll

TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, d 3 Irscrvice Testing Program System: Emergency Equipment Cooling Water (67) Orawing No. 47W859-1 Page 13 of 13 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Orawing Valve Si ze Val ve Actuator Normal Related Testing Justifictn. f Per ormed Number Function Class Coordtn. Category (in.) Type Type Posi tn. Posi tn. Req'd. (if appli c.) (if diffrnt.)67-839 H202 AnalYzer 25-340 1 CK SELF 0/C CV Supply Check 67-843 H202 Analyzer 25-341 0-7 1 CK SELF 0/C Supply Check 67-844 H202 Analyzer 25-341 0-7 1 CK SELF 0/C Supply Check 2-67-872 Shutdown Bd Rm Crosstie Check C-8 3 CK SELF 0/C 2-67-873 EECW/RCW Supply Check C-8 3 CK SELF 0/C CV PV-14 PV-14 2-67-876 2-67-877 EECW/RCW Supply Check

~Shutdown Bd Rm Crosstie Check 3 '8 0-8 3 3

. CK CK SELF SELF 0/C 0/C CV CV PV-14 PV-14 Page 65

. Cl

~ ~ ~

~ ~ ~ ~ ~ ~

l . ~

~ ~ ~ ~

~ ~

~ ~

~ ~

~ ~

~ ~

.

~ ~ ~ ~

~ ~ ~ ~ ~

~ ~

I . ~

'

~

~ ~ ~ ~ ~ ~

~ ~ ~ ~ ~

~ ~

~ ~

~ ~

~ ~

.

4

'

TENNESSEE VA UTHORITY Browns Ferry r Plant Units 1, nd 3 Inservice Testing Program System: Reactor Core Isolation Cooling (71) Drawing No. 47W813-1 Page 1 of 6 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Val ve ASHE Drawing Val ve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Posi tn. Positn. Req'd. (if applic.) (if diffrnt.)

71-2 Steam Line Inbd Isol B-3 0/C Q PV-21 ST ST LT LT (R) 71-3 Steam Line Outbd Isol 0/C Q ST ST LT LT (R) 71-6A Steam Line to Cond Drain E-10 AO 0/C Q ST Page 75

~ ~

~ . ~ ~ ~

I ~ ~ ~ ~ ~ ~

~ ~

~ ~

~ ~ ~ ~ ~ ~ ~ ~ ~

~ ~

.0 Cl

TENNESSEE VAL THORITY Browns Ferry Plant Units 1, d 3 Inservice Testing Program System: High Pressure Coolant Injection,(73) Drawing No. 47W812-1 'age 1 of 6 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Val ve Number Function ASHE Class Drawing Coordtn.

Valve Category Si ze (in.)

Val ve Type Actuator Normal Type Posi tn.

Related Posi tn.

Testing Req'd. 'if applic.)

Justifictn. Per formed (if diffrnt.)

73-2 Steam Line Inbd Isol B-3 10 0/C Q PV-21 ST ST LT LT (R) 73-3 Steam Line Ougbd Isol 8-4 10 0 0/C Q ST ST LT LT (R) 73-6A Steam Line to Cond Drain 0-10 AO 0/C Q ST Page 81

0 TENNESSEE VA Browns Ferry Units 1, THORITY r Plant d 3 Inservice Testing Program System: High Pressure Coolant Injection (73) Drawing No. 47M812-1 Page 2 of 6 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Perf ormed Number Function Class Coordtn. Category (in.) Type Type Positn. Positn. Req'd: (if applic.) (if diffrnt.)

73-16 Turbine Steam Supply 8-9 10 Q ST 73-18 Turbine Stop 8-9 10 E/H Q PV-25 ST FS Page 82

~ ~ ~

~ ~ ~ ~ ~

~

'

~ ~ ~ ~ ~ ~ ~

I oo

~ ~ I

Cl tq1

TENNESSEE VAL THORITY Browns Ferry Plant Units 1, 3 Inservice Testing Program System: High Pressure Coolant Injection (73) Drawing No. 47W812-1 Page 5 of 6 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Val ve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Positn. Positn. Req'd. (if applic.) (if diffrnt.)73-506 Pump Suction Relief 8-6/7 RV SELF RV 73-517 PSC Suction Check 16 CK SELF CV PV<0 RR 73-559 Hin Flow Bypass Check F-5 AC CK SELF 0/C CV PV-16 RR 73-574 Cooling Water to Gland Seal Cond Relief F-7/8 RV SELF LT RV LT

~

73-603 Turb Exhaust Check E-2/3 AC 20 CK SELF 0/C CV PV-18 RR LT LT 73-609 Turb Exhaust Dr Check E-4 AC CK SELF CV PV-18 RR LT LT Page 85

I I W%

TENNESSEE VAL THORITY Browns Ferry Plant Units 1, 3 In'service Testing Program System: Residual Heat Removal (74) Drawing No. 47W811-1 Page 3 of 13 Rel i e f Req./

Sect. XI Safety- Cold Shutdn. Testing Val ve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn., Category (in.) Type Type Posi tn. Posi tn. Req'd. (if applic.) (if diffrnt.)

74-48 SD Cooling Inbd Isol C-6 20 0/C Q CSD3-5 CSD ST ST LT LT 74-52 Loop I Throttle 24 Q ST 74-53 Loop I Injection 24 0/C Q ST ST LT LT 74-54 Loop I Testable Check AC 24 CK AO/SELF 0/C CV PV-27 CSD/PV-27 LT LT 74-57 Loop I PSC Return 8-2/3 18 GA 0/C Q ST LT Page 89-

TENNESSEE VAL THORITY Browns Ferry Plant Units 1, 3 Inservice Testing Program System: Residual Heat Removal (74) Drawing No. 47W811-1 Page 5 of 13 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASME Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Per formed Number Function Class Coordtn. Category (in.) Type Type Positn. Positn. Req'd. (if applic.) (if diffrnt.)

74-66 Loop II Throttle 8-7 24 Q ST 74-67 Loop II Injection BC-7/8 24 0/C Q ST ST LT LT 74-68 Loop II Testable Check C-7 AC 24 CK AO/SELF C 0/C CV PV-27 CSD/PV-27 LT LT 74-71 Loop II PSC Return 8-9 18 0/C Q ST LT 74-72 Loop II PSC Spray C-9 A. GL 0/C Q ST LT Page 91

f ~l TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program System: Residual Heat Removal (74) Drawing No. 47W811-1 Page 12 of 13 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category (in. ) Type Type Positn. Positn. Req'd.. (if applic.) (if diffrnt.)

74-587A Loop I Disch Hdr Relief 8-3 RV SELF RV 74-5878 Loop II Disch Hdr Relief 8-8 RV SELF RV 74-659 SD Cooling Supply Relief D-5 RV SELF RV 74-661 74-662 Thermal Thermal Relief Relief Check Check C-5 C-5 AC AC 3/4 3/4 CK CK SELF SELF 0/C 0/C CV LT CV PV-30 PV-30 RR RR

~

LT LT 74-722 PSC Drain D-7/8 A(P) LT 74-792 Loop I Fill from Hd Tk AC CK SELF 0/C CV CSD3-13 CSD LT Page 98

'l TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, 3 Inservice Testing Prcgran System: Residual Heat Removal (74) Drawing No. 47W811-1 Page 13 of 13 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Positn. Posi tn. Req'd. (if applic.) (if diffrnt.)74-802 Loop II Fill from Hd Tk A-8 AC CK SELF 0/C CV LT CSD3-13 CSD I

74-803 Loop II Fill from Hd Tk A-8 AC CK SELF 0/C CV LT CSD3-13 CSD 74-804 Loop I Fill from Hd Tk AC CK SELF 0/C CV LT CSD3-13 cso

~

Page 99

WI TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, 3 Inservice Testing Program System: Core Spray (75) Drawing No. 47W814-1 Page 2 of 5 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Val ve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Positn. Positn. Req'd. (if applic.) (if diffrnt.)

75-50 Loop II Pump Test 8-6 10 GL Q ST 75-51 Loop II Injection 12 Q ST 75-53 Loop II Injection 8-3 12 0/C Q ST LT 75-54 Loop II Testable Check 8-3 AC 12 CK AO/SELF C 0/C CV PV-27 CSD/PV-27 LT LT 75-57 Drain Pump A Inbd Isol H-7 AO Q Q ST ST LT LT(R)

Page 101

TENNESSEE VAL THORITY Browns Ferry Plant Units 1, 3 Inservice Testing Program System: Core Spray (75) Drawing No. 47M814-1 Page 5 of 5 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Si ze Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Posi tn. Positn. Req'd. (if applic.) (if diffrnt.)75-606 Loop I Fill from Hd Tank AC CK SELF 0/C CV CS03-13 CSD LT 75-607 Loop I Fill from Hd Tank AC CK SELF 0/C CV CSOJ-13 CSD LT 75-609 Loop II Fill from Hd Tank AC CK SELF ~ 0/C CV LT CSOJ-13 cso

~

75-610 Loop II Fill from Hd Tank AC CK SELF 0/C CV LT CSD3-13 CSO Page 104

TENNESSEE VA THORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program System: Fuel Pool Cooling System (78) Drawing No. 47W855-1 Page 1 of 1 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Si ze Val ve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Posi tn. Positn. Req'd. (if applic.) (if diffrnt.)

78-61 RHR to FPC Supply A-5 Q ST 78-62 RHR to FPC Supply A-6 78-526 To Pool Diffuser A CK SELF 0 CV 78-527 To Pool Di ffuser B 3 A-7 CK SELF CV Page 112

0

~l*

TENNESSEE VAL THORITY Browns Ferry Plant Units 1, 3 Inservice Testing Program System: Containment Atmosphere Dilution (84) Drawing No. 47W862-1 Page 2 of 3 Sect. XI Safety- 'elief Req./

Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Positn. Posi tn. Req'd. (if applic.) (if diffrnt.)

84-20 DW/PSC Oisch to SBGT 8-3 AO 0/C Q ST LT 84-600 DW Supply Check A 0-2 CK SELF 0/C CSO-9 CSD(0)

Q PV-30 RR(C)

LT LT 84-601 PSC Supply Check A D-2 CK SELF 0/C CSO-9 CSO(0)

Q PV-30 RR(C)

LT LT 84-602 DW Supply Check 8 CK SELF 0/C CSD-9 CSO(0)

Q PV-30 RR(C)

LT LT Page 114

TENNESSEE VA UTHORITY Browns Ferry r Plant Units 1, d 3 Inservice Testing Program System: Containment Atmosphere Dilution (84) Drawing No. 478862-1 Page 3 of 3 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Val ASHE Drawing Valve Si ze Valve Actuator Normal Related Testing Justifictn. Performed ve'umber Function Class Coordtn. Category (in.) Type Type Posi tn. Posi tn. Req'd. (if applic.) (if diffrnt.)84-603 PSC Supply Check 8 CK SELF 0/C CSD-9 CSD(0)

PV-30 RR(C)

LT LT 84-617 Containment Isol Valve C-7 CK SELF 0/C Q PV-30 CSD(0)

LT CSD-9 RR(C)

LT 84-680 Containment Isol Valv'e NNCC F-6 AC 1/2 CK SELF 0/C Q PV-30 CSD(0)

.LT CSD-9 RR(C)

LT Page 115

.

TENNESSEE VA UTHORITY Drowns Ferry r Plant Units 1, d 3 Inservice Testing Program System: Control Rod Drive (85) Drawing No. 47W820-2 Page 1 of 1 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn. Category (in.) Type Type Positn.. Positn. Req'd. (if applic.) (if diffrnt.)85-39A Scram Inlet C-8 PL AO Q PV-23 Per PV-23 (1-185) ST I

85-398 Scram Outlet C-7 3/4 PL AO Q PV-23 Per PV-23 (1-185) ST 85-576 Isol check to RWCU F-9 AC CK SELF 0/C CV PV-28 RR LT 85-589 Charging Water Check C-9 1/2 CK SELF 0/C CV CSD-11 CSD-11(C)

(1-185) PV-23 PV-23(0)85-597 Cooling Water Check B-9 1/2 CK SELF CV PV-23 PV-23(0)

(1-185)85-616 Scram Outlet Check 0-7 3/4 CK SELF CV (1-185) PV-23 PV-23(0)

Page 116

L'

lift pled

TENNESSEE VAL THORITY Browns Ferry Plant Units 1, 3 Inservice Testing Program A Page 1 of 2 System: Control Rod Drive (85) Drawing No. 47W820-6 (units 1 & 3) 47W820-5 (unit 2)

Relief Req /

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Performed Number Function Class Coordtn Category (in.) Type Type Posi tn. Posi tn. Req'd. (if applic.) (if diffrnt.)85-37C SDIV Drain Isol West H-5 2. GL AO Q ST FS85-370 SDIV Drain Isol West H-5 GL AO Q ST FS85-37E SDIV Drain Isol East H-8 GL AO Q ST FS85-37F SDIV Drain Isol East H-9 GL AO ST FS 85-82 Scram Disch Header Vent West A-2 8 GL AO Q ST FS Page 117

TENNESSEE VAL THORITY Browns Ferry r Plant Units 1, 3 Inservice Testing Program System: Control Rod Drive (85) Drawing No. 47W820-6 Page 2 of 2 Relief Req./

Sect. XI Safety- Cold Shutdn. Testing Valve ASHE Drawing Valve Size Valve Actuator Normal Related Testing Justifictn. Perf ormed Number Function Class Coordtn. Category (in.) Type Type Positn. Posi tn. Req'd. (if applic.) (if diffrnt.)85-82A Scram Disch Header Vent Hest A-2 GL AO Q ST FS 85-83 Scram Disch Header Vent East A-9/10 GL AO Q ST FS85-83A Scram Disch Header Vent East A-10 GL AO Q ST FS Page 118 1228C/COC3/TLH

~

~

Page 126

. System: EEIEWE7 CATEGORY B - PASSIVE VALVES Drawing No. ~47W -i

~P<<~ii42n Dr win or ins67-504 F-3 67-505 F-3 1303C

,b w, Page 137 Relief Re uest Number PV-5 Page 1 of 2 System: As listed on page 12 Drawing: As listed on page Components: Installed plant instrumentation used to measure pump parameters. V Class: 2, 3, and NC Function: Measurement of pump parameters.

Impractical Test Requirement: a. Instrument accuracy shall be within the limits of table IWP-4110-1, Paragraph IWP-3210, Allowable Ranges of Inservice Test Quantities and Paragraph IWP-4120, Full-Scale Range Requirement.

b. Velocity measurement shall be used instead of displacement as an alternative method of determining vibration amplitude.

Basis for Relief: The accuracy of installed plant indicators is + 2'L of full scale. However, the accuracy of installed transmitters and square rooters is 0.57. and, when these are taken into account, the i'nstrument loop accuracies are 2.5% and 3.0% for pressure loops and flow loops, respectively. The diesel fuel transfer pumps are not instrumented to measure flow other than a level gage on the day tank.'he plant installed instruments will continue to be used since any alternate method such as connecting instruments into the system -or replacing plant instrumentation will not significantly increase the repeatability of the instruments for trending.

(.

0302B

s

'l

Page 147 e System:

Relief Re uest Number PV-14 Emergency Cooling Water (67) and

~

Page 1 of 1 Raw Cooling Water (24)

Drawing: 47W859-1 47W859-2 47W866-7 Valves:

67-541, 542, 584, 585, 648, 649, 657, 558; 559, 638, 639, 600, 601, 659, 660 528, 529, 634, 635, 521, 522, 630, 631 624, 625, 514, 515, 627, 628,. 507, 508 502, 622, 619, '656, 671, 679, 638; 873, 876 3-24-831, 833, 796, 798., 852 3-67-639, 694, 695, 696, 703, 704, 705, 706 715, 716, 713, 714, 723, 724, 725, 726 771, 772, 774, 775, 761, 762, 764, 765 737, 738, 735, 736 Function: EECW: Pass rated flow for the emergency coolers and prevent backflow from opposite header.

RCW: Prevent backflow of EECW into RCW.

Impractical Test Requirement: Exercise valves closed every three months.

Basis for Relief: System design prevents the valves from being verified closed by reverse flow or other conventional means.

Therefore, an alternate test such as acoustic monitor verification'r disassembly will be required. Since the valves can be verified open quarterly by flow verification, apparent disc free movement will be indicated.

Alternative Testing: Valves will be proven to close once per refueling cycle by other positive means such as disassembly, acoustic monitoring techniques, or other proven methods.

0302B

I~

Relief Request Number PV-23 Page 1 of 2 System: Control Rod Drive Hydraulic (85)

Drawing: 47H820-2 47820-5 (U2) 47820-6 (U163)

~e~r Valves: 85-39K (1-185)85-39B (1-185)85-589 (1-185) C 85-597(1-185)85-616 (1-185)

Class:

Function: Control Rod Scram Hater Flow Path Impractical Test Requirement: Exercise once every three months and measure stroke times.

Basis for Relief: These valves located on the dhydraulic control units for the 185 control rod drives function on a reactor scram signal from the reactor protection system to insert the control rods rapidly into the reactor core.

Cycling these valves requires scramming a control rod.

There are 185 control rods in the reactor. Scramming every rod once every three months is not practical for the followinq reasons:

a. A power reduction is required to test the scram function. Reducing power for the length of time required to scram 185 rods is not practical.
b. Fuel preconditioning must follow this power reduction to avoid possible fuel damage. The longer the reduction in power, the longer the preconditioning.

Their proper functioning is most practically verified by an actual scram test.

1310C

.;0

'

~&

( '

Page 164 RELIEF RE E T B R PV- Page 1 of 1 System: RHR (74)

CAD (84)

Drawing: 47W811-1 47W862-1 Valves: 74-661, 74-662 84-600, 601, 602, 603 84-617, 680 Class: RHRt 1 CAD! 2 Function: RHR: Thermal Relief/Containment Isolation CAD: Containment Atmosphere Control MSRV Air Supply Impractical Test Requirement! Cycle valve quarterly.

Basis for Relief: RHR: These valves provide thermal relief between the inboard and outboard shutdown cooling suction valves. Since these valves are in series with no isolation valve or test connection between them, they individually cannot be proven to close". Since these valves are located inside containment, access to perform testing during operation is impractical due to the drywell being inerted. Cycling by system manipulation is not possible during reactor operation due to pressure interlocks which prevent the suction valves from operating.

CAD: These valves provide an injection path when open and containment isolation when closed. Cycling the valve closed would require setup of temporary test equipment and abnormal valve lineups. l Alternative Testing: Proper valve opening will be proven by alternative test methods such as passing flow during CSD, assuming DW entry and adequate time. Proper valve closure will be verified by completion of local leak rate testing performed in accordance with'10 CFR 50 Appendix J.

I 1310C

Page 172 Cold Shutdown Justification Number 6 Deleted

Page l.74 Cold Shutdown Justification Number 8 Deleted

e 4'

~ ~ '

Page 175 ifi i n N System: CAD (84)

Drawing: '-47W862-1 Valves: 84-600, 601, 602, 603, 617, and 680 Category:

Class:

Function: DW/PSC Supply Check Valves (CIV)

Justification: Proving the valves open quarterly requires injection of nitrogen into the drywell which is not practical due to the effects on drywell pressure.

0 1310C

ri s ~ ~

C L

Cl

Page 7 of 7 1 h wn ifi i n N 1 Page 177b System: Residual Heat Removal (74)

Core Spray (75)

Drawing: 47W811-1 47W814-1 Valves: 74 792 802 ~ 803 i 804 75-606, 607, 609, 610 Category:

Class:

Function: Provides isolation between the safety system and the non-safety system which is used to it fill the safety system and maintain it filled while is in the standby status.

Justification: The valve alignments which is necessary to provide positive indication of the full, or partial exercising of these check valves requires that the safety system be declared inoperable during the testing procedure. Normal testing of these valves during unit operation would require placing the plant in

-

~ limiting condition operation (LCO) on a quarterly basis for the testing of each valve. As required by paragraph IWV-3522 of. the Code, these valves cold shutdown basis.

will be full stroke exercised on a 1310C

I. L f